Multilin
FEEDER PROTECTION SYSTEM
APPLICATIONS
Industrial feeders with enhanced breaker monitoring diagnostics, etc. Distribution utility down stream breaker protection Medium voltage Utility feeders with advanced control features Cold Load Pickup, auto reclose, multiple settings group, etc
FEATURES
Protection and Control
Phase, neutral and ground TOC and IOC Undervoltage, overvoltage, frequency Neutral/ground directional Negative sequence Overcurrent ANSI, IAC, IEC, flex curves Cable Thermal Model Protection Breaker Failure Cold Load Pick Up Four-shot auto-reclose 8 digital inputs, 7 contact outputs Two setting groups
User Interface
4 line display for easy viewing of key data 10 LED indicators for quick diagnostics Front USB and rear RS485 serial communications Multiple Communication Protocols: IEC 61850 IEC 61850 GOOSE, MODBUS TCP/IP, MODBUS RTU, DNP 3.0, IEC 60870-5-104, IEC 60870-5-103
EnerVistaTM Software
EnerVista Software- an industry-leading suite of software tools that simplifies every aspect of working with Multilin devices. Quick & easy configuration requiring minimal settings for most feeder applications.
Digital Energy
270
Overview
The 350 relay is a member of the 3 Series family of Multilin relays. This protective device is used to perform primary circuit protection on medium voltage feeders and down stream protection for distribution utilities.
Distribution Feeder Protection
Easy to Use
Drawout Construction
The 350 offers a complete drawout feature eliminating the need for rewiring after testing has been concluded. The withdrawable feature also eliminates the need to open the switch gear door and disconnect communication cables, eg. Ethernet fiber, copper, RJ45, etc prior to removing the relay from the chasis
Easy to Configure
Fast & Simple Configuration
The 350 requires minimal settings for configuring standard feeder protection applications. The entire feeder protection setup can be completed in one easy step.
The basic protection function of this relay includes multiple phase, ground, and neutral time and instantaneous overcurrent elements for coordination with upstream and downstream devices. Additionally, the device provides essential feeder breaker control features such as cold load pick up blocking, breaker failure, and auto reclose. The robust 350 streamlines user work flow processes and simplifies engineering tasks such as configuration, wiring, testing, commissioning, and maintenance. This cost-effective relay also offers enhanced features such as diagnostics, preventative maintenance, arc flash mitigation and security.
Advanced Communications
Easy integration into new or existing infrastructure
With several Ethernet and serial port options, and a variety of protocols, the 350 provides advanced and flexible communication selections for new and existing energy management, SCADA, and DCS systems.
Effortless Retrofit
The small and compact 350 enables multiple relays to be mounted side by side on medium voltage panels. It also allows easy retrofit into existing S1 and S2 cutouts with adapter plates.
Diagnostic Alarms
271
Enhanced Diagnostics
Preventative Maintenance
The 350 allows users to track relay exposure to extreme environmental conditions by monitoring and alarming at high ambient temperatures. This data allows users to proactively schedule regular maintenance work and schedule upgrade activities. The diagnostics data enables the user to understand degradation of electronics due to extreme conditions.
Multiple Options
Several option for protection & communications are provided to match basic to high end application requirements.
Neutral Overcurrent
The neutral signal is derived as the residual sum of the three phase CTs eliminating the need for an additional ground sensor.
Protection
The 350 feeder protection system offers protection, control and monitoring in one integrated, economical and compact package.
Cost Effective
Robust Design
The 350 is subjected to Accelerated Life Testing (ALT) to validate accurate relay function under specified normal conditions. The device is further tested for durability through Highly Accelerated Life Testing (HALT) where it undergoes extreme operating conditions. The robust 350 design ensures long term operation.
Frequency Protection
The 350 offers overfrequency and underfrequency elements to improve network (grid) stability using voltage or frequency based load shedding techniques. It also provides back up protection when protecting feeders and other frequency sensitive power equipment.
Protection Features
BUS BUS VT 52 79 TRIP 3 CLOSE 1 MONITORING 50P 2 50N 2 CLP 1 50G 2 50G/ 51G 51G 1 51P 1 51N 1 50BF 79 50_2 1 49 1 METERING 27P 1 59P 1 27X 1 59X 1 59_2 1 59N 1 81U 2 81O 2
Function
Phase Undervoltage Auxiliary Undervoltage Thermal Model Phase Instantaneous Overcurrent Neutral Instantaneous Overcurrent Ground/Sensitive Ground Instantaneous Overcurrent Breaker Failure Negative Sequence Overcurrent Phase Timed Overcurrent Ground Timed Overcurrent Neutral Timed Overcurrent Phase Overvoltage Auxiliary Overvoltage Neutral Overvoltage Negative Sequence Overvoltage Ground Directional Overcurrent Neutral Directional Overcurrent Autoreclose Underfrequency Overfrequency Cold Load Pickup
350 RELAY
LOAD
272
Logic Designer
Sixteen logic elements available for applications such as manual control, interlocking, and peer to peer tripping.
flash, the relay can be set to communicate to any upstream or downstream devices via IEC 61850 GOOSE messaging.
of overcurrent elements to override the higher overload currents resulting from re-energization of feeder after a long period of time.
8 contact Inputs with programmable thresholds 2 Form A output relays for breaker trip and close with coil monitoring 5 Form C output relays
Breaker Failure
The Breaker Failure function is used to determine when a trip command sent to a breaker has not been executed within a selectable time delay. In the event of a breaker failure, the 350 will issue an additional signal to trip the breakers connected to the same busbar or signal the trip of upstream breakers.
Autoreclose
Reclose can be initiated externally or from an overcurrent protection. Up to four reclose operations are available, each with a programmable dead time. For each reclose shot, the relay can be programmed to block any overcurrent element.
Control
Cold Load Pick Up
Cold Load Pick up allows automatic or manual blocking or raising of trip settings for a period after the breaker has been closed. This feature adapts the pick up
273
Logic Elements
The 350 relay has sixteen Logic Elements available for the user to build simple logic using the state of any programmed contact, virtual, remote input or the output operand of a protection or control element. The logic provides for assigning up to three triggering inputs in an AND/OR gate for the logic element operation and up to three blocking inputs in an AND/OR gate for defining the block signal. Pickup and dropout timers are available for delaying the logic element operation and reset respectively.
Basic Metering
Metered values include: Current: Ia, Ib, Ic, In, Ig, Isg Phase-to-phase and phase-to-ground voltages for bus and line: Van, Vbn, Vcn, Vab, Vbc, Vca Active power (3-Phase) Frequency
Distribution Feeder Protection
Virtual Inputs
Virtual inputs allow communication devices the ability to write digital commands to the 350 relay. These commands could be open/close the breaker, changing setting groups, or blocking protection elements.
IRIG-B
IRIG-B is a standard time code format that allows time stamping of events to be synchronized among connected devices within 1 millisecond. An IRIG-B input is provided in the 350 to allow time synchronization using a GPS clock over a wide area. The 350 IRIG-B supports both AM and DC time synchronization with an auto detect feature that removes the requirement for manual selection.
274
Temperature Monitoring
The 350 continually monitors ambient temperature around the relay and alarms when the device is exposed to extreme temperatures and undesirable conditions such as air-conditioning unit or station heater failures.
Distribution Feeder Protection
If Password was required to change settings MAC address of user making setting changes Listing of modified changes Method of setting changes - Keypad, Front serial port, Ethernet, etc.
Advanced Communications
The 350 incorporates the latest communication technologies making it the easiest and the most flexible feeder protection relay for use and integration into new and existing infrastructures. The 350 relay provides the user with one front USB and one rear RS485 communication port. Also available with the 350 is a rear communication port with Ethernet Fiber and Copper. Through the use of these ports, continuous monitoring and control from a remote computer, SCADA system or PLC is possible. The 350 supports popular industry standard protocols enabling easy, direct integration into electrical SCADA and HMI systems. The protocols supported by the 350 include: IEC 61850 IEC 61850 GOOSE DNP 3.0 Modbus RTU
The EnerVista Viewpoint maintenance tool allows users to review and analyze the time period a 350 relay is exposed to certain temperature ranges.
Password Control
With the implementation of the Password Security feature in the 350 relay, extra measures have been taken to ensure unauthorized changes are not made to the relay. When password security is enabled, changing of setpoints or issuing of commands will require passwords to be entered. Separate passwords are supported for remote and local operators, and separate access levels support changing of setpoints or sending commands.
Security
Security Audit Trail
The Security Audit Trail feature provides complete traceability of relay setting changes at any given time and is NERC CIP compliant. The 350 maintains a history of the last 10 changes made to the 350 configuration, including modifications to settings and firmware upgrades. Security Setting Reports include the following information:
275
Modbus TCP/IP IEC 60870-5-103 IEC 60870-5-104 These protocols make it easy to connect to a Utility or Industrial automation system, eliminating the need for external protocol converter devices.
Display
Distribution Feeder Protection
EnerVistaTM Software
The EnerVista TM suite is an industry leading set of software programs that simplifies every aspect of using the 350 relay. The EnerVista suite provides all the tools to monitor the status of the protected asset, maintain the relay, and integrate the information measured into DCS or SCADA monitoring systems. Convenient COMTRADE and sequence of event viewers are an integral part of the 350 set up software and are included to ensure proper protection and system operation.
A 4 line liquid crystal display (LCD) allows visibility under varied lighting conditions. When the keypad and display are not being used, the metering summary page is displayed to show critical metered values.
Viewpoint Monitoring
Viewpoint Monitoring is a simple to use and full featured monitoring and data recording software package for small systems. Viewpoint monitoring provides a complete HMI package with the following functionality: Plug and play device monitoring System single line monitoring and control Annunciator alarm screens
LEDs
The 350 relay has ten LEDs that provide status indication for various conditions of the relay and the system. The LED indications are color coded to indicate the type of event.
3 Series setup software protection summary for viewing a summary of Protection & Control configuration.
276
BUS Vts 52
FEEDER
WYE VT CONNECTION
+ CONTROL - POWER
E5 D5 E6 D6 E7 D7 E8 D8 IA IA IB IB IC IC IG IG E9 D9 E10D10E11D11E12D12 VA V A V B V B V C V C V X V X B1 A1 B2
chassis gnd
+ -
POWER SUPPLY
CURRENT INPUTS
VOLTAGE INPUTS
GROUND BUS
A2 1 TRIP B3
V
C1 52a (C1 #1) C2 52b (C1 #2) C3 INPUT 3 C4 INPUT 4 C5 INPUT 5 C6 INPUT 6 C7 INPUT 7 C8 INPUT 8 C9 INPUT 9 C10 INPUT 10 C11 COMMON C12 CHASSIS GND
52b
DIGITAL INPUTS
A3 B4 A4
52a
TRIP COIL
+ +
TRIP CIRCUIT
2 CLOSE
V
B5 A5 B6 A6 B7 A7 B8 A8
52b
CLOSE COIL
CLOSE CIRCUIT
3 AUXILIARY
4 AUXILIARY
PERSONAL COMPUTER
Front Panel
USB TYPE B
5 AUXILIARY
Rear Pane l
ETHERNET RJ45 mTRJ
COMMUNICATIONS
IRIG-B
4 WIRE ETHERNET
10/100 BASE-T
100 BASE-FX
- +
RS485
COM
- +
OPTIONAL
F2 F1 F5 F4 F3
COM RS485
898728.CDR
Mounting
C
0.200 (5.1 mm)
6.000 0.010 (152.4 mm 0.25 mm) 4.000 0.010 (101.6 mm 0.25 mm)
277
User Interface
SETPOINT GROUP 1, 2: These indicators are continuously on if corresponding group provides settings for protection elements. TRIP: Indicator turns on when relay detects a trip condition. Operates the Trip Relay to open the breaker. ALARM: While relay detects an alarm condition, indicator flashes. PICKUP: Indicator lights steady when any protection feature pickup threshold exceeded. DISPLAY: 4 line text for easy viewing of key data
KEYPAD: Ten button keypad for access to device interrogation and change of settings.
Dimensions
Front Top
7.935
3.960
1.725 6.621
7.795
Rear
Side
6.820
278
Technical Specifications
PHASE/NEUTRAL/GROUND TIME OVERCURRENT (51P/51N/51G) Pickup Level: 0.05 to 20.00 x CT in steps of 0.01 x CT Dropout Level: 97 to 99% of Pickup @ I > 1 x CT Pickup - 0.02 x CT @ I < 1 x CT Curve Shape: ANSI Extremely/Very/Moderately/ Normally Inverse Definite Time (0.05 s base curve) IEC Curve A/B/C/Short IAC Extreme/Very/Inverse/Short User Curve, FlexCurve A/B (programmable curves) Curve Multiplier: 0.05 to 20.00 in steps of 0.01 Reset Time: Instantaneous, Linear Time Delay 3% of expected inverse time or 1 Accuracy: cycle, whichever is greater Level Accuracy: per CT input SENSITIVE GROUND TIME OVERCURRENT (51SG) Pickup Level: 0.005 to 3 x CT in steps of 0.001 x CT Dropout Level: 97 to 99% of Pickup @ I > 0.1 x CT Pickup - 0.002 x CT @ I < 0.1 x CT Curve Shape: ANSI Extremely/Very/Moderately/ Normally Inverse DefiniteTime IEC Curve A/B/C/Short Inverse IAC Extreme/Very/Inverse/Short Inverse User Curve, FlexCurve A/B Curve Multiplier: 0.05 to 20.00 in steps of 0.01 Reset Time: Instantaneous, Linear Time Delay 3% of expected inverse time or 1 Accuracy: cycle, whichever is greater Level Accuracy: per CT input PHASE/NEUTRAL/GROUND NEGATIVE SEQUENCE INSTANTANEOUS OVERCURRENT (50P/50N/50G/50_2) Pickup Level: 0.05 to 20 x CT in steps of 0.01 x CT Dropout Level: 97 to 99% of Pickup @ I > 1 x CT Pickup - 0.02 x CT @ I <1 x CT Time delay: 0.00 to 300.00 sec in steps of 0.01 Operate Time: <30 ms @ 60Hz (I > 2.0 x PKP, No time delay) <35 ms @ 50Hz (I > 2.0 x PKP, No time delay) Time Delay 0 to 1 cycle (Time Delay selected) Accuracy: Level Accuracy: per CT input SENSITIVE GROUND INSTANTANEOUS OVERCURRENT (50SG) Pickup Level: 0.005 to 3 x CT in steps of 0.001 x CT Dropout Level: 97 to 99% of Pickup @ I > 0.1 x CT Pickup - 0.002 x CT @ I < 0.1 x CT Time delay: 0.00 to 300.00 sec in steps of 0.01 <30 ms @ 60Hz (I > 2.0 x PKP, No time Operate Time: delay) <35 ms @ 50Hz (I > 2.0 x PKP, No time delay) Time Delay 0 to 1 cycle (Time Delay selected) Accuracy: Level Accuracy: per CT input GROUND DIRECTIONAL Directionality: Co-existing forward and reverse Operating: Ground Current (Ig) Polarizing Voltage: V0 calculated using phase voltages (VTs must be connected in Wye) - V0 measured from Vaux input. (3V0 provided by an external open delta connection). MTA: From 0 to 359 in steps of 1 Angle Accuracy: 4 Operation Delay: 20 to 30 ms NEUTRAL DIRECTIONAL Directionality: Co-existing forward and reverse Polarizing: Voltage, Current, Dual Polarizing Voltage: V0 calculated using phase voltages (VTs must be connected in Wye) - V0 measured by Vaux input (3V0 provided by an external open delta connection). Polarizing Current: Ig MTA: From 0 to 359 in steps of 1 Angle Accuracy: 4 Operation Delay: 20 to 30 ms PHASE/AUXILIARY UNDERVOLTAGE (27P/27X) Minimum Voltage: Programmable from 0.00 to 1.25 x VT in steps of 0.01 Pickup Level: 0.00 to 1.25 x VT in steps of 0.01 Dropout Level: 101 to 104% of pickup Curve: Definite Time, Inverse Time Time Delay: 0.0 to 600.0 s in steps of 0.1 Operate Time: Time delay 30 ms @ 60Hz (V < 0.85 x PKP) Time delay 40 ms @ 50Hz (V < 0.85 x PKP) Time Delay 3% of expected inverse time or 1 Accuracy: cycle, whichever is greater Level Accuracy: Per voltage input PHASE/AUXILIARY/NEUTRAL/NEG SEQ OVERVOLTAGE (59P/59X/59N/59_2) Minimum Voltage: Programmable from 0.00 to 1.25 x VT in steps of 0.01 Pickup Level: 0.00 to 1.25 x VT in steps of 0.01 Dropout Level: 96 to 99% of pickup Time Delay: 0.0 to 600.0 s in steps of 0.1 Operate Time: Time delay 35 ms @ 60Hz (V > 1.1 x PKP) Time delay 40 ms @ 50Hz (V > 1.1 x PKP) Time Delay 0 to 1 cycle (Time Delay selected) Accuracy: Level Accuracy: Per voltage input UNDERFREQUENCY (81U) Minimum Voltage: 0.00 to 1.25 x VT in steps of 0.01 Pickup Level: 40.00 to 70.00 Hz in steps of 0.01 Dropout Level: Pickup +0.03 Hz Time Delay: 0.0 to 600.0 s in steps of 0.1 Time Delay 0 to 6 cycles (Time Delay selected) Accuracy: Operate Time: Typically 10 cycles @ 0.1Hz/s change Level Accuracy: 0.01 Hz OVERFREQUENCY (81O) Pickup Level: 40.00 to 70.00 Hz in steps of 0.01 Dropout Level: Pickup -0.03 Hz Time Delay: 0.0 to 600.0 s in steps of 0.1 Time Delay 0 to 6 cycles (Time Delay selected) Accuracy: Operate Time: Typically 10 cycles @ 0.1Hz/s change Level Accuracy: 0.01 Hz TRANSIENT RECORDER Buffer size: 3s No. of buffers: 1x192, 3x64, 6x32 No. of channels: 14 Sampling rate: 32 samples per cycle Triggers: Manual Command Contact Input Virtual Input Logic Element Element Pickup/Trip/Dropout/Alarm Data: AC input channels Contact input state Contact output state Virtual input state Logic element state Data storage: RAM - battery backed-up EVENT RECORDER Number of events: Header: Content: 256 relay name, order code, firmware revision event number, date of event, cause of event, per-phase current, ground current , sensitive ground current , neutral current, per-phase voltage (VTs connected in Wye), or phasephase voltages (VTs connected in Delta), system frequency, power, power factor, thermal capacity Retained for 3 days
Data Storage:
Date and time Daylight Saving Time Auto-detect (DC shift or Amplitude Modulated) Amplitude modulated: 1 to 10 V pk-pk DC shift: TTL Input impedance: 40kOhm 10% RTC Accuracy: 1 min / month
LOGIC ELEMENTS Number of logic elements: Trigger source inputs per element: Block inputs per element: Supported operations: Pickup timer: Dropout timer:
8 3 3 AND, OR, NOT, Pickup / Dropout timers 0 to 6000 ms in steps of 1 ms 0 to 6000 ms in steps of 1 ms
BREAKER CONTROL Operation: Asserted Contact Input , Logic Element , Virtual Input , Manual Command Function: Opens / closes the feeder breaker AUTORECLOSE Reclose attempts: Time Delay Accuracy: Elements: BREAKER FAILURE Pickup Level: Dropout Level: Time Delay Accuracy: Level Accuracy: Up to 4 shots 0 to 3 cycles (AR Dead Time selected) Inputs, Outputs, Breaker Status (52 status) 0.05 to 20.00 x CT in steps of 0.01 97 to 98% of pickup 0 to 1 cycle (Timer 1, Timer 2) per CT input
BREAKER TRIP COUNTER Trip Counter Limit 1 to 10000 in steps of 1 (Pickup): COLD LOAD PICKUP BLOCKING Operation: Automatically (current level), or by command (asserted input) Function: Block IOC functions, raise TOC pickup, for selected period of time Time Delay 0 to 1 cycle (block Time) Accuracy: 50 ms (outage time? ?5 min) 1 s (outage time > 5 min) AMBIENT TEMPERATURE High Temperature 20C to 80C in steps of 1C Pickup: Low Temperature -40C to 20C in steps of 1C Pickup: Time Delay: 1 to 60 min in steps of 1 min 50 ms (outage time? ?5 min) 1 s (outage time > 5 min) Temperature Configurable 90 to 98% of pickup Dropout: Temperature 10C Accuracy: Timing Accuracy: 1 second
METERING SPECIFICATIONS Parameter 3-Phase Real Power (MW) 3-Phase Reactive Power (Mvar) 3-Phase Apparent Power (MVA) Power Factor Frequency
Range 3000 MW 3000 Mvar 3000 MVA -0.99 to 1.00 40.00 to 70.00 Hz
279
CONTACT INPUTS Inputs: Selectable thresholds: Recognition time: Debounce time: Continuous current draw: Type: External switch: Maximum input voltage:
8 17, 33, 84, 166 VDC 1/2 cycle 1 to 64 ms, selectable, in steps of 1 ms 2 mA opto-isolated inputs wet contact 300 VDC
TRIP / CLOSE SEAL-IN Relay 1 trip seal-in: 0.00 to 9.99 s in steps of 0.01 Relay 2 close 0.00 to 9.99 s in steps of 0.01 seal-in: HIGH RANGE POWER SUPPLY Nominal: 120 to 240 VAC 125 to 250 VDC Range: 60 to 300 VAC (50 and 60 Hz) 84 to 250 VDC Ride-through time: 35 ms LOW RANGE POWER SUPPLY Nominal: 24 to 48 VDC Range: 20 to 60 VDC ALL RANGES Voltage withstand: 2 highest nominal voltage for 10 ms Power 15 W nominal, 20 W maximum consumption: 20 VA nominal, 28 VA maximum SERIAL RS485 port: Baud rates: Response time: Parity: Maximum Distance: Isolation: Protocol: Opto-coupled up to 115 kbps 1 ms typical None, Odd, Even 1200 m (4000 feet) 2 kV Modbus RTU, DNP 3.0, IEC 60870-5-103
Fast Transient Disturbance: Surge Immunity: Conducted RF Immunity: Power Frequency Immunity: Voltage interruptionand Ripple DC: Radiated & Conducted: Emissions Sinusoidal Vibration: Shock & Bump: Siesmic: Power magnetic Immunity: Pulse Magnetic Immunity: Damped Magnetic Immunity: Voltage Dip & interruption: Damped Oscillatory: Conducted RF Immunity 0-150khz: Voltage Ripple: Ingress Protection: Environmental (Cold): Environmental (Dry heat): Relative Humidity Cyclic: EFT: Damped Oscillatrory: RF Immunity: ESD: Safety: DIMENSIONS Size: Weight:
Class A and B Level 3 & 4 Level 3 Class A & B 15% ripple, 200ms interupts Class A Class 1 Class 1 Class 2 Level 5 Level 4 Level 4 0, 40, 70, 80% dips, 250/ 300 cycle interrupts 2.5KV CM, 1KV DM Level 4 15% ripple IP40 front , IP10 Back -40C 16 hrs 85C 16hrs 6day variant 2
PHASE & GROUND CURRENT INPUTS CT Primary: 1 to 6000 A Range: 0.02 to 20 CT Input type: 1 A or 5 A (must be specified with order) Nominal 50/60 Hz frequency: Burden: <0.1 VA at rated load Accuracy: 1% of reading at 1 CT 3% of reading from 0.2 to 20 CT 20% of reading from 0.02 to 0.19 CT CT withstand: 1 second at 100 rated current 2 seconds at 40 rated current continuous at 3 rated current SENSITIVE GROUND CURRENT INPUT CT Primary: 1 to 600 A Range: 0.002 to 3 CT Input type: 1 A or 5 A (must be specified with order) Nominal 50/60 Hz frequency: Burden: <0.1 VA at rated load Accuracy: 1% of reading at 0.1 CT 3% of reading from 0.02 to 3 CT 20% of reading from 0.002 to 0.019 CT CT withstand: 1 second at 100 rated current 2 seconds at 40 rated current continuous at 3 rated current PHASE/AUX VOLTAGE INPUTS Source VT: 0.12 to 65 kV / 50 to 220 V VT secondary: 50 to 240 V VT ratio: 1 to 5000 in steps of 1 Nominal 50/60 Hz frequency: Accuracy: 1.0% of reading Voltage withstand: 260 VAC continuous FORM-A RELAYS Configuration: Contact material: Operate time: Continuous current: Make and carry for 0.2s: Break (DC inductive, L/R=40 ms): Break (DC resistive): Break (AC inductive): Break (AC resistive): 2 (two) electromechanical silver-alloy <8 ms 10 A 30 A per ANSI C37.90 24 V / 1 A 48 V / 0.5 A A 250 V / 0.2 A 125 V / 0.3
CISPR11 /CISPR22/ IEC 60255-25 IEC 60255-21-1 IEC 60255-21-2 IEC 60255-21-3 IEC 61000-4-8 IEC 61000-4-9 IEC 61000-4-10 IEC 61000-4-11
ETHERNET (COPPER) Modes: 10/100 MB (auto-detect) Connector: RJ-45 Protocol: Modbus TCP/IP, DNP 3.0, IEC 60870-5-104, IEC 61850 GOOSE ETHERNET (FIBER) Fiber type: Wavelength: Connector: Transmit power: Receiver sensitivity: Power budget: Maximum input power: Typical distance: Duplex: Protocol: 100 MB Multi-mode 1300 nm MTRJ -20 dBm -31 dBm 9 dB -11.8 dBm 2 km (1.25 miles) half/full Modbus TCP/IP, DNP 3.0, IEC 60870-5-104, IEC 61850 GOOSE
IEC 61000-4-12 IEC 61000-4-16 IEC 61000-4-17 IEC 60529 IEC 60068-2-1 IEC 60068-2-2 IEC 60068-2-30
USB Standard Compliant with USB 2.0 specification: Data transfer rate: 115 kbps CERTIFICATION CE: North America: ISO: Low voltage directive EN60255-5 / EN60255-27 / EN61010-1 EMC Directive EN60255-26/ EN50263, EN61000-6-2, UL508 cULus UL1053, C22.2.No 14 Manufactured under a registered quality program ISO9001
IEEE/ANSI C37.90.1 4KV, 2.5Khz IEEE/ANSI C37.90.1 2.5KV,1Mhz IEEE/ANSIC37.90.2 IEEE/ANSIC37.90.3 UL508 UL C22.2-14 UL1053 20V/m 80-1Ghz 8KV CD/ 15KV AD e83849 NKCR e83849 NKCR7 e83849 NKCR
24 V / 10 A 48 V / 6 A 125 V / 0.5 A 250 V / 0.3 A 720 VA @ 250 VAC Pilot duty A300 277 VAC / 10 A
FORM-A VOLTAGE MONITOR Applicable voltage: 20 to 250 VDC Trickle current: 1 to 2.5 mA FORM-C RELAYS Configuration: Contact material: Operate time: Continuous current: Make and carry for 0.2s: Break (DC inductive, L/R=40 ms): Break (DC resistive): Break (AC inductive): Break (AC resistive):
5 (five) electromechanical silver-alloy <8 ms 10 A 30 A per ANSI C37.90 24 V / 1 A 48 V / 0.5 A A 250 V / 0.2 A 125 V / 0.3
OPERATING ENVIRONMENT Ambient operating 40C to +60C [-40F to +140F] temperature: Ambient storage / 40C to +85C [-40F to +185F] shipping temperature: Humidity: Operating up to 95% (non condensing) @ 55C (As per IEC 60068-2-30 Variant 2, 6days) Pollution degree: II Overvoltage III category: Ingress Protection: IP40 Front , IP10 back
24 V / 10 A 48 V / 6 A 125 V / 0.5 A 250 V / 0.3 A 720 VA @ 250 VAC Pilot duty A300 277 VAC / 10 A
280
TYPE TESTS Dielectric voltage withstand: Impulse voltage withstand: Damped Oscillatory: Electrostatic Discharge: RF immunity:
2.3KV EN60255-5 IEC 61000-4-18 IEC 60255-22-1 EN61000-4-2/ IEC 60255-22-2 EN61000-4-3/ IEC 60255-22-3 EN61000-4-4/ IEC 60255-22-4 EN61000-4-5/ IEC 60255-22-5 EN61000-4-6/ IEC 60255-22-6 EN61000-4-7/ IEC 60255-22-7 IEC 60255-11 5KV 2.5KV CM, 1KV DM Level 4 Level 3
Ordering
350
Base Unit Language Phase Currents Ground Currents 350 E P1 P5 G1 G5 S1 S5 L H S E Current Protection S E M N C N D M R P Communications SN 1E 2E Case Design Harsh Environment 3E D N H English 1A three phase current inputs 5A three phase current inputs 1A ground current input 5A ground current input 1A sensitive ground current input 5A sensitive ground current input 24 - 48 Vdc 125 - 250 Vdc/120 - 240Vac Standard faceplate (LCD, full menu, actual values and setpoints) with 8 Inputs, 7 Outputs (2 Form A, 5 Form C) --- Only for 350 Standard faceplate (LCD, full menu, actual values and setpoints) with 10 Inputs, 7 Outputs (2 Form A, 5 Form C) Standard Overcurrent Protection - 50P(1), 50G(1), 50N(1), 51P(1), 51G(1), 51N(1) Extended Overcurrent Protection - 49, 50P(2), 50G(2), 50N(2), 51P(1), 51G(1), 51N(1) Advanced overcurrent protection - 49, 50P(2), 50G(2), 50N(2), 51P(1), 51G(1), 51N(1), 50_2 (46) No Selection CLP, 50BF, Autoreclose (79), Lockout (86) No Selection Directional Neutral Overcurrent Protection 67N(1), 67G(1) Voltage Metering Neutral and Ground Directional elements 67N(1), 67G(1) + Voltage Metering Voltage Protection, Neutral and Ground Directional elements - 27P(1), 27X(1), 59P(1), 59N(1), 59X(1), 59_2(1), 81O(2), 81U(2), 67N(1), 67G(1) Standard :Front USB, Rear RS485 : Modbus RTU, DNP3.0, IEC 60870-5-103 Standard + Ethernet (Copper & Fiber - MTRJ) MODBUS TCP/IP, DNP3.0, IEC 60870-5-104 Standard + Ethernet (Copper & Fiber - MTRJ) MODBUS TCP/IP, DNP3.0, IEC 60870-5-104, IEC 61850 GOOSE Standard + Ethernet (Copper & Fiber - MTRJ) MODBUS TCP/IP, DNP3.0, IEC 60870-5-104, IEC 61850 Draw-out Design None Harsh Environment Conformal coating
**
**
**
Description
Control Options
Note: 1) G1/G5 and S1/S5 must match corresponding P1/P5 - there cannot be 5A and 1A mixing
281
110609 - V19