Laminar Flow Panels

air master Laminar flow panel


Model: ALP

Construction:
• Frame: High quality extruded aluminium profiles
with 30 mm flange width as standard.
• Perforated panel: 0.8 mm thick galvanized
perforated steel sheet.

Description:
• Frame is fabricated from high quality extruded
aluminium profiles with the advantages of corro-
sion resistance and rigidity.

• Perforated panel is fixed to the frame by screws.


Panel can be removed easily by loosening the
screws.

• Laminar flow panels are supplied with an inbuilt


plenum box. Standard finishes:
• Powder coated colour finish RAL 9010.
• Air master laminar flow panels used for a low • Powder coated colour finish as per other RAL
velocity, evenly distributed, down word throw. colour codes available.
Mostly used in operation theatres.

How to order:
Model Size Quantity Finish
Specify ceiling Specify in B = RAL - 9010
ALP module size numbers
mm x mm C = Other RAL colours.

To select laminar flow panel for a size 600 x 600 mm of quantity 75 nos with RAL9010.
Order as : ALP- 600 x 600 -75 -B.

Copyright reserved. Specifications subject to change without notice.

8.5
ISO 9002 certified company
Disc Valves

air master

Chapter 9

INDEX
A. Disc valves

1. Disc valve .......................................: ADV...............9.1

• Standard sizes ................................... .....................9.2


• Fixing details..................................... .....................9.2
• How to order...................................... .....................9.2

B. Air flow data.

1. Supply air disc valves Vs throw in meters.: Tab: 9.1..........9.2


2. Supply air disc valves.........................: Tab: 9.2(A) ......9.3
3. Return air disc valves.........................: Tab: 9.2(B)......9.4

Copyright reserved. Specifications subject to change without notice.

ISO 9002 certified company


Disc Valves

air master Disc valve


Model: ADV

Construction:
• Frame and disc: Steel sheet construction.
• Mounting rings: Galvanized sheet steel.

Description:
• Frame and disc is made of high quality galva-
nized steel sheet construction with powder coat-
ing to RAL colours.
• Disc is attached to the frame by threaded rod.
• Air flow can be adjusted by regulating the cone
up or down (+A or -A)
• Foam gasket is sealed around the back of the
ADV
frame to avoid air leakage.
• These valves can be used for supply, exhaust
and ventilation applications.
• Air master disc valves are best suited to air dis-
tribution systems handling relatively low air flow
rates within small circular duct work.
• Can be mounted in wall, ceiling or exposed air
ducts with mounting rings.
• Recommended for exhaust of greasy and damp
air in damp areas such as toilets, bathrooms and POSITION OF THE DISC
kitchens.

Standard finishes:
Steel sheet powder coated to RAL 9010 colour.
Flexibility of finishing is available as option.

ADV
Size A B C
80 80 106 15
100 100 135 15
125 125 160 15
160 160 194 15
200 200 238 18

Copyright reserved. Specifications subject to change without notice.

9.1
ISO 9002 certified company
Disc Valves

air master
Standard sizes:
N = Neck size in mm dia 80 100 125 160 200

Fixing details:
Direct fixing into the duct with mounting rings.
First mounting ring has to be fixed into the duct outlet before the valve is pushed into the ring.
How to order:
Model Size Quantity Finish
Specify neck Specify in B = steel sheet with
ADV diameter of the numbers RAL 9010
valve in mm
dia. C = Other RAL colour

Ordering example:
To select Air master disc valves of dia 200 mm, quantity 50 nos with RAL 9010 colour.
Order as: ADV 200-50-B.

Performance data:

Table 9.1 Supply air valves Vs Throw in meters (A = 0)

Note:
• For position A = +10, reduce throw by 30%.
• For position A=-10, increase throw by 40%

Copyright reserved. Specifications subject to change without notice.

9.2
ISO 9002 certified company
Disc Valves

air master
Disc valve
Model: ADV

Table 9.2(A) Air flow data


Supply air disc valve.
Air flow rate
Neck
Position
size in CFM 10 20 40 60 80 100 120 140
of disc
mm dia
M3/sec 0.0047 0.0094 0.0189 0.0283 0.0378 0.0472 0.0567 0.0661
Pt in mm H 20 0.76 1.83 5.6
A =+10 ---------- ---------- ---------- ---------- ----------
NC in dB <20 22 38
Pt in mm H 20 1.22 3.4 9.6
80 A =0 ---------- ---------- ---------- ---------- ----------
NC in dB <20 26 44
Pt in mm H 20 2.04 5.6 >20
A =–10 ---------- ---------- ---------- ---------- ----------
NC in dB <20 35 >45
Pt in mm H 20 0.51 1.12 3.46 6.6
A =+10 ---------- ---------- ---------- ----------
NC in dB <20 <20 30 38
Pt in mm H 20 0.71 2.04 6.11 11.21
100 A =0 ---------- ---------- ---------- ----------
NC in dB <20 20 36 44
Pt in mm H 20 1.43 4.08 12.23 >20
A =–10 ---------- ---------- ---------- ----------
NC in dB <20 31 45 >45
Pt in mm H 20 0.41 1.12 3.06 5.61 9.2
A =+10 ---------- ---------- ----------
NC in dB <20 <20 26 33 42
Pt in mm H 20 0.82 1.83 5.61 9.4 14.78
125 A =0 ---------- ---------- ----------
NC in dB <20 <20 33 40 >45
Pt in mm H 20 1.22 3.06 8.87 16.3 >20
A =–10 ---------- ---------- ----------
NC in dB <20 26 42 >45 >45
Pt in mm H 20 <0.4 0.61 1.83 4.3 5.7 9.2 12.7
A =+10 ----------
NC in dB <20 <20 20 25 31 37 40
Pt in mm H 20 <0.4 1.22 3.78 8.2 11.2 18.3 >20
160 A =0 ----------
NC in dB <20 <20 25 35 41 45 >45
Pt in mm H 20 1.0 2.75 8.2 16.3 >20 >20 >20
A =–10 ----------
NC in dB <20 30 41 >45 >45 >45 >45
Pt in mm H 20 <0.4 <0.4 0.82 1.63 3.1 4.1 5.1 7.9
A =+10
NC in dB <20 <20 <20 <20 22 25 33 37
Pt in mm H 20 <0.4 0.71 1.83 4.1 5.61 9.1 10.7 18.3
200 A =0
NC in dB <20 <20 <20 24 30 36 40 45
Pt in mm H 20 <0.4 1.22 4.3 7.6 10.7 18.3 >20 >20
A =–10
NC in dB <20 <20 26 35 39 45 >45 >45

• Pt = Total pressure loss across the disc valve in mm of H2O.


• NC based on a room attenuation of 10 dB.
• A = +10,0 & -10 = Position of the disc 10 mm down of normal position, at normal position, and
10 mm above normal position.

Copyright reserved. Specifications subject to change without notice.

9.3
ISO 9002 certified company
Disc Valves

air master
Disc valve
Model: ADV

Table 9.2(B) Air flow data


Return air disc valve.
Air flow rate
Neck
Position
size in CFM 10 20 40 60 80 100 150 200
of disc
mm dia
M3/sec 0.0047 0.0094 0.0189 0.0283 0.0378 0.0472 0.071 0.094
Pt in mm H 20 <0.4 0.91 4.3 10.2
A =+10 ---------- ---------- ---------- ----------
NC in dB <20 <20 26 37
Pt in mm H 20 <0.4 1.43 7.1 17.3
80 A =0 ---------- ---------- ---------- ----------
NC in dB <20 <20 32 45
Pt in mm H 20 1.83 5.1 18 >20
A =–10 ---------- ---------- ---------- ----------
NC in dB <20 23 45 >45
Pt in mm H 20 <0.4 <0.4 1.63 3.8 5.8 9.7
A =+10 ---------- ----------
NC in dB <20 <20 <20 23 31 37
Pt in mm H 20 <0.4 0.76 2.5 5.6 9.7 14.7
100 A =0 ---------- ----------
NC in dB <20 <20 <20 30 35 45
Pt in mm H 20 0.61 2.24 7.6 15.2 >20 >20
A =–10 ---------- ----------
NC in dB <20 <20 35 40 >45 >45
Pt in mm H 20 <0.4 <0.4 0.71 1.42 2.9 4.1 9.7
A =+10 ----------
NC in dB <20 <20 <20 <20 20 25 37
Pt in mm H 20 <0.4 <0.4 1.83 4.1 8.15 11.2 >20
125 A =0 ----------
NC in dB <20 <20 <20 21 30 35 >45
Pt in mm H 20 <0.4 2.1 7.1 16.8 >20 >20 >20
A =–10 ----------
NC in dB <20 <20 23 35 >45 >45 >45
Pt in mm H 20 <0.4 <0.4 0.4 0.81 1.43 2.1 5.2 9.7
A =+10
NC in dB <20 <20 <20 <20 <20 <20 28 37
Pt in mm H 20 <0.4 <0.4 0.81 1.74 3.4 5.3 12.2 >20
160 A =0
NC in dB <20 <20 <20 <20 <20 25 37 45
Pt in mm H 20 <0.4 0.5 1.74 3.8 7.6 14.7 >20 >20
A =–10 NC in dB <20 <20 <20 <20 27 35 >45 >45
Pt in mm H 20 <0.4 <0.4 <0.4 <0.4 0.76 1.12 2.6 4.38
A =+10
NC in dB <20 <20 <20 <20 <20 <20 27 34
Pt in mm H 20 <0.4 <0.4 0.7 1.4 2.3 3.4 8.4 12.2
200 A =0
NC in dB <20 <20 <20 <20 <20 20 35 42
Pt in mm H 20 <0.4 0.5 1.62 3.4 7.1 11.2 >20 >20
A =–10
NC in dB <20 <20 <20 <20 <20 34 >45 >45

• Pt = Total pressure loss across the disc valve in mm of H2O.


• NC based on a room attenuation of 10 dB.
• A = +10,0 & -10 = Position of the disc 10 mm down of normal position, at normal position, and
10 mm above normal position.