WAPDA Specification for Solid State
Whole Current Energy Meter DD-S-60:07
_____________________________________________________________________________
CONTENTS
Section Page
0. Foreword …………………………………………… 3
1. Scope …………………………………………… 3
2. Reference Standards …………………………………………… 3
3. Definitions …………………………………………… 4
4. Performance Standards …………………………………………… 7
5. Mechanical Requirements …………………………………………… 8
6. Electrical Requirement …………………………………………… 10
7. Influence of Other Quantities …………………………………………. 12
8. Meter Characteristics …………………………………………… 14
9. Tests …………………………………………… 16
10. Name & Rating Plate …………………………………………… 17
11. Packing …………………………………………… 17
12. Sample …………………………………………… 18
13. Prototype …………………………………………… 18
14. Inspection …………………………………………… 18
15. Warranty …………………………………………… 21
16. Training …………………………………………… 21
17. Bid Data, Test Certificates, Drawings, Literature,
Reference List & Manufacturing Experience. …………………… 21
17. Annex – I (Reference Standards) …………………….…………… 22
18. Schedule of Technical Data …………………………………… 25
19. Annex – II (Format of Software) …………………………………... 30
Table
*********************
-2-
WAPDA Specification for Solid State
Whole Current Energy Meter DD-S-60:07
_____________________________________________________________________________
SPECIFICATION
DD-S-60:2007
0 FOREWORD
0.1 This Specification has been prepared by the Standard, Directorate of Distribution Engg.
Department of WAPDA.
0.2 This Specification is intended for the purpose of technical specification only for the
procurement of material and does not include provisions of contract, unless otherwise
provided in the contract.
0.4 This specification will supercede the previous specification DDS-60:2003 with all relevant
amendments
1. SCOPE
1.1 The Specification covers total static poly-phase energy meters capable of measuring MDI-
KW, KWH, along with other quantities and built-in programmable features mentioned in
this specification.
2. REFERENCE STANDARDS.
-3-
WAPDA Specification for Solid State
Whole Current Energy Meter DD-S-60:07
_____________________________________________________________________________
3.0 DEFINITIONS
3.6 MEMORY
Element which stores digital information
3.8 DISPLAY
Device which displays the content(s) of (a) memory (ies)
3.9 REGISTER
Electronic device comprising both memory and display which stores and displays
information.
-4-
WAPDA Specification for Solid State
Whole Current Energy Meter DD-S-60:07
_____________________________________________________________________________
3.13 CONSTANT
Value expressing the relation between the energy registered by the meter and the
corresponding value of the test output. If this value is a number of pulses, the constant
should be either pulses per kilowatt-hour (imp/kWh) or watt hours per pulse (Wh/imp).
3.17 COVER
Enclosure on the front of the meter, made either wholly of transparent material or opaque
material provided with window (s) through which the operation indicator (if fitted) and the
display can be read.
3.18 CASE
Comprises the base and the cover.
3.22 CLEARANCE
Shortest distance measured in air between two conductive parts.
-5-
WAPDA Specification for Solid State
Whole Current Energy Meter DD-S-60:07
_____________________________________________________________________________
Since the true value cannot be determined, it is approximated by a value with a stated
uncertainty that can be traced to standards agreed upon between manufacturer and user or
to national standards.
-6-
WAPDA Specification for Solid State
Whole Current Energy Meter DD-S-60:07
_____________________________________________________________________________
4. PERFORMANCE STANDARDS
-7-
WAPDA Specification for Solid State
Whole Current Energy Meter DD-S-60:07
_____________________________________________________________________________
5. MECHANICAL REQUIREMENTS
Meters shall be designed and constructed for Outdoor use in such a way as to avoid
introducing any danger in normal use and under normal conditions, so as to ensure
especially:-
All parts which are subject to corrosion under normal working conditions shall be
protected effectively. Any protective coating shall not be liable to damage by ordinary
handling nor damage due to exposure to air, under normal working conditions. Meters
shall withstand solar radiation test.
5.2 The electrical connections in the meter shall be resistant to tampering. These shall be made
so as to prevent their opening from outside the meter base/cover accidentally or
deliberately without breaking the seals.
5.3 CASE
5.3.1 The meter shall have a reasonably dust proof and moisture proof case, which can be sealed
in such a way that the internal parts of the meter are accessible only after breaking the
seals. The meter shall comply with the dust proof and water proof requirements of IEC-
60529 amended to date.
5.4.1 The terminals shall be grouped in a terminal block having adequate insulating properties
and mechanical strength. The material (Bakelite or similar material) of which the terminal
block is made shall be capable of passing the tests given in ISO Standard 75 for a
temperature of 135 Deg. C and glow wire test of 960 Degree C.
5.4.2 Arrangements may be provided to prevent the exit of terminal block by force from outside
without opening the meter cover.
5.4.3 The terminal shall be pressure plate type to permit the connection of both solid and
stranded aluminum conductor of diameter 11mm to a depth of atleast 25mm without being
directly bitten by the screws used for fixing the conductors. The terminals in which screws
bite directly into the conductor shall not be acceptable.
5.4.4 The moving parts of the terminals including screws shall be made of brass having
minimum electrical conductivity of 65% of copper. The fixed part of terminal i.e. pressure
plate shall be made of copper having a thickness of 5mm and minimum electrical
conductivity of 99 % of stranded copper.
5.4.5 The terminals shall be Tin or Nickel-plated. In case of Tin plating the thickness shall be 20
microns on all parts except threaded portions on which it shall be min 10 microns on all
parts except the threaded portion on which it shall be min 7 microns.
-9-
WAPDA Specification for Solid State
Whole Current Energy Meter DD-S-60:07
_____________________________________________________________________________
The complete meter i.e. case terminal block shall meet the requirements of clauses 5 & 6
of IEC 620529. For protection against penetration of dust &Water the meter shall be IP51
compliant.
6. ELECTRICAL REQUIREMENTS
Reference Frequency 50 Hz
Running with no load From 0.8 to 1.15 of reference voltage but with no
current.
Meter shall not produce more than one pulse or shall
not complete one revolution.
- 10 -
WAPDA Specification for Solid State
Whole Current Energy Meter DD-S-60:07
_____________________________________________________________________________
When the meter is Under reference conditions given in clause 8.5 of IEC 62053-21, the
percentage errors shall not exceed the limits given in Table I & II.
TABLE–I
Percentage error limits with balanced loads
- 11 -
WAPDA Specification for Solid State
Whole Current Energy Meter DD-S-60:07
_____________________________________________________________________________
T A B L E – II
Percentage error limits
(Meter carrying a single phase load but with balanced polyphase voltages applied to the voltage circuits)
The difference between the percentage error when the meter is carrying a single phase load and a
balanced polyphase load at basic current and unity power factor, shall not exceed 1.5%.
The additional percentage error due to the change of influence quantities with respect to
reference conditions, as given in clause 8.5 of IEC 62053-21 shall not exceed the limits
given in Table-III.
T A B L E – III
Influence Quantities
- 12 -
WAPDA Specification for Solid State
Whole Current Energy Meter DD-S-60:07
_____________________________________________________________________________
1) For the voltage ranges from -20% to -10% and +10% to +15% the limits of variation in
%age errors are three times the values given in table-III.
Below 0.8Un, the error of the meter may vary between +10% and –100%.
2) The distortion factor of the voltage shall be less than 1%.
3) Polyphase meters shall measure and register within the limits of variation in %age error
shown in table-3 if one or two phases of the 3-phase network are interrupted.
The magnetic induction shall be obtained by placing the meter in the centre of a circular
coil, 1m in mean diameter, of square section and a small radial thickness relative to the
diameter, and having 400 At.
6) Such an accessory, when enclosed in the meter case, is energized intermittently, for
example the electromagnet of a multi rate register.
It is preferable that the connection to the auxiliary device(s) is marked to indicate the
correct method of connection. If these connections are made by means of plugs and
sockets, they should be irreversible.
T A B L E – IV
Temperature Coefficient
Value of Current Power Factor Mean Temp. coefficient %K
for meters
From 0.1 Ib to Imax 1 0.05
From 0.2 Ib to Imax 0.5 lagging 0.07
- 13 -
WAPDA Specification for Solid State
Whole Current Energy Meter DD-S-60:07
_____________________________________________________________________________
The relation between the test output and the indication in the display shall comply with the
marking on the name plate.
Output devices generally do not produce homogeneous pulse sequences. Therefore, the
manufacturer shall state the necessary number of pulses to ensure a measuring accuracy of
atleast 1/10 of the class of the meter at the different test points.
7. METER CHARACTERISTICS
The meter shall generally comprise of the following characteristics as a minimum. A list
of characteristics is appended below :
¾ Energy (KWh).
¾ Max. Demand (KW), Block and Rolling both shall be programmable.
¾ Demand Interval shall be programmable for 15, 30 and 60 minutes for Block Demand.
Which should be divisible in five equal sub-intervals in case of Rolling Demand.
¾ Cumulative Max. Demand (KW).
¾ No. of Resets.
¾ Time left in Interval.
¾ At-least twelve months Billing Data kWh, KW and number of resets shall be available
at all times.
¾ The battery shall be connected using standard connectors, it shall not be welded,
brazed or soldered and it shall be replaceable in the field.
¾ Every Meter shall have a unique serial No. in its memory which can be
displayed/reported.
¾ The No. of times programmed and the identification of the last programmer along-with
Date & Time stamp shall be reported/displayed.
¾ A programmable meter ID code shall be provided.
¾ At-least two levels of access/security codes shall be provided one for meter reading
(only) by the authorized personnel and a second one for programming and reading.
¾ Meter shall keep on recording/operating as long as voltage exists on any two terminal
of the meter with or without neutral.
¾ If data entry keys/button are provided in the meter for manual entry of data these shall
be inside the meter cover except the reset device and display scroll push button. No
data shall be changeable modified by the simultaneous operation of these switches or
in any way without opening the meter cover.
¾ The meter shall be protected against any external interference such as influence of
Strong Electromagnet, CD drive, Mobile phones and shall comply to all relevant
IEC/ANSI standards for functional performance and loss of data.
¾ A strong magnet having strength of 0.7 Tesla, when measured in an air gap of 3mm,
rectangular in shape with minimum dimension of 65 x 35 x 35mm shall not effect the
accuracy of meter by more than 4% at Basic Current and Unity Power Factor when
applied on the meter from any direction. After the test meter shall perform within
prescribed limit of Accuracy
7.2.3 Diagnostics
The meter shall display cautions and diagnostics for the following conditions;
¾ Un-programmed Meter.
¾ Self check diagnostics for RAM/ROM, Processor, non-volatile memory failure and
other essential hardware circuitry.
7.3 DISPLAY
¾ The Display shall be LCD type with at-least 6 digits for Energy consumption.
¾ Display scrolling time shall be programmable.
¾ Min. three programmable Display modes shall be available.
- 15 -
WAPDA Specification for Solid State
Whole Current Energy Meter DD-S-60:07
_____________________________________________________________________________
¾ First Display mode shall be the Normal or Automatic display mode. Second display
mode shall be for Security / Diagnostics etc. The third Display mode shall be for Test
Purposes. Activation of Display Mode shall either be with a secure Push Button or an
equally secure alternate method.
¾ Phase Indicators shall be permanently displayed in all Display modes.
¾ All Segment Check.
¾ Display Mode Indicator.
¾ Display Quantity Labels.
¾ Pulse Output for field testing of Meter shall be available optically.
8. TESTS
Following routine, type and sample tests shall be carried out as per requirements of IEC
standards.
Accuracy Test
Running with no load test
Starting current test
Insulation resistance test
8.2.5 Tests of Accuracy requirements (for KWH meter parts as per IEC 62053-21 where
applicable
¾ Test of Accuracy
¾ Test of influence quantities
¾ Test of ambient temperature influence
¾ Test of no load condition
¾ Test of starting condition
9.1 A suitable name/rating plate shall be provided inside at the front of the meter, indicating
the following informations:
10. PACKING
10.1 Each meter shall be individually packed in Corrugated packing with thermopore lined
packing, covered with adhesive tape at joints or plastic strips etc.
- 17 -
WAPDA Specification for Solid State
Whole Current Energy Meter DD-S-60:07
_____________________________________________________________________________
10.2 For overseas shipment, a suitable number of individually thermopore packed meters shall
then further be packed in sea worthy packing.
10.3 The packing shall be strong enough to withstand rigors of ocean, rail, road etc.
11. SAMPLE
At least one number sample of multirate meter shall be submitted with the bid.
13. INSPECTION
The successful bidder shall offer the meters for testing/inspection, Procedure for pre-
shipment inspection is given below:
13.1.1 The meters offered for acceptance shall be grouped into lots containing upto 1000 meters.
A sample comprising of five (05) meters shall be selected at random from each lot and
subjected to tests as below:
13.1.2 The meters offered for acceptance shall be grouped into lots containing upto 1000 meters.
A sample comprising of two (02) meters shall be selected at random from each lot and
subjected to following tests:
Impulse Test
Power Loss Test
13.1.3 The lot shall be accepted if all the meters qualify in the tests described in clause 13.1.1 &
13.1.2 above. The lot shall be rejected if two or more meters fail in any of the tests. If any
one meter fails in any of the above tests re-sampling shall be carried out after collecting
- 18 -
WAPDA Specification for Solid State
Whole Current Energy Meter DD-S-60:07
_____________________________________________________________________________
same No. of meters and subjected to the tests described in clause 13.1.1 & 13.1.2 above. If
any one meter fails in any of the above tests the whole lot shall be rejected.
13.2.1 The meter offered for acceptance shall be grouped into lots containing upto 1000 meters.
Sample comprising of three (03) meters shall be selected at random from each lot and
subjected to tests as below:
The lot shall be accepted if meters qualify the above tests in clause 13.2.1. In case any
meter fails in the relevant test, another sample of double the size shall be selected and
test/tests repeated. If any meter fails in the relevant in the second group, the entire lot shall
be rejected.
13.3.1 Verification test of the functionality of software and display features on offered meters
shall be promoted by loading/unloading of programme and auditing the diagnostic reports.
The number of meters shall be three if any meter fails to comply with the functionality
requirements the entire offered lot shall be rejected.
13.4.1 The remaining type tests not performed on the above samples shall be carried out (as per
recommended sequence of IEC 62052-11 Annexure (F) on three (03) Nos. meters out of
the total offered meters. If two meters fail in any of the above tests, the lot shall be
rejected. If one of the meters fails to qualify any of the above tests, re-sampling shall be
carried out. In case of failure of any of the tests the lot shall be rejected.
Following routine tests shall be carried out by manufacturer on each meter and
witnessed by the Inspector as per respective clauses of IEC 62053-21.
If failure exceeds than 5%, the group offered for routine inspection be rejected:-
- 19 -
WAPDA Specification for Solid State
Whole Current Energy Meter DD-S-60:07
_____________________________________________________________________________
- Impulse test
- Power loss test
- Influence of DC and even harmonics.
- Accuracy test
- Starting current test
- Running with no load test (Creep test)
(c) Following EMC tests be performed on each of two selected sample meters:-
- Impact test
- Tin coating test
- Dimensional check
- Shock and vibration test
- Rain fall test
a) Electrical Test
• The lot shall be accepted if one meter fails in any one of the tests described in
clause 13.5.2 (i).
- 20 -
WAPDA Specification for Solid State
Whole Current Energy Meter DD-S-60:07
_____________________________________________________________________________
b) Mechanical Test
• The lot shall be accepted if meters qualify the above tests in clause 13.5.2 (ii) (a).
• In case any meter fails in the relevant test, another sample of double the size shall
be selected and test be repeated.
• If any meter fails in any test during re-sampling, the entire lot shall be rejected.
13.6.1 Verification test of the functionality of software and display features on offered
meters shall be performed by loading/down loading of and auditing of the reports.
Copy of the report be retained for official record. The number of meters shall be
two. If any meter fails to comply with the functionality requirements, the entire
offered lot shall be rejected.
14. WARRANTY
The supplier shall provide two years warranty for the successful operation of the meter
including its maintenance where ever required.
15. TRAINING
All the bidders shall submit complete technical data, detailed drawings test certificates,
literature in English language, supply reference list and manufacturing experience
alongwith the bid.
- 21 -
WAPDA Specification for Solid State
Whole Current Energy Meter DD-S-60:07
_____________________________________________________________________________
Annex – I
REFERENCE STANDARDS
When following standards referred to in this document have been superseded, the latest revisions
shall apply.
1. METERING STANDARDS
a. IEC
b. ANSI
C12.1 - 1995 Electric Meters Code for Electricity Metering
60060-1: 1989 High voltage test techniques-Part 1 General definitions and test
requirements
- 22 -
WAPDA Specification for Solid State
Whole Current Energy Meter DD-S-60:07
_____________________________________________________________________________
b. ANSI
a. IEC
60529:1989 Degrees of protection provided by enclosures (IP Code)
Amendment 1:1999
60695-2-11:2000 Fire hazard testing – Part 2-11: Glowing/hot-wire based test methods –
Glow-wire flammability test method for end-products
b. ISO Standard
4. ENVIRONMENTAL STANDARDS
a. IEC
60068-2-30:1980 Test Db and guidance: Damp heat, cyclic (12 + 12-hour cycle)
PREPARED BY:
- FAISAL MEHMOOD
Asst. Director
Design & Standard ________________________
- MANSOOR NASIR
Deputy Director
Design & Standard ________________________
- MAHBOOB ALAM
Director
Design & Standard ________________________
********************************
- 24 -
WAPDA Specification for Solid State
Whole Current Energy Meter DD-S-60:07
_____________________________________________________________________________
A. GENERAL
B. ENERGY METERS
7. Accuracy class
9. Detail of:
10. Losses in
- 25 -
WAPDA Specification for Solid State
Whole Current Energy Meter DD-S-60:07
_____________________________________________________________________________
a. Base ____________________
b. Cover ____________________
e. Terminals ____________________
b. Clearance ____________________
- 26 -
WAPDA Specification for Solid State
Whole Current Energy Meter DD-S-60:07
_____________________________________________________________________________
c. Display; ____________________
(as per clause 7.3 of the spec.),
give details.
i) KWH _____________________
ii) Demand KW _____________________
iii) Cumulative KW _____________________
iv) No. of Reset digits _____________________
- 27 -
WAPDA Specification for Solid State
Whole Current Energy Meter DD-S-60:07
_____________________________________________________________________________
- KWH _____________________
- KW _____________________
- 28 -
WAPDA Specification for Solid State
Whole Current Energy Meter DD-S-60:07
_____________________________________________________________________________
41. Attachments
Whether the following material has been attached;
- 29 -
WAPDA Specification for Solid State
Whole Current Energy Meter DD-S-60:07
_____________________________________________________________________________
Annex. – II
FORMAT OF SOFTWARE
1- Normal Mode 1
2. Alternate Mode 2
3. Programming Report 3
4. Billing Report 4-5
5. Security Report 6
6. Event Log Report 7-8