Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

GMV 3P Service Manual PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 18

Gree Central Air conditioners

GMV5 HR HEAT RECOVERY UNITS


,167$//$7,21‡&200,66,21,1*‡0$,17(1$1&(0$18$/
Installation, Commissioning, and Maintenance Manual for Export-oriented GMV5 DC Inverter VRF Units

2.2 Introduction to Functions


2.2.1 List of functions
Function Factory Settings Remark
Function Name Function Meaning
Code Code Meaning
Fully or partially recovers
refrigerants in a faulty module
Refrigerant or IDU pipeline according to It can only
A2 —— ——
recovery operation the system pressure after be set.
automatic startup during
maintenance.
Sets the unit to
cooling/heating,
Unit
single-cooling, Cooling/Heating It can be set
A6 cooling/heating nA
single-heating, or air supply function and queried.
function
mode for centralized
management.
Sets different silent modes to
Outdoor silent No silent It can be set
A7 meet users' noise 00
mode settings and queried.
requirements.
Automatically
enables all electronic
expansion valves and
Aftersales It can only
A8 electromagnetic valves —— ——
vacuuming mode be set.
during maintenance to
guarantee vacuum
processing in all pipelines.
Automatically decreases the
No automatic
Conservation power consumption of the It can be set
n0 01 conservation
control 1 unit according to system and queried.
settings
operation parameters.
Forcible defrosting Forcibly enables ODU It can only
n3 —— ——
operation defrosting operation. be set.
Forcibly decreases No capacity
Conservation It can be set
n4 the maximum power 00 output limitation
control 2 and queried.
consumption of the unit. settings
Prevents IDU project number
conflicts when different
Indoor unit project It can only
n5 refrigerating systems are —— ——
number offset be set.
controlled in a centralized
manner.
Queries historical fault It can only be
n6 Fault query —— ——
information of the ODU. queried.
Queries real-time operation It can only be
n7 Parameter query —— ——
parameters of the ODU. queried.
Displays project numbers of
Indoor unit project It can only be
n8 all IDUs through ODU —— ——
number query queried.
operations.
Online IDU Displays the number of It can only be
n9 —— ——
quantity query online IDUs. queried.
Outdoor unit bar Queries the entire-unit bar
It can only be
nb code function code and controller bar code —— ——
queried.
query of ODU.

2.2.2. Description of Functions


(1) A2 Refrigerant recovery operation
This function partially recovers refrigerants in a faulty module or IDU pipeline during unit maintenance. The
93
Installation, Commissioning, and Maintenance Manual for Export-oriented GMV5 DC Inverter VRF Units

refrigerant recovery volume of each basic module is as follows:


Model of Basic Module Maximum Refrigerant Recovery Volume (kg)
GMV-Q224WM/B-X 7.5
GMV-Q280WM/B-X 7.5
GMV-Q335WM/B-X 8.7
GMV-Q400WM/B-X
13.5
GMV-Q450WM/B-X
This function falls into two modes: faulty module refrigerant recovery and IDU pipeline refrigerant recovery.
Refrigerant Recovery Refrigerant Recovery
Remark
Mode Code Mode Name
Basic module refrigerant This mode is selected when a basic module fails and it is required
01
recovery to recover refrigerants from this basic module.
Indoor unit pipeline This mode is selected when an IDU fails and it is required to
02
refrigerant recovery recover refrigerants from the IDU pipeline.

When this function is enabled, the ODU automatically starts and recovers refrigerants to the ODU or IDU
pipeline.
(2) A6 Unit cooling/heating function
This function sets operation modes of the entire unit, including:
Function Mode of ODU
Operation Mode of IDU
Code Name
Cooling mode, dehumidifying mode, heating mode, and air
supply mode.
nA Cooling/Heating
(Note: The heating mode cannot work with other modes at the
same time.) (factory settings)
nC Single-cooling Cooling mode, dehumidifying mode, and air supply mode.
Heating mode and air supply mode.
nH Single-heating (Note: The heating mode cannot work with the air supply
mode at the same time.)
nF Air supply Air supply mode.

The user or administrator can set operation modes of the ODU based on actual situations to prevent
conflicts.
When it is required to set different refrigerating systems to the same function mode, set the master system
according to the above requirements. For the master system settings, see the "Centralized Control Address DIP
Switch (SA2_Addr-CC)" section.
(3) A7 Outdoor silent mode
This function is used when users require lower environment noises, including nighttime automatic silent
mode and forcible silent mode.
For the nighttime automatic silent mode, the system automatically judges the highest daytime environment
temperature and then starts silent operations in a certain interval to guarantee nighttime low-noise operations.
The nighttime automatic silent mode falls into nine categories:
Starting the Silent Mode X Hours Stopping the Nighttime Silent
Silent Mode Code after the Daytime Temperature Mode after Continual Operations Noise Degree
Reaches the Highest for Y Hours
Mode 1 01 6 10
Mode 2 02 6 12
Mode 3 03 8 8
Low-noise mode
Mode 4 04 8 10
Mode 5 05 10 8
Mode 6 06 10 10
94
Installation, Commissioning, and Maintenance Manual for Export-oriented GMV5 DC Inverter VRF Units
Mode 7 07 4 14
Low- and
Mode 8 08 6 8
medium-noise mode
Mode 9 09 12 10 superlow-noise mode

Note: The highest daytime temperature is generally in 13:00-15:00.


For the forcible silent mode, the system runs in low-noise mode no matter in the daytime or nighttime. The
forcible silent mode falls in three categories:
Silent Mode Code Noise Degree
Mode 10 10 Low-noise mode
Low- and
Mode 11 11 medium-noise
mode
superlow-noise
Mode 12 12
mode
Note: The system capacity may fall off after the silent mode is set. Therefore, try to balance the noise with
the capacity in selecting a silent mode category.
The factory setting is “00”.
(4) A8 Aftersales vacuuming mode
This function ensures the vacuum degree of the entire system during maintenance to prevent operation
functions of dead zones. Expansion valves and electromagnetic valves of the unit will be enabled after this
function is set.
(5) n0 Conservation control 1
System conservation is set when conservation operations are required. The default factory setting is
capacity priority control mode. The system capacity may fall off after the conservation mode is set.
Code Function Name
Conservation control – invalid (factory
01
settings)
02 Conservation control - valid

(6) n3 Forcible defrosting operation


This function is set when forcible defrosting is required for the unit during maintenance. After this function is
enabled, the system automatically quits based on quitting conditions and then automatically runs based on
system conditions.
(7) n4 Conservation control 2
The highest capacity output limitation is set when users require forcibly limiting the system power
consumption. The setting scope is as follows:
Code Highest Output Capacity
10 100% (factory settings)
09 90%
08 80%

Note: The cooling or heating effect may fall off after the capacity limitation is set.
(8) n5 Indoor unit project number offset
This function sets the IDU project number when multiple refrigerating systems are controlled in a centralized
manner (by using a remote monitor or centralized controller), avoiding the same project number between
different systems. If the project number is not set, project number conflicts may occur between systems.
These function only needs to be set on the master system, which is the system with the centralized control
address SA2 DIP switch being “00000”. For details, see the "Centralized Control Address DIP Switch
95
Installation, Commissioning, and Maintenance Manual for Export-oriented GMV5 DC Inverter VRF Units

(SA2_Addr-CC)" section.
(9) n6 Fault query
This function queries historical faults of the system. Up to five historical faults can be memorized in time
order.
(10) n7 Parameter query
This function queries operation parameters of each module of the ODU in real time.
(11) n8 Indoor unit address query
This function queries addresses of all IDUs through one operation of the ODU.
(12) n9 Online IDU quantity query
This function queries the number of online IDUs through the ODU.
2.2.3 Function Setting Operations
Step 1: Open the commissioning window of the master unit panel.
Step 2: Power on the entire unit.
Step 3: Press "SW3" on the master unit to enter the to-be-selected status of function settings. By default, the
master unit is displayed as follows:
LED1 LED2 LED3

Function Code Display Mode Current Progress Display Mode Current Status Display Mode

A7 Blinking 00 Blinking 00 Blinking

Users can select corresponding functions by pressing "SW1 (UP)" or "SW2 (DOWN)" on the master unit,
including:
LED1 LED2 LED3

Function Code Display Mode Current Progress Display Mode Current Status Display Mode

A7 Blinking 00 Blinking 00 Blinking


A6 Blinking 00 Blinking 00 Blinking
A2 Blinking 00 Blinking 00 Blinking
A8 Blinking 00 Blinking 00 Blinking
n0 Blinking 01 Blinking 00 Blinking
n3 Blinking 00 Blinking 00 Blinking
n4 Blinking 00 Blinking 00 Blinking
n5 Blinking 00 Blinking 00 Blinking

After selecting the functions to be set, press "SW7" to confirm entering function settings. The master unit is
displayed as follows:
LED1 LED2 LED3

Function Code Display Mode Current Progress Display Mode Current Status Display Mode
A7 On 00 Blinking OC Blinking
A6 On nC Blinking nC Blinking
A2 On 01 Blinking 00 Blinking
A8 On 00 Blinking OC Blinking
n0 On 01 Blinking OC Blinking
n3 On 00 Blinking 00 Blinking
n4 On 10 Blinking OC Blinking
n5 On 00 Blinking OC Blinking

Then go to step 4 to set corresponding functions.


96
Installation, Commissioning, and Maintenance Manual for Export-oriented GMV5 DC Inverter VRF Units
Step 4: Set function parameters.
Setting methods of function parameters are as follows:
• A7 Outdoor silent mode settings
Step 1: Confirm entering the A7 outdoor silent mode settings. The master unit is displayed as follows:
LED1 LED2 LED3
Function Display Silent Mode Display Display
Current Status
Code Mode Code Mode Mode
A7 On 00 Blinking OC Blinking

Step 2: Select a corresponding silent mode by pressing "SW1 (UP)" or "SW2 (DOWN)".
LED1 LED2 LED3
Silent
Function Display Display Current Display
Mode
Code Mode Mode Status Mode
Code
A7 On 00 Blinking OC Blinking
A7 On 01 Blinking OC Blinking
A7 On 02 Blinking OC Blinking
A7 On 03 Blinking OC Blinking
A7 On 04 Blinking OC Blinking
A7 On 05 Blinking OC Blinking
A7 On 06 Blinking OC Blinking
A7 On 07 Blinking OC Blinking
A7 On 08 Blinking OC Blinking
A7 On 09 Blinking OC Blinking
A7 On 10 Blinking OC Blinking
A7 On 11 Blinking OC Blinking
A7 On 12 Blinking OC Blinking

Step 3: Press "SW7" to confirm selecting the mode. The master unit is displayed as follows:
LED1 LED2 LED3
Silent
Function Display Display Current Display
Mode
Code Mode Mode Status Mode
Code
A7 On 00 On OC On
A7 On 01 On OC On
A7 On 02 On OC On
A7 On 03 On OC On
A7 On 04 On OC On
A7 On 05 On OC On
A7 On 06 On OC On
A7 On 07 On OC On
A7 On 08 On OC On
A7 On 09 On OC On
A7 On 10 On OC On
A7 On 11 On OC On
A7 On 12 On OC On

On the master unit, press "SW6" to return to the upper level (press "SW6" in setting status to return to the
upper level; press "SW6" after settings are completed to restore the normal operating status of the unit).
If no button operations are performed on the master unit for five minutes, the function setting automatically
97
Installation, Commissioning, and Maintenance Manual for Export-oriented GMV5 DC Inverter VRF Units

quits and the unit restores the current status.


The default factory setting is “00”, that is, no silent mode.
‚ A6 Unit cooling/heating function settings
Step 1: Confirm entering the A6 unit cooling/heating function settings. The master unit is displayed as
follows:
LED1 LED2 LED3
ODU ODU
Function Display Function Display Function Display
Code Mode Mode Mode Mode Mode
Code Code
A6 On nC Blinking nC Blinking

Step 2: Select a corresponding cooling/heating function by pressing "SW1 (UP)" or "SW2 (DOWN)".
LED1 LED2 LED3

Function Code Display Mode ODU Function Mode Code Display Mode ODU Function Mode Code Display Mode

A6 On nC Blinking nC Blinking
A6 On nH Blinking nH Blinking
A6 On nA Blinking nA Blinking
A6 On nF Blinking nF Blinking
Step 3: Press "SW7" to confirm selecting the mode. The master unit is displayed as follows:
LED1 LED2 LED3

Function Code Display Mode ODU Function Mode Code Display Mode ODU Function Mode Code Display Mode
A6 On nC On nC On
A6 On nH On nH On
A6 On nA On nA On
A6 On nF On nF On

On the master unit, press "SW6" to return to the upper level (press "SW6" in setting status to return to the
upper level; press "SW6" after settings are completed to restore the normal operating status of the unit).
If no button operations are performed on the master unit for five minutes, the function setting automatically
quits and the unit restores the current status.
The default factory setting is “nA” cooling/heating.
ƒ A2 Refrigerant recovery operation settings
Step 1: Confirm entering the A2 refrigerant recovery operation settings. The master unit is displayed as
follows:
LED1 LED2 LED3
Refrigerant
Function Display Display Current Display
Recovery
Code Mode Mode Status Mode
Code
A2 On 01 Blinking 00 Blinking

Step 2: The default setting is “01”. Select "01" or "02" by pressing "SW1 (UP)" or "SW2 (DOWN)". Press
"SW7" to confirm selecting the mode.
On the master unit, press "SW6" to return to the upper level.
If no button operations are performed on the master unit for five minutes, the function setting automatically
quits and the unit restores the current status.
² Indoor unit refrigerant recovery
98
Installation, Commissioning, and Maintenance Manual for Export-oriented GMV5 DC Inverter VRF Units

Step 3: Select "01” as in step 2 to enter IDU refrigerant recovery. Digital LEDs and status LEDs of all basic
modules are displayed as follows:
LED1 LED2 LED3
Function Code Display Mode Refrigerant Recovery Code Display Mode Current Status Display Mode
A2 On 01 On [Module low-pressure Ps] On

LED3 shows the low-pressure value of a module. If the value is negative, LED3 circularly displays the
negative code "nE” and the numeric value every one second. For example, for -30°C, LED3 alternately displays
“nE” for one second and then “30” for another second.
Step 4: Close liquid-tube stop valves of all basic modules of the ODU. When the low-pressure value
displayed on LED3 continually blinks, quickly close air-tube stop valves of all basic modules and then press
"SW7" on the master unit to confirm completing refrigerant recovery or power off the entire unit.
If no operations are performed after the low-pressure value displayed on LED3 continually blinks for three
minutes, the entire unit will be forcibly stopped.
On the master unit, press "SW6" to return to the upper level for restoring the standby status of the entire unit
(press "SW6" in setting status to return to the upper level; press "SW6" after settings are completed to restore
the normal operating status of the unit).
Note:
Another startup is not allowed within 10 minutes after refrigerant recovery.
² Basic module refrigerant recovery
Step 3: Set the basic module requiring refrigerant recovery to module emergency operation status and close
the liquid-tube stop valve of the emergency status module. Select "02” as in step 2 to enter basic module
refrigerant recovery. The display is as follows:
LED1 LED2 LED3
Function Display Current Display Display
Current Status
Code Mode Progress Mode Mode
Module
A2 On 02 On On
high-pressure
LED3 shows the high-pressure value of the module.
Step 4: When the high-pressure value displayed on LED3 continually blinks (displayed as 0°C if the high
pressure is less than 0°C), quickly close the air-tube stop valve of the emergency module and then press "SW7"
on the master unit to confirm completing refrigerant recovery or power off the entire unit.
If no operations are performed after the high-pressure value displayed on LED3 continually blinks for three
minutes, the entire unit will be forcibly stopped.
On the master unit, press "SW6" to return to the upper level for restoring the standby status of the entire unit
(press "SW6" in setting status to return to the upper level; press "SW6" after settings are completed to restore
the normal operating status of the unit).
Note:
Before the basic module refrigerant recovery operation, users must close the liquid-tube stop valve of
the basic module requiring refrigerant recovery.
Another startup is not allowed within 10 minutes after refrigerant recovery.
„ A8 Aftersales vacuuming mode settings
Step 1: Confirm entering the A8 aftersales vacuuming mode settings. The master unit is displayed as
follows:
99
Installation, Commissioning, and Maintenance Manual for Export-oriented GMV5 DC Inverter VRF Units

LED1 LED2 LED3


Function Display Current Display Current Display
Code Mode Progress Mode Status Mode
A8 On 00 Blinking OC Blinking

Enter the to-be-confirmed status of system vacuuming mode settings.


Step 2: Press "SW7" to confirm entering the to-be-confirmed status of system vacuuming mode settings. All
modules are displayed as follows:
LED1 LED2 LED3
Function Display Current Display Current Display
Code Mode Progress Mode Status Mode
A8 On 00 On OC On

Expansion valves and electromagnetic valves of all outdoor and IDUs are opened, and the entire unit cannot
be enabled.
Press "SW6" on the master unit to quit the vacuuming status. Alternatively, the entire unit quits the
vacuuming status after 24 hours.
… n0 System conservation operation settings
Step 1: Confirm entering the n0 system conservation operation settings. The master unit is displayed as
follows:
LED1 LED2 LED3

Function Code Display Mode Code Display Mode Current Status Display Mode

n0 On 01 Blinking OC Blinking

Step 2: Select a corresponding mode by pressing "SW1 (UP)" or "SW2 (DOWN)".


LED1 LED2 LED3

Function Code Display Mode Code Display Mode Current Status Display Mode

n0 On 01 Blinking OC Blinking

n0 On 02 Blinking OC Blinking

Step 3: Press "SW7" to confirm selecting the mode. The master unit is displayed as follows:
LED1 LED2 LED3

Function Code Display Mode Code Display Mode Current Status Display Mode

n0 On 01 On OC On
n0 On 02 On OC On

If no button operations are performed for five minutes, the function setting automatically quits and the unit
restores the current status. (Press "SW6" in setting status to return to the upper level; press "SW6" after settings
are completed to restore the normal operating status of the unit.)
† n3 Forcible defrosting operation settings
Step 1: Confirm entering the n3 forcible defrosting operation settings. The master unit is displayed as
follows:
LED1 LED2 LED3
Function Code Display Mode Current Progress/Mode Display Mode Current Status Display Mode
n3 On 00 Blinking 00 Blinking

Step 2: Press "SW7" to confirm entering forcible defrosting. The master module is displayed as follows:
LED1 LED2 LED3
100
Installation, Commissioning, and Maintenance Manual for Export-oriented GMV5 DC Inverter VRF Units

Function Code Display Mode Current Progress/Mode Display Mode Current Status Display Mode
n3 On 00 On 00 On

When the unit reaches defrosting quit conditions, the system automatically quits and restores the normal
operation control.
‡ n4 Highest capacity output limitation settings
Step 1: Confirm entering the n4 highest capacity output limitation settings. The master unit is displayed as
follows:
LED1 LED2 LED3
Function Code Display Mode Highest Output Capacity Display Mode Current Status Display Mode
n4 On 10 Blinking OC Blinking

Step 2: Select a corresponding capacity limitation value by pressing "SW1 (UP)" or "SW2 (DOWN)".
LED1 LED2 LED3
Function Code Display Mode Highest Output Capacity Display Mode Current Status Display Mode
n4 On 10 Blinking OC Blinking
n4 On 09 Blinking OC Blinking
n4 On 08 Blinking OC Blinking

Step 3: Press "SW7" to confirm selecting the mode. The master module is displayed as follows:
LED1 LED2 LED3
Function Code Display Mode Highest Output Capacity Display Mode Current Status Display Mode
n4 On 10 On OC On
n4 On 09 On OC On
n4 On 08 On OC On

If no button operations are performed on the master unit for five minutes, the function setting automatically
quits and the unit restores the current status. (Press "SW6" in setting status to return to the upper level; press
"SW6" after settings are completed to restore the normal operating status of the unit.)
ˆ n5 Indoor unit project number offset settings
Step 1: Confirm entering the n5 IDU project number offset settings. The master unit is displayed as follows:
LED1 LED2 LED3
Function Code Display Mode Current Progress/Mode Display Mode Current Status Display Mode

n5 On 00 Blinking 00 Blinking

Step 2: Press "SW7" to send the project number offset command. The master module is displayed as
follows:
LED1 LED2 LED3
Function Code Display Mode Current Progress/Mode Display Mode Current Status Display Mode
n5 On 00 On OC On

After 10 seconds, the system quits this mode and restores the normal operation mode.
Note: This function only needs to be set on the master system, which is the system with the centralized
control address SA2 DIP switch being "00000". For details, see the "Centralized Control Address DIP Switch
(SA2_Addr-CC)" section.

101
Installation, Commissioning, and Maintenance Manual for Export-oriented GMV5 DC Inverter VRF Units

2.3 Function Query Operations


Step 1: Open the commissioning window of the master unit panel.
Step 2: Power on the entire unit.
Step 3: Press "SW4" on the master unit to enter the query status.
Step 4: Select a function to be queried by pressing "SW1 (UP)" or "SW2 (DOWN)" on the master unit. By default,
the A7 outdoor silent mode is displayed for query.
For example, select the A6 unit cooling/heating function. The display is as follows:
LED1 LED2 LED3
Function Code Display Mode ODU Function Mode Code Display Mode ODU Function Mode Code Display Mode
A6 On nA On nA On
Step 5: If the n8 IDU address query is selected, the display is as follows. Enter the to-be-confirmed status of IDU
project number query.
LED1 LED2 LED3
Function Code Display Mode Current Progress/Mode Display Mode Current Status Display Mode
n8 Blinking 00 Blinking 00 Blinking

Press "SW7" and select the IDU project number query on the master unit. The master unit is displayed as
follows. Other modules are displayed in normal status.
LED1 LED2 LED3
Function Code Display Mode Current Progress/Mode Display Mode Current Status Display Mode
n8 On 00 On 00 On

Regardless of the current display status of wired controllers or display panels of all IDUs, the current display
status is all switched to the IDU project number. However, it does not influence the settings and operation status
of outdoor and IDUs.
On the master unit, press "SW6" to return to the upper level. The IDU retains the project number display
status.
On the master unit, press and hold "SW6" to quit the address display status for all IDUs and return to the
upper level.
If no quit button operations are performed on the master unit for 30 minutes, the function setting
automatically quits and the unit restores the current status.
Step 6: If the n9 IDU address query is selected, the display is as follows:
LED1 LED2 LED3
Function Display Number of IDUs (Thousands-place Display Number of IDUs (Tens-place Display
Code Mode Hundreds-place) Mode Ones-place) Mode
n9 On 00 On 00 Blinking

The digital LED2 displays the number of IDUs (thousands-place hundreds-place) and the digital LED3
displays the number of IDUs (tens-place ones place). For example, if the number of IDUs is 75, "0075" is
displayed.
If no button operations are performed on the master unit for five minutes, the function setting automatically
quits and the unit restores the current status.
Note: The online IDU quantity query function applies to a single refrigerating system only.
Step 7: If the n6 fault query is selected, the display is as follows. Enter the to-be-confirmed status of fault query.
LED1 LED2 LED3
Function Code Display Mode Current Progress/Mode Display Mode Current Status Display Mode
n6 Blinking 00 Blinking 00 Blinking

102
Installation, Commissioning, and Maintenance Manual for Export-oriented GMV5 DC Inverter VRF Units

Press "SW7" on the master unit to confirm fault query.


Select a fault to be queried by pressing "SW1 (UP)" or "SW2 (DOWN)". LED3 alternately displays the
historical fault code and module address in an interval of one second in the sequence of fault records. LED2
displays the fault sequence number. If there not historical faults, LED2 and LED3 display “00” by default. Up to
five historical faults can be queried. The faults that can be queried are as follows:
Code Code
E1 High-pressure protection P9 Inverter compressor out-of-step protection
Communication failure between the master
E3 Low-pressure protection C2
unit and inverter compressor driver
Over-high temperature protection for inverter
U4 Lack of refrigerant protection P8
compressor driver module
Temperature sensor failure of inverter
E2 Discharge low-temperature protection P7
compressor driver module
Charge circuit failure of inverter compressor
J9 Over-low pressure ratio protection PF
driver
DC bus line over-low voltage protection for
J8 Over-high pressure ratio protection HL
inverter outdoor fan driver
DC bus line over-high voltage protection for
J7 Four-way valve leakage protection HH
inverter outdoor fan driver
High-temperature protection of compressor Inverter outdoor fan driver IPM module
E5 H6
1 protection
High-temperature protection of compressor
E6 HJ Inverter outdoor fan startup failure
2
J2 Over-current protection of compressor 2 HE Inverter outdoor fan phase lack protection
Top high-temperature protection of
EU H3 Inverter outdoor fan driver module reset
compressor 1
Top high-temperature protection of
Eb H5 Inverter outdoor fan over-current protection
compressor 2
DC bus line over-low voltage protection for Current detection circuit failure of inverter
PL HC
inverter compressor driver outdoor fan driver
DC bus line over-high voltage protection for
PH H9 Inverter outdoor fan out-of-step protection
inverter compressor driver
Inverter compressor driver IPM module Communication failure between the master
P6 C3
protection unit and inverter outdoor fan driver
Over-high temperature protection for inverter
PJ Inverter compressor startup failure H8
outdoor fan driver module
Temperature sensor failure of inverter
PE Inverter compressor phase lack protection H7
outdoor fan driver module
Malfunction of exit tube temperature sensor
P3 Inverter compressor driver module reset Fd
of mode exchanger
Malfunction of inlet tube temperature sensor
P5 Inverter compressor over-current protection Fn
of mode exchanger
Current detection circuit failure of inverter Communication malfunction between mode
PC CE
compressor driver exchanger and IDU
Communication malfunction between mode
qC Cooling code for main unit Cd
exchanger and ODU
Malfunction of network for IDU and ODU of
qH Heating code for main unit Cn
mode exchanger
Communication malfunction of mode
qA Code for heat recovery status Cy
exchanger
Indoor unit’s branch is not inconsistent for
LU
one-to-more unit of heat recovery system
The display is as follows:
LED1 LED2 LED3
Function Display Fault
Display Mode Current Status Display Mode
Code Mode Sequence
n6 On 01 On Displayed alternately
n6 On 02 On Displayed alternately
n6 Historical
On 03 On Displayed alternately
fault/module address
n6 On 04 On Displayed alternately
n6 On 05 On Displayed alternately
103
Installation, Commissioning, and Maintenance Manual for Export-oriented GMV5 DC Inverter VRF Units

"01-05" indicates the fault sequence from the earliest to the latest.
If there are less than five historical faults, LED2 and LED3 display “00” indicating there are no more
historical faults after the last fault is displayed.
In fault query status, press and hold "SW7" for five seconds to clear all historical faults of the ODU.
Step 8: If the n7 parameter query is selected, the display is as follows. Enter the to-be-confirmed status of
parameter query.
LED1 LED2 LED3
Function Code Display Mode Current Progress/Mode Display Mode Current Status Display Mode
n7 Blinking 00 Blinking 00 Blinking

On the master unit, press "SW7" to confirm parameter query and enter the module confirmation status for
parameter query. The display is as follows:
LED1 LED2 LED3
Function Code Display Mode Module Address Display Mode Current Status Display Mode
n7 On 01 Blinking 00 Blinking
n7 On 02 Blinking 00 Blinking
n7 On 03 Blinking 00 Blinking
n7 On 04 Blinking 00 Blinking

Select a module for parameter query by pressing "SW1 (UP)" or "SW2 (DOWN)" and then press "SW7". The
display is as follows:
LED1 LED2 LED3
Function Code Display Mode Parameter Code Display Mode Current Status Display Mode
n7 On XX On Parameter value Blinking

LED2 displays the parameter code of the module and LED3 displays the parameter value. Parameters are
displayed in the following sequence. By default, the outdoor environment temperature value is displayed. Select
a corresponding parameter value by pressing "SW1 (UP)" or "SW2 (DOWN)".

Parameter
Parameter Name Unit Remark
Code
01 Outdoor environment temperature °C
02 Operation frequency of compressor 1 Hz
03 Operation frequency of compressor 2 Hz
04 Operation frequency of outdoor fan Hz
05 Module high-pressure °C
06 Module low-pressure °C
07 Discharge temperature of compressor 1 °C
08 Discharge temperature of compressor 2 °C
09 Discharge temperature of compressor 3 °C This parameter is invalid for the GMV5 series.
10 Discharge temperature of compressor 4 °C This parameter is invalid for the GMV5 series.
11 Discharge temperature of compressor 5 °C This parameter is invalid for the GMV5 series.
12 Discharge temperature of compressor 6 °C This parameter is invalid for the GMV5 series.
13 Operation frequency of compressor 3 Hz This parameter is invalid for the GMV5 series.
14 Current value of compressor 1 A

104
Installation, Commissioning, and Maintenance Manual for Export-oriented GMV5 DC Inverter VRF Units

15 Current value of compressor 2 A


16 Current value of compressor 3 A This parameter is invalid for the GMV5 series.
17 Current value of compressor 4 A This parameter is invalid for the GMV series.
18 Current value of compressor 5 A This parameter is invalid for the GMV5 series.
19 Current value of compressor 6 A This parameter is invalid for the GMV5 series.
20 Reserved
21 Module temperature of compressor 1 °C
22 Module temperature of compressor 2 °C
23 Module temperature of outdoor fan 1 °C
24 Module temperature of outdoor fan 2 °C
25 Outdoor unit heating EXV1 PLS
26 Outdoor unit heating EXV2 PLS
27 Subcooler EXV PLS
28 Defrosting temperature °C
Liquid-extracting temperature of
29 °C
subcooler
30 Outlet temperature of accumulator °C
31 Oil return temperature °C This parameter is invalid for the GMV5 series.
32 Inlet-tube temperature of condenser °C This parameter is invalid for the GMV5 series.
Note:
If a parameter value is negative, LED3 circularly displays the negative code "nE” and the numeric value
every one second. For example, for -30°C, LED3 alternately displays “nE” for one second and then “30” for
another second.
The discharge temperature and environment temperature are displayed as four-digit values, circularly
displaying the higher two digits and the lower two digits. For example, if "01" and "15" are alternately displayed, it
indicates 115°C. If "nE", "00", and "28" are alternately displayed, it indicates -28°C.
If a parameter is invalid for the unit, “00” is displayed.
If no button operations are performed on the master unit for five minutes, the function setting automatically
quits and the unit restores the current status.
Step 9: If the nb ODU bar code query is selected, the display is as follows. Enter the to-be-confirmed status of
ODU bar code query.
LED1 LED2 LED3
Function Code Display Mode Current Progress/Mode Display Mode Current Status Display Mode
nb Blinking 00 Blinking 00 Blinking

Press "SW7" on the master unit to enter the next-level menu selection. The display is as follows:
LED1 LED2 LED3
Function Code Display Mode Module Address Display Mode Current Status Display Mode
nb On 01 Blinking 00 Blinking
nb On 02 Blinking 00 Blinking
nb On 03 Blinking 00 Blinking
nb On 04 Blinking 00 Blinking

Select a module for query by pressing "SW1 (▲)" or "SW2 (▼)" and then press "SW7". The display is as
105
Installation, Commissioning, and Maintenance Manual for Export-oriented GMV5 DC Inverter VRF Units

follows:
LED1 LED2 LED3
Function Code Display Mode Parameter Code Display Mode Current Status Display Mode
nb On Un/Pc Blinking -n Blinking

Note: Un indicates the entire-unit bar code and Pc indicates the controller bar code.
After confirming the module, select a bar code sequence by pressing "SW1 (▲)" or "SW2 (▼)". The display
sequence is as follows:
Entire-unit bar code (bits 1-13) and controller bar code (bits 1-13), that is, entire-unit bar code header →
entire-unit bar code (bits 1-6) → entire-unit bar code (bits 7-12) → entire-unit bar code (bit 13) → controller bar
code header → controller bar code (bits 1-6) → controller bar code (bits 7-12) → controller bar code (bit 13). The
display is as follows:
LED1 LED2 LED3
Parameter Code Display Mode Parameter Code Display Mode Parameter Code Display Mode
Code On Code On Code On

Example:
Entire-unit bar code: N1R0128150066
Controller bar code: N1M0128150067
The display sequence is as follows:
LED1 LED2 LED3
Parameter Code Display Mode Parameter Code Display Mode Parameter Code Display Mode
nb On Un Blinking -n Blinking

LED1 LED2 LED3
Parameter Code Display Mode Parameter Code Display Mode Parameter Code Display Mode
N1 On R0 On 12 On

LED1 LED2 LED3
Parameter Code Display Mode Parameter Code Display Mode Parameter Code Display Mode
81 On 50 On 06 On

LED1 LED2 LED3
Parameter Code Display Mode Parameter Code Display Mode Parameter Code Display Mode
6X On/Off XX Off XX Off

LED1 LED2 LED3
Parameter Code Display Mode Parameter Code Display Mode Parameter Code Display Mode
nb On Pc Blinking -n Blinking

LED1 LED2 LED3
Parameter Code Display Mode Parameter Code Display Mode Parameter Code Display Mode
N1 On M0 On 12 On

LED1 LED2 LED3
106
Installation, Commissioning, and Maintenance Manual for Export-oriented GMV5 DC Inverter VRF Units

Parameter Code Display Mode Parameter Code Display Mode Parameter Code Display Mode
81 On 50 On 06 On

LED1 LED2 LED3
Parameter Code Display Mode Parameter Code Display Mode Parameter Code Display Mode
7X On/Off XX Off XX Off

If a parameter is invalid for the unit, "00" is displayed.


On the master unit, press "SW6" to return to the upper level if there are two levels of menu. Press "SW4" to
quit the query status.
If no button operations are performed on the master unit for five minutes, the function setting automatically
quits and the unit restores the current status.

Step 4: In query status, press "SW4" to quit.

2.4 Basic Operations for Engineering Commissioning


2.4.1 Basic Operations
Basic Operations Operation Method Remark
Starting engineering Press and hold "SW7" on the master unit
commissioning for more than five seconds.  ——
In this mode, the system does not detect the
Selecting Press "SW4" and "SW5" simultaneously communication status between the IDU and
no-wired-controller in any commissioning progress after the wired controller any more. Commissioning
commissioning mode unit enters the commissioning status. can be performed on the IDU without
configuring the wired controller.
In engineering commissioning status,
Quitting engineering press and hold "SW7" for more than five
 ——
commissioning seconds on the master unit to quit
commissioning.
This function is valid after step 9. For
In engineering commissioning status, example, if receiving a pausing engineering
press "SW6" on the master unit to retain commissioning signal during the process of
Pausing engineering
the previous commissioning completion "10. Pre-startup ODU valve status judging
commissioning
phase of the current commissioning phase" in step 11, the system will restore
phase. the completion phase of "9. Pre-startup
refrigerant judging phase" in step 10.
Continuing In engineering commissioning pause
engineering status, press "SW6" on the master unit to  ——
commissioning continue engineering commissioning.

2.4.2 Restoring Factory Settings


Restoring Factory Prompt for
Setting Method Remark
Settings Successful Settings
Press and hold "SW8" All factory settings of the ODU are
Restoring setting All LEDs blink for
on the master unit for restored and the unit waits for
1 three seconds.
more than 10 seconds. re-commissioning.
Re-commissioning is not required. The
Press and hold "SW3"
number of outdoor and IDUs is
Restoring setting and "SW8" on the All LEDs blink for
memorized. Addresses of outdoor and
2 master unit for more five seconds.
IDUs are all cleared. All the other function
than 10 seconds.
settings are cleared.
Re-commissioning is not required. The
Press and hold "SW5"
number of outdoor and IDUs is
Restoring setting and "SW8" on the All LEDs blink for
memorized. Addresses of outdoor and
3 master unit for more seven seconds.
IDUs retain the preceding settings. All the
than 10 seconds.
other function settings are cleared.

107
Installation, Commissioning, and Maintenance Manual for Export-oriented GMV5 DC Inverter VRF Units

Part 3 Commissioning Process


Note:
! It is forbidden to directly connect the compressor with power supply and forcibly power it on during
commissioning and maintenance.
! Engineering commissioning operations must be performed on the GMV5 serial unit. Otherwise, the unit
cannot properly run.
! Before commissioning is completed, the main board of ODU displays "module address 0F A0" and that
of IDU displays “A0”.
! A module must be set to master module and only one can be set during commissioning.
! An IDU must be set to master IDU and only one can be set during commissioning.
! Other functions can use the factory settings if there are not special engineering requirements.

1 Necessity of VRF Engineering Commissioning


Different form ordinary air conditioning units, the VRF system raises high design requirements and easily
incurs operation-affected factors such as impurities and water during engineering installation. Due to the
requirements on engineering design/installation complexity and high-precise system control, commissioning is
mandatory after engineering installation. Only a qualified unit can be delivered for use.

2 Required Files and Tools for Engineering


Commissioning
2.1 Required Tools for Engineering Commissioning of GREE VRF
Inner hexagon spanner Digital thermometer
Shifting spanner Noise meter
Cross screwdriver Clamp meter
Straight screwdriver Digital multimeter
Vacuum pump Electricity meter
Electronic balance Timer
System high and low pressure gauges for
Step ladder
corresponding refrigerants
Wind-speed transmitter

The GMV5 VRF provides two commissioning methods. One is to perform commissioning by pressing
buttons on the main board of ODU. The other is to perform commissioning on a PC through professional
software. Parameters of the ODU and IDU can be simultaneously displayed with the second method. (For details
about these methods, refer to respective instructions.)
2.2 Commissioning Files
The following commissioning files are required to record installation and commissioning of units:
pre-commissioning scheme determination meeting minutes, commissioning personnel record tables,
commissioning system appearance check record tables, commissioning data record tables, and commissioning
reports. See attached tables for file formats.

3 Engineering Commissioning Procedures


Step 1: Pre-commissioning Preparations
˄1˅Overall Commissioning Plan
108
Installation, Commissioning, and Maintenance Manual for Export-oriented GMV5 DC Inverter VRF Units

Before commissioning, the person-in-charge should learn about the overall engineering progress plan,
overall workload of engineering commissioning, possible influence factors in achieving the commissioning
progress, and required labors and materials.
˄2˅Composition of Commissioning Members
Commissioning members comprise aftersales commissioning personnel and installation personnel.
All commissioning participants must take part in professional training courses before unit commissioning. All
participants can be grouped as required and each group should include at least professional commissioning
personnel and assistants.
˄3˅Preparations of Commissioning Tools and Instruments
a. Make sure that the following tools or instruments are prepared before commissioning.
b. Make sure that the commissioning software is correct before commissioning.
c. The professional aftersales commissioning software provided by GREE should be used for
commissioning of GREE VRF system.
d. Make sure that all required files and parameter records are prepared.
Step 2: Pre-commissioning Check
Installation environment check covers the heat exchange environment of unit and electromagnetic radiant
components. All requirements should comply with national and local electrical standards. For any installation
incompliance, records should be made for providing an analysis basis during refrigerating system testing.
˄1˅Installation Appearance Check
Installation appearance check covers whether pipeline installation complies with specifications, whether
refrigerant pipes and condensing drainage pipes are thermal insulated, and whether
Refrigerant pipes should be tidily installed, with outdoor and indoor disperse pipes leaning in the required
scope. For any installation incompliance, records should be made for providing an analysis basis during
refrigerating system testing.
Refrigerant pipes and condensing drainage pipes should not be exposed. If any pipe is exposed, an
immediate amendment is required to avoid serious loss.
˄2˅Refrigerating System Check
1) Before commissioning, make sure that the stop valve of each module reaches the maximum opening
degree. Check whether there is any refrigerator oil leakage around the valve. If there is, immediately check for
leakage with soap bubbles or leak detectors. If confirming that leakage exists, immediately stop commissioning
and solve the problem before continuing commissioning.

2) Check system refrigerants before startup.


Before the system is started, connect the liquid-tube valve of ODU with a high pressure gauge and the

109

You might also like