Calculate SCCR
Calculate SCCR
Calculate SCCR
Basics, Maximum Fault Current” which spoke to this topic but did not get into
the math. I have received many requests ever since to get into the math. I
trust this article will satisfy inquiring minds with details around calculating
available fault current and provide some equations for the student to
explore.
equipment is being applied within its rating and the system is performing to
applications as well.
The National Electrical Code demands this data point for enforcement of
Circuit Current Ratings, and other Characteristics; and 110.24 Available Fault
Current. Whether you are a designer, installer or inspector, you will at some
also help us realize that a qualified individual should be the one making
these calculations. So for the sake understanding, I offer this article to get
simple single-line diagram that very well could be your basic service
that would be used to calculate available fault current at any point in the
above simple single line diagram. Engineers will call that which you see in
the Figure 1 above into impedance values. For those of you who are up on
circuits 101, what you see below, when all impedances are added together,
voltage source. This basic circuit will be used throughout this article.
Figure 2. Impedance Diagram (Circuit)
Assumptions will have to be made for calculations and to simplify our work
The assumptions for the transformer that will be used as part of the example
for this article will include that which follows. This information should be
% Impedance 5.75%
The assumption is for the utility available short-circuit current. For this
exercise 50,000 amps will be used. Before a study is conducted, the utility is
contacted to obtain this information. They may provide the available fault
probably most seen data from the utility will be an available fault current in
kA. Some utilities may provide the data as short-circuit MVA instead. This
article will provide equations to accommodate both forms of input but cater
the resistance of the conductor and only use the reactance. This will do two
things for the sake of this article. First, it will result in a higher fault current
resistance and reactance. Second, it will keep the math simple. A final
section of this article will provide analysis results that include the resistance
and reactance of the conductors and the utility. The methods used mirror
This article will also assume no motor contribution. Maximum available short-
will have to perform at some point in their career and that some perform
many times a day. The equations for calculating FLA are included below:
This 1500 kVA transformer has a secondary FLA of 1,804 amps. This
transformer. Based on this FLA and the use of Table 310.15(B)(16) from NEC
transformer will let through, as if the power generation facility was hooked
directly to the line side of the transformer, or we can calculate the available
fault current considering the provided available fault current from the utility.
The former approach which results in the maximum amount of fault current
for the utility which will reduce the overall impedance of the circuit and so
increase the value of calculated short-circuit current. Figure 3 will yield the
calculate the maximum available fault current that a transformer can supply
is as follows:
Using the information stated above for the example 1500 kVA transformer
for this example, the maximum available fault current that this specific
What this tells us is that the secondary of the transformer cannot see any
more fault current than what we have calculated. There are NO changes on
the utility side that can impact this available fault current to a point where it
would be greater than 31,378 amps. The only way this service would see
more than 31,378 amps would be if we changed the transformer and the
the results of varying the impedance of the subject transformer +/- 20% in
the facility owner or resident employees to understand how that change may
impact their power distribution system. When changes are made, labels like
nor does it include any load-side conductors. Let’s next explore the impact of
side of safety, until situations present themselves that warrant digging into
the details. The above shortcut for calculating fault current is conservative,
in that it did NOT consider the utility available fault current yielding a
available fault current. Specifically, 50 kA available from the utility. This will
illustrate that the calculated 31,378 amps could be reduced by doing so.
Below, are two equations that address when kA is available and when Short-
Circuit MVA is available. For this example, we will use the equation below
that assumes the utility has provided you with an available fault current in
kA.
The circuit diagram now looks like that shown in figure 5.
Figure 5. Circuit diagram that includes both transformer and utility source
impedance.
The first step required is to convert the utility provided available fault current
For a given utility available fault current of 50 kA, the %Z of the utility is
calculated as follows
Figure 6 provides utility source impedance values for varying utility available
fault currents for this specific example. As noted above, the transformer kVA
Figure 6. Utility source impedance values for various levels of utility available
fault current
The equation for calculating the available fault current at the secondary of
Inserting all of the known variables, the new available fault current is
calculated as follows:
If we compare the infinite bus calculation and that which included the source
impedance of the utility (available fault current of 50,000 amps) we see that
This table shows how the calculated available short-circuit current varies for
changing utility source fault current values. The 50 kA utility available fault
to see that increasing the available fault current from the utility, assuming a
think. For example, doubling the utility available fault current from 50 kA to
3%, or 1,022 amps. For most overcurrent protective device application, this
change should not be significant. I have heard some say we should not label
changes on the line side which would impact the number on the label. Figure
7 is a good example that shows that even if an infinite bus was not used,
Figure 7. Impact of varying utility available fault currents on the power
distribution system
Just to recap where we are in this discussion, the available fault currents are
as in figure 7a.
The next thing we have to consider is the conductor on the secondary of the
transformer. This will reduce the available fault current even further.
continue the analysis of this 1500 kVA transformer example adding parallel
The equivalent circuit has already been provided as part of figure 1. Now
The data needed for this example is retrieved from the National Electrical
Code. From Table 9 of NEC 2014 for a 500 MCM conductor in steel conduit,
stated earlier, we are only using the reactance value which will result in
slightly higher short-circuit current values and make the math for this
publication more palatable. For a 1500 kVA transformer with 1,804 full load
<img
src="https://www.iaeimagazine.org/images/2015_05/15c_DomFig7aForm2.jp
impedance, is as follows:
To summarize again,
As can be seen here, including more details reduces the available fault
current. In this case the fault current was reduced from 31,378 amps to
Figure 8. Summary of calculations and comparison with other tools to calculate
available fault current.
FINAL CALIBRATION
So we have walked through the calculation of available fault current for
a more detailed analysis can be achieved but takes more effort and
expertise. Let’s look at the above example with an eye on other tools that
may be available.
available fault current. Some are quite expensive and take trained specialists
Analysis tools. These applications are indeed quite thorough and produce
very detailed reports. There are also tools that are free such as the Eaton
accomplished above AND provides a comparison with SKM and with the
available on the web or for any IPHONE or ANDROID via either products App
note that the SKM software result leverages both the real and reactive
component of the conductor. The impedance values were taken straight from
Again, none of the examples shown above and included in this article
our friend. Motor contribution can be very important for these calculations.
From a math and/or system circuit perspective, when you include motor
contribution the impedance is in parallel with the utility source impedance,
the overall impedance in the circuit of figure 2 and hence increasing the
calculated short-circuit current. The reset is left to the student. (I’ve always
CLOSING REMARKS
Available fault current is a very important parameter to consider in your
design, installation and inspection. Tools are available on the market that
As always, keep safety at the top of your list and ensure you and those