This document provides calculations for sizing a pump for a hose reel system based on system parameters. It lists key parameters such as the total number of hose reels, pipe lengths, bends, and valves. It then calculates head losses for various system components using the Hazen-Williams friction loss formula. The total head required is calculated to be 95.24 meters. The selected pump performance is 100 meters of head.
This document provides calculations for sizing a pump for a hose reel system based on system parameters. It lists key parameters such as the total number of hose reels, pipe lengths, bends, and valves. It then calculates head losses for various system components using the Hazen-Williams friction loss formula. The total head required is calculated to be 95.24 meters. The selected pump performance is 100 meters of head.
This document provides calculations for sizing a pump for a hose reel system based on system parameters. It lists key parameters such as the total number of hose reels, pipe lengths, bends, and valves. It then calculates head losses for various system components using the Hazen-Williams friction loss formula. The total head required is calculated to be 95.24 meters. The selected pump performance is 100 meters of head.
This document provides calculations for sizing a pump for a hose reel system based on system parameters. It lists key parameters such as the total number of hose reels, pipe lengths, bends, and valves. It then calculates head losses for various system components using the Hazen-Williams friction loss formula. The total head required is calculated to be 95.24 meters. The selected pump performance is 100 meters of head.
Download as XLSX, PDF, TXT or read online from Scribd
Download as xlsx, pdf, or txt
You are on page 1of 2
PROJECT : ???
HOSE REEL SYSTEM (???)
HYDRAULIC CALCULATION PERTAINING TO PUMP SIZING FOR HOSE REEL SYSTEM
*Pump performance shall be based on not more than 80% efficiency factor.
Items Value Unit
135 Litre/min (i) Hose reel pump selection 0.00225 meter3/s (ii) Total number of hose reel 88 Nos. (iii) Total pipe length from HR pump to furthest HR location 200 meter (iv) Total pipe length of highest vertical riser piping 60 meter (v) Total number of 90° bends (0.05 m diameter) 17 Nos. (vi) Total number gate valve (0.05 m diameter) 3 Nos. (vii) Hose Reel (0.025 m diameter & 30 m length) Type of tubing: Non Kink Single Braided
Friction Loss (Hazen Williams Formula) Value Unit
(i) Pipe length 100 meter (ii) Volumetric flow rate 0.00225 meter3/s (iii) Pipe roughness coefficient, C 120 (iv) Pipe diameter 0.05 meter HEAD LOSS PER PIPE LENGTH 4.161337 meter head HEAD LOSS PER 1 METER PIPE LENGTH 0.041613 meter head
Head Loss Value unit
(i) Linear length of pipe 200 meter Head Loss 8.322673 meter head (ii) Number of Bends 17 Nos. Equivalent length of smooth 90° bends (0.05 m diameter) 0.5 meter Total equivalent length of smooth 90° bends (0.05 m diameter) 8.5 meter Head Loss 0.353714 meter head (iii) Number of valves 3 Nos. Equivalent length of gate valve (0.05 m diameter) 0.5 meter Total equivalent length of gate valve (0.05 m diameter) 1.5 meter Head Loss 0.06242 meter head (iv) Canvas Tubing Length 30 meter Diameter 0.025 meter Head Loss 1.5 meter head (v) Vertical riser piping Head Loss 60 meter head (vi) Hose reel outlet Head Loss 25 meter head
TOTAL HEAD REQUIRED 95.23881 meter head
SELECTED PUMP PERFORMANCE (METER HEAD) 100 meter head SELECTED PUMP PERFORMANCE (FEET HEAD) 328 feet head Hazen Williams Friction Loss Formula (SI Unit)
L = Length of pipe in meters
Q = Volumetric flow rate, m3/s (cubic meter per second) C = Pipe roughness coefficient d = Inside pipe diameter, m (meter) hf = Head loss in meters (water) over the length of pipe (meter head) S = Hydraulic slope