MWM Gas Engine tcg2020 EN
MWM Gas Engine tcg2020 EN
MWM Gas Engine tcg2020 EN
net
TCG 2020
Top marks for
ecology and economy.
For natural gas and biogas with an output from 1,000 to 2,000 kWel
Our experience for your success. The TCG 2020. Top performance from
MWM – used successfully worldwide.
Strong partner for your progress NanJi Water Recycle Centre, Korea
With MWM you can benefit from 140 years of experience in gas engine technology Korea District Heating Corp. is one of the largest suppliers
and energy production. Since 2011 the traditional company, Motorenwerke of district heating in the world. In March 2013, two TCG 2020
Mannheim, has belonged to the worldwide network of Caterpillar Inc. This gives us V16 engines were taken into operation, providing an electri-
an even more unique expertise that benefits you in the development of individual cal output of 1.6 MW each. The units are part of the first plant
complete solutions. installed in South Korea that generates electricity and heat
from biogas.
More profit
The TCG 2020 is highly efficient thanks to its opti-
mized inlet duct, combustion chamber and spark
plugs. Save as much as 15 % per annum on fuel costs
– and increase your plant’s profitability.
Flexible usage
The latest technology such as our gas-mixer and TEM
allows you to use a wide variety of gases. Even the
most problematic gases such as colliery gas, landfill
gas and sewage gas can be used without difficulty. TCG 2020 V20
Technical data 50 Hz Technical data 60 Hz
Engine type TCG 2020 V12 K1 1) V12 K 1) V12 2) V16 K 1) V16 2) V20 2) Engine type TCG 2020 V12 K 1) V12 2) V16 K 1) V16 2) V20 2)
Bore / stroke mm 170/195 170/195 170/195 170/195 170/195 170/195 Bore/stroke mm 170/195 170/195 170/195 170/195 170/195
Displacement dm3 53.1 53.1 53.1 70.8 70.8 88.5 Displacement dm3 53.1 53.1 70.8 70.8 88.5
Speed min -1
1,500 1,500 1,500 1,500 1,500 1,500 Speed min -1
1,500 1,500 1,500 1,500 1,500
Mean piston speed m/s 9.8 9.8 9.8 9.8 9.8 9.8 Mean piston speed m/s 9.8 9.8 9.8 9.8 9.8
Length 3)
mm 4,660 4,790 4,790 5,430 5,430 6,200 Length 3)
mm 5,970 5,970 6,640 6,640 7,470
Width 3) mm 1,810 1,810 1,810 1,810 1,810 1,710 Width 3) mm 1,790 1,790 1,790 1,790 1,710
Height 3)
mm 2,210 2,210 2,210 2,210 2,210 2,190 Height 3)
mm 2,210 2,210 2,210 2,210 2,190
Dry weight genset kg 11,200 11,700 11,700 13,300 13,300 17,900 Dry weight genset kg 13,000 13,000 14,900 14,900 19,800
Engine type TCG 2020 V12 K1 1) V12 K 1) V12 2) V16 K 1) V16 2) V20 2) Engine type TCG 2020 V12 K 1) V12 2) V16 K 1) V16 2) V20 2)
Electrical power 4) kW 1,000 1,125 1,200 1,500 1,560 2,000 Electrical power 4) kW 1,125 1,200 1,500 1,560 2,000
Mean effective pressure bar 15.5 17.4 18.6 17.5 18.1 18.6 Mean effective pressure bar 17.4 18.7 17.6 18.3 18.7
Thermal output 5)
±8 % kW 1,177 1,253 1,190 1,675 1,580 1,977 Thermal output 5)
±8 % kW 1,261 1,196 1,686 1,589 1,991
Electrical efficiency 4) % 40.0 40.9 43.6 40.9 43.2 43.7 Electrical efficiency 4) % 40.7 43.4 40.6 43.0 43.4
Thermal efficiency 4)
% 47.0 45.6 43.3 45.7 43.8 43.2 Thermal efficiency 4)
% 45.6 43.2 45.7 43.8 43.2
Total efficiency 4) % 87.0 86.5 86.9 86.6 87.0 86.9 Total efficiency 4) % 86.3 86.6 86.3 86.8 86.6
Engine type TCG 2020 V12 2) V16 2) V20 2) Engine type TCG 2020 V12 2) V16 2) V20 2)
Electrical power 4) kW 1,200 1,560 2,000 Electrical power 4) kW 1,200 1,560 2,000
Mean effective pressure bar 18.6 18.1 18.6 Mean effective pressure bar 18.7 18.3 18.7
Thermal output 5)
±8 % kW 1,194 1,577 2,012 Thermal output 5)
±8 % kW 1,200 1,588 2,026
Electrical efficiency 4) % 43.0 42.6 43.0 Electrical efficiency 4) % 42.8 42.3 42.7
Thermal efficiency 4)
% 42.8 43.1 43.3 Thermal efficiency 4)
% 42.8 43.1 43.2
Total efficiency 4) % 85.8 85.7 86.3 Total efficiency 4) % 85.6 85.4 85.9
1) Version optimized for standalone operation and load 4) According to ISO 3046/1 at U = 0.4 kV, cosphi = 1.0 for Data for special gas and dual gas operation on request. 1) Version optimized for standalone operation and load 4) According to ISO 3046/1 at U = 0.48kV, cosphi = 1.0 for Data for special gas and dual gas operation on request.
compensation. 50 Hz and a methane number of MN 80 (TCG 2020) or compensation. 60 Hz and a methane number of MN 80 (TCG 2020) or
2) Optimized efficiency version. MN 70 (TCG 2020K) for natural gas. The values given on these datasheets are for information 2) Optimized efficiency version. MN 70 (TCG 2020K) for natural gas. The values given on these datasheets are for information
3) Transport dimensions for gensets; components set up 5) Exhaust gas cooled to 120°C for natural gas and 180°C purposes only and not binding. The information given in the 3) Transport dimensions for gensets; components set up 5) Exhaust gas cooled to 120°C for natural gas and purposes only and not binding. The information given in the
separately must be taken into consideration. for biogas. offer is decisive. separately must be taken into consideration. 180°C for biogas. offer is decisive.
6) NO x ≤ 500 mg/Nm³; exhaust gas dry at 5 % O 2. 6) NO x ≤ 500 mg/Nm³; exhaust gas dry at 5 % O 2.
For additional MWM locations, scan
the QR code or visit the website
www.mwm.net/en/mwm-worldwide