Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Deltav Bulk Power Supplies: Product Data Sheet Deltav Distributed Control System

Download as pdf or txt
Download as pdf or txt
You are on page 1of 20

DeltaV Distributed Control System Product Data Sheet

December 2017

DeltaV™ Bulk Power Supplies

DeltaV 5 A, 10A, 20 A, 40 A Bulk Power Supplies.

DeltaV 20 A, 40 A and 80 A Bulk Power Supply Redundancy Modules.

„„Easy to use Benefits


„„Improved availability Easy to use. . The DeltaV Bulk Power Supplies provide reliable
12 and 24 V DC power for your DeltaV system power and
„„Flexible and cost effective
bussed field power needs. They mount easily onto a T-type
„„Small footprint DIN rail—easy!

Improved availability. Redundancy modules based on active


Introduction MOSFET technology offer significantly higher efficiencies and
lower voltage drop than traditional diode based modules,
Power — your system won’t operate without it. DeltaV™ Bulk leading to less heat dissipation and better system reliability.
Power Supplies offer you the most efficient and reliable power
Flexible and cost effective. The DeltaV Bulk Power Supplies
solution for your money. The DeltaV Bulk Power Supply suite
are flexible to use and cost effective, as external redundancy
provides power to the system electronics and to the field.
modules can be applied, for example, if load sharing is desired.
This is all the power required for your DeltaV system.
Models are available both with and without conformal coating.

Small footprint. The DeltaV Bulk Power Supplies provide very


competitive small footprints!
DeltaV Bulk Power Supplies December 2017

Hardware Specifications
Common Environmental Specifications

Operational Temperature* -40 to + 70°C (-40 to 158°F) with linear derating to 75% power from 60 to 70°C

Storage Temperature -40 to + 85°C (-40 to 185°F)

Relative Humidity 5 to 95%, non-condensing

Protection Rating IP20

Airborne Contaminants ISA-S71.04-1985 airborne contaminants class G3, Conformal coating**

Shock 10(g) RMS, three axes, 11ms for each axis

Vibration 2.5(g) RMS, 10-2000 Hz (random); three axes for 20 minutes each - IEC 60068-2-6

Mounting Mount only on horizontally-oriented DIN Rail, with label text right-side up.

*Operating any electronics at the higher end of its temperature range for long periods of time will shorten its expected lifetime,
see Effects of Heat and Airflow Inside an Enclosure White Paper for more information.
** Only applies to conformal coated models, see ordering information for more details.

Certificates and Compliances*


Listed, Ind. Control Equipment, E61379
- UL 508, CSA C22.2 No 107.1

UL Recognized Component, ITE, E137632


- UL 60950-1/CSA C22.2 No. 60950-1, 2nd Edition

Low Voltage Directive


- IEC/EN60950-1, 2nd Edition

UL Recognized Component, Haz. Loc., E234790

- UL60079-15/CSA E60079-15
- Class I, Zone 2, AEx nA nC IIC, Ex nA nC IIC

ATEX Directive
- EN60079-0, EN60079-7, EN60079-15
- II 3 G, Ex ec nC IIC Gc
IECEx Certified
- IEC 60079-0, IEC 60079-7, IEC 60079-15
- Ex ec nC IIC Gc
- ExEAC TR CU 012/2011 Safety of Equipment intended for
Explosive Atmospheres
ABS Type Approval
DNV-GL Type Approval
* Refer to user manual for installation requirements when used in hazardous locations.

www.emerson.com/deltav 2
DeltaV Bulk Power Supplies December 2017

DeltaV Bulk Power Supply 100-240 V AC to 24 V DC, 5 A


Description DeltaV Bulk AC to 24 V DC, 5 A Power Supply Specifications

Output Voltage 24 V DC

Output Voltage Adjustment Range 23.5 - 28.5 V DC

Output Current 5A
1.5 × Nominal Current for > 4 seconds minimum while holding voltage > 20 V DC
Output Power 120 W
180 W for 4 seconds minimum while holding voltage > 20 V DC
Output Ripple Typ. < 50 mV peak-to-peak from 0Hz to 20MHz

Output Hold-up Time >20 ms (Full load, 100-230 V AC Input @ Tamb=+25°C) to 95% output voltage

AC Input Voltage 100-240V nominal (85 – 264 V range)

AC Mains Frequency 43 - 67 Hz

AC Input Current 1.65 A at 85 V AC


0.55 A at 264 V AC
AC Power Factor Correction Active power factor correction typ. 0.98 @ 115V AC/ 0.92 @ 230 V AC

AC Inrush Current Typ. <3.7A at 120 V AC, < 7.4A at 230 V AC, measured at 25°C

AC Efficiency > 88% typ.

AC Losses 14 W typ.

DC Input Voltage 100 – 340 V nominal (90 - 375 V range)

DC Input Current 1.65 at 90 V DC


0.55 A at 375 V DC

www.emerson.com/deltav 3
DeltaV Bulk Power Supplies December 2017

Input Protection Internally fused, non-replaceable fuses.


Note: The internal fuse is for an internal fault condition only.
Shorts and overload will not cause the fuse to fail.
Alarm Relay Contact Rating N.O. contact rated 200mA/50 V DC, Signal Active when Vout> 18.5 V DC +/-5%

Dimensions Height: 123 mm (4.85 in)


Width: 50 mm (1.97 in)
Depth: 110 mm (4.36 in)
Weight 1.3 lb (0.6 kg)

Free Spacing Above & Below 25 mm (0.98 in)

Left & Right 10 mm (0.39 in)

Front 15 mm (0.59 in)

Terminals and wiring


Input Output DC-OK-Signal
Screw-Type Screw-Type Screw-Type
Terminals Terminals Terminals
Solid & 1.5-6 mm2 1.5-6 mm2 1.5-6 mm2
Stranded Wire 16-10 AWG 16-10 AWG 16-10 AWG
Screw Torque 4.4 lb-in 7 lb-in 7 lb-in
(50 N-cm) (80 N-cm) (80 N-cm)

www.emerson.com/deltav 4
DeltaV Bulk Power Supplies December 2017

DeltaV Bulk Power Supply 100-240 V AC to 24 V DC, 10 A


Description DeltaV Bulk AC to 24 V DC, 10 A Power Supply Specifications

Output Voltage 24 V DC

Output Voltage Adjustment Range 23.5 - 28.5 V DC

Output Current 10A


1.5 × Nominal Current for > 4 seconds minimum while holding voltage > 20 V DC
Output Power 240 W
360 W for 4 seconds minimum while holding voltage > 20 V DC
Output Ripple Typ. < 50 mV peak-to-peak from 0Hz to 20MHz

Output Hold-up Time >20 ms (Full load, 100-230 V AC Input @ Tamb=+25°C) to 95% output voltage

AC Input Voltage 100-240V nominal (85 – 264 V range)

AC Mains Frequency 43 - 67 Hz

AC Input Current 3.2 A at 85 V AC


1.0 A at 264 V AC
AC Power Factor Correction Active power factor correction typ. 0.98 @ 115V AC/ 0.92 @ 230 V AC

AC Inrush Current Typ. <12.7A at 120 V AC, < 24.8A at 230 V AC, measured at 25°C

AC Efficiency > 90% typ.

AC Losses 24 W typ.

DC Input Voltage 100 – 340 V nominal (90 - 375 V range)

DC Input Current 3.2 at 90 V DC


1.0 A at 375 V DC

www.emerson.com/deltav 5
DeltaV Bulk Power Supplies December 2017

Input Protection Internally fused, non-replaceable fuses.


Note: The internal fuse is for an internal fault condition only.
Shorts and overload will not cause the fuse to fail.
Alarm Relay Contact Rating N.O. contact rated 200mA/50 V DC, Signal Active when Vout> 18.5 V DC +/-5%

Dimensions Height: 123 mm (4.85 in)


Width: 60 mm (2.36 in)
Depth: 110 mm (4.36 in)
Weight 1.7 lb (0.8 kg)

Free Spacing Above & Below 25 mm (0.98 in)

Left & Right 10 mm (0.39 in)

Front 15 mm (0.59 in)

Terminals and wiring


Input Output DC-OK-Signal
Screw-Type Screw-Type Screw-Type
Terminals Terminals Terminals
Solid & 1.5-6 mm2 1.5-6 mm2 1.5-6 mm2
Stranded Wire 16-10 AWG 16-10 AWG 16-10 AWG
Screw Torque 4.4 lb-in 7 lb-in 7 lb-in
(50 N-cm) (80 N-cm) (80 N-cm)

www.emerson.com/deltav 6
DeltaV Bulk Power Supplies December 2017

DeltaV Bulk Power Supply 100-240 V AC to 24 V DC, 20 A


Description DeltaV Bulk AC to 24 V DC, 20 A Power Supply Specifications

Output Voltage 24 V DC

Output Voltage Adjustment Range 23.5 - 28.5 V DC

Output Current 20A


1.5 × Nominal Current for > 4 seconds minimum while holding voltage > 20 V DC
Output Power 480 W
720 W for 4 seconds minimum while holding voltage > 20 V DC
Output Ripple Typ. < 100 mV peak-to-peak from 0Hz to 20MHz

Output Hold-up Time >20 ms (Full load, 100-230 V AC Input @ Tamb=+25°C) to 95% output voltage

AC Input Voltage 100-240V nominal (85 – 264 V range)

AC Mains Frequency 43 - 67 Hz

AC Input Current 6 A at 85 V AC
3 A at 264 V AC
AC Power Factor Correction Active power factor correction typ. 0.98 @ 115V AC/ 0.92 @ 230 V AC

AC Inrush Current Typ. <5.8A at 120 V AC, < 11.5A at 230 V AC, measured at 25°C

AC Efficiency > 92% typ.

AC Losses 38 W typ.

DC Input Voltage 100 – 250 V nominal (90 - 275 V range)

DC Input Current 6 A at 90 V DC
3 A at 275 V DC

www.emerson.com/deltav 7
DeltaV Bulk Power Supplies December 2017

Input Protection Internally fused, non-replaceable fuses.


Note: The internal fuse is for an internal fault condition only.
Shorts and overload will not cause the fuse to fail.
Alarm Relay Contact Rating N.O. contact rated 200mA/50 V DC, Signal Active when Vout> 18.5 V DC +/-5%

Dimensions Height: 123 mm (4.85 in)


Width: 87 mm (3.42 in)
Depth: 127 mm (4.98 in)
Weight 3.0 lb (1.4 kg)

Free Spacing Above & Below 40 mm (1.6 in)

Left & Right 10 mm (0.39 in)

Front 15 mm (0.59 in)

Terminals and wiring


Input Output DC-OK-Signal
Screw-Type Screw-Type Screw-Type
Terminals Terminals Terminals
Solid & 1.5-6 mm2 1.5-6 mm2 1.5-6 mm2
Stranded Wire 16-10 AWG 16-10 AWG 16-10 AWG
Screw Torque 4.4 lb-in 7 lb-in 7 lb-in
(50 N-cm) (80 N-cm) (80 N-cm

www.emerson.com/deltav 8
DeltaV Bulk Power Supplies December 2017

DeltaV Bulk Power Supply 100-240 V AC to 24 V DC, 40 A


Description DeltaV Bulk AC to 24 V DC, 40 A Power Supply Specifications

Output Voltage 24 V DC

Output Voltage Adjustment Range 23.5 - 28.5 V DC

Output Current 40A


1.5 × Nominal Current for > 4 seconds minimum while holding voltage > 20 V DC
Output Power 960 W
1,440 W for 4 seconds minimum while holding voltage > 20 V DC
Output Ripple Typ. < 200 mV peak-to-peak from 0Hz to 20MHz

Output Hold-up Time >20 ms (Full load, 100-230 V AC Input @ Tamb=+25°C) to 95% output voltage

AC Input Voltage 100-240V nominal (85 – 264 V range)

AC Mains Frequency 43 - 67 Hz

AC Input Current 12 A at 85 V AC
4 A at 264 V AC
AC Power Factor Correction Active power factor correction typ. 0.98 @ 115V AC/ 0.92 @ 230V AC

AC Inrush Current Typ. <5.8A at 120 V AC, < 11.5A at 230 V AC, measured at 25°C

AC Efficiency > 93% typ.

AC Losses 67 W typ.

DC Input Voltage 120 – 340 V nominal (108 - 375 V range)

DC Input Current 12 A at 108 V DC


4 A at 375 V DC

www.emerson.com/deltav 9
DeltaV Bulk Power Supplies December 2017

Input Protection Internally fused, non-replaceable fuses.


Note: The internal fuse is for an internal fault condition only. Shorts and overload
will not cause the fuse to fail.
Alarm Relay Contact Rating N.O. contact rated 200mA/50 V DC, Signal Active when Vout> 18.5 V DC +/-5%

Dimensions Height: 123 mm (4.85 in)


Width: 180 mm (7.09 in)
Depth: 122 mm (4.81 in)
Weight 6.0 lb (2.8 kg)

Free Spacing Above & Below 25 mm (0.98 in)


Left & Right 15 mm (0.59 in)
Front 15 mm (0.59 in)

Terminals and wiring


Input Output DC-OK-Signal
Screw-Type Screw-Type Screw-Type
Terminals Terminals Terminals
Solid & 3-6 mm2 10.6-13 mm2 0.14-2 mm2
Stranded Wire 13-10 AWG 7-6 AWG 26-14 AWG
Screw Torque 4.4 lb-in 15.6 lb-in 1.7 lb-in
(50 N-cm) (176 N-cm) (20 N-cm)

www.emerson.com/deltav 10
DeltaV Bulk Power Supplies December 2017

DeltaV Bulk Power Supply 100-240 V AC to 12 V DC, 15A


Description DeltaV Bulk AC to 12 V DC, 15 A Power Supply Specifications

Output Voltage 12 V DC

Output Voltage Adjustment Range 11.5 - 15.5 V DC

Output Current 15A


1.5 × Nominal Current for > 4 seconds minimum while holding voltage > 10 V DC
Output Power 180 W
270 W for 4 seconds minimum while holding voltage > 10 V DC
Output Ripple Typ. < 100 mV peak-to-peak from 0Hz to 20MHz

Output Hold-up Time >80ms (Full load, 100 V AC Input @ T =+25°C) to 95% output voltage

AC Input Voltage 100-240V nominal (85 – 264 V range)

AC Mains Frequency 43 - 67 Hz

AC Input Current 1.77 A at 85 V AC


0.9 A at 264 V AC
AC Power Factor Correction Active power factor correction typ. 0.98 @ 115V AC/ 0.95 @ 230V AC

AC Inrush Current Typ. <5.8A at 120 V AC, < 12.7A at 230 V AC, measured at 25°C

AC Efficiency > 86.5% typ.

AC Losses 24 W typ.

DC Input Voltage 100 – 340 V nominal (90 - 375 V range)

DC Input Current 1.77 A at 90 V DC


0.9 A at 375 V DC

www.emerson.com/deltav 11
DeltaV Bulk Power Supplies December 2017

Input Protection Internally fused, non-replaceable fuses.


Note: The internal fuse is for an internal fault condition only. Shorts and overload
will not cause the fuse to fail.
Alarm Relay Contact Rating N.O. contact rated 200mA/50 V DC, Signal Active when Vout> 90% of
output voltage
Dimensions Height: 123 mm (4.85 in)
Width: 60 mm (2.36 in)
Depth: 110 mm (4.36 in)
Weight 1.76 lb (0.8 kg)

Free Spacing Above & Below 25 mm (0.98 in)


Left & Right 10 mm (0.39 in)
Front 15 mm (0.59 in)

Terminals and wiring


Input Output DC-OK-Signal
Screw-Type Screw-Type Screw-Type
Terminals Terminals Terminals
Solid & 1.5-6 mm2 1.5-6 mm2 1.5-6 mm2
Stranded Wire 16-10 AWG 16-10 AWG 16-10 AWG
Screw Torque 4.4 lb-in 7 lb-in 7 lb-in
(50 N-cm) (80 N-cm) (80 N-cm)

www.emerson.com/deltav 12
DeltaV Bulk Power Supplies December 2017

DeltaV Bulk Power Supply Redundancy Module, 12 V DC to 28 V DC, 20 A


Description Redundancy Module 12 to 28 V DC, 20 A Specifications

Input Voltage 12-28 V DC

Input Voltage Range 10.8-30.8 V DC

Nominal Input Current 2 x 10A, 1 x 20A (-40°C to +70°C)


2 x 12A , 1 x 24A (-40C°C to +60°C)
2 x 12.5A, 1 x 25A (-40C°C to +50°C)
2 x 13A, 1 x 26A (-40C°C to +40°C)
Output Current 0-26 A continuous
26-50 A for 5 seconds
26 A continuous overload/short circuit
Input to Output Voltage Drop 0.2V Typical

Power Losses 0.5 mW at no load (typical)


0.64 mW at 2 x 5 A input (typical)
0.82 mW at 1 x 10 A input(typical)
2.08 W at 2 x 10 A input (typical)
Alarm Relay Contact Rating N.O. DC OK Contact 60 V DC max @1A

Dimensions Height: 123.2 mm (4.85 in)


Width: 35 mm (1.38 in)
Depth: 113.3 mm (4.46 in)
Weight 0.8 lb (0.36 kg)

Terminals and wiring


Input Output DC-OK-Signal
Screw-Type Screw-Type Screw-Type
Terminals Terminals Terminals
Solid & 3.3-5.3 mm2 8.4-13.3 mm2 0.33-3.3 mm2
Stranded Wire 12-10 AWG 8-6 AWG 22-12 AWG
Screw Torque 7 lb-inch 15.6 lb-in 4.4 lb-inch
(79.1 N-cm) ( 176 N-cm) (49.7 N-cm)

www.emerson.com/deltav 13
DeltaV Bulk Power Supplies December 2017

DeltaV Bulk Power Supply Redundancy Module, 12 V DC to 28 V DC, 40 A


Description Redundancy Module 12 to 28 V DC, 40 A Specifications

Input Voltage 12-28 V DC

Input Voltage Range 10.8-30.8 V DC

Nominal Input Current 2 x 20A, 1 x 40A (-40°C to +70°C)


2 x 24A , 1 x 48A (-40°C to +60°C)
2 x 25A, 1 x 50A (-40°C to +50°C)
2 x 26A, 1 x 52A (-40°C to +40°C)
Output Current 0-40 A continuous
40-65 A for 5 seconds
40 A continuous overload/short circuit
Input to Output Voltage Drop 0.2V Typical

Power Losses 0.5 mW at no load (typical)


2.08 W at 2x 10 A input (typical)
2.32 W at 1x 20 A input (typical)
7.68 W at 2x 20 A input (typical)
Alarm Relay Contact Rating N.O. DC OK Contact 60 V DC max @1A

Dimensions Height: 123.2 mm (4.85 in)


Width: 35 mm (1.38 in)
Depth: 113.3 mm (4.46 in)
Weight 0.8 lb (0.36 kg)

Terminals and wiring


Input Output DC-OK-Signal
Screw-Type Screw-Type Screw-Type
Terminals Terminals Terminals
Solid & 3.3-5.3 mm2 8.4-13.3 mm2 0.33-3.3 mm2
Stranded Wire 12-10 AWG 8-6 AWG 22-12 AWG
Screw Torque 7 lb-inch 15.6 lb-in 4.4 lb-inch
(79.1 N-cm) ( 176 N-cm) (49.7 N-cm)

www.emerson.com/deltav 14
DeltaV Bulk Power Supplies December 2017

DeltaV Bulk Power Supply Redundancy Module, 12 V DC to 28 V DC, 80 A


Description Redundancy Module 12 to 28 V DC, 80 A Specifications

Input Voltage 12-28 V DC

Input Voltage Range 10.8-30.8 V DC

Nominal Input Current 2 x 35A, 1 x 70A (-40°C to +70°C)


2 x 40A , 1 x 80A (-40°C to +60°C)
2 x 42.5A, 1 x 85A (-40°C to +50°C)
2 x 45A, 1 x 90A (-40°C to +40°C)
Output Current 0-80 A continuous
80-120 A for 5 seconds
80 A continuous overload/short circuit
Input to Output Voltage Drop 0.2V Typical

Power Losses 1.18 mW at no load (typical)


4.88 W at 2x 20 A input (typical)
6.08 W at 1x 40 A input (typical)
14.24 W at 2x 40 A input (typical)
Alarm Relay Contact Rating N.O. DC OK Contact 60 V DC max @1A

Dimensions Height: 123.2 mm (4.85 in)


Width: 46 mm (1.81 in)
Depth: 117 mm (4.61 in)
Weight 1.1 lb (0.48 kg)

Terminals and wiring


Input Output DC-OK-Signal
Screw-Type Screw-Type Screw-Type
Terminals Terminals Terminals
Solid & 8.4-13.3 mm2 13.3-33.6 mm2 0.33-3.3 mm2
Stranded Wire 8-6 AWG 6-2 AWG 22-12 AWG
Screw Torque 15.6 lb-in 33.6 lb-in 4.4 lb-inch
( 176 N-cm) ( 380 N-cm) (49.7 N-cm)

www.emerson.com/deltav 15
DeltaV Bulk Power Supplies December 2017

Hardware Specifications for Legacy Power Supplies


Common Environmental Specifications

Operational Temperature* -25 to + 70°C (-13 to 158°F) Output derating may be required.

Storage Temperature -40 to + 85°C (-40 to 185°F)

Relative Humidity 5 to 95%, non-condensing

Protection Rating IP20

Airborne Contaminants ISA-S71.04-1985 airborne contaminants class G3, Conformal coating**

Shock 15 g ½ sign wave for 6 ms, 10 g ½ sign wave for 11 ms.

Vibration 1.6 mm peak to peak from 2-17.8 Hz; 2 g from 17.8 to 500 Hz.

Mounting Mount only on horizontally-oriented DIN Rail, with label text right-side up.

Required Spacing 40 mm on top, 20 mm on the bottom, 5 mm on both sides.


Required Spacing Between Multiple Units 15 mm on each side adjacent to another Bulk PS.

*Operating any electronics at the higher end of its temperature range for long periods of time will shorten its expected lifetime,
see Effects of Heat and Airflow Inside an Enclosure White Paper for more information.
**Only applies to conformal coated models, see ordering information for more details.

Certificates and Compliances* CSA certified to C22.2 No. 60-950 CE EN61326


UL 508, ATEX, IEC-EX
GL Marine Certificate
* No Hazardous Area Certificates for model marked for safe are installation only, see ordering information for details.

www.emerson.com/deltav 16
DeltaV Bulk Power Supplies December 2017

DeltaV Bulk Power Supply 100-240 V AC to 12 V DC, 15 A (Legacy)


Description DeltaV Bulk AC to 12 V DC, 15 A Power Supply Specifications

Output Voltage 12 V DC

Output Voltage Adjustment Range 12-15 V DC

Output Current 15-13.5 A continuous


22.5-20.3 A for 4 seconds (typical)
Output Power 180 W continuous
270 W for 4 seconds (typical)
Output Ripple < 50 mV peak-to-peak at 20 Hz to 20 MHz

Output Hold-up Time AC input


- 72 ms typical at 100 V AC, 12V, 7.5 A
- 31 ms typical at 100 V AC, 12V, 15 A
- 72 ms typical at 120 V AC, 12V, 7.5 A
- 32 ms typical at 120 V AC, 12V, 15 A
- 72 ms typical at 230 V AC, 12V, 7.5 A
- 32 ms typical at 230 V AC, 12V, 15 A

DC input
- 31 ms typical at 110 V DC
Operational Temperature Range -25°C to + 70°C

Output Derating at Higher Temperature 5 W/°C at +60°C to +70°C

AC Input Voltage 100-240 V AC ±15%, single-phase

AC Mains Frequency 50-60 Hz ± 6%

AC Input Current 1.65 A at 120 V AC


0.93 A at 230 V AC
AC Power Factor 0.98 at 120 V AC
0.92 at 230 V AC
AC Inrush Current 10 A peak maximum at 100 V AC
(Over Entire Temperature Range) 5 A peak typical at 100 V AC
10 A peak maximum at 120 V AC
4 A peak typical at 120 V AC
10 A peak maximum at 230 V AC
7 A peak typical at 230 V AC
AC Efficiency 91.5% at 120 V AC
91.8% at 230 V AC
AC Losses 16.7 W at 120 V AC
16.1 W at 230 V AC
DC Input Voltage 110 to 150 V DC -20%/+25% single-phase

DC Input Current 1.78 A at 110 V DC

DC Power Factor 1 or N/A at 110 V DC

DC Inrush Current 10 A peak maximum


5 A peak typical
DC Efficiency 91.0% at 110 V DC

DC Losses 17.8 W at 110 V DC

www.emerson.com/deltav 17
DeltaV Bulk Power Supplies December 2017

Input Protection Internally fused, non-replaceable fuses.


Note: The internal fuse is for an internal fault condition only.
Shorts and overload will not cause the fuse to fail.
Alarm Relay Contact Rating 60 V DC at 0.3 A, 30 V DC at 1 A, 30 V AC at 0.5 A

Dimensions Height (max): 12.4 cm (4.9 in.)


Width (max): 6.0 cm (2.4 in.)
Depth (max): 11.7 cm (4.6 in.)
Weight 1.98 lb (0.9 kg)

Terminals and wiring

Bistable, quick-connect spring-clamp terminals with IP20 finger-safe


construction are used. The terminals are shipped in the open position
and suitable for field installation.

Input Output DC-OK-Signal


Spring-Clamp Spring-Clamp Spring-Clamp
Terminals Terminals Terminals
Solid Wire 0.5-6 mm2 0.5-6 mm2 0.5-6 mm2
20-10 AWG 20-10 AWG 20-10 AWG
Stranded Wire 0.5-4 mm2 0.5-4 mm2 0.5-4 mm2
20-10 AWG 20-10 AWG 20-10 AWG

www.emerson.com/deltav 18
DeltaV Bulk Power Supplies December 2017

Ordering Information
DeltaV Bulk Power Supplies

Description Model Number


DeltaV Bulk Power Supply 100-240 V AC to 24 V DC, 5A VE5138

DeltaV Bulk Power Supply 100-240 V AC to 24 V DC, 10A VE5123

DeltaV Bulk Power Supply 100-240 V AC to 24 V DC, 20A VE5126

DeltaV Bulk Power Supply 100-240 V AC to 24 V DC, 40A VE5128

DeltaV Bulk Power Supply 100-240 V AC to 12 V DC, 15A VE5137

DeltaV Bulk Power Supply Redundancy Module,12-28V, 20A VE5134

DeltaV Bulk Power Supply Redundancy Module,12-28V, 40A VE5135

DeltaV Bulk Power Supply Redundancy Module,12-28V, 80A VE5136

DeltaV Bulk Power Supply 100-240 V AC to 24 V DC, 5A, conformal coating VE5122

DeltaV Bulk Power Supply 100-240 V AC to 24 V DC, 10A, conformal coating VE5124

DeltaV Bulk Power Supply 100-240 V AC to 24 V DC, 20A, conformal coating VE5127

DeltaV Bulk Power Supply 100-240 V AC to 24 V DC, 40A, conformal coating VE5129

DeltaV Bulk Power Supply 100-240 V AC to 12 V DC, 15A, 12V, conformal coating VE5121

DeltaV Bulk Power Supply Redundancy Module,12-28V, 20A, conformal coating VE5131

DeltaV Bulk Power Supply Redundancy Module,12-28V, 40A, conformal coating VE5132

DeltaV Bulk Power Supply Redundancy Module,12-28V, 80A, conformal coating VE5133

Legacy Bulk Power Supplies

Description Model Number


DeltaV Bulk Power Supply 100-240 V AC to 12 V DC, VE5021
15 A with certifications for Hazardous Areas, conformal coating

www.emerson.com/deltav 19
DeltaV Bulk Power Supplies December 2017

Emerson
North America, Latin America: ©2017, Emerson. All rights reserved.
+1 800 833 8314 or
The Emerson logo is a trademark and service mark of Emerson Electric Co. The DeltaV logo is
+1 512 832 3774
a mark of one of the Emerson family of companies. All other marks are the property of their
respective owners.
Asia Pacific:
+65 6777 8211 The contents of this publication are presented for informational purposes only, and while every
effort has been made to ensure their accuracy, they are not to be construed as warranties or
Europe, Middle East: guarantees, express or implied, regarding the products or services described herein or their
+41 41 768 6111 use or applicability. All sales are governed by our terms and conditions, which are available on
request. We reserve the right to modify or improve the designs or specifications of our products
www.emerson.com/deltav at any time without notice.

You might also like