Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Cubicle Bus

Download as pdf or txt
Download as pdf or txt
You are on page 1of 32
At a glance
Powered by AI
This document provides contact information for various Siemens offices across India, including addresses and phone numbers. It also mentions that Siemens offers products for industry such as circuit breakers.

Siemens offers industrial products such as air circuit breakers and other products for industry under their Sentron 3WL brand. They also provide services for product upgradation.

Contact details including addresses, phone numbers and emails are provided for various Siemens offices located across different cities in India. Regions covered include states like Maharashtra, Karnataka, Tamil Nadu, Gujarat and others.

The Intelligent Simplicity

Sentron 3WL
Air Circuit Breaker
Answers for industry.

SENTRON - Intelligent Simplicity


In essence, modularity means: User-friendly ease of planning, multiple use of standard configurations - also, simple management of changes and modification on site

The Art of Intelligent Simplicity - Sentron WL


Circuit Breakers today are no longer simple switching and protecting devices with ON/OFF and trip indications. Users today are looking at circuit breakers as a device, which integrates switching, protection, metering and power management including quality of power from remote locations. Modern power systems are also characterized by the methods used to network circuit breakers - both with each other and with other components. Siemens offers SENTRON WL family, which have a lot more to offer than even the socalled new circuit breaker in the market. In future, it will not only be possible to carry out diagnosis and maintenance procedures remotely on the Internet, but real-time information about system malfunctions and alarm signals will be made available immediately to operating staff through SMS and mobile phones.

This is not a fantasy for the future; in fact its hard reality. This is Sentron. A new generation of circuit breakers from 100 A to 6300 A available in three different sizes with the following advantages.

Intelligent Modularity with Cost Savings: Same internal and external accessories for the entire range reducing inventory cost. Compact in size. A 6300 A 3WL requires only 800mm wide cabinet. Practically no deration till 55 Deg C with the permissible service temperature upto 70 Deg C. A 5000 A 3WL can deliver 5000 Amp even at 70 Deg C. High electrical life reduces the frequency of replacement of contacts. Unique rating plug facility allows a 3200 Amp 3WL to have thermal overload setting as low as 100A. This ensures complete protections even when the system is partially loaded. Integrated CubicleBUS provides unmatched flexibility and cost economic solutions to all panels - metering, protections and annunciations requirements. Sentron stands for complete energy management - solution for continuous energy cost supervision and optimization in short intelligent savings.

Whether for rapid retrofitting, reduced handling or optimal energy managementanybody choosing SENTRON will profit from clear and definite economic

Easy Planning: Sentron WL is available in three frame sizes yet with identical door cutouts for all the frames and at same locations on the breakers to ensure standardization, symmetry and aesthetics in panel design. Software such as 'SIMARIS' designed to support you with evaluation, planning and calculation of the entire system, thus saving considerable time and energy in designing an electrical system. Contact erosion indicator on the main contacts will help to plan shutdown for the contact maintenance. 3 breakers frame size, 3 breaking capacity, single family and modular construction allows optimum selection of breaker. Maximum Safety: Distinct mechanical Ready-to-close indicator is provided as an inherent safety feature. This ensures safe switching ON of ACB and eases the diagnosis. Ready-to-close interlocking will verify the following condition: 3WL is switched OFF Storage spring is charged Undervoltage released is energized Shunt trip not energized Closing coil not energized No external interlocks activated Mechanical reclosing lockout reset

Crank release lever ensures breaker removal from the guide frame only when the contacts are seperated. SAFE LOCK suitable for isolation. Castell key can be removed only when the contacts are seperated. Lockable guide frame on removal of circuit breaker available as standard. Lockable withdrawable circuit breaker to protect against unauthorized removal provided as a standard. High degree of IP protection class upto IP 55 Mechanical reclosing lock out after overload or short-circuit release provided as standard feature. The front cover cannot be removed if the circuit breaker is in closed condition. 3WL confirms to isolation requirement as per DIN EN 60 947 - 2 System Solutions: The Breaker Data Adapter(BDA) with integrated Web-server allows local parameterization, operation and observation of SENTRON circuit breaker. BDA plus provides additional Ethernet interface for remote diagnosis via LAN / WAN. The Switch ES Power software with the same functionality via PROFIBUS - DP and with integrated object manager for integration of the SENTRON circuit breakers into SIMATIC system

Standards:- The Sentron WL Circuit Breakers satisfy:


! IEC 60947 - 2, IS 13947 - 2 ! DIN VDE 0660 Part 101 ! UL 489 / ANSI C 37.13, UL 1066 ! Climate Proof according to DIN IEC 68 Part 30 - 2 ! CE Conformance ! Lloyds Register of shipping

User-friendly and precise: Planning with SENTRON

3 and 4 pole, up to 6300 A fixed - mounted and withdrawable version


Description Microprocessor based electronic over-current release (ETU) During the development of our over- current release we have consistently striven to ensure modularity. The following are just some modules that are simple to retrofit at any time Earth-fault protection module Communication modules Metering function Displays Rating plugs This enables fast local adaptation to new network conditions. At the same time, the ETU are provided with new, innovative functions like:Rating Plug The Rating Plug is a replaceable module that enables users to reduce the rated device current for optimum adaptation to the system; e.g. during startup of a plant section. The Rating Plug should be selected so that it roughly corresponds to the rated current of the system. Switch-selectable I t2or I t characteristic curve for the overload range. The best possible protection for the overall switchgear assembly is achieved by ensuring optimum setting of the release characteristic. To achieve optimum selectivity of the upstream fuses or medium-voltage protective devices, the inclination of the characteristic curve can be switched over in the overload range. Switch-selectable parameters In the event of a sudden change in network conditions e.g. switchover of the transformers to generator operation or shut down of a part of the supply network at the change of shift, SENTRON WL now supports fast adaptation of the required protective parameters to the new circumstances. Two release characteristics (parameter sets) that are independent of one another are stored on the ETUs. The transfer is executed in under 100ms and is initiated by an external signal.
4

Overcurrent release ETU 45B


Mechanical RESET for reclosing lockout
Scroll up

Option: safety lock prevents pressing of reset button after overcurrent release
Option: alphanumeric display Scroll down

Indicators: Over Current release activated Overload alarm Communication Expanded Rated current module

Indicator: fault in over current release


Thermal memory on/off N-conductor protection on/off Setting value N-conductor overload N-conductor overload Transfer of overload characteristic I2 t1I4t
Rotary switch for delay, overload release
Rotary switch for delay, short-circuit release Indicator: cause of release Sealing ring Option: earth-fault module Indicator: earth-fault alarm Rotary switch for delay earth-fault protection Indicator: earth-fault tripped Clear push button

Rotary switch for setting value, overload releases

Rotary switch for setting value, instantaneous short-circuit releases


Rotary switch for setting value, short-circuit protection
Selector for earth-fault protection

Rotary switch for setting value, earth-fault protection


Rotary switch for setting value, earth-fault alarm
Test push button

Test socket Query push button

Rating Plug-in size I 250A 315A 400A 500A 630A 700A 800A 1000A 1250A 1600A size II 250A 315A 400A 500A 630A 700A 800A 1000A 1250A 1600A 2000A 2500A 3200A size III

Sample configuration of an ETU 45B


Manual trip indicator

Text display with 15 inclination and rotatable through 180

Micro-switch for switch selectable overload characteristic curve

1250A 1600A 2000A 2500A 3200A 4000A 5000A 6300A

Rated current module rating plug Earth-fault protection module (retrofittable)

example : 1000A - 3WL -> up to 1000A rating Plug 250A ; Ir setting = 0.4 X 250 = 100A

Application: Cost-effective intelligent allrounder for building and all types of industrial applications- Cubicle BUS integrated. Properties: 1. Adjustable time-lag class for overload protection 2. Short-time delayed short-circuit protection, adjustable from 1.25... 12 x In 3. Instantaneous short-circuit protection adjusting 12 In /Max/Off 4. Replaceable Rating Plug allows instant adaptability to required plant currents, thus ensuring overload protection of 100 A to 6300 A. 5. Switch-selectable characteristic of the overload and short-time delay short-circuit range (current discriminate) for finer selectivity conditioning to downstream fuses or protective devices 6. Thermal memory as restart protection in case of tripped motor circuits

7. Connectable and adjustable neutral conductor protection 8. Modular earth-fault protection, with separately adjustable alarm and trip function 9. Communication interface, metering function (Plus), connection of external modules as option or retrofit option. 10. Optional high-contrast display with viewing angle adjustment 11. Overload indicator 12. Display of cause of trip through LED 13. Option for testing the release 14. Setting of protective functions by means of rotary or slide switch.

Overcurrent release ETU 76B

Mechanical RESET for reclosing lockout

Option: safety lock prevents pressing of reset button after overcurrent release
Graphical display Control keys for setting the release parameters

Indicators: Over Current release activated Overload alarm COMMUNICATION EXPANDED

Indicator: cause of release

Rated current module Option: earth-fault module


Fields for noting setting values Test push button Query push button

Indicator: fault in overcurrent release


Indicator: Earth-fault alarm Earth-fault tripped

Fields for noting setting values Clear push button Test socket

Selection of the overcurrent releases

ETU 76B ETU 45B ETU 27B ETU 25B ETU 15B

Application: The multitalent with graphical display for network analysis CubicleBUS integrated. Properties: As for ETU45B plus the following: 1. Two protective parameter steps that can be stored seperately in the release (switch-selectable through external signal). 2. Overload protection that can be switched off for use with modern operating mechanism. 3. Adjustable lag of the delayed short-circuit protection up to 4000ms. 4. Neutral conductor protection adjustable to In = 2 In . 5. Setting of protective functions by means of control keys or Breaker Data Adapter or through communication interface. 6. Graphical display of all parameters and event/curve characteristics. 7. Storage of events and causes of release for specific error analysis. 8. High-contrast background - lit graphical display with sleep mode.

Short-time delayed short-circuit protection

Instantaneous shortcircuit protection

Overload protection

Communication via Profibus DP/MODBUS

ETU 15B ETU 25B ETU 27B ETU 45B ETU 76B

Available

not available

optional

Freely programmable parameters


9

Protection of neutral conductor

ZSI (zone-selective interlocking)

Metering functions

Ranges / Functions

Earth-fault protection

Selectable parameter sets

LCD graphic

LCD 4 lines

Tripping characteristics Every release type and every setting has its own characteristic. You will find just a small selection of these illustrated below. The characteristics show the respective greatest and smallest setting range of SENTRON WL circuit-breakers with 1000A rated current, 690V rated voltage with various releases. The characteristics show the behavior of the overcurrent release when it is activated by a current already flowing before the release. If the overcurrent release is not activated, the opening time is prolonged up to 15ms, depending on the value of the overcurrent. To determine the total break-times of the circuit-breakers about 15ms must be added to the displayed opening times for the arc duration. The displayed characteristics apply for ambient temperature at the circuitbreaker of -5 to +55 Deg C. The release can be operated at ambient temperatures of -20 to +70 Deg C.

SENTRON WL circuit-breakers with I = 1000 A and ETU 45B or ETU 55B electronic release Inverse-time delayed overload range L 10000

SENTRON WL circuit-breakers with I = 1000 A and ETU 45B or ETU 55B electronic release Instantaneous short-circuit range l
10000

t [s]

1000 100 10

t [s]

1000 100

10 1 .1 .01

1 .1 .01 100 1000 10000 100000

100

1000

10000

100000

I [A]

I [A]

SENTRON WL circuit-breakers with I = 1000 A and ETU 45B or ETU 55B electronic release Earth-fault protection range G
10000

SENTRON WL circuit-breakers with I = 1000 A and ETU 45B or ETU 55B electronic release Short-time delayshort-circuit range S l
10000

t [s]

t [s]

1000 100 10 1 .1 .01 100

1000 100 10 1 .1 .01 100

1000

10000

I [A]
2

100000

1000

10000

100000

I [A]

Inverse-time delayed overload range L I t=constant Overlapping of the Inverse-time delayed overload range L I t and I t Inverse-time delayed overload range L I4 = constant Instantaneous short-circuit range I Earth-fault protection range G Short-time delayed short-circuit range S
2 4

You will find further characteristics in the manual or in the SIMARIS deSign planning and configuring tool Or if you have any further queries, please contact your partner.

10

Cost Saving
Simple, rapid retrofitting Reduced parts variance No derating till 55 C High power rating - low space requirement
O

Easy to Plan
Perfectly Modular Circuit-breakers from 100A to 6300A Simple planning with SIMARIS design

System Solutions
State-of-the-art communication Diagnosis also possible via the Internet Power Management

11

Technical Overview : SENTRON


Size Type
Rated current In at 55 C, at 50/60 Hz Main conductor N-conductor (only with 4 poles) Rated operational voltage Ue at 50/60 Hz Rated insulation voltage Ui Rated impulse withstand voltage Uimp Main conducting paths Auxiliary circuits Control circuits Isolating function according to DIN EN 60 947-2 Utilization category Permissible ambient temperature Operation Storage Permissible load for rear horizontal main contacts up to 55 C up to 60 C up to 70 C
o o o o

I
up to 3WL11 10 A A AC V AC V kV kV kV up to 1000 up to 1000 up to 690 1000 12 4 2.5 yes 3WL 11 12 1250 1250 up to 690 1000 12 4 2.5 yes B
o o

II
3WL 11 16 1600 1600 up to 690 1000 12 4 2.5 yes 3WL 12 08 800 800 up to 690/ 1000 1000 12 4 2.5 yes 3WL 12 10 1000 1000 up to 690/ 1000 1000 12 4 2.5 yes B -25/+70 -40/+70 1600 1600 1490 S 145 105 S 66 50 S 50 -25/+70 -40/+70 800 800 800 S 176 165 S 80 75 S 66 -25/+70 -40/70 1000 1000 1000 / / / / / / / / / / -25/+70 -40/+70 1250 1250 1250 H 220 187 105 H 100 85 50 H 80
-25/+70 -40/+70 1600 1600 1600

3WL 12 12 1250 1250 up to 690/ 1000 1000 12 4 2.5 yes

3WL 12 16

1600 1600 up to 690/ 1000 1000 12 4 2.5 yes

C C A A A

-25/+70 -40/+70 1000 1000 1000 N 121 88 N 55 42 N 50


4)

-25/+70 -40/+70 1250 1250 1210 / / / / / / / / / /

Rated short circuit making capacity lcm (peak) kA

Rating Class 2) upto 500V upto 690V upto 1000V/1150V 3) Rating Class 2) upto 500V upto 690V upto 1000V/1150V 3) Rating Class 2) 1 Sec Rating

Rated service short circuit breaking capacity, lcs (r.m.s) kA (lcs = lcu)

Rated short time withstand current, lcw. kA For 1 Sec at 50/60 Hz Power loss at In with 3-phase symmetrical load Fixed-mounted circuit-breaker Withdrawable circuit-breaker Operating times Make-time Break-time Endurance Mechanical (without maintenance) Mechanical (with maintenance) Electrical (without maintenance) Electrical (with maintenance) Switching frequency 690 V version 3) 1000V/1150V version Minimum interval Between release by overcurrent release and next closing of the circuit-breaker (only with autom mechanical reset of the reclosing lockout) Mounting position

W W ms ms
operating cycles operating cycles operating cycles operating cycles

100 195 35 38 10 000 20 000 10 000 20 000

105 205 35 38 10 000 20 000 10 000 20 000

150 350 35 38 10 000 20 000 10 000 20 000

40 85 35 34 10 000 15 000 75 00 15 000

45 95 35 34 10 000 15 000 75 00 15 000

80 165 35 34 10 000 15 000 75 00 15 000

85 175 35 34 10 000 15 000 75 00 15 000

1/h 1/h ms

60 80

60 80

60 80

60 20 80

60 20 80

60 20 80

60 20 80

NS1-5149

NS1-5150

and/ or

h max = 1 mm

300 300

30

30

NSE00927

Degree of protection Weights 3-pole Fixed-mounted circuit-breaker Withdrawable circuit-breaker Guide frame Fixed-mounted circuit-breaker Withdrawable circuit-breaker Guide frame kg kg kg kg kg kg 43 45 25 50 54 30

upto IP 55 43 45 25
50 54 30

upto IP 55
43 45 25 50 54 30 56 60 31 67 72 37 56 60 31 67 72 37 56 60 31 67 72 37
56 60 31 67 72 37

4-pole

SENTRON WL: An air circuitbreaker family for the complete spectrum of power distribution whether in building infrastructure or industrial applications.
12

WL Air Circuit Breakers


Size Type
Rated current In at 55 C, at 50/60 Hz Main conductor N-conductor (only with 4 poles) Rated operational voltage Ue at 50/60 Hz Rated insulation voltage Ui Rated impulse withstand voltage Uimp Main conducting paths Auxiliary circuits Control circuits Isolating function according to DIN EN 60 947-2 Utilization category Permissible ambient temperature Operation Storage Permissible load for rear horizontal main contacts up to 55o C up to 60o C up to 70o C
o

3WL 12 20
A A AC V AC V kV kV kV

II 3WL 12 25

3WL 12 32

3WL 1240
40003) 40003) up to 690/ 1000 1000 12 4 2.5 yes

3WL 13 40

III 3WL 13 50

3WL 13 63
1)

2000 2000 up to 690/ 1000 1000 12 4 2.5 yes

2500 2500 up to 690/ 1000 1000 12 4 2.5 yes B

3200 3200 up to 690/ 1000 1000 12 4 2.5 yes

4000 4000 up to 690/ 1000 1000 12 4 2.5 yes

5000 5000 up to 690/ 1000 1000 12 4 2.5 yes B -25/+70 -40/+70 5000 5000 5000

6300 6300 up to 690/ 1000 1000 12 4 2.5 yes

o o

C C A A A

-25/+70 -40/+70 2000 2000 2000

-25/+70 -40/+70 2500 2500 2280

-25/+70 -40/+70 3200 3070 2870

-25/+70 -40/+70 3950 3810 3600

-25/+70 -40/+70 4000 4000 4000

-25/+70 -40/70 5920 5810 5500

2) Rated short circuit making capacity lcm (peak) kA Rating Class upto 500V upto 690V upto 1000V/1150V3)

N
145 105 -

/
/ / /

S
176 165 -

/
/ / /

H
220 187 105

220 / 330(3P), 286(4P) 187 / 330(3P), 286(4P) 105 / 154 H 100 85 50 C / / 150(3P), 130(4P) / 150(3P), 130(4P) 70 / C 100

Rated service short circuit breaking capacity, lcs (r.m.s) kA (lcs = lcu)

Rating Class

2)

N
66 50 / / /

S
80 75 -

/
/ / /

H
100 85 50

upto 500V upto 690V 3) upto 1000V/1150V Rating Class 1 Sec Rating
2)

Rated short time withstand current, lcw. KA For 1 Sec at 50/60 Hz Power loss at In with 3-phase symmetrical load Fixed-mounted circuit-breaker Withdrawable circuit-breaker Operating times Make-time Break-time Endurance Mechanical (without maintenance) Mechanical (with maintenance) Electrical (without maintenance) Electrical (with maintenance) Switching frequency 690 V version 1000V/1150V3) version Minimum interval Between release by overcurrent release and next closing of the circuit-breaker (only with autom mechanical reset of the reclosing lockout) Mounting position

N
55 /

S
66

/
/

H
80

H / 100 /

W W ms ms
operating cycles operating cycles operating cycles operating cycles

180 320 35 34 10 000 15 000 75 00 15 000

270 520 35 34 10 000 15 000 7500 15 000

410 710 35 34 10 000 15 000 4000 15 000

750 925 35 34 10 000 15 000 4000 15 000

520 810 35 34 5000 10 000 2000 10 000

630 1050 35 34 5000 10 000 2000 10 000

900 1600 35 34 5000 10 000 2000 10 000

1/h 1/h ms

60 20 80

60 20 80

60 20 80

60 20 80

60 20 80

60 20 80

60 20 80

30

30

30
NS1-5150

30

NS1-5149

and/ or

h max = 1 mm

NSE00927

Degree of protection Weights 3-pole Fixed-mounted circuit-breaker Withdrawable circuit-breaker Guide frame Fixed-mounted circuit-breaker Withdrawable circuit-breaker Guide frame
O

upto IP 55
kg kg kg kg kg kg

upto IP 55 64 68 45 77 82 54 85 121 52 103 146 62 82 88 60 99 106 84 82 88 60 99 106 84 90 96 70 108 108 119

56 60 31 67 72 37

59 63 39 71 76 47

4-pole

* 1) At 40 C * 2) N-Normal; S-Standard; H-High 3) Class C - Very high breaking capacity 4) for 0.5 sec

13

Customised solutions: SENTRON

WL

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25

Draw-Out-Frame Main Terminals Front, Flange, Horizontal, Vertical Position-Indicating Switches Leading Earth Contact Shutters COM 15 PROFIBUS/MODBUS COM 16 module External CubicleBUS Module Closing Coil, Auxiliary Releases Auxiliary Plug-in System Auxiliary Contact Block Door Sealing Frame Interlocking Kit Transparent Cover, Function Block Emergency Stop Pushbutton, Key Operator Motorized Operator Switch Operation Counter Breaker Status Sensor (BSS) Electronic Trip Unit (ETU) Reset Coil Breaker Data Adapter (BDA) Four line LCD Module Earth-Fault Protection Module Rating Plug Module Metering Module Sentron WL Circuit-Breaker

14

with optional accessories


SENTRON WL: superior individual products, integrated into comprehensive power distribution system-to the extent of providing solutions specific to particular industrial sector and infrastructure projects

15

3 and 4 pole, up to 6300A- fixed mounted and withdrawable version


Description CIRCUIT-BREAKERS
(28) (27) (26) (25) (24) (23) (22) (21) (8) (20) (19) (18) (17) (16) (12) (13) (14) (15) (9) (10) (11) (1) (2) (3) (4) (5) (6) (7)

Arc chute Handle ID label Motor switch (optional) or electrical ON (optional) 5) Type label of circuit-breaker 6) Spring charge indicator 7) Mechanical ON button 8) Rated current data 9) Insertion pologramm 10) Operating cycle counter (optional) 11) Charging lever 12) Crank handle 13) Transport shalt for withdrawable unit 14) Equipment label 15) Earth terminal 16) Position indicator 17) Earth fault protection table 18) Crank handle safety lock 19) Mechanical OFF button or emergency OFF mushroom push button (optional) 20) Ready-to-close indicator 21) Contact position indicator 22) Trip indicator (reset button) 23) Locking device Safe OFF (optional) 24) Front panel 25) Terminal strip for auxiliary contacts

1) 2) 3) 4)

Description GUIDE FRAME

(1) (2) (18) (3)

(17) (16)

(4) (5) (6) (7)

(15) (14) (13) (12) (11) (10)

(8)

1) Arc chute cover (optional) 2) Arcing openings 3) Opening for crane hooks 4) Shutter (optional) 5) Locking device (shutter) (optional) 6) Type label for guide frame 7) Disconnecting contact 8) Earthing terminal O14 mm 9) Locking device travel rail 10) Locking device against moving if the cubicle door is open (optional) 11) Door interlock for guide frame (optional) 12) Guide rail 13) Ampere rating coding by factory 14) Sliding contact for circuit-breaker earthing (optional) 15) Option related coding 16) Shutter operating device (optional) 17) Position signal switch (optonal) 18) Sliding contact module for auxiliary conductor (quantity is equipment-dependent)

(9)

16

Description Auxiliary release


Up to two auxiliary releases can be installed at the same time. The following are available: 1 shunt release or 1 undervoltage release or 2 shunt releases or 1 shunt release + 1 undervoltage release. Shunt release The shunt release instantly turns off the circuit-breaker when the working voltage is applied. The shunt release F1 is available in two versions; 5% duty ratio for over excitation and 100% duty ratio for permanentmagnet excitation. This can be used as lock-out against startup. An energy storage device for the shunt release allows the circuit breaker to be turned off after a control voltage failure. Undervoltage release The undervoltage release turns off the circuit breaker when the working voltage falls below a specific value or is not applied. The circuit breaker cannot be switched ON manually or by means of an electrical ON command if the undervoltage release is not given the rated voltage. The under voltage release Y1 is without time lag as standard and the customer can switch between t1 < 80ms and t1 < 200ms. A further version is available : undervoltage release with 0.2 to 3.2 s lag. Signal contact for auxiliary release One signal contact per auxiliary release is available to interrogate the switching positions of the auxiliary release. Closing solenoid Serves to electrically close the circuit breaker by means of a local or remote electrical ON button. Motorized operating mechanism For automatic charging of the stored energy mechanism. Is switched on when the stored energy mechanism is released and the control voltage is available. Automatically switch off after charging. Manual actuation of the storage can function independently. Display message and control elements. Interlocking set The interlocking set is required when the operability of the mechanical ON and OFF buttons need to be adapted to special demands of the switchgear operation by retrofitting various accessories (e.g. Safety locks, access lock-outs preventing tool operation, seals.) Motor switch Knob-operated switch for turning off the motorized operating mechanism. Operating cycle counter A 5-digit operating cycle counter is available with the motorized operating mechanism. The display is incremented by 1 as soon as the stored energy mechanism is fully charged. Resetting the manual trip signal If the circuit breaker has been tripped, this is indicated by the protruding red reset button on the ETU. Actuation of the reset button resets the trip solenoid and the trip signal. If this manual indicator is to be remotely reset, the option is available to equip the reset button with a reset solenoid. With this option, the circuit breaker can be reset both manually and electrically. Automatic reset of the reclosing lockout If the ETU is released the circuit breaker cannot be reclosed until the release has been either electrically or manually reset with the option automatic reset of the reclosing lockout, the circuit breaker is ready-to-close immediately after a release. The reset of the manual trip indicator is not contained in this option. Trip signal switch If the circuit breaker is tripped through overload, shortcircuit or earth fault, this can be indicated by the trip signal switch. This signal switch is available as an optional extra. If the circuit breaker is communication capable, this option is available as standard. Ready-to-close signal contact The SENTRON WL circuit breakers are equipped with a visual ready-to-close facility as standard. The option to transmit this readiness to close over a signal contact is also available. If the circuit breaker is operated through communication, this signal switch is fitted as standard.

17

Locking Device
Locking device in OFF position This function prevents the circuit breaker being closed and fulfils the main switch-characteristics according to EN 60 204 (VDE 0113)- line disconnector. This locking only affects this circuit breaker. After a circuit breaker is replaced, it is no longer possible to prevent it being closed unless the new circuit breaker is also protected against unauthorized closing. To activate the locking device, the circuit breaker must be open. If the circuit breaker is closed, the locking device is blocked. The blocking is only effective if the key is withdrawn. The safety key can only be withdrawn in the OFF position. Locking device for electrical ON Prevents unauthorized electrical closing at the front panel. Mechanical and remote closing are still possible. The blocking is only effective if the key is withdrawn. Locking device for mechanical ON Prevents unauthorized mechanical closing. The mechanical ON button can only be actuated if the key is inserted (key operation). Closing through the electrical ON or remote closing are still possible. The blocking is only effective if the key is withdrawn. Safe OFF switch independent locking device against unauthorized closing. This special function for withdrawable circuit breakers prevents closing, independent of circuit breaker, and fulfils the main switch-characteristics according to EN 60 204 (VDE 0113)- line disconnector. Unauthorized closing is also not possible after replacement of a circuit breaker. To activate the locking, the circuit breaker must be switched off. If the circuit breaker is switched on, the locking device is blocked. The blocking is only effective if the key is withdrawn. The safety key can only be withdrawn in the OFF position. Locking device for crank handle Prevents withdrawal of the crank handle. The circuit breaker is protected against moving. The blocking is only effective if the key is withdrawn. Locking device for mechanical OFF Prevents unauthorized mechanical disconnection at the front panel. The mechanical OFF button can only be actuated if the key is inserted (key operation). Remote disconnection is still possible. The blocking is only effective if the key is withdrawn. Locking device for charging lever The charging lever can be locked with a padlock making it impossible to manually charge the stored energy mechanism. Locking device against resetting the trip indicator A lockable cover prevents the manual resetting of the trip indicator after an overcurrent release. This locking device is delivered together with the option tranparent cover for overcurrent release.

Sealing devices
Sealing cap over electrical ON button The electrical ON button is fitted with a sealing cap as standard. Sealing cap over mechanical ON and OFF button The interlocking set includes blanking caps that can be sealed. Sealing device for overcurrent release The transparent cover can be sealed. The areas of the parameter setting are covered against unauthorized access. Openings enable access to the query and test button. Closing lockout with open cubicle door The readiness to close is mechanically deactivated if the cubicle door is open. The circuit breaker cannot be closed either mechanically or electrically. Transmission of the locking signal by means of the Bowden wire. Locking device against moving if the cubicle door is open for withdrawable circuit-breakers The crank handle is blocked if the cubicle door is open and cannot be withdrawn. It is not possible to move withdrawable circuit breakers. The blocking is only effective if the crank handle is inserted.

18

Rated current coding between circuit-breaker and guide frame

(1)

(4)
NSE01031

(2) (3)
NSE01032

(5)

(1) Guide frame, inside left; inside right are the same (2) Coding bolt on the guide rail in the guide frame (3) Guide rail (4) Withdrawable circuit-breaker right side; left side are the same (5) Coding bolt on guide frame

Interlocking of cubicle door The cubicle door cannot be opened if the - fixed-mounted circuit breaker is closed(transmission of the locking signal by means of Bowden wire) or - if the withdrawable circuit breaker is in connected position. Access locking through the mechanical ON and OFF button The mechanical ON and OFF buttons are protected by a cover that only permits actuation with a tool. These caps are components of the interlocking set. Additional equipment for guide frames Shutter The cover strips of the shutter lock the laminated contacts of the guide frame if the withdrawable circuit breaker is withdrawn so that they fulfil the function of a touch guard. The cover strips can be manually opened with the strip lifter. The cover strips can be fixed in different positions with padlocks and protected from unauthorized manipulation.

Rated current coding between circuit breaker and guide frame Withdrawable circuit breakers and guide frames are equipped with a rated current coding as standard. This ensures that in a guide frame only those circuit breakers can be inserted whose contact strips match the laminated contacts of the guide frame. (see picture above) Option related coding Withdrawable circuit breakers and guide frames can be retrofitted with an option related coding. This permits the unique assignment of circuit breakers and guide frames, taking into account different equipment. If circuit breakers and guide frames do not have the same coding. It is not possible to insert the circuit breaker. Circuit breakers and guide frames, taking into account different equipment. If circuit breakers and guide frames do not have the same coding. It is not possible to insert the circuit breaker. There are 36 selectable coding options.

19

Position of the withdrawable circuit breaker in the guide frame

Position signal contact for guide frame Position signal contacts can be retrofitted to the guide frame. These can be used to analyze the position of the circuit breaker in the guide frame. Mutual mechanical circuit breaker interlocking The module for mutual mechanical interlocking can be implemented for two or three SENTRON WL circuit breakers and is simple to adapt to the respective version. Fixed mounted and withdrawable circuit breakers are compatible and can be implemented together in a single system. This is also possible with circuit breakers 3WT. The circuit breakers can be installed either next to one another or on top of one another, whereby the distance between the circuit breakers is determined only by the length of the Bowden wire. The Bowden wire are available upto a length of 6m. Lockout signal are forwarded over the Bowden wires with withdrawable circuit breakers the interlocking is only effective in connected position. The mechanical service life of Bowden wires is 10000 operating cycles. For the mutual mechanical interlocking of circuit breakers also see the adjacent table. Phase barriers Plant manufacturers can make phase barriers out of insulation material as a protection against internal arcs Guiding grooves are provided at the rear of the fixed-mounted circuit breaker or guide frame.

Representation

Position indicator Main circuit Auxiliary circuit


CONNECT

Cubicle door Open

Shutter Closed

Maintenance position

(2) (1)

Disconnected

Disconnected

TEST

(4)
DISCONN

NSE01033

NSE01037

Disconnected position

CONNECT

(3)
TEST

Disconnected

Disconnected

Closed

Closed

DISCONN

NSE01034

NSE01038

CONNECT

Test position
TEST

Disconnected

Connected Closed

Closed

DISCONN

NSE01035

NSE01039

Connected position

CONNECT

Connected Connected Closed

Open

TEST

DISCONN

NSE01036

NSE01040

(1) Auxiliary circuit (2) Main circuit (3) Cubicle door (4) Shutter Mutual mechanical interlocking of circuit breaker - examples Interlocking of two mutual circuit breakers
G S2

Interlocking of three non- mutual circuit breakers

Interlocking of three mutual circuit breakers

Interlocking of three circuit breakers, two of which are mutual

S1

S1 S2

S3 S1 S2 S3

G S1 S2 S3 S1 S2

G S3

NSE01041

NSE01042

NSE01043

NSE01044

NSE01045

Arc chute cover The arc chute cover is available as an optional features for the guide frame. It serves to protect switchgear parts that are located directly next to the circuit breaker.

20

TOTALLY INTEGRATED POWER BY Siemens

TOTALLY INTEGRATED AUTOMATION BY Siemens

21

Technological leaders amongst the Circuit breakers:


1 2 3 4 5 6 7 8 9 10 11 SENTRON 3VL Circuit Breaker Microprocessor based release with LCD Microprocessor based release COM10 PROFIBUS /COM11 MODBUS module with. ZSI COM20 PROFIBUS /COM21 MODBUS module with. ZSI Breaker Data Adapter (BDA) BDA Plus with Ethernet Interface Browser-capable input & output (e.g notebook) SENTRON 3WL Circuit Breaker COM 15 PROFIBUS / COM 16 MODBUS Module Breaker Status Sensor (BSS)
1) For a MODBUS connection the COM16 module is required 2) For a MODBUS connection the COM21 module is required

12 13 14 15 16 17 18 19 20 21 22
22

Microprocessor based release Metering function Plus ZSI (Zone-Selective Interlocking) module Digital output module as relay contacts Digital output module as relay contacts, configurable Analog output module Digital input module Switch ES Power on PC PLC e.g. SIMATIC S7 Power Management System Communication capable SENTRON Power Monitoring Devices

SENTRON Communication Solution

23

The Cubicle BUS is the internal bus system, providing the interconnection between all the intelligent components within the SENTRON WL (e.g. trip unit, Breaker Status Sensor, metering function, communication module). It also permits the simple connection of external accessory components (CubicleBUS Module, BDA Plus) to the circuit-breaker. It is integrated as standard on all SENTRON WL circuit breakers equipped with ETU45B and above.

External CubicleBUS Module: By means of CubicleBUS, external accessory modules can be connected to the SENTRON WL with minimum wiring. Available modules include: digital output modules, analog output modules, digital input modules as well as ZSI modules for zone-selective interlocking. By using these accessories, one can save the need for similar discrete peripheral modules.

Digital output module with rotary switch 6 binary signals on the breaker status(causes of trip and warning) can be output over this module to external signaling devices (e.g. Light, horn) or used to switch off of other specific plant parts (e.g. Frequency converter ) Digital output modules are available with or without rotart switches. With rotary switch modules, you can choose between two signal blocks each with 6 defined assignment and an additional response delay. All digital output modules are available either as an optocoupler output (NO contact, 150 mA) or a relay output version (change-over, up to 12A). Two module of this type may be connected to a SENTRON WL. Digital output module configurable The configurable output module is available for more powerful solutions. In this case, many events on the CubicleBUS can be directly switched to one of the six available outputs, or three of the outputs can be assigned up to six events, i.e. Up to six events can be applied to a single physical output with an OR logic operation. The configuration is executed either with BDA/BDA Plus or Switch ES Power. As with the output modules with rotary switch, an optocoupler and a relay variant are available. Only one module of this type can be implemented through SENTRON WL. Analog output module The analog output module can be used to output the following measured values of the circuit breaker to analog display devices on the cubicle door Il1, IL2, IL3, IN or UL12, UL23 UL31, ULIN or Pl1, PL2, PL3, Stot or COS 1,COS 2 COS 3, I% or favg, ULLavg, Ptot, COS avg

Four 4-20-mA/0-10V interfaces are available for this purpose. The measured values to be output are selected with a rotary switch. This analog output module means there is no need for additional transformers requiring conventional installation/wiring in the main bus. Two modules of this type may be connected to a SENTRON WL. Digital input module The digital input module supports connection of 6 additional binary signals (24V DC) within the circuit breaker environment to the system. This enables, for example, the status signaling of a switch disconnector or of a cubicle door to be transmitted to PROFIBUS-DP. With the digital input module on the Cubicle BUS, it is also possible to automatically switch the two different protective parameter set held in the ETU 55B. And ETU- 76B releases. This allows, among other things, the automatic changing of the parameters of a tie switch in the event of a power supply failure. One module each of this type can be implemented for the input of the six digital signals and for the automatic switchover of the parameters. ZSI module If Siemens circuit-breakers are arranged in several levels and minimal delays are desired, it is advisable to use the ZSI module. The circuit breakers are interconnected by these modules. In the event of a short-circuit all circuit breakers communicate to determine and isolate the exact short-circuit location. This way only the next upstream circuit breaker line energy flow direction will be opened.

24

COM15 / COM16 By means of the PROFIBUS module COM15 or MODBUS module COM16 the circuit breakers can be connected directly to the PROFIBUS-DP or Modbus network. The COM modules support the innovative DPV1functions. This guarantee the simplest commissioning and diagnosis of the circuit-breaker as well as facilitates optimal visualization of the data.

Metering Function PLUS: The integrated metering function can be used with all trip units, equipped with CubicleBUS interface. It is an interesting alternative to external multifunction metering devices. Measured values include currents, voltages, powers, energy, cos o and frequency. The data can be shown on the display of the overcurrent releases, transmitted to the PROFIBUS-DP through the COM15(or MODBUS through COM16) and transferred to the outputs external CubicleBUS modules.
Measured parameters Currents I L1, IL2, IL 3, IN, Ig Line Voltages VL12,VL23,VL31 Phase Volatage VL1N, VL2N, VL3N Present average of line voltages V avg Apparent Power SL1,SL2,SL3 Total apparent power Active power PL1, PL2,PL3 Total active power Total reactive power Reactive power QL1, QL2,QL3 Power factor Cos 1, Cos 2, Cos 3 Power factor total Long term average of currents Il1, Il2, Il3 Long term average of 3-phase current Long term average of active power in L1, L2, L3. Long term average of active power 3 phase. Long term average of apparent power in L1, L2, L3 and Total apparent power Long term average of reactive power 3 phase. Energy consumed Energy delivered Reactive energy consumed Reactive energy delivered Frequency Range 30 .. 8000 A 15 130V and 130 . 1150 V 10.75V and 75.700 V 10.75V and 75 700 V 13.8000 kVA 13..24000kVA -8000 .+ 8000 kW -24000 . + 24000 kW -20000 .... + 20000 kVar -6400 .. +6400 kVar -0.6 . 1 . +0.6 -0.6 . 1 . +0.6 30 . 8000 A 30 . 8000 A 13 . 8000 kW 13 . 8000 kW 13 . 8000 kVA - 8000 + 8000 kVar 1 10000 MWh 1 10000 MWh 1.. 10000 MVarh 1.. 10000 Mvarh 15 40 Hz 40 ---- 70 Hz 70 ---- 440 Hz 2 . 100% 2 .. 150% Accuracy + 1% of measurement range. + 1% of measurement range. + 1% of measurement range. + 1% of measurement range. + 2% of measurement range. + 2% of measurement range. + 2% of apparent power ( cos > 0.6) + 2% of apparent power ( cos > 0.6) + 4% of apparent power + 2% of apparent power . + 4% + 4% + 1% of measurement range. + 1% of measurement range. + 2% of apparent power ( cos > 0.6) + 2% of measurement range. + 2% of measurement range. + 2% of apparent power . + 2% + 2% + 2% + 2% + 0.1 Hz + 2% of measurement range upto 29th harmonic + 1% of displayed value.

Distortion factor of current and voltage Phase unbalance of current and voltage

25

Extended Protective functions: The Metering Function PLUS is used to implement extended protective functions beyond the functionality of the overcurrent releases. If one of these parameters exceeds or falls below its default settings, the overcurrent release is tripped if the set event persists longer than the delay time.

Parameters Under voltage pickup Over voltage pickup Active power in normal direction Active power in reverse direction Overfrequency pickup Under frequency pickup Phase current unbalnce pickup Phase voltage unbalnce pickup Phase rotation Pickup THD current Pickup THD volatge

Range 100 . 1100 V 200 1200 V 13 . 4000 kW 13 . 4000 kW 40 70 Hz 40 .70 Hz 5. 50% 5.50% 5 ..50% 5 ..50%

Delay 1. 15 s 1..15 s 2 .15 s 2 .15 s 1.15 s 1.15 s 1.15 s 1.15 s 5 .15 s 5 .15 s

Setpoints: The metering function PLUS provides Setpoint Function for automatic monitoring of operating conditions and generating warnings on violation to set threshold values. These can be communicated on the CubicleBUS and transferred via COM15. Please Note: violation of setpoint values never sends tripping signal to ETU.

Parameters Phase overcurrent grond overcurrent neutral overcurrent phase current unbalance current demand under voltage phase voltage unbalance over voltage over power in normal direction kW reverse kW demand kVA demand kVAR demand KVAR consumed KVA over frequency under frequency under power factors over power factor current THD voltage THD crest factor form factor

Range 30 . 10000 A 30 . 10000 A 30 . 10000 A 5 ..50% 30 10000 A 15 1200 V 5 . 50% 15 .. 1200 V 13 10000 kW 13 10000 kW 13 . 10000 kW 13 . 10000 kVA 13 . 10000 kVar 13 . 10000 kVAR 13 . 10000 kVA 40 . 70 Hz 40 .. 70 Hz 0 + 0.99 0 - 0.99 5 . 50% 5 50% 1.3.000 1.3.000

Delay 1 .. 255 s 1 .. 255 s 1 .. 255 s 1 .. 255 s 1 .. 255 s 1 .. 255 s 1 .. 255 s 1 .. 255 s 1 .. 255 s 1 .. 255 s 1 .. 255 s 1 .. 255 s 1 .. 255 s 1 .. 255 s 1 .. 255 s 1 .. 255 s 1 .. 255 s 1 .. 255 s 1 .. 255 s 5 255 s 5 255 s 1 .. 255 s 1 .. 255 s

26

Waveform Memories: The metering function Plus offers two additional functions: Two independent waveform memories. Harmonic analysis. The two independent waveform memories can be used to analyze the current and voltages values at the time of the event.

If the waveform memories are programmed to "recording" (standard setting), there is continuous recording until a previously defined event occurs. Then, the recording is stopped, and the current or voltage waveforms at the time of the event can be observed through a visual display (graphical LCD, laptop or PC). The time window is one second; the resolution is 1649 values/second.

The values that can be selected for one of the waveform memories are:

Currents Voltages

I L1, I L 2 , I L 3, I L N , I g UL1; UL2: Ul3

The waveform memories can also be started or stopped individually through the communications channels (PROFIBUS-DP, MODBUS and Cubicle BUS).

27

Breaker Data Adapter BDA: The BDA is the first circuit breaker parameterisation device with integrated web server for the local programming, operation and monitoring of the SENTRON WL and SENTRON VL. The data may be read out on any output device with browser capabilities(e.g. Notebook), without the need for special software. The only system requirement for the input / output device is a standard browser with JAVA2 virtual machine. Once the BDA is connected to the circuit breaker, the browser is filled with Web pages from BDA and the data of the circuit breaker as shown in the following pictures. In addition, the BDAPlus incorporates an Ethernet interface for direct connection to the Ethernet/Intranet/Internet. Switch ES Power: By means of the Switch ES Power software, the SENTRON WL and SENTRON VL circuit breakers can be parameterized, operated and monitored via PROFIBUS-DP. Operational philosophy of switches has been harmonized with that of the BDA. An object manager ensures complete integration into the SIMATIC world. Thus, SENTRON becomes an important component in Totally Integrated Automation(TIA). Power Management: SENTRON circuit breakers can be easily integrated into Power Management Systems. This facilitates efficient diagnosis, alarm, maintenance, cost center and load management. SENTRON circuit breakers play a key role in solutions provided by Totally Integrated Power(TIP).

Breaker Data Adapter - diagnostics


Cubicle BUS
SENTRON WL

Notebook

SENTRON VL Modem

Modem
You can use modems to extend the serial connection from the notebook to the BDA to enable the circuit breaker data to be accessed irrespective of your geographical location

28

Data that can be transmitted using COM15 / COM16 or the breaker data adapter

BSS

BDA

BSS

COM15 / COM16

Transmittable circuit breaker data

Order code (Order no. Of circuit breaker + -Z ) Order no.


Application options
Transmission of circuit breaker data to PROFIBUS-DP or Modbus - TCP / IP Network and Integration in higher-level visualization system possible e.g. In PCS7 Power Management Systems, WinCC (Incl. Add Ons, such as SMS radio server) Transmission of circuit breaker data and software (i.e. HTML pages Incl. Data) to local output device or remotely controlled via the Ethernet/Intranet/Internet (no Integration option in higher-level visualization systems) e.g. for monitoring diagnostics, maintenance and configuration of individual circuit breaker Use of the functionality of all CubicleBUS modules E.g. Programming of the configurable digital output modules, status interrogation of digital input modules diagnostics, testing

F01 +BDA/BDA Plus order no. F02/F12

Transmittable circuit breaker data without integrated metering function


Device Identification: Communication address, circuit breaker order no., Circuit breaker characteristic data (Size no. Of poles, rated current module etc.) ID numbers, release type, free text for equipment identifier and comments Operating states: Closed / open signal spring store mechanism, tripped, readiness to close, Circuit breaker position (connected, test, disconnected and absent) for withdrawable circuit-breakers, PROFIBUS write protection on/off, free user input Control commands Closed / open circuit breakers, enable/disable free user output Reset trip signal Clear event and trip log Reset the min/max measured values, reset maintenance information History Readout of event log, readout of trip log Maintenance Information Number of L, S, I releases and total, contact erosion Number of switch operations under load and total operating hours Event signaling Trip signal with identificatio of the current casuing the trip Alarm signaling (e.g. Overload) with incoming/outgoing information All named event signaling with time stamp Configuration of protective functions Readout of protective function parameters Change the settings of the protective function parameters through communication Parameter set changeover option (set A to set B) Measured values Phase currents, each with min/max, value Temperature in the circuit breaker with min/max. value Temperature in the cubicle with min/max, value All named measured values with time stamp

1)

1) 1) 1) 1)

1)

1)

2)

2)

* 1) Possible in connections with the COM15 / COM16 (Bus connection not required)

Module

* 2) Possible with ETU 76B


Additional transmittable circuit breaker data with integrated metering functions as mentioned on page 24, 25 & 26

29

Advantages through Siemens SENTRON Communication:

Startup and Configuration: PROFIBUS-DP enables faster and more reliable connections than conventional point-to-point wiring. (Option with MODBUS also) Minimum plant down times for necessary expansion Simple startup test Transparent startup process with good documentation options Fast and reliable local configuration via PROFIBUS-DP or MODBUS or the Ethernet / Intranet / Internet with intelligent configuration software. Operator Control and Monitoring: Increase transparency in power distribution through transmission of current status information, alarm signals and set point monitoring. Fault management enables a fast response when leaving the normal state. Important message (e.g. trip signal and reasons) can be transmitted by SMS to the cell phone of the plant personnel. Options for the central readout of parameters and their automatic transmission to interchangeable circuit breakers minimizes fault liability and shortens down times. Effective diagnostics management e.g. through determinations of the precise cause of fault and recording of the phase current. Remote control of the circuit breaker enables both the manual and automatic switching on and off of plant parts. Power Management: The balancing of load peaks and troughs allows the realization of energy imports costs. Efficient load management enables the demand-orientated switching. Analysis of the archived power values (output curves) enables creation of a power consumption profile. This can be the basis for future power procurement. The quality of energy (harmonics, flickers) can be logged and documented. This enables effective power quality management. Cost center management makes power consumption more transparent for commercial analysis. Cost can be clearly assigned and optimized. Maintenance and Service: Information for preventive maintenance (e.g. number of switching operations, operating hours, contact erosion estimation) enables timely and calculated planning of necessary maintenance work. This reduces the risk of costly damage to sensitive plant parts. The central control of maintenance work and the ability to SMS key information considerably reduce costs for maintenance and service.

30

The two available waveform buffer enable currents and voltages to be recorded on an event controlled basis.

31

Your partners
Sales offices:
Ahmedabad
3rd Floor, Prerna Arbour Girish Cold Drinks Cross Roads, Off. C. G. Road Ahmedabad - 380009 ( : +91 79 40207600 Fax: +91 79 40207699

Chennai
4, Mahatma Gandhi Road, Chennai - 600034 ( : +91 44 28334000 Fax: +91 44 28334088

Kolkata
43 Shanti Palli, R B Connector Eastern Metropolitan Bypass, Kolkata - 700042 ( : +91 33 24449000, 24428641-47 Fax: +91 33 24449010 / 13

Nagpur
5th Floor, Landmark Building, Ramdas Peth Nagpur - 440010 ( : +91 712 6633000 Fax: +91 712 6633111

Coimbatore
7th Floor, East Wing, Global Towers 1057, Avinashi Road, Coimbatore - 641018 ( : +91 422 4336300 Fax: +91 422 4336310

Lucknow
28/45, Ashok Marg, Opposite Indira Bhawan Lucknow - 226001 ( : +91 522 4031022, 4031000 Fax : +91 522 4031019

New Delhi
4A, Ring Road, I.P. Estate, New Delhi - 110002 ( : +91 11 42995000-09 Fax: +91 11 42995030

Bangalore
1st Floor, Jyothimahal, #49, St. Marks Road Bangalore - 560001 ( : +91 80 22042000 Fax: +91 80 22224131

Hyderabad
5-9-19, Lakshmi Narsinh Estate, 4th Floor Secretariat Road, Opp. Secretariat, Saifabad Hyderabad - 500004 ( : +91 40 23482500 Fax: +91 40 23243145

Pune
Tower B / 701 - 705, ICC Trade Tower 403A, Senapati Bapat Road, Pune - 411016 ( 6000 : +91 20 2570 Fax: +91 20 2570 6060

Mumbai
130, Pandurang Budhkar Marg, Worli Mumbai - 400018 ( : +91 22 24987000-02 Fax: +91 22 24987312

Chandigarh
SCO 189 - 191, 3rd Floor, Sector 17C Chandigarh - 160017 ( : +91 172 4690300 Fax: +91 172 4690399

Territory managers :
Aurangabad
A9, Yogeshwari Vrundavan Nr. Malhar Chowk, Garkheda Parisar, Prema Nagar Aurangabad - 431210, Maharashtra Mobile: +91 9766316446 E-mail: santosh.rajhans@siemens.com

Faridabad
House No 237, Sector-B Faridabad - 121006, Haryana Mobile: +91 987396350 E-mail: ramit.mehra@siemens.com

Kolhapur
B-7, Mahagaonkar Complex 1147/E, Rajaram Road, Opp. Kamala College Kolhapur - 416001, Maharashtra ( : +91 231 2536626 Mobile: +91 9822558876 E-mail: amol.pandit@siemens.com

Rourkela
T-15, Civil Town, Rourkela - 769004, Orissa ( : +91 661 2400880 Mobile: +91 9437041724 E-mail: sanjoy.ganguly@siemens.com

Gurgaon
117-C, First Floor, Sector-30, Behind Jalvayu Vihar Gurgaon - 122001, Haryana Mobile: +91 9971091588 E-mail: siemens.ggn@gmail.com

Salem
3/25 Santosh Nagar, PACB Backside Chinnathirupathi, Salem - 636008, Tamilnadu Mobile: +91 9894617772 E-mail: rubengerald@siemens.com

Bareilly
Bareilly - 243001, Uttar Pradesh Mobile: +91 9415012500 E-mail: saket.dwivedi@siemens.com Mobile: +91 9897070133 E-mail: naveen.khare@siemens.com

Kota
48, Model Town, Khedli Phatak Kota - 324002, Rajasthan Mobile: +91 9784842605 E-mail: ajit.parashar@siemens.com

Guwahati
G1, Hill View Apartment, Navagraha Path Chenikuthi Hill Side, Guwahati - 781003, Assam ( : +91 361 2663988 Mobile: +91 9864037562 E-mail: sourav.bhattacharya@siemens.com Mobile: +91 9864110684 E-mail: biplab.datta@siemens.com

Sambalpur
Pradhan Para, Near Jamkani Mandir Beside LIC Div Off, Ainthapalli Sambalpur - 768004, Orissa ( : +91 663 2541258 Mobile: +91 9438529778 E-mail: samir.chaintak@siemens.com

Baroda
1st Floor, Vaniiya Bhavan, Race Course Road Baroda - 390007, Gujarat ( : +91 265 2325810/12, 6692110 Mobile: +91 9825506963 E-mail: ankur.chokshi@siemens.com

Ludhiana
H.No 3746, First Floor, Sector 32-A Chandigarh Road, Ludhiana - 141010, Punjab Mobile: +91 9872317702 E-mail: rajeev.kapoor@siemens.com

Ludhiana
H.No 92, Lajpat Nagar, Near Bus Stand Ludhiana - 141010, Punjab ( : +91 161 2770574 Mobile: +91 9815502480 E-mail: rohit.jagga@siemens.com

Surat
59, Ground Floor, Shreejinagar Part-1 Dhabholi Char Rasta, Ved Road, Katagram Surat - 395004, Gujarat Mobile: +91 9925001779 E-mail: chandrakant.keshrani@siemens.com

Belgaum
H.No.713, Narvekar Lane, Shahpur Belgaum - 590003, Karnataka ( & Fax: +91 831 2495156 Mobile: +91 9740277991 E-mail: anand.gawade@siemens.com

Hardwar
758, 1st Floor, Model Colony, Awas Vikas, Jwalapur Hardwar - 249407, Uttarakhand Mobile: +91 9897070133 Fax: +91 1334 265491 E-mail: naveen.khare@siemens.com

Madurai
8/12, Ground Floor, Sakhti Vellammal Street SS Colony, Madurai - 625010, Tamilnadu Mobile : +91 9894617780 E-mail: mahendiran.murugan@siemens.com

Tiruchirappali
T3, 3rd Floor, Vishranthi Daffodils Apartments Old Friends Eye Hospital, Puthur Tiruchirappali - 620017, Tamilnadu ( & Fax: +91 431 4030390 Mobile: +91 9444911221 E-mail: akhilesh.nair@siemens.com

Bhilai
C/o Mr. S.H Siddiqui Sector-1, Street-9, Quarter No 1A Bhilai - 490001, Chhattisgarh Mobile: +91 9826127525 E-mail: sandeep.barde@siemens.com

Indore
Indore - 452001, Madhya Pradesh Mobile: +91 9823011883 E-mail: vineet.saxsena@siemens.com

Jaipur
6, Park Street, Opp Pink City Petrol Pump, M.I.Road Jaipur - 302006, Rajasthan ( : +91 141 2370274 / 2377956 Fax: +91 141 2370482 Mobile: +91 9829244313 E-mail: peeyush.gupta@siemens.com

Nashik
Flat No 2, Shivam Park, Rajiv Nagar Rane Nagar, Nasik-Mumbai Highway Nashik - 422009, Maharashtra Mobile: +91 9822193204 E-mail: kiran.vaidya@siemens.com

Bhubaneswar
109, Harapriya Apartment, Vivekananda Marg Bhubaneswar - 751002, Orissa ( : +91 674 2430734 Mobile: +91 9937009749 E-mail: anirban.aditya@siemens.com Mobile: +91 9937097504 E-mail: sumit.sengupta@siemens.com

Trivandrum
Sonu, TC9/2082, 5, Thamarakulam Lane Sathamangalam, Trivandrum - 695010, Kerala Mobile: +91 9895979604 E-mail: jonsa-82@yahoo.com

Pondicherry
32, Second Floor, St. Theresa Street Pondicherry - 605001 ( : +91 413 4500101 Mobile: +91 9840472727 E-mail: elankumarak.pandian@siemens.com

Jalandar
H.No 448R, First Floor, Pushpa Niwas Near Geeta Mandir, Model Town Jalandar - 144001, Punjab Mobile: +91 9779194445 E-mail: sunil.singla@siemens.com

Udaipur
303, Oasis Park, PP Singhal Marg, Ambavgarh Udaipur - 313001, Rajasthan ( & Fax: +91 294 2430345 Mobile: +91 9829039120 E-mail: ankur.singh@siemens.com

Calicut
Dist : Kozhikode, Calicut - 673001, Kerala Mobile: +91 9895052944 E-mail: sreekanth.p@siemens.com

Raipur
Flat No.103, First Floor, Block B, Shilp Enclave Near LAS Colony, Shankar Nagar Raipur - 492007, Chhattisgarh Mobile: +91 9425057945 E-mail: brajesh.rathor@siemens.com

Jamshedpur
823, Udaigiri, Vijaya Heritage, Uliyan, Kadma Jamshedpur - 831005, Jharkhand ( : +91 657 6451637 Mobile: +91 9934311352 E-mail: shaibal.parial@siemens.com

Vapi
Flat No. 302, Samrajya IV, Royal Residency Charwada Road, Vapi - 396195, Gujarat ( : +91 260 6451156 Mobile: +91 9825147957 E-mail: siemens_vapi@sancharnet.in

Cochin
KG Oxford Busienss Centre 39/4609, Third Floor, SreekandathRoad, Ravipuram Cochin - 682016, Kerala ( : +91 484 4028611, 22 Fax: +91 484 2380201 Mobile: +91 9744511109 E-mail: sajeen.s@siemens.com

Rajkot
D-3 Aalap Century, University Road Rajkot - 360005, Gujarat Mobile: +91 9825506962 E-mail: bhushan.sawant@siemens.com

Jodhpur
371, Gauri House, Kamala Nehru Nagar Near SBI Bank, Jodhpur - 342008, Rajasthan Mobile: +91 9828327200 E-mail: naveen.sahariya@siemens.com

Vijayawada
G-2,Shreya Tower, Moghalrajapuram Near Jammichettu Centre Vijayawada - 520010, Andhra Pradesh ( : +91 866 6629933 Mobile: +91 9866463639 E-mail: santosh.p@siemens.com

Deharadun
122, Vihar Lane No 1, Ajabpur Kalan Deharadun - 248001, Uttaranchal Mobile: +91 9760033117 E-mail: manish.bajpai@siemens.com

Ranchi
H-1/187, Harmu Housing Colony, Harmu Ranchi - 834002, Jharkhand Mobile: +91 9234610953 E-mail: sourav.dasgupta@siemens.com

Kanpur
106, Agarwal Aparment Near Hari Har Dham Mandir, Shyam Nagar Kanpur - 208013, Uttar Pradesh ( & Fax: +91 512 2423348 Mobile: +91 9839102434 E-mail: atul.shukla@siemens.com

Visakhapatanam
84, Mount Moriah Residency, Waltair Uplands Visakhapatanam - 530003, Andhra Pradesh ( : +91 891 2712535 Mobile: +91 9849212555 E-mail: siemensvaizag@rediffmail.com

Durgapur
4/6, Matangini Hazra Bithi Ground Floor, City center Durgapur - 713216, West Bengal ( : +91 343 2605286 Mobile: +91 9830185007 E-mail: sourav.paul@siemens.com

Renukoot
Above ICICI Prudentail Office, Patel Nagar Murdhawa, Dist-Sonebhadra Renukoot - 231217, Uttar Pradesh Mobile: +91 9838007897 E-mail: siemens_upeast@sify.com

Siemens Ltd., Industry Sector LV Control & Distribution Products Thane Belapur Road, Thane - 400601 Fax: +91 22 27623729 E-mail: lvsgr-mktg.india@siemens.com

Order No.: 102276646 SGR-01-115-023


(This replaces SGR-01-115-008)

www.siemens.com/industry

Customer Care Toll free no. 1800 220 987 Email: adscs.india@siemens.com

Product upgradation is a continuous process. Hence, data in this flyer is subject to change without prior notice. For the latest information, please get in touch with our Sales Offices.

You might also like