1LAC000003 DistTrHandbook
1LAC000003 DistTrHandbook
1LAC000003 DistTrHandbook
1
0. FOREWORD
The objective of this Distribution Transformer Handbook is to facilitate the selection, ordering and
operation of distribution transformers.
The target readers are personnel involved in the various stages of a transformer’s service life, from
planning the investment to the disposal of the transformer after use. It may also be useful to ABB
personnel.
The handbook is arranged with the sections following the transformers life from planning through
ordering, installation, operation, maintenance and scrapping.
Other useful information, including more theoretical topics, may be found at the end of this
handbook.
Navigation through this handbook is facilitated through a three level contents following this
foreword, and the index at the end.
ABB Power Technologies Division thanks the International Electrotechnical Commission (IEC) for
permission to reproduce information from its International Standards. All such extracts are
copyright of IEC, Geneva, Switzerland. All rights reserved. Further information on the IEC is
available from www.iec.ch. IEC has no responsibility for the placement and context in which the
extracts and contents are reproduced by ABB Power Technologies Division; nor is IEC in any way
responsible for the other content or accuracy therein."
The standards, IEC, CENELEC, IEEE, mentioned in the text refer to the edition given in the list of
standards. For practical use only latest editions of the standards should be used.
Extracts from the ABB Switchgear Manual are quoted by kind approval by the issuer.
UK English has been selected for this document to comply with the text in IEC standards.
1.1. ABB-GROUP
ABB is a leader in power and automation technologies that enable utility and industry customers to
improve performance while reducing environmental impact. The ABB Group of companies operates
in around 100 countries and employs about 135,000 people.
ABB Power Technologies serves electric, gas and water utilities as well as industrial and
commercial customers, with a broad range of products, systems and services for power
transmission, distribution and automation.
ABB Automation Technologies blends a robust product and service portfolio with end-user
expertise and global presence to deliver solutions for control, motion, protection, and plant
integration across the full range of process and utility industries.
Industrial IT is the ABB name for a powerful commitment to solutions for Real-Time Automation
and Information. Industrial IT guides every step ABB takes going forward in technology, business
processes, and more.
All ABB Distribution Transformer products are Industrial IT certified, which guarantees structured,
easy accessible and on-line documentation. It can be viewed on its own but also as a part of a
larger system.
As a business-to-business supplier ABB knows that value creation grows out of close relationships
with customers. That means the better we know our customers’ business challenges, the better we
can serve them. We strengthen our relationships by building trust as a socially responsible supplier
of environmental sound products and services.
ABB offers a full range of transformers fulfilling the requirements in IEC, CENELEC, ANSI, other
standards and customer-specific requirements.
Distribution transformers, liquid filled have primary voltages up to 72,5 kV and dry-type
transformers with open or encapsulated windings for primary voltages up to 52 kV.
Transformers of this type are generally oil immersed and suitable for pole
mounting. They represent an economical option for certain networks,
particularly those with low population densities. Depending on customer
requirements, transformers may be connected between two phases of a
three phase system (two HV bushings) or from one phase to ground (single HV bushing). They are
suitable for residential overhead distribution loads, as well as light commercial or industrial loads
and diversified power applications.
Any information regarding the required corrosion resistance of the surface treatment in reference to
the geographic zone and pollution zone.
4.2.13. Energizing
After the transformer has been found to be in good condition and the protective equipment is found
in order, the transformer can be connected to the network.
When connecting the transformer to the network, fuses may blow immediately caused by high
inrush current. This does not necessarily mean that there is a fault in the transformer. Replace
blown fuses and try energizing again because the magnitude of the inrush current is a statistical
variable large spread. Modern over-current and differential relays contain a control circuit which
makes the relays in sensitive to inrush currents. Older relays may trip the circuit breaker
immediately. See also section 6, paragraph “Inrush current”.
After the transformer has been connected to the network, gas may be present which gives an
alarm in the gas relay. It could be a false alarm caused by an air bubble, trapped under the cover,
and then moved into the gas relay.
Air is colour less and odor less. If not air, a gas and an oil sample should be taken for analysis.
4.3.1. Lifetime
The lifetime of a transformer can be divided into two categories; economical and technical.
Economical lifetime:
Economical lifetime ends when the capitalized cost of continued operation of the existing
transformer exceeds the capitalized cost of a new investment.
In practical terms; typically when the cost of the total losses of the old transformer is too high.
Consequential risks and costs associated with electricity downtime are of increasing importance.
Technical lifetime:
Solid insulation materials consist mainly of organic materials. These materials change over time,
they become brittle and the mechanical strength is reduced, while there is very little reduction in the
dielectric strength.
These detrimental processes, which are affected by temperature, humidity and oxygen, are called
ageing. Ageing consists of several oxidation processes, where the chemical reaction rate increases
strongly with temperature.
As a rule of thumb, lifetime is halved at a temperature rise of 7-8 ºC and vice versa, this is called
Montsinger’s rule.
Thus, the expected technical lifetime for a transformer depends mainly on its accumulated load
cycle and the ambient temperature. This varies with customer, application, location etc.
IEC 60354 provides guidelines on how to overload oil-immersed transformers.
There is no clear definition of "end of life" in any international standard. This is a matter where high
degree of judgment is involved.
To illustrate this, an old transformer can work perfectly well in normal conditions for several years
more, but as soon as it gets a surge, be it a voltage peak, heavy overload or short- circuit currents,
it may collapse.
Also a number of transformers are exchanged due to change in system voltage or insufficient
capacity.
A typical technical lifetime of a distribution transformer under normal conditions is at least 30 years.
4.3.4. Frequency
A transformer designed for 50 Hz can be used for 60 Hz but not vice versa.
4.4. MAINTENANCE
4.4.10. Gaskets
The gaskets of the cover and flanges, as well as between bushings and cover, are usually made of
liquid resistant vulcanized cork sheet or silicone sealant.
If the gaskets are leaking, leaks can usually be sealed by tightening the screws (bolts).
When these gaskets have to be replaced, it is recommended to contact ABB.
Liquid resistant rubber rings are used as gasket for bushing bolts, shafts and spindles. All these
gaskets can be tightened and replaced from outside the tank.
When tightening the gaskets special care must be taken to prevent the breaking of screws (bolts)
or the gasket “floats away” (if not in a groove) caused by the heavy pressure. In particular stud nuts
must be tightened very carefully.
5.2. REUSE
Transformers contain valuable materials, which may be reused either as is or after reprocessing.
Examples are:
• Copper,
• Aluminium,
• Oil,
• Steel.
Insulation material, pressboard and paper, represent energy.
5.3. LANDFILL
Materials not re-circulated go to landfill or energy production. The landfill portion of the transformer
should be minimized.
p = 3 ⋅ R ⋅ I2 (W) (1)
At a system voltage U the transmitted active power is:
Figure 6-1
If the loop is replaced by a coil with N number of series-connected turns, the same induced voltage
will take place in each of the turns. The voltage induced in the whole coil will then be:
dΦ
ui = −N ⋅ (V) (7)
dt
The other physical phenomenon is that a conductor carrying an electrical current is surrounded by
a magnetic field.
H
I
Figure 6-2
To create a magnetic field that varies in time in a transformer a sinusoidal voltage is applied to the
primary winding which creates a magnetising current.
The windings are made as concentric shells around a central core of laminated steel plates, which
is formed as a closed loop for the magnetic field. Due to the magnetic properties of the steel the
magnetic flux will be several thousand times higher than it would have been without the steel core,
which makes the magnetic coupling between the windings strong.
When the terminals of the secondary winding are open, the relation between the applied voltage on
the primary side and the output voltage on the secondary side is the same as the relation between
the number of turns in the primary winding and the secondary winding respectively:
U1 N
= 1 (8)
U2 N2
or
When the secondary winding is loaded, the voltage ratio may differ considerably from the turn ratio
(see 6.5.), while the ratio between the primary and secondary currents fulfils the equation:
I1 ⋅ N1 = I 2 ⋅ N 2 (10)
with a deviation of one percent or less.
I2
Z0 U20 U2 ZL
Figure 6-3
In no load condition (open secondary terminals) the total magnetising current and the active power
consumption are measured at rated voltage. The current has one dominant inductive component
and one smaller active component. These can be calculated from the measurements, and the real
and the imaginary components of transformer’s no load impedance Z0 can be found. This
impedance is not constant but will vary non-linearly with the applied voltage due to the non-linearity
of the magnetisation curve. The real part of Z0 represents the no load losses.
The other impedance in the diagram, Z, is found by short-circuiting the secondary terminals and
applying a voltage at the primary side. The current in the windings during this measurement shall
be equal to the rated current. To achieve this current an applied voltage of just a fraction of the
rated voltage will be sufficient. This voltage is called the short-circuit voltage and is usually
expressed as a percentage of the rated voltage. The impedance of the circuit is given by the
quotient of the short-circuit voltage divided by the rated current. The circuit is a parallel connection
of Z0 and Z. Because Z0>>Z the impedance of the parallel connection is equal to Z with a negligible
difference. The real part of Z represents the load losses of the transformer, and the imaginary part
is attributed to the magnetic leakage field. That is the part of the magnetic field, which is situated
outside the core.
ur
I2
U2
Figure 6-4
From the vector diagram in Figure 6-4 the following relationship appears:
∆U2 is the voltage drop, the arithmetic difference between U20 and U2. ur and ux are the active and
the reactive short-circuit voltages at rated current related to the rated voltage U20.
To calculate the relative voltage drop at any relative loading n equation (11) can be rewritten as
∆U2
= n(ur cos ϕ + u x sin ϕ) + 1 − 1 − n2 (ur sin ϕ − u x cos ϕ)
2 (12)
U20
I2 (13)
n=
I 2N
In other words, when a transformer with these values for ur and ux is loaded with rated current with
a power factor of 0,8 inductive the voltage on the secondary terminals decreases to 95,5% of the
voltage at no load.
6.6. EFFICIENCY
The efficiency of a transformer is calculated according to:
1
η% = ⋅ 100
P0 + PL ⋅ n 2
1+
P2 ⋅ n
where
P0 is the no load loss k(W) at rated voltage
PL is the load loss (kW) at rated current
P2 is the active power (kW) supplied to the load
n is the relative degree of loading. At rated current n=1.
T=Vs/m2
d
B
e
f c
H
A/m
Figure 6-7
At point e the current has decreased to zero. And again there is a remanent flux floating in the
core, this time with the opposite direction compared to the remanent flux at point b. Increasing the
current now in the negative direction, the flux decreases further and becomes zero at point f. From
point f on the flux changes direction and increases in the negative direction until it reaches point a.
Now one cycle of the applied voltage is completed.
u = dΦ (V) (18)
dt
This can also be seen the opposite way, the magnetic flux is the time integral of the voltage:
dΦ = u ⋅ dt (Vs) (19)
Φ = ∫ u ⋅ dt (Vs) (20)
Assuming that the voltage is sinusoidal and the integral is taken over the first half cycle of the
voltage, that is from 0 to π, where 0 is the time when the circuit breaker makes and π is the time
when the voltage changes direction:
π
Φ = ∫ U ⋅ sin( ωt ) ⋅ d(ωt ) = U(− cos π − ( − cos 0)) = 2U (Vs) (21)
0
To compare this result with the situation when the circuit breaker makes at the peak value of the
voltage, the integral is taken between the limits π/2 and π.
Φ t = 2Φ + Φ r (Vs) (23)
which makes the inrush current even higher.
Figure 6-9
Figure 6-9 illustrates the situation. The light grey curve marked Φ’ is the magnetic flux in the normal
stationary condition.
When the voltage changes direction at π, the current will decrease. But at 2π the current will
increase again. This course of events will continue with gradually decreasing peak values of the
current. The influence of the original remanent flux will also gradually disappear. The number of
cycles before stationary normal operation is reached ranges from less than 10 cycles for small
transformers up to several minutes for larger transformers.
A sudden increased sound level that follows the same declining development as the magnetic flux
can be heard.
The statistical probability that the absolute worst case will occur is not high. In most cases electrical
connection between the two poles of the circuit breaker will be established before metallic contact
between the poles takes place because of arcing between the poles. There is higher probability
that such arching will occur when the voltage difference between the poles is in the range of the
voltage maximum than when this voltage difference is close to zero.
The short-circuit power of the feeding source has also influence on the magnitude of the inrush
current. If the short–circuit impedance of the source is high, the inrush current will cause a voltage
drop across this impedance which will reduce the voltage at the transformer terminals. It can also
be noted that the worst case only occurs in one out of the three phases.
A characteristic of the inrush current is that it contains a second harmonic component because of
unsymmetrical half-cycles. Modern overcurrent relays and differential relays contain a control
circuit that reduces the sensivity of the relay when a second harmonic in the current exists. In that
u z% ⋅ U r u z% U r2
Z= = ⋅ Ω (27)
3 ⋅ 100 ⋅ Ir 100 Sr
R ⋅ Ir
ur = p.u. (31)
Ur
R ⋅ Ir
u r% = ⋅ 100 % (32)
Ur
For three-phase transformers a factor √3 is inserted in the nominator. There is a simple relation
between ur, the load losses PL and the rated power Sr of the transformer:
R ⋅ Ir R ⋅ Ir2 P
ur = = = L p.u. (33)
Ur Ur ⋅ Ir Sr
The relation ur = PL/Sr is also valid for 3-phase transformers. The imaginary part of uz can be
calculated as
u x = u r2 − u r2 p.u.
(34)
or %
X = Z2 − R2 Ω (35)
While X0 is mainly linked to the magnetic field in the core, X is linked to magnetic leakage field,
which mainly runs through the windings and the ducts between windings.
Dimensions in meter. N is the number of turns in the winding on the side to which X shall be
referred. See Figure 6-11.
t1 t12 t2
Figure 6-11
In the formula (37) L1 and L2 are the mean circumference for the inner and outer windings
respectively. The formula is based on the assumption that the magnetic field lines goes vertically
along the whole height hw of the windings. This is in reality not the case. It can be seen from Figure
10 that some of the field lines towards the ends of the windings have an increasing horizontal or
radial component. The German professor W. Rogowski made a careful study on how to
compensate for this deviation from the assumption in the formula. The result of this study
(published early in the last century) was a correction factor
(t 1 + t 12 + t 2 ) −
πh w
kR = 1− 1 − e (t1 + t12 + t 2 ) (38)
πh w
This factor has is known as the the Rogowski factor. In most practical cases its numerical value is
within the range 0,95 – 0,99. It makes the length of the leakage field duct a little longer, hw/kR
instead of hw.
The formula for ux expressed as a percentage of the rated voltage Ur is
u x = 2( t 12 +
t1 + t 2 L1 + L 2
) kR
(IN) f 10 − 2
% (39)
3 hw e t 0 50
where et0 is the number of volts per turn in no load condition.
Corresponding hand formulas exist also for more complicated winding arrangements. The short-
circuit reactance or short-circuit voltage calculated by means of these formulas comply very well
with the measured values. However, for high currents an addition for the reactance in the lead
assembly must be made.
U
I sc = kA (40)
3 ⋅ (Z + Z s )
Where Zs is the short-circuit impedance of the system.
U 2s
Zs = In ohms per phase (equivalent star connection) (41)
S
R X
Û sin(ωt + α )
i(t
Figure 6-12
Consider the circuit in Figure 6-12. Assume that the switch makes at the instant t = 0, thus
simulating a short-circuit. The current i(t) is expressed by the following equation:
i( t ) = Î ⋅ (sin(ωt + α − ϕ) − e
−t
τ
⋅ sin(α − ϕ)) A (43)
in which
Û
Î = A (44)
Z
that is the peak value of the symmetrical, stationary short-circuit current
Z = R + j ωL [Ω]
α = switching angle of the voltage u(t) at the instant of the short circuit [rad]
ϕ = phase angle of the circuit impedance (=arctg ωL/R) [rad]
τ = L/R = tgϕ/ ω [ s] (the time constant of the circuit)
-1
ω = 2·π·f [s ]
π −t
i( t ) = Î ⋅ (sin(ωt − ) + e τ ) A (45)
2
The first current peak closely corresponds to the time when ωt = π.
1,5
1
Isc p.u.
0,5
0
0 20 40 60 80
-0,5
-1
t (ms)
Figure 6-13
i = Î ⋅ k = I sc ⋅ 2 ⋅ k = I sc max A (46)
Figure 6-13 shows an example on how the short-circuit current elapses. In this example X/R = 8, k
= 1,68.
The peak factor is k·√2 and its dependence of X/R is shown in Figure 6-14. The peak factor value
in the example in Figure 6-13 is 2,38. The value of the first peak of the short circuit current is the
r.m.s. value of the stationary short circuit current multiplied with the peak factor.
In a real case with a transformer installed in a network:
X = the sum of the network and the transformer reactance [Ω]
R = the sum of the network and the transformer resistance [Ω]
X/R and the peak factor increase with increasing transformer power rating.
k√2
2,2
2,0
1,8
1,6
1,4
1 10 100
X/R
Figure 6-14
Mechanical forces in the windings
Current flows through the winding conductors, which are situated in the magnetic leakage field. The
conductors are then subject to mechanical forces.
These forces are not static. They are pulsating. Each time the current passes through zero the
forces are also zero. At normal load current the forces are small. They increase with the square of
the current, so during the high overcurrents that arise if a short-circuit in the system occur, the
forces must be given attention when designing the transformer. The short circuit current may
amount to 10 – 20 times the rated current of the transformer, which means that the forces in the
windings may be 100 – 400 times larger at a short circuit than in normal service.
The forces cause large movements in the windings. These movements are invisible for the human
eye. But rapid film recordings played in slow motion show the size of the movements and illustrate
the violence of the forces.
I
B
F=IХB
Figure 6-15
When considering the ability of a design to withstand it is usual to split the forces into radial and
axial components as indicated in Figure 6-15, which shows an upper part of an outer winding. The
radial force is directed outwards and causes a tensile force in the winding conductors. In the
corresponding inner winding the radial component is directed inwards. That may cause buckling of
the winding if it has not been made robust enough.
The axial forces are caused by the radial component of the magnetic field at the ends of the
windings. These forces may lead to tilting of the conductors between the axial spacers in the
winding. The force on each turn or disc adds together. The sum of the forces is balanced at the
other end of the winding. The whole winding is subject to a strong axial pressure. See Figure 6-16.
Figure 6-16
The ability to withstand tilting of the conductors depends on the diameter of the winding, the
distance between the spacers around the circumference and the dimensions of the conductor.
In case of axial “openings” in the winding, that is one or more places along the height of the
winding where there are no ampere-turns, there will be axial forces directed towards the yokes.
The framework keeping the core and windings together must be designed to be able to withstand
such forces.
In case of axial “openings” in the winding, that is one or more places along the height of the
winding where there are no ampere-turns, there will be axial forces directed towards the yokes.
The framework keeping the core and windings together must be designed to be able to withstand
such forces.
A more comprehensive treatment of the short-circuit topic is given in the book “SHORT-CIRCUIT
DUTY OF POWER TRANSFORMERS – THE ABB APPROACH” by Giorgio Bertagnolli, issued by
ABB. The book is available from ABB at request.
p2
L p = 10 ⋅ lg dB (48)
p 02
where p is the sound pressure measured by a microphone. Sound pressure is a scalar quantity,
which means it has magnitude only.
To provide a feeling of how a few well-known types of sound are situated on the dB-scale some
values are listed below.
Source of sound Sound pressure level in dB
Quiet living area 45
Normal conversation at 1 m distance 60
Medium factory noise 75
Factory maximum limit 85
City street with heavy traffic 95
Circle saw at 1 m distance 105
Comprehensive investigations are made to correlate human perception of ‘loudness’ at various
frequencies and sound pressures. The curves in Figure 6-17 are results of such investigations.
These curves will vary somewhat from one person to another, but they can be regarded as average
curves for how young persons with healthy ears respond.
Each curve represents sound that is perceived as ‘equally loud’ across the whole frequency range.
The lowest curve that goes through zero dB sound pressure at1000 Hz represents the hearing
threshold. The human ear is not able to hear anything below this curve. It appears that the ear is
most sensitive in the frequency range between 3 and 4 kHz, where a sound pressure even below
20 µPa is audible.
For frequencies below 700 Hz the threshold curve ascends, which means that for the lower
frequencies the sound pressure has to be increased to make the sound audible. The curve also
rises at frequencies above 4 kHz.
The three upper curves go through 40, 70 and 100 dB at 1 kHz. A microphone responds quite
differently to sound pressure. In order to imitate the response curves of the human ear filters are
inserted in the measuring equipment. Three different filters are standardized, named A, B and C
filters. They imitate the curves going through 40, 70 and 100 dB at 1 kHz respectively.
Measurement results made with one of the three filters inserted are denoted dB(A), dB(B) or dB(C).
120
C-weighted filter
110
100
90 B-weighted filter
Sound pressure (dB)
80
70
60 A-weighted filter
50
40
30
20 Hearing threshold
10
0
-10
10 100 1000 10000 100000
Sound frequency (Hz)
Figure 6-17
W
L w = 10 ⋅ lg db (49)
W0
-13
In this formula W0 is an arbitrarily chosen reference value equal to 10 Watt, which corresponds to
a quite weak sound source. This reference value is chosen without regard to the previously
mentioned reference value for sound pressure.
The sound power of one of the strongest sound power sources of concern, a large jet motor, has a
18
sound power of about 100 000 Watts. The total power range to deal with is then 10 . Instead of
working with such extremely high figures in acoustical subjects, the whole power range is covered
by 180 dB.
Based on the measured sound pressure the sound power of the transformer in dB can be
calculated according to formulas given in IEC 60076-10 Ed. 1.0.
In a large free field the sound pressure at larger distances from the transformer can be calculated.
In practice there are often one or more walls or other items in the surroundings of the transformer
that will reflect sound from the transformer and make a prediction of the sound pressure at various
places in the neighbourhood difficult.
Sources of sound generation
The dominant generating source of transformer sound is magnetostriction. Magnetostriction is the
change in dimensions which takes place in certain materials when they are subjected to a change
-7 -5
in magnetic flux. In magnetic core steel the dimensional change is in the range of 10 to 10
meters per meter length at typical induction levels.
The effect does not depend on the sign of the flux, only on its magnitude and orientation relative to
certain crystallographic axes of the material. Therefore, when excited by a sinusoidal flux, the
fundamental frequency of the dimensional change will be twice the exciting frequency. The effect is
highly non-linear, especially at high, near saturation, induction levels. The non-linearity results in a
significant harmonic content in the vibration spectrum of the core.
In three-phase cores the change in dimension in each core limb does not occur simultaneously,
which means that the whole core will be subject to pulsating distortions that also generate sound.
A DC bias in addition to the AC magnetization of the core may significantly increase the vibration
amplitudes of the core and consequently the sound level. The DC bias may also cause a
considerable difference in the positive and negative peaks of the flux density, which in turn makes
the fundamental frequency of the sound equal to the frequency of the service voltage instead of
twice this frequency.
Physical Additional
Viscosity Low particle content
Appearance Compatibility with other transformer
materials
Density Gassing properties
Pour point Aromatic structure
Surface tension Poly-aromatic structure
Flash point Solubility properties
10.3. IP-CLASSIFICATION
10.3.1. General
IP classification describes to what extent electrical equipment, in this regard the transformer
terminals as well as accessories, are protected against touching and external influence such as
dust, pollution, moisture etc.
Reference is made to IEC 60529 for a detailed description on this subject. *Copyright © IEC,
Geneva, Switzerland. www.iec.ch
Explanation of numerals : IP23
The first characteristic numeral (2) describes the protection against solid foreign objects of 12.5mm
diameter and greater.
The second characteristic numeral (3) describes the protection against spraying water.
Figure 10-1
10.6.1. Definitions
*Copyright © IEC, Geneva, Switzerland. www.iec.ch
The International Electrotechnical Vocabulary (IEV) gives the following definition of EMC:
”The ability of an equipment or system to function satisfactorily in its electromagnetic environment
without introducing intolerable electromagnetic disturbances to anything in that environment.” [IEV
161-01-07]
Other relevant definitions are:
Electromagnetic disturbance
Any electromagnetic phenomenon which, by being present in the electromagnetic environment,
can cause electrical equipment to depart from its intended performance [IEV 161-01-05, modified]
Electromagnetic interference (EMI)
Degradation of the performance of equipment, transmission channel or system caused by an
electromagnetic disturbance.
NOTE The terms “electromagnetic disturbance” and “electromagnetic interference” denote
respectively cause and effect, but they are often used indiscriminately. [IEV 161-01-06]
Disturbance level
The amount or magnitude of an electromagnetic disturbance, measured and evaluated in a
specified way [IEV 161-03-01, modified]
Electromagnetic compatibility level
10.7.1. Quality
The functional reliability of transformer installations depends of the suitability and quality of the
transformer, components and the processes employed. ABB transformer factories have adopted
the European and International standard of quality
EN ISO 9001:2000 Quality management systems
Requirements
This standard emphasizes customer satisfaction, process approach and continuous improvement.
Most factories operate ISO 9001 certified management systems.
10.7.2. Environment
ABB requires that all manufacturing sites operate a certified environmental management system
according to the International standard
ISO 14001:1996 Environmental management systems
Specification with guidance for use
Thus, ABB has committed itself to work for environmental improvement and pollution reduction.
1)
New edition in process
1)
New edition in process
Distribution Transformer Handbook Page 72
IEC 60867 (1993-09)
Insulating liquids – Specifications for unused liquids based on synthetic aromatic
hydrocarbons
IEC 60897 (1987-03)
Methods for the determination of the lightning breakdown voltage of insulating liquids
IEC 60905 (1987-12)
Loading guide for dry-type transformers
IEC 60944 (1988-09)
Guide for the maintenance of silicone transformer liquids
IEC 60970 (1989-06)
Methods for counting and sizing particles in insulating liquids
IEC 61039 (1990-10)
General classification of insulating liquids
IEC 61065 (1991-05)
Method for evaluating the low temperature flow properties of mineral insulating oils after
ageing
IEC 61065 Corr. 1 (1993-12)
Corrigendum 1 - Method for evaluating the low temperature flow properties of mineral
insulating oils after ageing
IEC 61099 (1992-05)
Specification for unused synthetic organic esters for electrical purposes
IEC 61099 Corr. 1 (1993-1)
Corrigendum 1 - Specification for unused synthetic organic esters for electrical purposes
IEC 61100 (1992-05)
Classification of insulating liquids according to fire point and net calorific value
IEC 61125 (1992-08 + corrigendum 1992-09)
Unused hydrocarbon-based insulating liquids – Test methods for evaluating the oxidation
stability
IEC 61144 (1992-12)
Test method for the determination of oxygen index of insulating liquids
IEC 61181 (1993-06)
Impregnated insulating materials – Application of dissolved gas analysis (DGA) to factory
tests on electrical equipment
IEC 61197 (1993-09)
Insulating liquids – Linear flame propagation – Test method using a glass-fibre tape
IEC 61203 (1992-12)
Synthetic organic esters for electrical purposes – Guide for maintenance of transformer
esters in equipment
IEC/TR3 61294 (1993-10)
Insulating liquids – Determination of the partial discharge inception voltage (PDIV) – Test
procedure
IEC 61378-1 (1997-09)
Convertor transformers – Part 1: Transformers for industrial applications
IEC 61619 (1997-04)
Insulating liquids – Contamination by polychlorinated biphenyls(PCBs) – Method of
determination by capillary column gas chromatography
IEC 61620 (1998-11)
Insulating liquids – Determination of dielectric dissipation factor by measurement of the
conductance and capacitance – Test method
IEC 61868 (1998-11)
Mineral insulating oils – Determination of kinematic viscosity at very low temperatures
IEC 61936-1 (2002-10)
– Power installations exceeding 1 kV a.c. – Part 1: Common rules
11.3. CONTRIBUTORS
The following have contributed to the preparation of this Distribution Transformer Handbook
Name Section
Karlsen, Roar 2, 2.1, 2.2, 2.3, 2.4, 2.4.1, 2.4.2, 2.5, 10.5
roar.karlsen@no.abb.com
Parma, Diego 1, 1.1, 1.2
diego.parma@ch.abb.com
11.4. FEEDBACK
Any feedback regarding editorial changes, additional subject proposals etc. can be sent by E-mail
to Egil Stryken.
Any questions regarding the various subjects can be sent by E-mail to the author with a copy to
Egil Stryken.
4 FUNDAMENTAL REQUIREMENTS
4.1 General
Installations and equipment shall be capable of withstanding electrical, mechanical, climatic and
environmental influences anticipated on site.
The relevant laws or regulations of an authority having jurisdiction shall have precedence.
5 INSULATION
As conventional (air insulated) installations cannot be impulse tested, the installation requires
minimum clearances between live parts and earth and between live parts of phases in order to
avoid flashover below the impulse withstand level specified for individual tested components of the
installation.
Insulation coordination shall be in accordance with IEC 60071-1.
Table 1 – Minimum clearances in air – Voltage range I ( 1 kV < Um ≤ 245 kV
kV kV kV kV mm mm
20 60 120
3 3,6 10
40 60 120
40 60 120
6 7,2 20
60 90 120
60 90 150
10 12 28 75 120 150
95 160 160
75 120 160
15 17,5 38
95 160 160
95 160
20 24 50 125 220
145 270
145 270
30 36 70
170 320
I 45 52 95 250 480
66 72,5 140 325 630
185 b 450 900
110 123
230 550 1 100
185 b 450 b 900
132 145 230 550 1 100
275 650 1 300
230 b 550 b 1 100
150 170 275 650 1 300
325 750 1 500
275 b 650 b 1 300
b b
325 750 1 500
220 245 360 850 1 700
395 950 1 900
460 1 050 2 100
a The rated lightning impulse is applicable to phase-to-phase and phase-to-earth.
b If values are considered insufficient to prove that the required phase-to-phase withstand voltages are met,
additional phase-to-phase withstand tests are needed.
c For rod-structure.
7 INSTALLATIONS
8 SAFETY MEASURES
Installations shall be constructed in such a way as to enable the operating and maintenance
personnel to circulate and intervene within the framework of their duties and authorizations,
according to circumstances, at any point of the installation.
Specific maintenance work, preparation and repair work, which involve working in the vicinity of live
parts or actual work on live parts, are carried out observing the rules, procedures and work
distances as defined in national standards and regulations.
Care shall be taken that, in the event of fire, the escape and rescue paths and the emergency exits
can be used (see 7.1.6).
The user or owner of the installation shall specify any requirement for fire extinguishing equipment.
Automatic devices to protect against equipment burning due to severe overheating, overloading
and faults (internal/external) shall be provided, depending on the size and significance of the
installation.
Equipment in which there is a potential for sparks, arcing, explosion or high temperature, for
example electrical machines, transformers, resistors, switches and fuses, shall not be used in
operating areas subject to fire hazard unless the construction of this equipment is such that
flammable materials cannot be ignited by them.
If this cannot be ensured, special precautions, for example fire walls, fire-resistant separations,
vaults, enclosures and containment, are necessary.
8.6.2 Transformers, reactors
In the following subclauses, the word 'transformer' represents 'transformers and reactors'.
For the identification of coolant types, see 6.2.2.2. IEC 61100 classifies insulating liquids according
to fire point and net caloric value (heat of combustion). IEC 60726 classifies dry-type transformers
in terms of their behaviour when exposed to fire.
The fire hazard associated with transformers of outdoor and indoor installations is dependent on
the rating of the equipment, the volume and type of insulating mediums, the type and proximity and
exposure of nearby equipment and structures. The use of one or more recognized safeguard
measures shall be used in accordance with the evaluation of the risk.
NOTE For definition of risk, see ISO/IEC Guide 51.
Common sumps or catchment tanks, if required, for several transformers shall be arranged so that
a fire in one transformer cannot spread to another.
The same applies to individual sumps which are connected to the catchment tanks of other
transformers; gravel layers or pipes filled with fluid can, for example, be used for this purpose.
Arrangements which tend to minimize the fire hazard of the escaped fluid are preferred.
If automatically activated fire extinguishing equipment is installed, the clearance G can be reduced.
Doors shall have a fire resistance of at least 60 min. Doors which open to the outside are adequate
if they are of fire-retardant material and construction. Ventilation openings necessary for the
operation of the transformers are permitted. When designing the openings, the possible escape of
hot gases shall be considered.
NOTE In addition, the water from the fire extinguishing (if any) should be considered
a
Containment: the entire quantity of fluid of the transformer plus rain water
NOTE In addition, the water from fire estinguishing installation (if any) should be considered
a
Containment outdoor: the entire quantity of fluid of the largest transformer plus rain
Containment indoor: the entire quantity of fluid of the largest transformer
NOTE The dotted area denotes the volume of the entire quantity of insulating fluid of the
transformer spilled on the floor
Figure11 – Example for small transformer without gravel layer and catchment tank
10 EARTHING SYSTEMS
10.1 General
This clause provides the criteria for design, installation, testing and maintenance of an earthing
system such that it operates under all conditions and ensures the safety of human life in any place
to which persons have legitimate access. It also provides the criteria to ensure that the integrity of
equipment connected and in proximity to the earthing system is maintained.