Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

MT174 TD v1 - 2 Ang PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 36

Energy Measurement and Management

MT174
Three-Phase Static Electricity
Multi Tariff Meter
with Maximum Demand Indicator
and Load-profile

Technical Description
Version 1.2, 18.08.2011

Index:
MT174 - Electronic three-phase time-of-use 2.5.2.1. Meter test mode .......................... 13
electricity meters ........................................... 3 2.5.3. Signal and alarm flags ............................... 13
MT174 meter properties: ......................................... 4 2.5.3.1. Deleting alarm flags .................... 14
1. Meter appearance .......................................... 6 2.5.4. No-power reading option ........................... 14
1.1. Meter case....................................................... 6 2.6. LEDs .............................................................. 14
1.2. Terminal block ................................................. 6 2.7. Push-buttons .................................................. 14
1.2.1. Terminal block for direct connected meters 6 2.7.1. Display testing ........................................... 15
1.2.2. Terminal block of CT operated meters........ 7 2.7.2. Manual data display................................... 15
1.2.3. Auxiliary terminals ....................................... 7 2.7.3. Manual meter billing reset ......................... 15
1.3. Over-all dimensions......................................... 8 2.7.4. Meter setting mode .................................... 16
1.4. Meter sealing places ....................................... 8 2.7.4.1. Setting RTC time by pushbuttons16
2. Meter configuration ....................................... 9 2.7.4.2. Setting RTC date by pushbuttons
2.1. Metering elements ........................................... 9 16
2.2. Power supply stage ......................................... 9 2.7.4.3. Setting Baud rates by pushbuttons
2.3. Microcontroller ................................................. 9 17
2.3.1. Load-profile recorder ................................... 9 2.7.4.4. Meter parameters setting mode .. 17
2.3.2. Log-book ................................................... 10 2.7.4.5. Deleting alarm flags by
2.3.3. Billing results keeping ............................... 10 pushbuttons ................................................... 17
2.4. Real-time clock .............................................. 11 2.7.5. Meter testing mode .................................... 17
2.4.1. RTC back-up power supply....................... 11 2.7.6. Driving menus with pushbuttons................ 18
2.4.2. RTC accuracy testing ................................ 11 2.7.7. Flowchart of time setting with pushbuttons19
2.4.3. Time-of-use registration ............................ 11 2.8. Communication channels .............................. 20
2.4.3.1. Sleeping (passive) tariff program 11 2.8.1. Optical port ................................................ 20
2.4.3.2. Holidays ...................................... 12 2.8.2. RS485 interface ......................................... 20
2.4.4. Maximum demand measurement ............. 12 2.8.3. Data downloaded via optical port .............. 20
2.4.5. Meter billing reset ...................................... 12 2.8.4. Fatal error register ..................................... 20
2.5. LCD ............................................................... 12 2.8.5. Communication protocol ............................ 21
2.5.1. LCD testing ............................................... 13 2.9. Inputs and outputs ......................................... 21
2.5.2. Data display .............................................. 13 2.9.1. Tariff input .................................................. 21
Energy Measurement and Management

2.9.2. Pulse output............................................... 21 3.11. SEP2 MeterView software ............................ 24


2.9.3. Tariff output ............................................... 22 4. Meter installation ......................................... 24
3. Antifraud protection .................................... 22 5. Tools for meter managing .......................... 25
3.1. Meter seals .................................................... 22 6. Meter maintenance ...................................... 25
3.2. Always positive registration ........................... 22 7. Meter connection diagram ......................... 25
3.3. Passwords ..................................................... 22 8. Technical data ............................................. 26
3.4. Parameters change protected with a sealed 9. Meter type designation ............................... 28
pushbutton ..................................................... 23 10. Appendix I: MT174 meter in photovoltaic
3.5. Detectors of opening meter cover and terminal (PV) installations ......................................... 29
cover .............................................................. 23 11. Appendix II: EDIS codes, data stored in
3.6. Detector of external magnetic field ................ 23 registers, sequences, historical values .... 30
3.7. Fraud event counters ..................................... 23
3.8. Registers of elapsed time .............................. 23
3.9. Registers of fraud energy .............................. 24
3.10. Log-books ...................................................... 24
MT174 - Electronic three-phase electricity meters
with maximum demand and LP

MT174 - Electronic three-phase


time-of-use electricity meters
The MT174 electronic three-phase meters are The meter software complies with WELMEC 7.2
designed for measurement and registration of Issue 1 Software Guide (Measuring Instruments
active, reactive and apparent energy and Directive 2004/22/EC).
demand in three-phase four-wire networks.
They can be connected directly to the network. The MT174 meters are designed for mechanical
The metering and technical properties of the environment M1, electromagnetic environment
meters comply with the EN 50470-1 and -3 E2 and climatic environment -40C ... +60C,
European standards for active energy meters, relative humidity 95% non-condensing, closed
classes A and B, as well as with the IEC 62053- location. The meters can be installed in any
21 and IEC 62052-11 international standards for position.
electronic meters of active energy for classes 1
and 2, and optionally with the IEC 62053-23 The meters are designed and manufactured in
international standard for electronic meters of compliance with the ISO 9001 (2000) standard.
reactive energy for classes 2 and 3.

A built-in time-switch complies with the IEC


62054-21 and IEC 62052-21 standards. It enables
energy registration in up to four tariffs.

3 of 36
MT174 - Electronic three-phase electricity meters
with maximum demand and LP

MT174 meter properties:


Meter accuracy Optional tariff inputs for external tariff
Class A or B in compliance with EN 50470-3 change-over
(or 2 or 1 in compliance with IEC 62053-21) LCD-display:
for active energy Large LCD in compliance with the VDEW
Class 3 or 2 for reactive energy (option) requirements
Class 3 or 2 for apparent energy (option) EDIS code for data identification
Meter software in compliance with LCD back-light on request
WELMEC 7.2 Issue 1 Data display modes:
Measured quantities Automatic cyclic data display with default
Energy (active, reactive and apparent) display time of 8 sec.
Demand (active, reactive and apparent) Manual data display mode (by pressing the
Reactive energy and demand by quadrants Scroll push-button)
Instantaneous power Optional data display when the meter is in
Phase voltages (UL1, UL2, UL3) no-power state
Phase currents (IL1, IL2, IL3) Indicators:
Phase power factors LCD:
Frequency - Valid tariff at the moment
Modes of energy measurement and - Meter status and alarms
registration - Energy flow direction
For one-way energy flow direction (import), - Phase voltage presence and phase
with an electronic reverse running stop voltage sequence
For two energy flow directions (import, - reversed energy flow through a particular
export) metering element
For two-way energy flow direction, with al- LEDs:
ways positive registration, i.e. energy flowing - Imp/kWh
in the export direction is registered as it flows
- Imp/kvarh (at active and reactive energy
in import direction too (only for active energy)
meters)
Connection: - Imp/kVAh (at kWh-, kvarh-, kVAh-meters)
Direct
Powerful load-profile recorder:
Via CT
Up to 8-channels
Networks: More than 790 days of registration at 1
3-phase 4-wire channel, 1-hour registration period
3-phase 3-wire Communication channels:
1-phase 2-wire
Infrared optical port in compliance with IEC
Meter quality: 62056-21 for local programming and data
Due to high accuracy and long term stability down-loading
of the metering elements no meter recali- RS485 serial interface (option)
bration is required over its lifetime Protocol IEC 62056 - 21, mode C
Long meter lifetime and high meter reliability Pulse outputs:
High immunity to EMC
Class A by IEC 62053-31 (option)
Wide voltage range of measurement with
Optomos relay with make contact (option)
declared meter accuracy: 0.3Ur to 1.3Ur
Plastic meter case:
RTC:
Made of high quality self-extinguishing UV
Accuracy better than 3 min/year at 23C
stabilized material that can be recycled
RTC operation reserve 5 years
Double insulation
Back-up power supply Li-battery
IP54 protection against dust and water
Indication of low Li-battery (option) penetration (by IEC 60529)
Time-of-use registration (up to 4 tariffs): Mechanical environment: M1
Tariffs change-over by internal real-time
Electromagnetic environment: E2
clock

4 of 36
MT174 - Electronic three-phase electricity meters
with maximum demand and LP

At direct connected meters: Counters of events (optional)


Current terminals - meter cover opening
- Assure good connection with all types of - terminal cover opening
conductors - reversed energy flow direction
- Do not damage conductors - external permanent magnetic field
Potential links Counters of elapsed time (optional)
- Sliding self-braking potential links enable - since meter cover has been opened
quick disconnection of current and voltage - since terminal cover has been opened
circuitries - since reversed energy flow has been
- Can be located in a terminal block com- detected
partment or under a meter cover - since external permanent magnetic field
Antifraud functions: has been detected
Detectors (optional) - of total energy registration
- meter cover opening - of energy registration in a particular tariff
- terminal cover opening Time-stamps (optional)
- reversed energy flow direction - of the last meter cover opening
- external permanent magnetic field - of the last terminal cover opening
Indicators (optional) - of the last reversed energy flow
detection
- meter cover opening
- of the last external permanent magnetic
- terminal cover opening
field tampering
- reversed energy flow direction trough
Change of set parameters protected with
each of metering elements
a sealed pushbutton (optional)
- external permanent magnetic field
Fraud energy registers (optional)
- energy consumed since the meter cover
has been opened
- energy consumed since the terminal
cover has been opened
- energy consumed since reversed
energy flow has been detected
- energy consumed since external
permanent magnetic field has been
detected

5 of 36
MT174 - Electronic three-phase electricity meters
with maximum demand and LP

1. Meter appearance The meter cover is made of transparent poly-


8 carbonate. It is fixed to the meter base with two
10 2 sealing screws, which prevents access to the meter
4 interior without breaking the seals.
13 9 5
A nickel-plated iron ring in the right top corner is
6 used for attaching an optical probe to the optical
14 port (item 5). A push-button for data scrolling is
positioned on the meter right side (item 6). The
7 reset push-button cover (item 7) is joined with a
hinge to the meter cover and can be sealed
independently.
3 3
1.2. Terminal block
1
The terminal block is made of self-extinguishing
polycarbonate. It can be used either for direct or CT
12 12 meter connection.

The terminal block cover (item 11) can be long or


11 short. A meter connection diagram is stuck on its
inner side. The terminal block cover is fixed with
two sealing screws (item 12).

1.2.1. Terminal block for direct connected


meters
The terminal block for direct connected meters
contains current terminals, auxiliary terminals and
Fig. 1: Meter parts potential links for power supply of the voltage
metering circuitry.
1. Meter base 8. LED imp/kWh
2. Meter cover 9. LED imp/kvarh (option)
3. Meter cover fixing 10. LED imp/kVAh (option)
screw 11. Terminal block cover
4. LCD 12. Terminal cover fixing
5. Optical port Screw
6. Scroll push-button 13. Meter data
7. Reset push-button 14. Legend
cover

Screws for fixing the meter cover (item 3) are


sealed with metrological seals.

Screws for fixing the terminal block cover (item 12)


are sealed with seals of electric utility.
Fig. 2: Terminal block of direct connected meters
1.1. Meter case
1. Current terminals 3. Auxiliary voltage terminals
A compact meter case consists of a meter base
(item 1) with a terminal block and three fixing for an add-on unit
elements for mounting the meter, a meter cover 2. Auxiliary terminals 4. Terminal cover opening
(item 2) and a terminal block cover (item 11). The detector
meter case is made of self-extinguishing UV
The current terminals (item 1) are cage type and
stabilized polycarbonate which can be recycled.
are made of nickel plated steel. They are universal
The meter case ensures double insulation and IP54
terminals for all types of conductors made either of
(IEC 60529) protection level against dust and water
copper or aluminium. The current terminals are
penetration.
made in two sizes:
On the back side of the meter base under the top For conductors with maximum cross section
edge there is the top meter fixing element. On up to 25 mm2 (Imax = 85 A),
request an extended plastic or metal top fixing
element can be attached to the back side of the For conductors with maximum cross section
meter base. up to 35 mm2 (Imax = 120 A).

6 of 36
MT174 - Electronic three-phase electricity meters
with maximum demand and LP

The 85 A terminal blocks has only one screw per 1


current terminal, while 120 A terminal blocks has 2
two screws per current terminal. Due to indirect
pressure to the conductors the terminal screws do
not damage it. The current terminals make a reli-
able and durable contact regardless if the conductor
is made of copper or aluminium.
Voltage metering elements are power supplied via
potential links. Sliding potential links are self-
braking and enable easy disconnection of current
and voltage metering circuitry. In the metering
mode they should be in their lowest position (closed 3
contact), and in the meter testing mode they should
be in their highest position (opened contact). On 1. Detector of terminal 2. Phase voltage test
request, the potential links can be located under the cover opening contacts
meter cover.
3. Sliding potential links (opened contacts)
2
Fig. 4: Potential links in the terminal block of
direct connected meters for Imax = 120 A

1.2.2. Terminal block of CT operated meters


The CT operated meters have separate voltage
terminals (Fig. 5, item 2) in the terminal block. They
are used for supplying the voltage metering
circuitry. The voltage terminals are equal to the
1 current terminals (Fig. 5, item 1). The current and
3 voltage terminals are made of solid brass with a 5
mm bore diameter; the conductors are fixed in the
1. Sliding potential links 2. Phase voltage test terminals with two screws.
(opened contacts) contacts
3. Terminals of auxiliary voltages 4

a. Potential links in the terminal block


1
2

1 3
2

1. Detector of terminal 2. Phase voltage test 1. Current terminals 3. Auxiliary terminals


cover opening contacts 4. Auxiliary voltage
2. Voltage terminals
b. Potential links under meter cover terminals for add-on unit

Fig. 3: Terminal blocks of Fig. 5: Terminal block of a CT operated


direct connected meters for Imax = 85 A meter

1.2.3. Auxiliary terminals


Up to six auxiliary terminals can be built in a
terminal block. They are used for tariff inputs,
impulse outputs or tariff outputs or RS485 interface.
Due to a limited number of auxiliary terminals, all
stated inputs and outputs as well as the interface
can not be built in the meter at the same time. The
bore diameter of the auxiliary terminals is 3.5 mm.
Wires are fixed with a screw. Three auxiliary

7 of 36
MT174 - Electronic three-phase electricity meters
with maximum demand and LP

voltage terminals for power supply of an external Note:


device can be also built-in. On request, an additional top meter fixing
The auxiliary terminals are nickel-plated at a element shown in Fig. 7 can be attached to
tropical meter version. the MT174 meters with a long terminal cover
(shown in Fig. 6).
The auxiliary terminals enable combinations of the
following meter functionalities:
1.4. Meter sealing places
Left side Right side The meters are sealed at the following places:
Version auxiliary auxiliary
terminals terminals 1. The screws of the meter cover - metrological
seals
1 Two tariff inputs Two pulse outputs
2. The screws of the terminal cover - electric
2 Two tariff inputs RS485 interface utility seals
3 Two pulse or tariff RS485 interface
3. The hinged cover of the Reset pushbutton -
outputs
electric utility seals

1.3. Over-all dimensions


Meter fixing dimensions comply with the DIN 43857
standard.

1 1

2 2

Fig. 6 - Meter with a long terminal cover

Fig. 8 - Places of sealing the MT174 meters

Fig. 7 - Meter with a short terminal cover and


an additional top meter fixing element

8 of 36
MT174 - Electronic three-phase electricity meters
with maximum demand and LP

2. Meter configuration

Fig. 10: Metering element


The metering element ensures excellent metering
properties:
1. Negligible effect of influence quantities and elec-
tromagnetic disturbances
2. High long-term stability so that meter recali-
bration is not required over its lifetime
3. Long meter lifetime and high reliability in use

2.2. Power supply stage


The power supply stage is a capacitor type and is
supplied with all three phase voltages. It enables a
meter to operate accurately also if just one phase
Fig. 9: Meter block-diagram and neutral or two phases are connected to the
meter, and the voltage range is from 80% to 120%
The meter consists of: of the rated voltage.
1. Three (on request four) metering elements
2. Meter power supply unit 2.3. Microcontroller
3. Microcontroller with EEPROM The microcontroller acquires signals from the
4. RTC with a Li-battery metering elements, processes them and calculates
5. LCD values of measured energy. The metering results
6. Pulse emitting LED(s) are stored in energy registers for particular tariffs
and total. The microcontroller also generates pulses
7. Scroll push-button for the LED(s) and pulse output(s), enables two-
8. Reset push-button way communication via the optical port and a serial
9. IR optical port interface (if built-in), records load profile and events
10. RS 485 (option) as well as drives the LCD.
11. Tariff input(s) (option) All measured data are stored in a non-volatile
12. Pulse output(s) or tariff output(s) (option) memory and are kept for more than 10 years period
without an external power supply.
2.1. Metering elements Operation of the microcontroller is controlled with a
The MT174 meters are equipped with three watchdog.
metering elements.
The metering elements enable accurate measure- 2.3.1. Load-profile recorder
ment of active, reactive and apparent energy in a A load-profile recorder is provided with maximum
wide metering and a temperature range. The eight channels. The recording period can be set to
voltage range is from 0.3Ur to 1.3Ur - within it the 5, 15, 30 or 60 minutes.
MT174 meters measure energy with declared Note: If maximum demand is measured too, load-
accuracy. profile registration period and demand period
should be of the same value.
The metering elements consist of a current and a Energy or demand can be registered in load-
voltage sensor. The current sensor is a Rogowski profiles. Data in the load-profile recorder are
coil (a current transformer with an air core), while provided with a time stamp (date and time of the
the voltage sensor is a resistive voltage divider. end of a registration period), a meter status in the
Signals of currents and voltages are fed to the A/D last registration period and a check sum. A capacity
converters. Then they are digitally multiplied so that of the load-profile recorder depends on the
instantaneous power is calculated. The instan- registration period and a number of registered
taneous power is integrated in the microcontroller, quantities (channels) and is given in the following
where it is further processed. table.

9 of 36
MT174 - Electronic three-phase electricity meters
with maximum demand and LP

Number Load-profile capacity (days) Restoration of network voltage


of Deleted registers of the load-profile recorder
Reg. period Reg. period Reg. period
channels Deleted registers of the log-books 0 and 1
60 min 30 min 15 min
Deleted energy registers
1 793 396 198 Voltage failure in individual phase (L1, L2, L3)
2 476 238 149 Restoration of voltage in individual phases (L1,
L2, L3)
3 340 170 85
Voltage lower than set voltage low limit
4 261 130 65 Voltage higher than set voltage high limit
5 214 107 53 Opening / closing the meter cover
Opening / closing the terminal block cover
6 182 91 45.5
Manipulation with a permanent magnet start /
7 158 79 39.5 stop
8 140 70 35 Energy flowing in reversed direction (only at
meters for one energy flow direction and at
Warning: If the registration period is changed, the absolute meters)
data stored in the load profile will be lost. Energy loss detected
Before changing load-profile registration Fraud start / stop
period the load-profile data must be down- Phase voltages L1, L2, L3 below the low
loaded first in order not to be lost. voltage limit
Phase voltages L1, L2, L3 under the high
The following data can be stored in the load-profile: voltage limit
Positive active energy +A or demand +P Phase voltages L1, L2, L3 within voltage limits
Negative active energy A or demand -P Wrong password
Absolute active energy IAI or demand IPI Li-battery low
Positive reactive energy +R or demand +Q
Negative reactive energy -R or demand -Q The following events and meter statuses can be
Reactive energy in first quadrant R1 or registered in the P.98.1 log-book:
demand Q1 Opening / closing the meter cover
Reactive energy in second quadrant R2 or Opening / closing the terminal block cover
demand Q2 Manipulation with a permanent magnet start /
Reactive energy in third quadrant R3 or stop
demand Q3 Energy flowing in reversed direction (only at
Reactive energy in fourth quadrant R4 or meters for one energy flow direction and at
demand Q4 absolute meters)
Apparent energy S Deleted log-book P.98
Deleted load-profile recorder
Note: Load-profile data cant be displayed on the Deleted energy registers
LCD. Change of the meter parameters
Fraud start / stop
2.3.2. Log-book Watch-dog reset
The MT174 meters have two log-books. The log- Wrong password / log-in
book P.98 can register 209 events and meter Energy loss detected
statuses; the log-book P.98.1 can register 74
events - mostly fraud attempts. The log-books are
organized as a FIFO memory. In this way the last 2.3.3. Billing results keeping
209 respectively 74 events are always available. The MT174 meter keeps billing results (energy and
Every registered event or meter status is accom- maximum demand values registered by tariffs and
panied with a time stamp consisting of date and total) for up to the last 15 billing periods (months). A
time when it has occurred. number of billing periods (months) for which billing
results are kept is set in the factory and cant be
The following events and meter statuses can be changed subsequently. The billing results are
registered in the P.98 log-book: stored in a FIFO memory, so that they are always
Fatal meter error available for the last n (n = 1, 2, ,15) billing
Meter billing reset periods (months), regardless if the meter billing
Watch-dog reset reset was performed by means of the RTC, the
Changed a value of set parameters Reset push-button or via the optical port or remotely
Changed load-profile registration period via a serial interface. The metering results of the
Internal clock setting past billing periods (months) can be displayed for
Day-light save period time change max. 9 previous months, while they can be readout
Network voltage failure

10 of 36
MT174 - Electronic three-phase electricity meters
with maximum demand and LP

for 15 previous months by means of the optical port Sending a command for exiting the RTC test
or the serial interface (if it is built-in). mode operation by means of MeterView soft-
ware
The RTC can be set to perform a billing reset:
Disconnecting meter supply voltage
Once a year on a specified date and time
Every month on specified day in a month and
time 2.4.3. Time-of-use registration
Every month on a specified day in a week The meter is designed as a multi-tariff with maxi-
after specified day in a month and specified mum four tariffs. A tariff change-over time is defined
time with hour and minute. Minimal time period between
Every week on a specified day in a week and change-over is five minutes. The real-time clock
time enables complex daily and weekly tariff structures,
Every day as well as a couple of seasons in a year:
Up to 10 seasons in a year (i.e. 10 weekly tariff
Indexation of the registers keeping previous month programs)
billing data can be either linear (running from 01 to Up to 10 daily definitions of the tariff change-
15) or circular (running in circles from 00 to 99 and over program
then again 00 and so on).
Up to 10 tariff change-over inside individual
daily tariff programs
2.4. Real-time clock
Up to 46 holidays (including those based on a
A real-time clock is controlled with a 32.768 kHz lunar calendar) in which a special tariff
quartz crystal which is digitally trimmed. Its ac- program is defined
curacy is better than requested by the IEC 62054- The tariff programs control both energy end
21 standard for time-switches. The RTC involves an maximum demand registration.
internal calendar that assures information on year,
month, day, day in a week, hour, minute, second
and leap year. Tariffs can be changed-over also via tariff inputs -
maximum two tariff inputs are available for
The RTC enables: changing-over up to four tariffs. When tariff inputs
Time-of-use registration (in max. 4 tariffs) are used for tariff change-over the active tariff valid
Generating a demand period and load- both for energy and demand.
profile registration period
Generating of time stamp (date and time) 2.4.3.1. Sleeping (passive) tariff program
for demand and events in the log-books On request two tariff programs are available. The
Automatic meter billing reset at the end of second tariff program can be used as:
the billing period (month) 1. Separate tariff program for maximum demand
Automatic change-over to day-light saving - if this option is selected, the first tariff
period and back to the standard time program controls energy registration and the
(winter - summer time) second tariff program controls maximum
demand registration
2.4.1. RTC back-up power supply 2. Sleeping (passive) tariff program for both
A Li-battery is used as the RTC back-up power (energy and maximum demand registration) -
supply. It assures 5 years of the RTC operation re- with this option also the start date (day,
serve and has 20-year shelf-life. The Li-battery is month and year) for activation of passive tariff
positioned on the meter printed circuit board under program must be defined:
the meter cover. a. If current date is before start date, the
first tariff program is active
The Li-battery can enable data display on the LCD b. On start date at 00:00:00 the meter
when the meter is in a no-power state (see item switches from first to second tariff
2.5.4 No-power reading option). program (there is no overwriting of tariff
programs, both tariff programs stay
2.4.2. RTC accuracy testing intact and in the same place as before
The RTC accuracy is tested via imp/kWh LED (Fig. switching)
1, item 8) when the meter is in the RTC test mode. c. If current date is equal to or later than
The meter is set in the RTC test mode operation via start date, the second tariff program is
an optical interface by means of Iskraemeco active
MeterView software by sending the Clock control d. RTC setting:
command to the meter. When the meter is in the If the second tariff program is active
RTC test mode, 4.096 Hz test frequency of RTC is and RTC is set to date before
fed to the imp/kWh LED (Fig.1, item 8). The meter start date, the meter switches
exits the test mode operation by: from second to first tariff program

11 of 36
MT174 - Electronic three-phase electricity meters
with maximum demand and LP

If the first tariff program is active maximum demand value is added to a sum of
and RTC is set to date after start maximum demands in the cumulative demand regi-
date, the meter switches from ster and a counter of billing resets is incremented.
first to second tariff program
The meter billing reset can be performed not only
2.4.3.2. Holidays by means of RTC but also by pressing the Reset
push-button (see Item 2.7.3 Manual meter billing
The MT174 meters support the following holidays: reset), via the IR optical port or remotely via a
Single (on defined year, a month and a day serial interface, if it is built-in.
in a month)
Every year (on defined month and a day in 2.5. LCD
a month)
Every year with shift to Monday (on defined The 7-segment LCD, with additional characters and
month and a day in a month and if that date symbols, complies with the VDEW specifications.
is on Sunday, the holiday is shifted to Large characters and a wide angle view enable
Monday) easy data reading. The LCD back-light illumination
is available on request. The LCD is illuminated by
Holidays based on Lunar calendar
short (Tp < 2 s) pressing the blue pushbutton. On
request the back-light is turned-on all the time.
For holidays based on Lunar calendar the reference
holiday is Eastern according to Gregorian calendar.
All other lunar holidays are defined with a number
of days before or after the Eastern for that holiday -
shifted days. When defining the other lunar holidays
by shifted days, care should be taken that the
entered number of shifted days will not cause that
the defined lunar holiday will be in the next or the
previous year.
Fig. 11: LCD
2.4.4. Maximum demand measurement Data are displayed in the right-side by means of
The internal clock generates a demand period for eight alphanumeric characters. The size of data
demand calculation. Demand is calculated as a characters is 8 mm high and 4 mm width. The OBIS
mean value in the integration period. In the MT174 code (by IEC 62056-61), without the first two
meters the following demand periods can be set: 5, characters from the left side, is employed for data
15, 30 or 60 minutes. At the end of a demand identification. It is displayed in the left side corner
period the calculated demand is transferred from by means of five 6 mm high alphanumeric
the current demand period register into the register characters.
of the demand period that was just terminated. It is
compared with the value stored in the maximum An indicator of energy flow direction is displayed in
demand register in the billing period. If the new the left top corner.
calculated demand is greater than the value in the Note: If there is no load or the load current is lower
maximum demand register, a new demand value is than the meter starting current, the indicator
stored, otherwise the old value is kept. In this way, of energy flow direction is not displayed.
a maximum demand is also registered at the meter
billing reset. A physical unit of displayed physical quantity is
Note: If the meter registers load-profile, the demand shown in the right top corner. The indicator of L1,
period and the load-profile registration period L2, L3 phase voltages presence is displayed in the
should be of the same length. middle of the top row. If certain phase voltage is not
present, the indicator of that phase is not displayed.

2.4.5. Meter billing reset When the indicators L1L2L3 blink, this indicates
A meter billing reset is usually done by RTC once a wrong phase sequence.
month. However, any other period of a meter billing
When the indicator L1, L2 or L3 blinks and at the
reset can also be set (see Item 2.3.3 Billing results
same time the arrow indicating export energy
keeping). Day and time of the meter billing reset
flow direction is displayed, it indicates reverse
can be set for any day in a month and any time
energy flow through the metering element in that
during a day. At the meter billing reset the billing
phase.
data for a current month are copied from the
registers for a current month (a billing period) to the
In the LCD bottom row there are eleven signal flags
registers of a previous month (a billing period) and
that indicate current valid tariff, meter status and
registers for maximum demand in a current billing
alarms. The meaning of signal flags (see item 2.5.3)
period (month) are cleared. At the same time the
is engraved on the meter name plate below them.

12 of 36
MT174 - Electronic three-phase electricity meters
with maximum demand and LP

2.5.1. LCD testing 2.5.2.1. Meter test mode


The LCD can be tested automatically so that all The MT174 meters can be set into the meter test
LCD segments are displayed (Fig. 11) for 5 mode via their optical port by means of Iskraemeco
seconds to check whether they are in order. MeterView software (SET menu) or by means of the
pushbuttons on the meter front side (see item 2.7.6
The LCD test can be performed either: Driving menus with pushbuttons) in which energy
After voltage is applied to the meter data are displayed with higher resolution. Four
In Auto scroll sequence or decimals are displayed in the meter test mode (if
In Manual scroll sequence not requested less decimals to be displayed). At the
same time imp/kWh (and imp/kvarh LED and
With a command sent via a communication
imp/kVA if they are built-in) starts to emit pulses
interface
with a pulse rate 40.000 imp/kWh (40.000
imp/kvarh, 40.000 imp/kVAh). In this way time
2.5.2. Data display needed for meter accuracy testing at low load is
Data defined in Auto scroll sequence and in Manual shortened.
scroll sequence are displayed on the LCD.
2.5.3. Signal and alarm flags
Data from Auto scroll sequence are displayed in a
circle, and each data is displayed for 8 seconds as The signal flags in the LCD bottom row indicate
a standard (default) display time. On request, certain meter status and alarms. They are grouped
longer or shorter data display time can be set via into three groups:
the meter optical port by means of Iskraemeco actual tariff (first four flags on the left side)
MeterView software.
alarms (four flags in the middle)
Note: Maximum 34 registers can be included in
the AUTO scroll mode meter status (last three flags on the right
side)
At Manual scroll sequence the blue push-button
should be pressed for displaying the next piece of The MT174 meters enable indication of many
data. Data in Manual scroll sequence remains different alarms but only four of them can be
displayed until the push-button is pressed again or displayed on the LCD. Therefore a customer at
until time for automatic return into the Auto scroll meter ordering should specify which of them are to
sequence is elapsed. be displayed on the LCD. If more than four alarms
are to be indicated on the LCD, one signal flag can
On request, billing data for the maximum 9 elapsed
be used for two different alarms (e.g. one signal flag
billing periods (months) can be displayed in the
for both the meter cover and the terminal cover
LCD too.
opening)
Note: Maximum 50 registers can be included in
the MANUAL scroll mode The signal flags from left to right have the following
Data that can be displayed at different meter con- functions:
figurations required by the customer are shown in
the table in the Appendix: Data registers and No. FLAG STATUS MEANING
sequences. 1 T1 Lit Active first tariff
Energy data and demand can be displayed in data 2 T2 Lit Active second tariff
formats given in the table below. 3 T3 Lit Active third tariff
4 T4 Lit Active fourth tariff
Data format No. of integers No. of decimals Terminal cover has
TC Lit
Energy been opened1) (option)
6.0 6 0 Meter cover has been
MC Lit
7.1 6 1 opened1) (option)
7.0 7 0 Field detector2) (meter
8.2 6 2 has been tampered
FD Lit
with a permanent
8.1 7 1 magnet - option)
5 to 8
8.0 8 0 Energy flowing in
Maximum demand REV Lit reversed direction3)
4.2 2 2 (option)
4.3 1 3 BAT Lit Li-battery low4)
Cumulative maximum demand Data display on LCD in
PD Lit no-power meter state5)
6.2 4 2
6.3 3 3 Meter data down-
9 DRO Lit loading is in progress

13 of 36
MT174 - Electronic three-phase electricity meters
with maximum demand and LP

10 FF Lit Meter fatal error6) the meter is smaller than the meter starting current,
Meter in programming the LEDs (or a LED) are (is) permanently lit.
11 SET Lit mode
1)
LED STATUS INDICATION
The flag is active only if a corresponding cover
opening detector is built into the meter. Energy is registered.
2) Blinks The pulse rate is
The flag is active only if an external magnetic proportional to the
field detector is built into the meter (option) Imp/kWh consumed power.
3)
The flag could be implemented only at one Imp/kVAh Voltages applied to the
direction energy flow and at absolute energy
Imp/kvarh Lit meter, but load current
meters
4)
is lower than the meter
The flag indicates that Li-battery is low and starting current.
should be replaced.
5) Voltage not applied to
The flag is active only if no-power data Not lit
the meter.
displaying in the LCD was requested (option)
6)
If the FF signal flag is displayed, the meter The emitted pulse rate depends on the meter
should be dismounted from a place of measu- version and load current.
rement and sent to an authorized repair shop
or to the manufacturer for examination and
Meter version Imax Meter constant
repair. At the same time the F.F.0 register is
displayed. For its meaning see item 2.8.4 Fatal 500 imp/kWh
error register. Direct connected 120 A (500 imp/kVAh
(D2) 500 imp/kvarh)
2.5.3.1. Deleting alarm flags 1.000 imp/kWh
The alarm flags displayed on the LCD remain Direct connected 85 A (1.000 imp/kVAh
displayed even in a case of power-down / power- (D1) 1.000 imp/kvarh)
up. They can be deleted by:
10.000 imp/kWh
sending a formatted command to the meter via CT operated 6A (10.000 imp/kvarh,
its optical port or serial interface (if built-in) (T1) 10.000 imp/kVAh)
the meter pushbuttons - one of them is sealed
In the meter test mode pulse rate is increased to
(see item 2.7.4.5 Deleting alarm flags by push- 40.000 imp/kWh (kVAh/imp and kvarh/imp) in order
buttons) to shorten time needed for testing the meters at low
The customer should specify how the alarm flags loads.
are to be deleted at meters ordering. On request the imp/kWh - LED can have an ad-
ditional function. In the RTC test mode operation for
2.5.4. No-power reading option testing RTC accuracy it blinks with frequency that is
Optionally, data can be displayed on the LCD in a equal to the RTC test frequency i.e. 4.096 Hz (see
no-power meter state by pressing the Scroll push- Item 2.4.2 RTC accuracy testing).
button. Data from the Manual scroll sequence (with
exception of historical data if they are included in 2.7. Push-buttons
this sequence) are displayed on the LCD in the no-
power reading mode. For displaying each data on Two pushbuttons are built in the meter cover.
the LCD the Scroll pushbutton should be pressed
again. If the Scroll pushbutton has not been pres- 3 1
3 2 1
sed for a time longer than the time of scrolling data .
in the Auto display mode, the LCD automatically
turns-off in order to save the Li-battery.

2.6. LEDs
The meters for active energy only are provided with
a LED (imp/kWh). The meters for active and 1 Data scroll pushbutton
reactive energy are provided with two LEDs 2 Reset pushbutton
(imp/kWh and imp/kvarh). The meters for active, 3 Cover of the Reset pushbutton
reactive and apparent energy are provided with
Fig. 12: Pushbuttons on the meter cover
three LEDs (imp/kWh, imp/kVAh and imp/kvarh).
The LED(s) are used for testing the meter accuracy
RESET - an orange pushbutton under the
and indicating meter operation. If current through
hinged door that is fixed to the meter cover.

14 of 36
MT174 - Electronic three-phase electricity meters
with maximum demand and LP

Available sealing that does not depend on blue pushbutton should be pressed for a short time
the meter cover. (Tp < 2 s). The display is tested for 10 seconds and
Its primary function is to perform manual all its segments are displayed. After 10 seconds the
billing reset of the meter. meter returns to automatic data display mode
automatically (see item 2.5.1).
DATA SCROLL - a blue pushbutton that is
always accessible.
Its primary function is to display data from 2.7.2. Manual data display
the Manual sequence on request. Data are displayed on request as follows. The
meter is set to the display testing mode (see Item
Depending on how long the pushbuttons were 2.7.1). During the LCD test, the blue pushbutton is
pressed and the combination of pressing them, the pressed for a short time (Tp <2 s). The Std dAtA
pushbuttons enable: title is displayed. In this way a menu for selecting
Selection of the meter operation mode, data display on request is entered.
Testing of display,
Listing of metering results
LCD back-light turn-on (if this function was
requested)
Data display on the LCD in no-power meter
state (if this function was requested)
Manual billing reset of the meter In order to enter into the data display on request
Manual setting of the RTC time and date menu, the blue pushbutton should be pressed for a
(option), long time (2 s < Tp < 5 s). The first data from the
Manual scroll list is displayed on the LCD. For
Manual setting of data transmission rate
displaying the following data from the Manual scroll
(Baud rate) for optical port and serial
list, the blue pushbutton should be pressed for a
interface RS485 (if built-in)
short time again.
Manual deleting of alarm flags (option),
If the blue pushbutton has not been pressed for
At the orange pushbutton the time duration of some time, the meter automatically returns back
pressing does not influence to its function, while at into the Auto scroll mode.
the blue pushbutton there are three different time
durations of pressing - each of them causing The exit from the Manual data display mode is
different effect: performed by prolonged pressing the blue push-
button (Tp > 5 s).
a. Short - pressing shorter than 2 sec. - the
next data in the menu is displayed.
b. Long - pressing longer than 2 sec. and 2.7.3. Manual meter billing reset
shorter than 5 sec. - a submenu or a For a manual meter billing reset with which the
function whose name is displayed on the meter is prepared for a new billing period, the seal
LCD is selected. of the orange pushbutton door should be broken
c. Prolonged - pressing longer than 5 sec. first and the door should be opened. The orange
- the meter is returned up for one level of pushbutton should be pressed, when the meter is in
operation (e.g. on the third level it is the automatic data display mode. When meter
necessary to press the blue pushbutton billing reset is performed, a message donE is
three times and always keep it pressed for displayed on the LCD for a while.
more than 5 sec. in order to return to the
automatic data display mode).

On request the meters can be without the


Reset pushbutton. In such a case the hinged
door is ultrasonically welded to the meter cover
and it cant be opened. If there is no Reset
pushbutton, meter functions that requests In case of the meter billing reset, the billing data are
pressing it are disabled (e.g. manual meter transferred from the registers for a current month to
billing reset, manual setting date and time, the registers for a previous month, the registers for
etc.). demand in a current month are deleted, and the
counter of performed billing resets is incremented
2.7.1. Display testing by one.

A display is tested to check if all its segments In order to prevent misuse of the Reset push-button
function properly. In the automatic data display the after the meter billing reset, the orange pushbutton

15 of 36
MT174 - Electronic three-phase electricity meters
with maximum demand and LP

is disabled for one demand period or longer time C.57.1 register of data transmission rate at
(maximum 1.092 minutes) which can be set by the interface (if built-in) - the data trans-
MeterView. If the orange pushbutton is pressed in mission rate at the interface can be set by
time shorter than the Reset pushbutton disable means of the pushbuttons
period, the meter billing reset will not be performed Par SEt - an option for entering into the
and a message blockEd is displayed on the LCD. meter parameters setting mode which
enables setting meter parameters via the
optical port
Ad rESEt - an option for manual deleting
alarm flags on the LCD
All these functions are optional and can be acti-
vated by means of MeterView software. See also a
flow chart Pushbutton functions and meter modes in
The orange pushbutton cover should be closed and fig. 13 in the item 2.7.6 Driving menus with
sealed again after the manual meter biling reset pushbutton).
was performed.

On request, the function of manual meter billing 2.7.4.1. Setting RTC time by pushbuttons
reset can be disabled. When 0.9.1 register is displayed on the LCD, the
orange pushbutton should be pressed in order to
2.7.4. Meter setting mode edit current time.
The meter setting mode enables:
meter parameters setting via the optical port,
setting date and time of the RTC by means of
the pushbuttons separately for communication
via the optical port and RS485 (if built-in)
setting data transmission rates by means of
the pushbuttons The SET flag is displayed on the LCD indicating
deleting of the alarm flags on the LCD by that displayed time can be edited and the first digit
means of the pushbuttons. on the left side starts to blink. It can be incremented
by short pressing (Tp < 2s) the blue pushbutton.
All these functions are optional and can be enabled
or disabled. To enter into the meter setting mode When its value is suitable, the orange pushbutton
the orange pushbutton should be pressed when the should be pressed to confirm it. The next digit starts
meter is in the LCD testing mode. The menu title to blink. In this way all digits are to be edited. When
SEt is displayed. the last digit has been edited, the orange push-
button should be pressed to set the new time in the
RTC (see item 2.7.7 Flowchart of time setting with
pushbuttons). At the same time the meter returns
back into the SET menu.

2.7.4.2. Setting RTC date by pushbuttons


When 0.9.2 register is displayed on the LCD, the
Now the blue pushbutton should be pressed for a orange pushbutton should be pressed in order to
long time (2s < Tp < 5s) to enter into the SET edit current date.
menu. The first item in the Set menu is displayed.
The other items in the Set menu are displayed by
short pressing (Tp < 2s) the blue pushbutton. There
are the following options in the SET menu:
0.9.1 register of the RTC current time - the
RTC current time can be set by means of
the pushbuttons
0.9.2 register of the RTC date - the RTC The SET flag is displayed on the LCD indicating
date can be set by means of the push- that displayed date can be edited and the first digit
buttons on the left side starts to blink. It can be incremented
by short pressing (Tp < 2s) the blue pushbutton.
C.57.0 register of data transmission rate at
the optical port - the data transmission rate When its value is suitable, the orange pushbutton
at the optical port can be set by means of should be pressed to confirm it. The next digit starts
the pushbuttons to blink. In this way all digits are to be edited. When

16 of 36
MT174 - Electronic three-phase electricity meters
with maximum demand and LP

the last digit has been edited, the orange push-


button should be pressed to set the new date in the
RTC (see item 2.7.7 Flowchart of time setting with
pushbuttons). At the same time the meter returns
back into the SET menu.

2.7.4.3. Setting Baud rates by pushbuttons When the orange pushbutton has been pressed,
When C.57.0 register is displayed on the LCD, the the title Ad done and the SET flag are displayed
orange pushbutton should be pressed in order to indicating that the alarm flags have been deleted. At
set Baud rate of data transmission via the optical the same time the alarm flags displayed on the LCD
port. are turned-off.

The SET flag is displayed on the LCD indicating The orange pushbutton should be pressed again to
that the displayed Baud rate value can be edited return back into the SET menu - Ad rESEt title is
and at the same time the Buad rate value starts to displayed on the LCD.
blink. By short pressing (Tp < 2s) the blue
pushbutton, the possible Baud rate values are By short pressing (Tp < 2s) the blue pushbutton a
scrolled on the LCD (300, 600, 1.200, 2.400, 4.800, message End is displayed on the LCD indicating
9.600, 19.200 bit/s). When a suitable Baud rate is that there is no more items in the SET menu. If the
displayed on the LCD, the orange pushbutton blue pushbutton is pressed again, the first item in
should be pressed to save it. At the same time the SET menu is displayed on the LCD.
meter returns back into the SET menu.
In order to exit the SET menu the blue pushbutton
In the same manner can be set Baud rate of data should be prolonged pressed (Tp > 5s).
transmission via an interface (if it is built-in) in the
register C.57.1. 2.7.5. Meter testing mode
The MT174 meters can be set into the testing mode
2.7.4.4. Meter parameters setting mode
by means of the Reset and Scroll pushbuttons.
When a title PAr SEt is displayed on the LCD, the Data of energy are displayed with increased
orange pushbutton should be pressed in order to resolution in the meter testing mode - maximally
enter into the meter parameters setting mode. four decimals can be displayed. A number of
decimals that will be displayed in the meter testing
mode can be set with the MeterView software.

To enter into the meter test mode the Reset


(orange) push-button should be pressed, when the
meter is in the LCD testing mode. When title SEt is
displayed, the blue pushbutton should be pressed
short so that title tESt of the submenu meter testing
The SET signal flag is displayed on the LCD and mode is displayed.
the title PAr SEt starts to blink indicating that the
meter parameters can be programmed via the
optical port. To exit from the Meter parameters
setting mode the orange pushbutton should be
pressed again. At the same time the meter returns
back into the SET menu.

2.7.4.5. Deleting alarm flags by


pushbuttons The blue pushbutton should be pressed long (2s <
Tp < 5s) to display energy data with increased
When a title Ad rESEt is displayed on the LCD, the resolution.
orange pushbutton should be pressed in order to
delete the displayed alarm flags (e.g. meter cover
opening, terminal cover opening, reversed energy
flow, etc.).

17 of 36
MT174 - Electronic three-phase electricity meters
with maximum demand and LP

with prolonged pressing (Tp > 5s) the blue


push-button
to disconnect the meter from voltages.

2.7.6. Driving menus with pushbuttons


There are three different ways to return back into The MT174 meters can be set into different modes
the standard energy data resolution display mode: (see items 2.7.4, 2.7.4.1, 2.7.4.2, 2.7.4.3, 2.7.4.4
to send an appropriate formatted command and 2.7.4.5) by means of the pushbuttons. The
to the meter via its optical port pushbutton functions and the meter modes are
shown in the following flow-chart.

Note: Registers displayed on the LCD in the Manual scroll mode can differ from those shown in the flow-chart
as they are optional.
Fig. 13: Pushbutton functions and meter modes

18 of 36
MT174 - Electronic three-phase electricity meters
with maximum demand and LP

2.7.7. Flowchart of time setting with pushbuttons


Data scroll pushbutton Reset pushbutton
B SHORT (Tp < 2s): Increments digit that blinks O: Confirms value of digit that blinks and goes
to the next digit
B LONG (2s < Tp < 5s): Keeps old parameter
value Enters new value of parameter

Fig. 14: Flow-chart of time setting with pushbuttons

Date is set with the pushbuttons in the same manner.

19 of 36
MT174 - Electronic three-phase electricity meters
with maximum demand and LP

2.8. Communication channels communicator is 1.200 meters. At two-way


communication via the RS485 interface the IEC
The meters can be equipped with the following 62056-21, mode C protocol is used. The data
communication channels: transmission rate is fixed and default set to 9.600
Optical interface (always built-in) bit/s. Anyhow, any other data transmission rate in
the range from 300 bit/s to 19.200 bit/s can be set
RS485 interface (on request) depending on the data transmission rate of the
Built-in communication channels enable: master to which the meter is connected.
Billing data readout
The RS485 interface is connected to the auxiliary
Load-profiles readout terminals on the right side of the terminal block.
Log-book registers readout
Meter parameters readout Terminal Description
Meter parameters setting 27 RS485 A
Communication with the meter in progress is 29 RS485 B
indicated on the LCD by the DRO signal flag.
Note: The meter address could be long up to 20
characters and is stored in the register 0.0.0.
2.8.1. Optical port It is not allowed that two meters connected to
In the right top corner of the meter there is an one master device have the same address. If
optical port that complies with the IEC 62056-21 the meter address is not specified by a
standard. It is intended for a local setting of the customer at the meter ordering, the default
meter parameters and local data readout. meter address is the meter serial number.

2.8.3. Data downloaded via optical port


Data downloaded via an interface (optical port or
RS485 interface) are identified with OBIS (OBject
Identification System) codes in compliance with
IEC 62056-61 standard. On request the data
identification codes can be EDIS (Energy Data
Identification System) in compliance with DIN
43863, Part 3 standard. On request, historical data
for previous billing periods, besides data for a
current billing period, can be also downloaded via
the optical port and an interface (if it is built-in).
Fig. 15: Optical port Historical data can be downloaded for maximum 15
last billing periods.
The communication protocol is IEC 62056-21,
mode C. Communication mode is serial asyn-
chronous. All data transmission rates from 300 bit/s 2.8.4. Fatal error register
to 19.200 bit/s are available. However, the default The fatal error register F.F.0 is a hexadecimal value
data transmission rate is 9.600 bit/s. If data and generates the following alarms, when particular
transmission rate of the used optical probe is less bits are set to 1.
than 9.600 bit/s, than transmission rate of the
optical port should be set to the data transmission Bit Error Description
rate of the optical probe. 0 Firmware check-sum error
The wave length of the optical port light is 660 nm, 1 Parameters check-sum error
luminous intensity in active state is min. 1 mW/sr. 2 Energy / maximum demand check-sum error
3 Not implemented
2.8.2. RS485 interface 4 Not implemented
5 Not implemented
On request, an RS485 interface can be built into the
MT174 meters. It enables remote readout and 6 Warning of detected factory access level*
setting of the meter parameters. 7 Not implemented
* If only a factory access level has been detected,
The RS485 interface enables connection of 31
the Error message is not displayed
meters to one communicator with a built-in RS485
interface, e.g. Iskraemeco P2CC. Master-slave
architecture is used. The communicator is a master
device and the MT174 meters are slave devices.
Maximum distance between the meters and the

20 of 36
MT174 - Electronic three-phase electricity meters
with maximum demand and LP

2.8.5. Communication protocol A tariff input is controlled with AC line-to-neutral


The communication protocol is IEC 62056-21 mode voltage Un. The microcontroller recognize that there
C. The communication is asynchronous half-duplex. is logic 1, if voltage at the input is U 0.8 Un, and
logic 0, if voltage at the input is U 0.2 Un.
Data format:
1 start bit, 7 data bits, 1 parity bit, 1 stop bit A customer can specify at which voltage combi-
nation applied at the tariff inputs a certain tariff is
The entire data block is protected with a control valid. The customer can also specify whether a tariff
mark BCC in compliance with the DIN 66219 input has a ground connected to an auxiliary
standard. terminal or it has a common ground with the meter
After receiving a calling telegram at a 300 baud and is therefore connected inside it.
data transmission rate,
2.9.2. Pulse output
/ ? Device address ! CR LF or / ? ! CR LF
One pulse output (active energy meters for one
the meter reveals its identification at a 300 baud energy flow direction or absolute meters) or two
data transmission rate: pulse outputs (active and reactive energy meter for
one energy flow direction or active energy meters
/ I S K 5 M T174 Program version
for two energy flow directions) can be built into the
where Program version is a four digit code. The MT174 meters.
meter address refers to the contents of the 0.0.0 or
0.0.1 registers. Then the meter waits for 2 sec. so Note: Pulse output(s) are not available, if the meter
that the proposed data transmission rate is is equipped with tariff output(s).
confirmed:
ACK 0 5 0 CR LF. Terminal Designation Description
40 GND Ground
If the proposed baud rate is confirmed, commu-
nication at a 9.600 baud rate follows; if it is not 41 +AA Pulse output +A
confirmed, communication at 300 baud continues. 42 -AA Pulse output -A
The meter transmits the data telegram:
43 +RA Pulse output +R
STX Data ! CR LF ETX BCC
Note: Besides the 41 terminal either the 42 or the
where
43 auxiliary terminal can be used.
STX: stands for the start of a text;
Data: refers to codes and data The pulse output is passive and complies with the
! CR LF: stands for the end of data IEC 62053-32 standard, class A (S0 in compliance
ETX: stands for the end of a text with DIN 43864). The pulse constant is equal to the
BCC: stands for Block Check Character - half value of the meter constant and the standard
parity check pulse width is 40 ms. However, a smaller pulse
constant or a larger pulse length can be set on
2.9. Inputs and outputs request. The class A pulses can be transferred to
0.5 m distance.
Inputs and outputs are built in the MT174 meters on
request. The following inputs and outputs are The pulse output(s) can be performed as an opto-
available: mos relay with a make contact that can changeover
Impulse output 25 W (100 mA, 250 V) on request. In this case
Tariff output pulse transmission at a distance of 1 km is made
Tariff input possible. The pulse constant is equal to one tenth
For possible combinations of inputs and outputs of the meter constant and the standard pulse width
see the item 1.2.3. Auxiliary terminals. is 100 ms. However, a smaller pulse constant or
other pulse lengths can be set on request.
2.9.1. Tariff input Optional pulse widths are: 10 ms, 20 ms, 30 ms, 40
One (two-tariff meters) or two tariff inputs (three or ms, 50 ms, 60 ms, 80 ms and 100 ms. The default
four-tariff meters) for external tariff changeover can pulse width is 40 ms at class A pulse output and
be built into the MT174 meters. 100 ms at optomos relay pulse outputs.

Terminal Designation Description Optional pulse constants at direct connected meters


13 TE1/2 Tariff input 1 are: 1.000 pls/kWh, 500 pls/kWh, 250 pls/kWh, 200
pls/kWh, 100 pls/kWh, 50 pls/kWh, 25 pls/kWh, 20
15 GND Ground pls/kWh and 10 pls/kWh.
33 TE3/4 Tariff input 2

21 of 36
MT174 - Electronic three-phase electricity meters
with maximum demand and LP

The default pulse constants depending on the pulse 3. Antifraud protection


output type and the meter Imax current is given in the
table below: Special attention has been paid to a system of
meter data protection through the MT174 meter
Default output pulse design in order to prevent its tampering. Besides,
constant (pls/kWh) special tamper countermeasures are used hard-
Pulse output ware and software ones.
Imax up to Imax = 100 A
85 A or 120 A
Class A (S0) 500 250 3.1. Meter seals
Optomos relay 100 50 The meter and the terminal block cover are fixed
with two screws and are secured with a wire and a
lead or a plastic seal. The Reset pushbutton hinged
Warning: When other than default pulse width and
door is sealed separately.
pulse constant are required, attention
should be paid that the selected values
do not cause overlapping of the pulses 3.2. Always positive registration
at maximum load. The option of always positive energy registration at
kWh-meters regardless in which direction energy
The pulse outputs can be dedicated to any energy flows through the metering elements prevents
which is measured. meter misuse by wrong connection of the con-
ductors into the terminal block. In this way registe-
2.9.3. Tariff output red energy is equal to the one actually consumed
One or two tariff outputs can be built into the MT174 regardless of the meter connection.
meters for controlling an external device by a tariff A3f = IAL1I + IAL2I + IAL3I
program that is stored in the meter instead of pulse
output(s). In addition, an alarm flag REV is displayed on the
LCD, when energy flows in reversed direction.
Terminal Designation Description Besides, a corresponding indicator L1, L2 or L3 is
61 TA1/2 Tariff output 1 blinking indicating through which of the metering
elements energy flows in reversed direction.
65 GND Ground
Reversed energy can be registered into a separate
63 TA3/4 Tariff output 2 register on request too.
A tariff output is performed as an optomos relay Besides, the following registers can be implemen-
with a make contact that can switchover 25 W (100 ted into the MT174 meters:
mA, 250 V). Elapsed time during which energy flown in
reversed direction.
Note: Tariff output(s) are not available, if the meter
is equipped with pulse output(s). Events counter of reversed energy flow
Time-stamps of the last reversed energy
events

3.3. Passwords
The MT174 meters are protected with three pass-
words. They protect the meters against unautho-
rized:
reading the meter data
changing the meter parameters
setting time and date in the meter RTC.

The passwords can be up to 12 characters long. If


wrong password(s) is (are) entered into a meter
three times, the communication channel is disabled
for a certain time in order to prevent attempts of
hacking the meter. Such attempts are also
registered into the meter log-book.

Besides, the following registers can be implemen-


ted into the MT174 meters:
Events counter of wrong password entering

22 of 36
MT174 - Electronic three-phase electricity meters
with maximum demand and LP

Time-stamps of the last wrong password Events counter of a meter tampering with a
entering permanent magnet
3.4. Parameters change protected Time-stamps of the last meter tampering with a
with a sealed pushbutton permanent magnet events

Besides protection with a password the meter


parameters change can be protected with the Reset 3.7. Fraud event counters
pushbutton which is sealed. In such a case the On request, the meter is equipped with counters of
Reset pushbutton seal should be broken and the events that count particular events from 0000 to
Reset pushbutton should be pressed before the 9999. They are organized as ring buffers so that
meter parameters can be changed. after the 9999-th event the new event is registered
as 0000. To each event counter is associated a
3.5. Detectors of opening meter cover register that registers a time stamp (date and time)
of the last event that has occurred. All event
and terminal cover counters and registers containing their last time-
On request, a detector of the meter and/or the stamps can be downloaded in the DRO (Data Read
terminal cover opening can be built into the meter. Out) sequence via the optical port and via a serial
They are two switches with a pushbutton that interface (RS485), if it is built-in. The events and
trigger a signal in case of opening the cover. The their time-stamps are registered in the following
event is registered in the log-book together with its registers.
time-stamp (date and time) and the corresponding
flag is displayed in the LCD. REGISTER DATA CONTAINED
Besides, the following registers can be implemen- C.51.1 Terminal cover opening counter
ted into the MT174 meters: C.51.2 Timestamp of the last terminal cover
Fraud energy register (see item 3.10 Registers opening event
of fraud energy) C.51.3 Meter cover opening counter
Events counter of a cover opening C.51.4 Timestamp of the last meter cover
Time-stamps of the last reversed cover ope- opening event
ning events C.51.5 External magnetic field influence
event counter
C.51.6 Timestamp of the last external
magnetic field influence
C.51.7 Reversed energy flow event* counter
C.51.8 Timestamp of the last reversed
energy flow event*
* Available only at the meters for measurement
energy in one energy flow direction or absolute
energy.

Events of meter and terminal cover opening are


Fig. 16: A detector of opening the terminal cover registered even if they are opened when there is no
voltage applied to the meter.
3.6. Detector of external magnetic
field 3.8. Registers of elapsed time
On request, a detector of an external magnetic field The MT174 meters enable registration of elapsed
can be built into the meter. If an external magnetic time:
field is detected, this event is registered in the log- since the start of energy measurement
book together with its time stamp (date and time) how much time was energy measured in a
and the corresponding flag is displayed in the LCD. particular tariff
Consumed energy during meter tampering with a how much time energy has flown in reversed
permanent magnet can be registered into a direction (only at one energy flow direction
separate register on request too. meters and at absolute ones)
how much time the meter was exposed to a
Besides, the following registers can be implemen-
permanent magnetic field (if a magnetic field
ted into the MT174 meters:
detector is built-in)
Fraud energy register (see item 3.10 Registers
of fraud energy) Besides, the meters have a counter which registers
Elapsed time during which the meter was elapsed time during which no voltage has been
exposed to an external permanent magnetic applied to the meter.
field (if a magnetic field detector is built-in).

23 of 36
MT174 - Electronic three-phase electricity meters
with maximum demand and LP

Elapsed times can be expressed either in hours - in 4. Meter installation


such a case five digits are available or expressed in
a form of YYMMDDhhmmss 1. Check if voltage and maximum current printed
where: on the meter name plate correspond to the
YY - years, MM - months, DD - days, hh - hours voltage in the network and to the current which
mm - minutes, ss - seconds will flow through the meter.
2. Fix the meter with three screws to the measuring
3.9. Registers of fraud energy place.
The MT174 meters have four registers in which 3. Connect the meter in compliance with the
energy is separately registered during the meter connection diagram which is stuck in the inner
tampering besides energy registered in the cor- side of the terminal cover (or printed on the
responding registers. The fraud energy registers meter name plate).
are available for the following tamper attempts: 4. Tighten the terminal screws with appropriate
reversed energy flow direction (only at one torque. The recommended torque for tightening
energy flow direction meters and at current terminal screws is 2.5 Nm.
absolute ones) 5. Check the meter operation indicators:
permanent magnetic field exposure (if a kWh/imp (kvarh/imp) LED is lit (load current
magnetic field detector is built-in) is smaller than the meter starting current)
energy registered since the meter and/or
terminal cover has been opened kWh/imp (kvarh/imp) LED is blinking with
frequency that is proportional to the
Besides, time how long a particular fraud has lasted measured demand (the meter measures
is registered in the corresponding register of and registers energy)
elapsed time (see item 11.Tamper registers (energy kWh/imp (kvarh/imp) LED is not lit (the
registers and registers of elapsed time) in the 11. meter is in no-power state). In this case the
Appendix II: EDIS codes, data stored in registers, following should be checked:
sequences, historical values). a) At directly connected meters: voltage
links in lower position (if not, the voltage
3.10. Log-books links slides should be moved to their
All events are registered also in the log-books (see lower position)
item 2.3.2) together with their time stamps (date b) Connected current conductors to the
and time of the event occurence). meter (if not, they should be connected)
c) If both above conditions are fulfilled, it
3.11. SEP2 MeterView software means that there is no voltage in the
network. If there is a voltage in the
SEP2 MeterView software for meter managing is
network, something is wrong with the
available on request instead of the standard Meter-
meter. In such a case the meter should
View software. The SEP2 MeterVew enables:
be replaced.
Logging of a user to the SEP2 MeterView
software by entering its user name and its 6. Check the L1, L2 and L3 indicators on the LCD
password if current conductors are connected correctly:
Multi level authorisation (meter reading, L1 L2 L3 indicators are displayed - all three
time and date setting, changing meter phase voltages are present
parameters, deleting energy registers) Some of the L1 L2 L3 indicators are not
Data base keeping data who, when and displayed (voltage in these phases is not
what has done with a particular meter. present). Check if current conductors of
these phases are connected and/or their
voltage links are in the bottom position (at
direct connected meters) or find the reason
for the phase voltage absence and
eliminate it.
Some of the L1 L2 L3 indicators are
blinking and at the same time import energy
indicator is displayed indicating that current
through that metering element is reversed.
In such a case change the input and the
output of the corresponding current
terminals.
L1 L2 L3 indicators are blinking - reversed
phase sequence that causes rotation of

24 of 36
MT174 - Electronic three-phase electricity meters
with maximum demand and LP

magnetic field in reversed direction. In this 7. Meter connection diagram


case check current conductors sequence in
the meter or find the place of reversed The meter connection diagram is stuck on the inner
voltage phase sequence and connect them side of the terminal block cover or is printed on the
correctly. meter nameplate. The meters can be connected in
three-phase four- or three-wire networks, as well as
Note: Reversed phase sequence does not in a single-phase two-wire network.
influence in energy measurement accuracy

7. Check if alarm flags are displayed on the LCD


and delete them. If necessary, remove a cause
that they are displayed.
8. Check RTC date and time and correct them, if
necessary.
9. Perform a meter billing reset (press the orange
pushbutton)
10. Seal the meter (the terminal cover and the
orange pushbutton cover).

5. Tools for meter managing


The following tools are used for managing the
MT174 meters:

For service meter programming and


local data downloading:
1. MeterView or alternatively SEP2 MeterView
(Iskraemeco software)
2. Optical probe
3. PC: a desk-top or a lap-top with operating
system Windows XP or later Windows
version a. Connection diagrams of direct connected
meters MT174
The tool is intended for the operators who service
or reprogram the meters in the laboratory or in the
field.

For local data downloading and meters


programming in the field
4. MeterRead (Iskraemeco software) for all
type of palm-top PCs operating in the
Windows Mobile operating system
5. Optical probe
6. Palm-top PC with Windows Mobile

The tool is intended for a personal who read-out the b. Connection diagram of CT operated meter
meters in the field. MT174

6. Meter maintenance
The meter is designed and manufactured in such a Fig. 17: Connection diagrams of MT174
way that no maintenance is required in the entire
meter lifetime. Measuring stability assures that no
recalibration is required. If a battery is built into the
meter, its capacity is sufficient to backup all meter
functions for its entire lifetime.

25 of 36
MT174 - Electronic three-phase electricity meters
with maximum demand and LP

8. Technical data Operating temper. -40C ... +60C


range (for LCD : -25C ... +60C)
GENERAL METERING PROPERTIES Extended temper.
-40C ... +70C
3x230/400 V, 3x230 V, 3x400 V, range
Reference voltage
Ur 230 V Storing
-40C ... +80C
(other voltage on request) temperature
Voltage range 0.8 Ur ... 1.15 Ur Relative humidity 95%, non-condensing
Thermal current 1.2 Imax Voltage circuit < 0.6 W / 10VA (without RS485)
Max. current Imax Dir. connected meter: 85 A or 120 A burden < 0.8 W / 10VA (with RS485)
CT operated meter: 6 A Current circuit < 0.16 VA
burden (irrespective of reference / basic current)
Short-circuit current 30 x Imax
Reference 50 Hz or 60 Hz RTC
frequency Time base Quartz crystal 32 kHz
METERING PROPERTIES BY IEC 62053-21 and -23 Long-term
< 0.5 s/day at reference condition
Accuracy class accuracy of RTC
2 or 1
for active energy Time-keeping vs.
< 0.15 s/C/day
Accuracy class for temperature
3 or 2 Back-up power 5 years
reactive energy
Accuracy class for supply (Li-battery power supply source)
3 or 2
apparent energy Li-battery life-time 20 years
Direct connected meters LOAD PROFILE RECORDER
Basic current Ib 5A 10 A No. of channels max. 8
Class 2 Class 1 Class 2 Class 1 Registration period 5 min, 15 min, 30 min, 60 min
Starting current Ist 0.025 A 0.02 A 0.05 A 0.04 A OPTICAL INTERFACE
CT operated meters
Optical interface IEC 62056-21 (IEC 61107)
Basic current Ib 1A
Protocol IEC 62056-21 (IEC 61107) Mode C
Starting current Ist 20 mA
Data identif. code OBIS (IEC 62056-61)
METERING PROPERTIES BY EN 50470-3
Default data default 9.600 bit/s
Mechanical transmission rate (on request up to 19,200 bit/s)
environment M1
RS485 INTERFACE (option)
Electromagnetic
environment E1 Protocol IEC 62056-21 (IEC 61107) Mode C
Accuracy class Data identif. code OBIS (IEC 62056-61)
for active energy A or B Data transmission default 9.600 bit/s
Direct connected meters rate (on request up to 19,200 bit/s)
Reference current 5A 10 A Loop length 1.200 m
Iref Meters in a loop max. 31
Transitional current 0.5 A 1A OUTPUTS
Itr No. of outputs 1 or 2
Minimum current Class A Class B Class A Class B IEC 62053-31 class A
Imin 0.25 A 0.25 A 0.5 A 0.4 A Impulse output (S0 in compliance with DIN 43864)
Starting current Ist 0.025 A 0.02 A 0.05 A 0.04 A or optomos relay with make contact
Optomos relay with make contact
CT operated meters Tariff output (option instead of of impulse output)
Reference current 1A
INPUTS
Iref
No. of tariff inputs 1 or 2
Transitional current 100 mA
Control voltage Ur
Itr
METER RESISTANCE TO ELECTROMAGNETIC
Minimum current 50 mA
DISTURBANCES
Imin
Starting current Ist 20 mA Dielectric strength 4 kV, 50 Hz, 1 min
Electrostatic (IEC 61000-4-2) air discharge 15 kV
OTHER METER PROPERTIES
discharge contact discharge 8 kV
500 imp/kWh at Imax = 120 A
500 imp/ kvarh at Imax = 120 A High-frequency (IEC 61000-4-3 ) active: 20 V/m
Meter constant 500 imp/ kVAh at Imax = 120 A el.magnetic field passive: 30 V/m
(per LED) 1.000 imp/kWh at Imax = 85 A (80 MHz...2 GHz)
1.000 imp/ kvarh at Imax = 85 A Fast transients (IEC 61000-4-4) active: 6 kV
1.000 imp/ kVAh at Imax = 85 A (burst) passive: 6 kV
10.000 imp/kWh at Imax = 5 A Surge voltage (IEC 61000-4-5) 6 kV, 1.2/50 s
10.000 imp/ kvarh at Imax = 5 A Conduct. disturb.
10.000 imp/ kVAh at Imax = 5 A Induced by RF fields (IEC 61000-4-6) 20 V

26 of 36
MT174 - Electronic three-phase electricity meters
with maximum demand and LP

(150 kHz...80 MHz) Dimensions (w x h x d) 177x 216 x 55 mm


12 kV, 1,2/50 s - to main circuits Mass approx. 1,0 kg
Impulse voltage
6 kV, 1,2/50 s - to auxiliary circuits COMBUSTIBILIY OF METER CASE
Radio interf. supr. (EN 55022) class B equipment Class V0 (Standard UL 94)
DIMENSIONS AND MASS TORQUE FOR TERMINAL SCREWS
Meters with long terminal cover: Direct connected meters 2.5 Nm
Dimensions (w x h x d) 178 x 250 x 55 mm CT operated meters 1.0 Nm
Meters with short terminal cover:

27 of 36
MT174 - Electronic three-phase electricity meters
with maximum demand and LP

9. Meter type designation

MT174 - D1 A41 R51 S52 - V22 L21 - M3 K 0 3 Z *


M Static meter
T Three-phase three-element meter
174 Time-of-use meter with maximum demand
indicator and RTC
-
D1 Terminal block for Imax=85 A (DIN 43857)
D2 Terminal block for Imax=120 A
T1 Transformer terminal block for Imax=6 A
A4 Active energy, accuracy class 1 (B by MID)
A5 Active energy, accuracy class 2 (A by MID)
1 Active energy measurement in one
direction (+A)
2 Active energy measurement in two
directions (+A, -A)
4 Measurement of absolute active energy
value (IAI)
R5 Reactive energy measurement, accuracy
class 2 (option)
R6 Reactive energy measurement, accuracy
class 3 (option)
1 Reactive energy measurement in one
direction (+R)
2 Reactive energy measurement in two
directions (+R, -R)
6 Reactive energy measurement in four
quadrants and import and export (Q1, Q2,
Q3, Q4, +Q, -Q)
S52 Apparent energy, accuracy class 2 (option)
S=UxI
S62 Apparent energy, accuracy class 3 (option)
S=UxI
-
V12 One tariff input (option)
V22 Two tariff inputs (option)
G12 One pulse output class A (S0) - option
G22 Two pulse outputs class A (S0) - option
L11 One optomos relay (optional pulse or tariff
output)
L21 Two optomos relays (optional pulse or tariff
output)
-
M RTC
3 Back-up power supply Li-battery
K Communication channel
0 Optical interface (IEC 62056-21)
3 RS485 interface (option)

Z Load profile register (option)

* For possible combinations of inputs, outputs and interface built into the same meter see item 1.2.3 Auxiliary
terminals

28 of 36
MT174 - Electronic three-phase electricity meters
with maximum demand and LP

10. Appendix I: MT174 meter in photovoltaic (PV) installations

The renewable energy sources including photo-


voltaic panels, fuel cells and wind power plants
deliver environmentally friendly, sustainable
electrical power. In recent years, the power
generating photovoltaic systems have become
increasingly popular with the residential consumers.

To make the DC voltage produced by these


systems available to consumers or to feed it into the
power grid it needs to be transformed into AC
voltage of 230 V and 50 Hz. This transformation is
commonly made by the use of photovoltaic
converters. Unfortunately, these devices may Fig. 18: A typical residential solar installation
produce broad frequency disturbance signals
ranging from the low frequency harmonics to The three-phase electricity meter of type MT174
conductive and radiated electromagnetic complies with the requirements of the Leitfaden
interference in the MHz range. zur Bewertung der Zuverlssigkeit und
Messbestndigkeit von Elektrizittszhlern und
In a typical residential photovoltaic system a three- Zusatzeinrichtungen published by the German
phase electricity meter will be installed as shown on VDE (Verband der Elektrotechnik Elektronik
Fig. 18 below. This way it can measure the Informationstechnik) in March 2011. This means
consumed electric energy and the energy delivered that the meter is resistant to the symmetrical
to the grid (note: a second single-phase PV meter perturbation currents emitted by PV converters in
may be used to measure only the energy delivered the range 2 - 150 kHz and may therefore safely be
by the solar panels). used in a photovoltaic installation.

29 of 36
MT174 - Electronic three-phase electricity meters
with maximum demand and LP

11. Appendix II: EDIS codes, data stored in registers, sequences, historical values

EDIS Histor.
DESCRIPTION LCD DRO
CODE values
1. Active energy registers
1.8.0 Positive active energy (A+) total [kWh] x x x
1.8.1 Positive active energy (A+) in tariff T1 [kWh] x x x
1.8.2 Positive active energy (A+) in tariff T2 [kWh] x x x
1.8.3 Positive active energy (A+) in tariff T3 [kWh] x x x
1.8.4 Positive active energy (A+) in tariff T4 [kWh] x x x
2.8.0 Negative active energy (A-) total [kWh] x x x
2.8.1 Negative active energy (A-) in tariff T1 [kWh] x x x
2.8.2 Negative active energy (A-) in tariff T2 [kWh] x x x
2.8.3 Negative active energy (A-) in tariff T3 [kWh] x x x
2.8.4 Negative active energy (A-) in tariff T4 [kWh] x x x
15.8.0 Absolute active energy (|A|) total [kWh] x x x
15.8.1 Absolute active energy (|A|) in tariff T1 [kWh] x x x
15.8.2 Absolute active energy (|A|) in tariff T2 [kWh] x x x
15.8.3 Absolute active energy (|A|) in tariff T3 [kWh] x x x
15.8.4 Absolute active energy (|A|) in tariff T4 [kWh] x x x
16.8.0 Sum active energy without reverse blockade (A+ - A-) total [kWh] x x x
16.8.1 Sum active energy without reverse blockade (A+ - A-) in tariff T1 [kWh] x x x
16.8.2 Sum active energy without reverse blockade (A+ - A-) in tariff T2 [kWh] x x x
16.8.3 Sum active energy without reverse blockade (A+ - A-) in tariff T3 [kWh] x x x
16.8.4 Sum active energy without reverse blockade (A+ - A-) in tariff T4 [kWh] x x x
2. Reactive energy registers
3.8.0 Positive reactive energy (Q+) total [kvarh] x x x
3.8.1 Positive reactive energy (Q+) in tariff T1 [kvarh] x x x
3.8.2 Positive reactive energy (Q+) in tariff T2 [kvarh] x x x
3.8.3 Positive reactive energy (Q+) in tariff T3 [kvarh] x x x
3.8.4 Positive reactive energy (Q+) in tariff T4 [kvarh] x x x
4.8.0 Negative reactive energy (Q-) total [kvarh] x x x
4.8.1 Negative reactive energy (Q-) in tariff T1 [kvarh] x x x
4.8.2 Negative reactive energy (Q-) in tariff T2 [kvarh] x x x
4.8.3 Negative reactive energy (Q-) in tariff T3 [kvarh] x x x
4.8.4 Negative reactive energy (Q-) in tariff T4 [kvarh] x x x
5.8.0 Imported inductive reactive energy in 1-st quadrant (Q1) total [kvarh] x x x
5.8.1 Imported inductive reactive energy in 1-st quadrant (Q1) in tariff T1 [kvarh] x x x
5.8.2 Imported inductive reactive energy in 1-st quadrant (Q1) in tariff T2 [kvarh] x x x
5.8.3 Imported inductive reactive energy in 1-st quadrant (Q1) in tariff T3 [kvarh] x x x
5.8.4 Imported inductive reactive energy in 1-st quadrant (Q1) in tariff T4 [kvarh] x x x
6.8.0 Imported capacitive reactive energy in 2-nd quadrant (Q2) total [kvarh] x x x
6.8.1 Imported capacitive reactive energy in 2-nd quadr. (Q2) in tariff T1 [kvarh] x x x
6.8.2 Imported capacitive reactive energy in 2-nd quadr. (Q2) in tariff T2 [kvarh] x x x
6.8.3 Imported capacitive reactive energy in 2-nd quadr. (Q2) in tariff T3 [kvarh] x x x

30 of 36
MT174 - Electronic three-phase electricity meters
with maximum demand and LP

6.8.4 Imported capacitive reactive energy in 2-nd quadr. (Q2) in tariff T4 [kvarh] x x x
7.8.0 Exported inductive reactive energy in 3-rd quadrant (Q3) total [kvarh] x x x
7.8.1 Exported inductive reactive energy in 3-rd quadrant (Q3) in tariff T1 [kvarh] x x x
7.8.2 Exported inductive reactive energy in 3-rd quadrant (Q3) in tariff T2 [kvarh] x x x
7.8.3 Exported inductive reactive energy in 3-rd quadrant (Q3) in tariff T3 [kvarh] x x x
7.8.4 Exported inductive reactive energy in 3-rd quadrant (Q3) in tariff T4 [kvarh] x x x
8.8.0 Exported capacitive reactive energy in 4-th quadrant (Q4) total [kvarh] x x x
8.8.1 Exported capacitive reactive energy in 4-th quadr. (Q4) in tariff T1 [kvarh] x x x
8.8.2 Exported capacitive reactive energy in 4-th quadr. (Q4) in tariff T2 [kvarh] x x x
8.8.3 Exported capacitive reactive energy in 4-th quadr. (Q4) in tariff T3 [kvarh] x x x
8.8.4 Exported capacitive reactive energy in 4-th quadr. (Q4) in tariff T4 [kvarh] x x x
3. Apparent energy registers
9.8.0 Apparent energy (S+) total [kVAh] x x x
9.8.1 Apparent energy (S+) in tariff T1 [kVAh] x x x
9.8.2 Apparent energy (S+) in tariff T2 [kVAh] x x x
9.8.3 Apparent energy (S+) in tariff T3 [kVAh] x x x
9.8.4 Apparent energy (S+) in tariff T4 [kVAh] x x x
4. Registers of active energy per phases
21.8.0 Positive active energy (A+) in phase L1 total [kWh] x x x
41.8.0 Positive active energy (A+) in phase L2 total [kWh] x x x
61.8.0 Positive active energy (A+) in phase L3 total [kWh] x x x
22.8.0 Negative active energy (A-) in phase L1 total [kWh] x x x
42.8.0 Negative active energy (A-) in phase L2 total [kWh] x x x
62.8.0 Negative active energy (A-) in phase L3 total [kWh] x x x
35.8.0 Absolute active energy (|A|) in phase L1 total [kWh] x x x
55.8.0 Absolute active energy (|A|) in phase L2 total [kWh] x x x
75.8.0 Absolute active energy (|A|) in phase L3 total [kWh] x x x
5. Maximum demand registers:
1.6.0 Positive active maximum demand (A+) total [kW] x x x
1.6.1 Positive active maximum demand (A+) in tariff T1 [kW] x x x
1.6.2 Positive active maximum demand (A+) in tariff T2 [kW] x x x
1.6.3 Positive active maximum demand (A+) in tariff T3 [kW] x x x
1.6.4 Positive active maximum demand (A+) in tariff T4 [kW] x x x
2.6.0 Negative active maximum demand (A-) total [kW] x x x
2.6.1 Negative active maximum demand (A-) in tariff T1 [kW] x x x
2.6.2 Negative active maximum demand (A-) in tariff T2 [kW] x x x
2.6.3 Negative active maximum demand (A-) in tariff T3 [kW] x x x
2.6.4 Negative active maximum demand (A-) in tariff T4 [kW] x x x
15.6.0 Absolute active maximum demand (|A|) total [kW] x x x
15.6.1 Absolute active maximum demand (|A|) in tariff T1 [kW] x x x
15.6.2 Absolute active maximum demand (|A|) in tariff T2 [kW] x x x
15.6.3 Absolute active maximum demand (|A|) in tariff T3 [kW] x x x
15.6.4 Absolute active maximum demand (|A|) in tariff T4 [kW] x x x
3.6.0 Positive reactive maximum demand (Q+) total [kvar] x x x
4.6.0 Negative reactive maximum demand (Q-) total [kvar] x x x

31 of 36
MT174 - Electronic three-phase electricity meters
with maximum demand and LP

5.6.0 Reactive maximum demand in Q1 (Q1) total [kvar] x x x


6.6.0 Reactive maximum demand in Q2 (Q2) total [kvar] x x x
7.6.0 Reactive maximum demand in Q3 (Q3) total [kvar] x x x
8.6.0 Reactive maximum demand in Q4 (Q4) total [kvar] x x x
9.6.0 Apparent maximum demand (S+) total [kVA] x x x
6. Cumulative maximum demand registers
1.2.0 Positive active cumulative maximum demand (A+) total [kW] x x /
1.2.1 Positive active cumulative maximum demand (A+) in tariff T1 [kW] x x /
1.2.2 Positive active cumulative maximum demand (A+) in tariff T2 [kW] x x /
1.2.3 Positive active cumulative maximum demand (A+) in tariff T3 [kW] x x /
1.2.4 Positive active cumulative maximum demand (A+) in tariff T4 [kW] x x /
2.2.0 Negative active cumulative maximum demand (A-) total [kW] x x /
2.2.1 Negative active cumulative maximum demand (A-) in tariff T1 [kW] x x /
2.2.2 Negative active cumulative maximum demand (A-) in tariff T2 [kW] x x /
2.2.3 Negative active cumulative maximum demand (A-) in tariff T3 [kW] x x /
2.2.4 Negative active cumulative maximum demand (A-) in tariff T4 [kW] x x /
15.2.0 Absolute active cumulative maximum demand (|A|) total [kW] x x /
15.2.1 Absolute active cumulative maximum demand (|A|) in tariff T1 [kW] x x /
15.2.2 Absolute active cumulative maximum demand (|A|) in tariff T2 [kW] x x /
15.2.3 Absolute active cumulative maximum demand (|A|) in tariff T3 [kW] x x /
15.2.4 Absolute active cumulative maximum demand (|A|) in tariff T4 [kW] x x /
3.2.0 Positive reactive cumulative maximum demand (Q+) total [kvar] x x /
4.2.0 Negative reactive cumulative maximum demand (Q-) total [kvar] x x /
5.2.0 Reactive cumulative maximum demand in Q1 (Q1) total [kvar] x x /
6.2.0 Reactive cumulative maximum demand in Q2 (Q2) total [kvar] x x /
7.2.0 Reactive cumulative maximum demand in Q3 (Q3) total [kvar] x x /
8.2.0 Reactive cumulative maximum demand in Q4 (Q4) total [kvar] x x /
9.2.0 Apparent cumulative maximum demand (S+) total [kVA] x x /
7. Demands in a current demand period
1.4.0 Positive active demand in a current demand period (A+) [kW] x x /
2.4.0 Negative active demand in a current demand period (A-) [kW] x x /
15.4.0 Absolute active demand in a current demand period (|A|) [kW] x x /
3.4.0 Positive reactive demand in a current demand period (Q+) [kvar] x x /
4.4.0 Negative reactive demand in a current demand period (Q-) [kvar] x x /
5.4.0 Reactive demand in a current demand period in Q1 (Q1) [kvar] x x /
6.4.0 Reactive demand in a current demand period in Q2 (Q2) [kvar] x x /
7.4.0 Reactive demand in a current demand period in Q3 (Q3) [kvar] x x /
8.4.0 Reactive demand in a current demand period in Q4 (Q4) [kvar] x x /
9.4.0 Apparent demand in a current demand period (S+) [kVA] x x /
8. Demands in the last completed demand period
1.5.0 Positive active demand in the last completed demand period (A+) [kW] x x /
2.5.0 Negative active demand in the last completed demand period (A-) [kW] x x /
15.5.0 Absolute active demand in the last completed demand period (|A|) [kW] x x /
3.5.0 Positive reactive demand in the last completed demand period (Q+) [kvar] x x /
4.5.0 Negative reactive demand in the last completed demand period (Q-) [kvar] x x /

32 of 36
MT174 - Electronic three-phase electricity meters
with maximum demand and LP

5.5.0 Reactive demand in the last completed demand period in Q1 (Q1) [kvar] x x /
6.5.0 Reactive demand in the last completed demand period in Q2 (Q2) [kvar] x x /
7.5.0 Reactive demand in the last completed demand period in Q3 (Q3) [kvar] x x /
8.5.0 Reactive demand in the last completed demand period in Q4 (Q4) [kvar] x x /
9.5.0 Apparent demand in the last completed demand period (S+) [kVA] x x /
9. Instantaneous power registers
1.7.0 Positive active instantaneous power (A+) [kW] x x /
21.7.0 Positive active instantaneous power (A+) in phase L1 [kW] x x /
41.7.0 Positive active instantaneous power (A+) in phase L2 [kW] x x /
61.7.0 Positive active instantaneous power (A+) in phase L3 [kW] x x /
2.7.0 Negative active instantaneous power (A-) [kW] x x /
22.7.0 Negative active instantaneous power (A-) in phase L1 [kW] x x /
42.7.0 Negative active instantaneous power (A-) in phase L2 [kW] x x /
62.7.0 Negative active instantaneous power (A-) in phase L3 [kW] x x /
15.7.0 Absolute active instantaneous power (|A|) [kW] x x /
35.7.0 Absolute active instantaneous power (|A|) in phase L1 [kW] x x /
55.7.0 Absolute active instantaneous power (|A|) in phase L2 [kW] x x /
75.7.0 Absolute active instantaneous power (|A|) in phase L3 [kW] x x /
16.7.0 Sum active instantaneous power (A+ - A-) [kW] x x /
36.7.0 Sum active instantaneous power (A+ - A-) in phase L1 [kW] x x /
56.7.0 Sum active instantaneous power (A+ - A-) in phase L2 [kW] x x /
76.7.0 Sum active instantaneous power (A+ - A-) in phase L3 [kW] x x /
3.7.0 Positive reactive instantaneous power (Q+) [kvar] x x /
23.7.0 Positive reactive instantaneous power (Q+) in phase L1 [kvar] x x /
43.7.0 Positive reactive instantaneous power (Q+) in phase L2 [kvar] x x /
63.7.0 Positive reactive instantaneous power (Q+) in phase L3 [kvar] x x /
4.7.0 Negative reactive instantaneous power (Q-) [kvar] x x /
24.7.0 Negative reactive instantaneous power (Q-) in phase L1 [kvar] x x /
44.7.0 Negative reactive instantaneous power (Q-) in phase L2 [kvar] x x /
64.7.0 Negative reactive instantaneous power (Q-) in phase L3 [kvar] x x /
9.7.0 Apparent instantaneous power (S+) [kVA] x x /
29.7.0 Apparent instantaneous power (S+) in phase L1 [kVA] x x /
49.7.0 Apparent instantaneous power (S+) in phase L2 [kVA] x x /
69.7.0 Apparent instantaneous power (S+) in phase L3 [kVA] x x /
10. Electricity network quality registers
11.7.0 Instantaneous current (I) [A] x x /
31.7.0 Instantaneous current (I) in phase L1 [A] x x /
51.7.0 Instantaneous current (I) in phase L2 [A] x x /
71.7.0 Instantaneous current (I) in phase L3 [A] x x /
91.7.0 Instantaneous current (I) in neutral [A] x x /
11.6.0 Maximum current (I max) [A] x x /
31.6.0 Maximum current (I max) in phase L1 [A] x x /
51.6.0 Maximum current (I max) in phase L2 [A] x x /
71.6.0 Maximum current (I max) in phase L3 [A] x x /
91.6.0 Maximum current (I max) in neutral [A] x x /

33 of 36
MT174 - Electronic three-phase electricity meters
with maximum demand and LP

12.7.0 Instantaneous voltage (U) [V] x x /


32.7.0 Instantaneous voltage (U) in phase L1 [V] x x /
52.7.0 Instantaneous voltage (U) in phase L2 [V] x x /
72.7.0 Instantaneous voltage (U) in phase L3 [V] x x /
13.7.0 Instantaneous power factor x x /
33.7.0 Instantaneous power factor in phase L1 x x /
53.7.0 Instantaneous power factor in phase L2 x x /
73.7.0 Instantaneous power factor in phase L3 x x /
14.7.0 Frequency [Hz] x x /
11. Tamper registers (energy registers and registers of elapsed time)
C.53.1 Tamper 1 energy register x x /
C.53.2 Tamper 2 energy register x x /
C.53.3 Tamper 3 energy register x x /
C.53.4 Tamper 4 energy register x x /
C.53.11 Tamper 5 energy register x x /
C.53.5 Tamper 1 time counter register x x /
C.53.6 Tamper 2 time counter register x x /
C.53.7 Tamper 3 time counter register x x /
C.53.9 Tamper 4 time counter register x x /
C.53.10 Tamper 5 time counter register x x /
12. Events registers (counters and time-stamps)
C.2.0 Event parameters change - counter x x /
C.2.1 Event parameters change - timestamp x x *
C.51.1 Event terminal cover opened - counter x x /
C.51.2 Event terminal cover opened - timestamp x x *
C.51.3 Event main cover opened - counter x x /
C.51.4 Event main cover opened - timestamp x x *
C.51.5 Event magnetic field detection start - counter x x /
C.51.6 Event magnetic field detection start - timestamp x x *
C.51.7 Event reverse power flow - counter x x /
C.51.8 Event reverse power flow - timestamp x x *
C.7.0 Event power down - counter x x /
C.7.10 Event power down - timestamp x x *
C.51.13 Event power up - counter x x /
C.51.14 Event power up timestamp x x *
C.51.15 Event RTC (Real Time Clock) set - counter x x /
C.51.16 Event RTC (Real Time Clock) set - timestamp x x *
C.51.21 Event terminal cover closed - counter x x /
C.51.22 Event terminal cover closed - timestamp x x *
C.51.23 Event main cover closed - counter x x /
C.51.24 Event main cover closed - timestamp x x *
C.51.25 Event log-book 1 erased - counter x x /
C.51.26 Event log-book 1 erased - timestamp x x *
C.51.27 Event fraud start - counter x x /
C.51.28 Event fraud start - timestamp x x *

34 of 36
MT174 - Electronic three-phase electricity meters
with maximum demand and LP

C.51.29 Event fraud stop - counter x x /


C.51.30 Event fraud stop - timestamp x x *
13. Miscellaneous registers used in sequences
0.9.1 Current time (hh:mm:ss) x x /
0.9.2 Date (YY.MM.DD or DD.MM.YY) x x /
0.9.4 Date and Time (YYMMDDhhmmss) / x /
0.8.0 Demand period [min] x x /
0.8.4 Load profile period [min] (option) x x /
0.0.0 Device address 1 x x /
0.0.1 Device address 2 x x /
0.1.0 MD reset counter x x /
0.1.2 MD reset timestamp x x x
0.2.0 Firmware version x x /
0.2.2 Tariff program ID x x /
C.1.0 Meter serial number x x /
C.1.2 Parameters file code x x /
C.1.4 Parameters check sum x x /
C.1.5 Firmware built date x x /
C.1.6 Firmware check sum x x /
C.6.0 Power down time counter x x /
C.6.1 Battery remaining capacity x x /
F.F.0 Fatal error meter status x x /
C.87.0 Active tariff x x /
0.2.1 Parameters scheme ID x x /
C.60.9 Fraud flag x x /
0.3.0 Active energy meter constant x x /
0.4.2 Current transformer ratio x x /
0.4.3 Voltage transformer ratio x x /

* for up to 6 events the historical values time stamp can be configured

35 of 36
MT174 - Electronic three-phase electricity meters
with maximum demand and LP

Owing to periodically improvements of our products the supplied products


can differ in some details from data stated in this technical description.

Iskraemeco d.d., Energy Measurement and Management


4000 Kranj, Savska loka 4, Slovenia
Telephone (+386 4) 206 40 00, Fax: (+386 4) 206 43 76
http://www.iskraemeco.si, E-mail: info@iskraemeco.si
Published: Iskraemeco, Marketing, Data subjected to alteration without notice. MT174-TD-v1.2-ang.doc

36 of 36

You might also like