No Description Qty Points Point Type Pipe Locat Supply Sensor Wiring REMARKS
Information ion / installati
Senso on
r
DI DO AI AO SW
1 Electrical System

Transformer 1
Transformer room Temperature/Humidity 1 pt 100 - Room BMS BMS BMS
temperature contactor contactor contactor

ATS Panel
ATS Auto/Manual Status 1 Dry contact - Panel Elec - BMS
contractor contactor
ATS On/Off Status 1 Dry contact - Panel Elec - BMS
contractor contactor
ATS Alarm/Trip 1 Dry contact - Panel Elec - BMS
contractor contactor
ATS Room temperature and RH 1 pt 100 10K RTD - Temperature BMS BMS BMS
sensor contractor contractor contactor
Authority Power Healthy 1 Dry contact - Panel Elec - BMS
contractor contactor
Authority Breaker On/Off Status 1 Dry contact - Panel Elec - BMS
contractor contactor
Authority Breaker Trip Alarm 1 Dry contact - Panel Elec - BMS
contractor contactor
Authority voltag High 1 Dry contact - Panel Elec - BMS
contractor contactor
Authority voltag Low 1 Dry contact - Panel Elec - BMS
contractor contactor
Generato Power Healthy 1 Dry contact - Panel Elec - BMS
contractor contactor
Generator Breaker On/Off Status 1 Dry contact - Panel Elec - BMS
contractor contactor
Generator Breaker Trip Alarm 1 Dry contact - Panel Elec - BMS
contractor contactor
System On Authority Power 1 Dry contact - Panel Elec - BMS
contractor contactor
System On Generator Power 1 Dry contact - Panel Elec - BMS
contractor contactor

Power Analyzer @ ATS 2 Software - Power Elec Elec BMS Electrical


analyzer contractor contractor contactor Drawings
Line Voltage (V) - L1-L2, L2-L3, L3-L1 6 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
Line to Neutral Voltage (V) - L1-N, L2-N, L3-N 6 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
Currrent (A) - I(1), I(2), I(3) 6 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
Total Current 2 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
Total Real Power (in kW) 2 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
Real Power (L1,L2,L3 in kW) 6 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
Total Apparent Power (in kVA) 2 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
P.F. 2 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
Frequency (Hz) 2 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
Phases Over Current (A,B,C) 6 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
kWh (L1,L2,L3) 6 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
Total kWh 2 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
THDI 2 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
THDV 2 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings

Generator System
Generator 2 Software - Power Gen Supplier - BMS Electrical
analyzer contactor Drawings
Auto/Maual Status 2 Dry contact - Power Gen Supplier - BMS Electrical
analyzer contactor Drawings
Engine Start Stop Status 2 Dry contact - Power Gen Supplier - BMS Electrical
analyzer contactor Drawings
Common Alarm 2 Dry contact - Power Gen Supplier - BMS Electrical
analyzer contactor Drawings
Volts L1,L2,L3 6 BACnet/Modbus - Power Gen Supplier - BMS Electrical
analyzer contactor Drawings
Volts L1-N,L2-N,L3-N 6 BACnet/Modbus - Power Gen Supplier - BMS Electrical
analyzer contactor Drawings
Amps L1,L2,L3 6 BACnet/Modbus - Power Gen Supplier - BMS Electrical
analyzer contactor Drawings
Tatal kW 2 BACnet/Modbus - Power Gen Supplier - BMS Electrical
analyzer contactor Drawings
kW - L1,L2,L3 6 BACnet/Modbus - Power Gen Supplier - BMS Electrical
analyzer contactor Drawings
kVA - L1,L2,L3 6 BACnet/Modbus - Power Gen Supplier - BMS Electrical
analyzer contactor Drawings
Total kWh 2 BACnet/Modbus - Power Gen Supplier - BMS Electrical
analyzer contactor Drawings
Hz 2 BACnet/Modbus - Power Gen Supplier - BMS Electrical
analyzer contactor Drawings
RPM 2 BACnet/Modbus - Power Gen Supplier - BMS Electrical
analyzer contactor Drawings
Load % 2 BACnet/Modbus - Power Gen Supplier - BMS Electrical
analyzer contactor Drawings
Engine Temperature 2 BACnet/Modbus - Power Gen Supplier - BMS Electrical
analyzer contactor Drawings
Oil Pressure 2 BACnet/Modbus - Power Gen Supplier - BMS Electrical
analyzer contactor Drawings
Oil Temperature 2 BACnet/Modbus - Power Gen Supplier - BMS Electrical
analyzer contactor Drawings
Coolent Temperature 2 BACnet/Modbus - Power Gen Supplier - BMS Electrical
analyzer contactor Drawings
Exhaust Temperature 2 BACnet/Modbus - Power Gen Supplier - BMS Electrical
analyzer contactor Drawings
Coolent Level 2 BACnet/Modbus - Power Gen Supplier - BMS Electrical
analyzer contactor Drawings
Run Time 2 BACnet/Modbus - Power Gen Supplier - BMS Electrical
analyzer contactor Drawings
Battery Charged Level 2 BACnet/Modbus - Power Gen Supplier - BMS Electrical
analyzer contactor Drawings
Fuel Consumption 2 BACnet/Modbus - Power Gen Supplier - BMS Electrical
analyzer contactor Drawings
Generator room Temperature/Humidity 2 pt 100 - Room BMS BMS BMS
temperature contactor contactor contactor

Generator Side Breaker 2


Outgoing Breaker On/Off Status 2 Dry Contact Gen Supplier - BMS Electrical
contactor Drawings
Outgoing Breaker Trip Alarm 2 Dry Contact Gen Supplier - BMS Electrical
contactor Drawings

Bulk Fuel Tank 1


Present Level High 1 Dry Contact Gen: Supplier
Present Level Low 1 Dry Contact Gen: Supplier

Day Fuel Tank 1


Low Level 1 Dry Contact Gen: Supplier
Mid Level 1 Dry Contact Gen: Supplier
High Level 1 Dry Contact Gen: Supplier

Fuel Pumps 4
MCC Panel Power On 1
Fuel Pumps Auto/Manual 4 Dry Contact Gen: Supplier
Fuel Pumps On/Off status 4 Dry Contact Gen: Supplier
Fuel Pumps Trip/Alarm Signals 4 Dry Contact Gen: Supplier
Running Hours 1 BMS
Contractor

MDB
Incoming Power Analyzer 1 Software - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
Line Voltage (V) - L1-L2, L2-L3, L3-L1 3 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
Line to Neutral Voltage (V) - L1-N, L2-N, L3-N 3 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
Currrent (A) - I(1), I(2), I(3) 3 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
Total Current 1 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
Total Real Power (in kW) 1 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
Real Power (L1,L2,L3 in kW) 3 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
Total Apparent Power (in kVA) 1 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
P.F. 1 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
Frequency (Hz) 1 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
Phases Over Current (A,B,C) 3 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
kWh (L1,L2,L3) 3 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
Total kWh 1 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
THDI 1 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
THDV 1 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings

Authority power healthy 1 Dry contact - Panel Elec - BMS


contractor contactor
Main Circuit breaker Status 1 Dry contact - Panel Elec - BMS
contractor contactor
Main Circuit breaker Trip Alarm 1 Dry contact - Panel Elec - BMS
contractor contactor
Incoming EFR Trip Alarm 1 Dry contact - Panel Elec - BMS
contractor contactor
Outgoing Breaker-1 to 8 On/Off Status 13 Dry contact - Panel Elec - BMS
contractor contactor
Outgoing Breaker-1 to 8 Trip Status 13 Dry contact - Panel Elec - BMS
contractor contactor

Outgoing Power Analyzer 9 Software - Power Elec Elec BMS Electrical


analyzer contractor contractor contactor Drawings
Line Voltage (V) - L1-L2, L2-L3, L3-L1 27 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
Line to Neutral Voltage (V) - L1-N, L2-N, L3-N 27 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
Currrent (A) - I(1), I(2), I(3) 27 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
Total Current 9 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
Total Real Power (in kW) 9 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
Real Power (L1,L2,L3 in kW) 27 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
Total Apparent Power (in kVA) 9 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
P.F. 9 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
Frequency (Hz) 9 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
Phases Over Current (A,B,C) 27 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
kWh (L1,L2,L3) 27 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
Total kWh 9 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
THDI 9 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
THDV 9 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings

Capacitor Bank 1
Cap Bank Highlevel Interface 25 Modbus Elec Elec BMS Electrical
contractor contractor contactor Drawings

Power Analyzers for Car Charging 12 Software - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
Line Voltage (V) - L1-L2, L2-L3, L3-L1 27 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
Line to Neutral Voltage (V) - L1-N, L2-N, L3-N 27 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
Currrent (A) - I(1), I(2), I(3) 27 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
Total Current 12 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
Total Real Power (in kW) 12 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
Real Power (L1,L2,L3 in kW) 36 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
Total Apparent Power (in kVA) 12 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
P.F. 12 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
Frequency (Hz) 12 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
Phases Over Current (A,B,C) 36 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
kWh (L1,L2,L3) 36 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
Total kWh 12 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
THDI 12 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings
THDV 12 Modbus - Power Elec Elec BMS Electrical
analyzer contractor contractor contactor Drawings

Lighting Control 18
Common Area Lighting Control 18
Auto Manual 18 Dry contact Common DBs Elec Elec BMS Electrical
contractor contractor contractor Drawings
On/Off Control 18 Dry contact Common DBs Elec Elec BMS Electrical
contractor contractor contractor Drawings
On/Off Status 18 Dry contact Common DBs Elec Elec BMS Electrical
contractor contractor contractor Drawings

Lighting Control 5
Outdoor Area Lighting Control 5
Auto Manual 5 Dry contact Common DBs Elec Elec BMS Electrical
contractor contractor contractor Drawings
On/Off Control 5 Dry contact Common DBs Elec Elec BMS Electrical
contractor contractor contractor Drawings
On/Off Status 5 Dry contact Common DBs Elec Elec BMS Electrical
contractor contractor contractor Drawings

2 Cold Water System


Water Sump with Seperated Fire Sump 2
High level alarm 2 Dry contact - Plumbing Plumbing BMS Cold water
Level sensor Contractor Contractor contractor supply
Drawings
Mid level alarm 2 Dry contact - Plumbing Plumbing BMS Cold water
Contractor Contractor contractor supply
Drawings
Low level alarm 2 Dry contact - Plumbing Plumbing BMS Cold water
Contractor Contractor contractor supply
Drawings

Overhead water tank 2


High level alarm 2 Dry contact - Plumbing Plumbing BMS Cold water
Level sensor Contractor Contractor contractor supply
Drawings
Mid level alarm 2 Dry contact - Plumbing Plumbing BMS Cold water
Contractor Contractor contractor supply
Drawings
Low level alarm 2 Dry contact - Plumbing Plumbing BMS Cold water
Contractor Contractor contractor supply
Drawings

Domestic water transfer pump 2

Total pumps 2
Pump on off status 2 Dry contact - Pump panel Plumbing Plumbing BMS Cold water
contractor contractor contractor supply
Drawings
Pump on off command 2 Relay contact - Pump panel Plumbing Plumbing BMS Cold water
contractor contractor contractor supply
Drawings
Pump trip alarm 2 Dry contact - Pump panel Plumbing Plumbing BMS Cold water
contractor contractor contractor supply
Drawings
Auto manual status 2 Dry contact - Pump panel Plumbing Plumbing BMS Cold water
contractor contractor contractor supply
Drawings

Running hours 2 BMS

Cold Water Supply Header 1


Line Pressure 1 2-10V/4-20mA - Transfer BMS BMS BMS Cold water
Pump room contractor contractor contractor supply
Drawings
Flow Status 1 Flow Switch - Transfer BMS BMS BMS Cold water
Pump room contractor contractor contractor supply
Drawings

Domestic water booster pumps 2

Total pumps 2
Pump on off status 2 Dry contact - Pump panel Plumbing Plumbing BMS Cold water
contactor contactor contractor supply
Drawings
Pump on off command 2 24V AC Relay contact - Pump panel P&S Plumbing BMS Cold water
contractor contactor contractor supply
Drawings
Cold Water Pump VFD Control Signal 2 2-10V/4-20mA - Pump panel P&S Plumbing BMS Cold water
contractor contactor contractor supply
Drawings
Cold Water Pump VFD Feedback 2 2-10V/4-20mA - Pump panel P&S Plumbing BMS Cold water
contractor contactor contractor supply
Drawings
Pump trip alarm 2 Dry contact - Pump panel P&S Plumbing BMS Cold water
contractor contactor contractor supply
Drawings
Auto manual status 2 Dry contact - Pump panel P&S Plumbing BMS Cold water
contractor contactor contractor supply
Drawings
Running hours 2 - BMS - BMS Cold water
contractor supply
Drawings
Line Pressure 1 2-10V/4-20mA - Booster Pump BMS Plumbing BMS Cold water
Room contactor contractor supply
Drawings
Line Hiigh Pressure 1 Safety Cut out - Booster Pump BMS Plumbing BMS Cold water
Room contactor contractor supply
Drawings

Cold Water Supply Header 1


Cold Water Supply Line Pressure 1 2-10V/4-20mA Booster Line BMS BMS BMS Cold water
Contractor Contractor Contractor supply
Drawings

Water Meters monitoring & controlling 13


BMS Compatible Water Meters 13 M-Bus Plumbing

3 Sewer Waste System


Waste Pits 2
High level alarm 2 Dry contact - Level sensor Plumbing Plumbing BMS Sewer &
Contractor Contractor contractor waste
Drawings
Low level alarm 2 Dry contact - Plumbing Plumbing BMS Sewer &
Contractor Contractor contractor waste
Drawings

Sewerage Submersible Pumps 4

Total pumps 4
Pump on off status 4 Dry contact - Pump panel Plumbing Plumbing BMS
contractor contractor contractor
Pump on off command 4 Relay contact - Pump panel Plumbing Plumbing BMS
contractor contractor contractor
Pump trip alarm 4 Dry contact - Pump panel Plumbing Plumbing BMS
contractor contractor contractor
Auto manual status 4 Dry contact - Pump panel Plumbing Plumbing BMS
contractor contractor contractor
Running hours 4 BMS BMS
contractor contractor

4 MVAC system 4

PUMP
WATER CHILLERS - 1 PANEL
Water Leaving Temp 1 Micro processor based controller

Water Return/Entering Temp 1 "


Condenser Water Leaving Temp 1 "
Condenser Water Return/Entering Temp 1 "
%RLA 1 "
Water Leaving Temp 1 "
Water Return/Entering Temp 1 "
Condenser Water Leaving Temp 1 "
Evaporator Temp 1 "
Condensers Temp 1 "
Oil Tank Temp 1 "
Oil Differentials Pressure 1 "
Chilled Water Setpnt 1 "
Demand Limit Setpnt 1 "
Manual Reset Alarm 1 "
Auto Reset Alarm 1 "
Communication Status 1 "

Manual/Auto Status 1 DRY CONTACT

1
Chiller On/Off Control 24VAC RELAY COIL CONTACT
Chiller On/Off Status 1 DRY CONTACT
Emergency Stop Status 1 DRY CONTACT
Trip Alarm 1 DRY CONTACT
Power Supply Failure 1 DRY CONTACT
Glycol Flow Status 1 FLOW SWITCH

Glycol Flow Status 1 FLOW SWITCH

PUMP
WATER CHILLER ISOLATION PANEL

BUTTERFLY VALVE - CHW & CWS SIDES


Auto/Man Status 2 2 DRY CONTACT
On/Off Control 4 DRY CONTACT
Open/Close Status 4 DRY CONTACT
Alarm 2 DRY CONTACT

PUMP
PRIMARY CHILLED WATER PUMPS PANEL
CHWP - 1
Auto /Man Status 5 5 DRY CONTACT
On/Off Control 5 DRY CONTACT
On/Off Flow Status 5 DRY CONTACT
Power Failure Alarm 5 DRY CONTACT
Trip Alarm 5 DRY CONTACT
DRY CONTACT
PUMP
CONDENSER WATER PUMPS PANEL
CWP - 1
Auto /Man Status 5 5 DRY CONTACT
On/Off Control 5 DRY CONTACT
On/Off Flow Status 5 DRY CONTACT
Power Failure Alarm 5 DRY CONTACT
Trip Alarm 5 DRY CONTACT
PUMP
CHW RISER 1 PUMP PANEL
Auto/Man Status 2 2 DRY CONTACT
On/ Off Control 2 DRY CONTACT
On/ Off Status 2 DRY CONTACT
Speed Control 2 VSD Panel
Speed Feed Back 2 VSD Panel
Riser DIff Press. 1 Diff Pressure Sensor
Flow Status 1 DRY CONTACT
Trip Alarm 2 DRY CONTACT

PUMP
RISER BY-PASS VALVES PANEL
Auto / Man Status 1 1 Bypass Valve
Control signal 1 Bypass Valve
Feed Back Signal 1 Bypass Valve

PUMP
EXPANSION TANK PANEL
High Level 1 DRY CONTACT
Low Level 1 DRY CONTACT

PUMP
MAKEUP WATER PUMP PANEL
On / Off Status 2 DRY CONTACT
Trip Alarm 2 DRY CONTACT

PUMP
CHEMICAL DOSING PUMPS PANEL
On / Off Status 2 DRY CONTACT
Trip Alarm 2 DRY CONTACT

PUMP
MCC'S POWER QUALITY PANEL
(CHILLED WATER SYSTEM)

Voltage 1 3 3-PHASE VOLTAGE TRANSDUCER

Current 3 3-PHASE VOLTAGE TRANSDUCER

Killo Watt 1 3-PHASE VOLTAGE TRANSDUCER

Power Factor 1 3-PHASE VOLTAGE TRANSDUCER

Killo Watt Hour 1 3-PHASE VOLTAGE TRANSDUCER

Basement 3 Basement 3
FCU-1
FCU-2
FCU-3
FCU-4
Fan On / Off Status 4
Space Temperature 4

Basement 2 Basement 3
FCU-1
FCU-2
FCU-3
Fan On / Off Status 3
Space Temperature 3

Basement 1 Basement 1
FCU-1
Fan On / Off Status 1
Space Temperature 1

Ground Floor Ground Floor

Split-1
Split-2

On / Off Status 2 Diff Pressure Switch


Space Temperature 2 Space Tem Sensor

AHU-G Ahu Room

Auto/Manual Status 1 1 DRY CONTACT

On / Off Control 1 24VAC RELAY COIL CONTACT

Fan On / Off Status 1 DIFF. PRESSURE SWITCH


Trip Alarm 1 DRY CONTACT

Zone Temperatures 1 SPACE TEMPERATURE SENSOR

Supply Air Temperature from the AHU 1 DUCT TEMPERATURE SENSOR


Valve Control - Modulating 1 MOTORIZED VALVE
Valve Position 1 POTENTIOMETER

Filter Status 1 DIFF. PRESSURE SWITCH

Entrance Lobby Phase Damper 1 DAMPER ACTUATOR

Entrance Lobby Bypass Damper 1 DAMPER ACTUATOR

Upper Lobby Phase Damper 1 DAMPER ACTUATOR


Upper Lobby Bypass Damper 1 DAMPER ACTUATOR
Damper Position Feedback 1 POTENTIOMETER

Return Air CO2 1 DUCT CO2 DETECTOR

Fresh Air, Return Air, and Exhaust Air Damper Control 3 DAMPER ACTUATOR
Fresh Air, Return Air, and Exhaust Air Damper Status 3 POTENTIOMETER

Return Air Smoke Detection 1 DUCT SMOKE DETECTOR

Ahu Room
BTU Meter 1

ON/OFF 1

Status 1

EXF- G panel
Auto/Manual Status 1 1 DRY CONTACT

On / Off Control 1 24VAC RELAY COIL CONTACT


Fan On / Off Status 1 DRY CONTACT
Trip Alarm 1 DRY CONTACT

AHU-G+1 Ahu Room

Auto/Manual Status 1 1 DRY CONTACT

On / Off Control 1 24VAC RELAY COIL CONTACT

Fan On / Off Status 1 DIFF. PRESSURE SWITCH


VSD Speed Control 1 VSD
VSD Speed Feed back 1 VSD
VSD Fault Alarm 1 DRY CONTACT
Trip Alarm 1 DRY CONTACT

Return Duct Temperature Sensor 1 DUCT TEMPERATURE SENSOR

Duct Static Pressure 1 PRESSURE TRANSDUCER

Supply Air Temperature from the AHU 1 DUCT TEMPERATURE SENSOR


Valve Control - Modulating 1 MOTORIZED VALVE
Valve Position 1 POTENTIOMETER

Filter Status 1 DIFF. PRESSURE SWITCH

Return Air CO2 1 DUCT CO2 DETECTOR

Fresh Air, Return Air, and Exhaust Air Damper Control 3 DAMPER ACTUATOR
Fresh Air, Return Air, and Exhaust Air Damper Status 3 POTENTIOMETER

Return Air Smoke Detection 1 DUCT SMOKE DETECTOR

Ahu Room
BTU Meter 1

ON/OFF 1

Status 1

EXF- G+1 panel

Auto/Manual Status 1 1 DRY CONTACT

On / Off Control 1 24VAC RELAY COIL CONTACT


Fan On / Off Status 1 DRY CONTACT
Trip Alarm 1 DRY CONTACT

AHU-G+2 Ahu Room

Auto/Manual Status 1 1 DRY CONTACT

On / Off Control 1 24VAC RELAY COIL CONTACT

Fan On / Off Status 1 DIFF. PRESSURE SWITCH


VSD Speed Control 1 VSD
VSD Speed Feedback 1 VSD
VSD Fault Alarm 1 DRY CONTACT
Trip Alarm 1 DRY CONTACT

Return Duct Temperature Sensor 1 DUCT TEMPERATURE SENSOR

Duct Static Pressure 1 PRESSURE TRANSDUCER

Supply Air Temperature from the AHU 1 DUCT TEMPERATURE SENSOR


Valve Control - Modulating 1 MOTORIZED VALVE
Valve Position 1 POTENTIOMETER

Filter Status 1 DIFF. PRESSURE SWITCH

Return Air CO2 1 DUCT CO2 DETECTOR

Fresh Air, Return Air, and Exhaust Air Damper Control 3 DAMPER ACTUATOR
Fresh Air, Return Air, and Exhaust Air Damper Status 3 POTENTIOMETER

Return Air Smoke Detection 1 DUCT SMOKE DETECTOR

Ahu Room
BTU Meter 1

ON/OFF 1

Status 1

EXF- G+2 panel

Auto/Manual Status 1 1 DRY CONTACT

On / Off Control 1 24VAC RELAY COIL CONTACT


Fan On / Off Status 1 DRY CONTACT
Trip Alarm 1 DRY CONTACT

AHU-G+3 Ahu Room

Auto/Manual Status 1 1 DRY CONTACT

On / Off Control 1 24VAC RELAY COIL CONTACT

Fan On / Off Status 1 DIFF. PRESSURE SWITCH


VSD Speed Control 1 VSD
VSD Speed Feed back 1 VSD
VSD Fault Alarm 1 DRY CONTACT
Trip Alarm 1 DRY CONTACT

Return Duct Temperature Sensor 1 DUCT TEMPERATURE SENSOR

Duct Static Pressure 1 PRESSURE TRANSDUCER

Supply Air Temperature from the AHU 1 DUCT TEMPERATURE SENSOR


Valve Control - Modulating 1 MOTORIZED VALVE
Valve Position 1 POTENTIOMETER

Filter Status 1 DIFF. PRESSURE SWITCH

Return Air CO2 1 DUCT CO2 DETECTOR

Fresh Air, Return Air, and Exhaust Air Damper Control 3 DAMPER ACTUATOR
Fresh Air, Return Air, and Exhaust Air Damper Status 3 POTENTIOMETER

Return Air Smoke Detection 1 DUCT SMOKE DETECTOR

Ahu Room
BTU Meter 1

ON/OFF 1

Status 1

EXF- G+3 panel

Auto/Manual Status 1 1 DRY CONTACT

On / Off Control 1 24VAC RELAY COIL CONTACT


Fan On / Off Status 1 DRY CONTACT
Trip Alarm 1 DRY CONTACT

AHU-G+4 Ahu Room

Auto/Manual Status 1 1 DRY CONTACT

On / Off Control 1 24VAC RELAY COIL CONTACT

Fan On / Off Status 1 DIFF. PRESSURE SWITCH


VSD Speed Control 1 VSD

VSD Speed Feed back 1 VSD

VSD Fault Alarm 1 DRY CONTACT


Trip Alarm 1 DRY CONTACT
Return Duct Temperature Sensor 1 DUCT TEMPERATURE SENSOR

Duct Static Pressure 1 PRESSURE TRANSDUCER

Supply Air Temperature from the AHU 1 DUCT TEMPERATURE SENSOR

Valve Control - Modulating 1 MOTORIZED VALVE


Valve Position 1 POTENTIOMETER

Filter Status 1 DIFF. PRESSURE SWITCH

Return Air CO2 1 DUCT CO2 DETECTOR

Fresh Air, Return Air, and Exhaust Air Damper Control 3 DAMPER ACTUATOR

Fresh Air, Return Air, and Exhaust Air Damper Status 3 POTENTIOMETER

Return Air Smoke Detection 1 DUCT SMOKE DETECTOR

Ahu Room
BTU Meter 1

ON/OFF 1
Status 1

EXF- G+4 panel

Auto/Manual Status 1 1 DRY CONTACT


On / Off Control 1 24VAC RELAY COIL CONTACT
Fan On / Off Status 1 DRY CONTACT
Trip Alarm 1 DRY CONTACT

AHU-G+5 Ahu Room

Auto/Manual Status 1 1 DRY CONTACT

On / Off Control 1 24VAC RELAY COIL CONTACT

Fan On / Off Status 1 DIFF. PRESSURE SWITCH


VSD Speed Control 1 VSD
VSD Speed Feedback 1 VSD
VSD Fault Alarm 1 DRY CONTACT
Trip Alarm 1 DRY CONTACT

Return Duct Temperature Sensor 1 DUCT TEMPERATURE SENSOR

Duct Static Pressure 1 STATIC PRESSURE SENSOR

Supply Air Temperature from the AHU 1 DUCT TEMPERATURE SENSOR


Valve Control - Modulating 1 MOTORIZED VALVE
Valve Position 1 POTENTIOMETER

Filter Status 1 DIFF. PRESSURE SWITCH

Return Air CO2 1 DUCT CO2 DETECTOR

Fresh Air, Return Air, and Exhaust Air Damper Control 3 DAMPER ACTUATOR
Fresh Air, Return Air, and Exhaust Air Damper Status 3 POTENTIOMETER

Return Air Smoke Detection 1 DUCT SMOKE DETECTOR

Ahu Room

BTU Meter 1

ON/OFF 1

Status 1

EXF- G+5 panel

Auto/Manual Status 1 1 DRY CONTACT

On / Off Control 1 24VAC RELAY COIL CONTACT


Fan On / Off Status 1 DRY CONTACT
Trip Alarm 1 DRY CONTACT

AHU-G+6 Ahu Room


Auto/Manual Status 1 1 DRY CONTACT

On / Off Control 1 24VAC RELAY COIL CONTACT

Fan On / Off Status 1 DIFF. PRESSURE SWITCH


VSD Speed Control 1 VSD
VSD Speed Feedback 1 VSD
VSD Fault Alarm 1
Trip Alarm 1 DRY CONTACT

Return Duct Temperature Sensor 1 DUCT TEMPERATURE SENSOR


Duct Static Pressure 1

Supply Air Temperature from the AHU 1 DUCT TEMPERATURE SENSOR


Valve Control - Modulating 1 MOTORIZED VALVE
Valve Position 1 POTENTIOMETER

Filter Status 1 DIFF. PRESSURE SWITCH

Return Air CO2 1 DUCT CO2 DETECTOR

Fresh Air, Return Air, and Exhaust Air Damper Control 3 DAMPER ACTUATOR
Fresh Air, Return Air, and Exhaust Air Damper Status 3 POTENTIOMETER

Return Air Smoke Detection 1 DUCT SMOKE DETECTOR

Ahu Room
BTU Meter 1

ON/OFF 1

Status 1

EXF- G+6 panel

Auto/Manual Status 1 1 DRY CONTACT

On / Off Control 1 24VAC RELAY COIL CONTACT


Fan On / Off Status 1 DRY CONTACT
Trip Alarm 1 DRY CONTACT

AHU-G+7 Ahu Room

Auto/Manual Status 1 1 DRY CONTACT

On / Off Control 1 24VAC RELAY COIL CONTACT

Fan On / Off Status 1 DIFF. PRESSURE SWITCH


VSD Speed Control 1 VSD
VSD Speed Feedback 1 VSD

VSD Fault Alarm 1 STATIC PRESSURE TRANSDUCER


Trip Alarm 1 DRY CONTACT

Return Duct Temperature Sensor 1 DUCT TEMPERATURE SENSOR

Duct Static Pressure 1 STATIC PRESSURE TRANSDUCER

Supply Air Temperature from the AHU 1 DUCT TEMPERATURE SENSOR


Valve Control - Modulating 1 MOTORIZED VALVE
Valve Position 1 POTENTIOMETER

Filter Status 1 DIFF. PRESSURE SWITCH

Return Air CO2 1 DUCT CO2 DETECTOR

Fresh Air, Return Air, and Exhaust Air Damper Control 3 DAMPER ACTUATOR
Fresh Air, Return Air, and Exhaust Air Damper Status 3 POTENTIOMETER

Return Air Smoke Detection 1 DUCT SMOKE DETECTOR

Ahu Room

BTU Meter 1

ON/OFF 1

Status 1

EXF- G+7 panel

Auto/Manual Status 1 1 DRY CONTACT

On / Off Control 1 24VAC RELAY COIL CONTACT


Fan On / Off Status 1 DRY CONTACT
Trip Alarm 1 DRY CONTACT

AHU-G+8 Ahu Room

Auto/Manual Status 1 1 DRY CONTACT

On / Off Control 1 24VAC RELAY COIL CONTACT

Fan On / Off Status 1 DIFF. PRESSURE SWITCH


VSD Speed Control 1 VSD
VSD Speed Feedback 1 VSD
VSD Fault Alarm 1 DRY CONTACT
Trip Alarm 1 DRY CONTACT

Return Duct Temperature Sensor 1 DUCT TEMPERATURE SENSOR

Duct Static Pressure 1 STATIC PRESSURE TRANSDUCER

Supply Air Temperature from the AHU 1 DUCT TEMPERATURE SENSOR


Valve Control - Modulating 1 MOTORIZED VALVE
Valve Position 1 POTENTIOMETER

Filter Status 1 DIFF. PRESSURE SWITCH


Return Air CO2 1 DUCT CO2 DETECTOR

Fresh Air, Return Air, and Exhaust Air Damper Control 3 DAMPER ACTUATOR
Fresh Air, Return Air, and Exhaust Air Damper Status 3 POTENTIOMETER

Return Air Smoke Detection 1 DUCT SMOKE DETECTOR


Ahu Room
BTU Meter 1

ON/OFF 1

Status 1

EXF- G+8 panel

Auto/Manual Status 1 1 DRY CONTACT

On / Off Control 1 24VAC RELAY COIL CONTACT


Fan On / Off Status 1 DRY CONTACT
Trip Alarm 1 DRY CONTACT

AHU-G+9 Ahu Room

Auto/Manual Status 1 1 DRY CONTACT

On / Off Control 1 24VAC RELAY COIL CONTACT

Fan On / Off Status 1 DIFF. PRESSURE SWITCH


VSD Speed Control 1 VSD
VSD Speed Feedback 1 VSD
VSD Fault Alarm 1 DRY CONTACT
Trip Alarm 1 DRY CONTACT

Return Duct Temperature Sensor 1 DUCT TEMPERATURE SENSOR

Duct Static Pressure 1 STATIC PRESSURE TRANSDUCER

Supply Air Temperature from the AHU 1 DUCT TEMPERATURE SENSOR


Valve Control - Modulating 1 MOTORIZED VALVE
Valve Position 1 POTENTIOMETER

Filter Status 1 DIFF. PRESSURE SWITCH

Return Air CO2 1 DUCT CO2 DETECTOR

Fresh Air, Return Air, and Exhaust Air Damper Control 3 DAMPER ACTUATOR
Fresh Air, Return Air, and Exhaust Air Damper Status 3 POTENTIOMETER

Return Air Smoke Detection 1 DUCT SMOKE DETECTOR

Ahu Room

BTU Meter 1

ON/OFF 1

Status 1

EXF- G+9 panel

Auto/Manual Status 1 1 DRY CONTACT

On / Off Control 1 24VAC RELAY COIL CONTACT


Fan On / Off Status 1 DRY CONTACT
Trip Alarm 1 DRY CONTACT

5 Pond
Pondsand filter 2
Pond filter block status 2 Dry contact 65 Ø Liquid BMS BMS BMS
deferential contactor contactor contactor
pressure

Pond Balancing tank 1


High level alarm 1 Dry contact - Level sensor BMS BMS BMS
contactor contactor contactor
Low level alarm 1 Dry contact - BMS BMS BMS
contactor contactor contactor

Pond Pumps 3
Pump on off status 3 Dry contact - Pump panel Pool - BMS
Contractor contactor
Pump on off command 3 Relay contact - Pump panel Pool - BMS
Contractor contactor
Pump trip alarm 3 Dry contact - Pump panel Pool - BMS
Contractor contactor
Auto manual status 3 Dry contact - Pump panel Pool - BMS
Contractor contactor
Running Hours 3 BMS

Pond Dosing pump 2


Pump on off status 2 Dry contact - Pump panel P&S - BMS
contactor contactor
Pump on off command 2 Relay contact - Pump panel P&S - BMS
contactor contactor
Pump trip alarm 2 Dry contact - Pump panel P&S - BMS
contactor contactor
Auto manual status 2 Dry contact - Pump panel P&S - BMS
contactor contactor

Pond Lights 2
Lights on off status 2 Dry contact - Pump panel P&S - BMS
contactor contactor
Lights on off command 2 Relay contact - Pump panel P&S - BMS
contactor contactor
Lights trip alarm 2 Dry contact - Pump panel P&S - BMS
contactor contactor
Auto manual status 2 Dry contact - Pump panel P&S - BMS
contactor contactor

Drip Irrigation System (monitoring &controlling)


1
solenoid valves ( 4 for ground & 1 each for others) 14 Relay contact panel
solenoid valves on/off 14 Dry contact panel
solenoid valves status 14 Dry contact panel

6 Water Feature
Sand filter 2
Filter block status 2 Dry contact 65 Ø Liquid BMS BMS BMS
deferential contactor contactor contactor
pressure

Balancing tank 1
High level alarm 1 Dry contact - Level sensor BMS BMS BMS
contactor contactor contactor
Level sensor

Low level alarm 1 Dry contact - BMS BMS BMS


contactor contactor contactor

Water Feature Pumps 2


Pump on off status 2 Dry contact - Pump panel Pool - BMS
Contractor contactor
Pump on off command 2 Relay contact - Pump panel Pool - BMS
Contractor contactor
Pump trip alarm 2 Dry contact - Pump panel Pool - BMS
Contractor contactor
Auto manual status 2 Dry contact - Pump panel Pool - BMS
Contractor contactor
Running Hours 2 BMS

Dosing pump 2
Pump on off status 2 Dry contact - Pump panel Pool - BMS
contactor contactor
Pump on off command 2 Relay contact - Pump panel Pool - BMS
contactor contactor
Pump trip alarm 2 Dry contact - Pump panel Pool - BMS
contactor contactor
Auto manual status 2 Dry contact - Pump panel Pool - BMS
contactor contactor

Pond Lights 2
Lights on off status 2 Dry contact - Pump panel P&S - BMS
contactor contactor
Lights on off command 2 Relay contact - Pump panel P&S - BMS
contactor contactor
Lights trip alarm 2 Dry contact - Pump panel P&S - BMS
contactor contactor
Auto manual status 2 Dry contact - Pump panel P&S - BMS
contactor contactor

7 Fire Protection System


Fire Sump 1
High level alarm 1 Dry contact - Level sensor Fire contactor Fire contactor BMS
contactor
Low level alarm 1 Dry contact - Fire contactor BMS BMS
contactor contactor

Motor Driven Sprinkler Pumps 1


MCC Panel Power On 1 Dry contact Pump panel Fire BMS
Contractor contactor
Pump on off status 1 Dry contact - Pump panel Fire - BMS
Contractor contactor
Pump trip alarm 1 Dry contact - Pump panel Fire - BMS
Contractor contactor
Auto manual status 1 Dry contact - Pump panel Fire - BMS
Contractor contactor
Running Hours 1 BMS

Motor Driven Sprinkler Pumps 1


Diesel Engine Auto/Manual/Off 3 Dry contact Pump panel Fire BMS
Contractor contactor
Diesel Engine Run Stop status 1 Dry contact - Pump panel Fire - BMS
Contractor contactor
DC Power Fail 1 Dry contact - Pump panel Fire - BMS
Contractor contactor
Battery Charger Fail 1 Dry contact - Pump panel Fire - BMS
Contractor contactor
Overspeed shut down 1 Dry contact - Pump panel Fire - BMS
Contractor contactor
Fail to Start 1 Dry contact - Pump panel Fire - BMS
Contractor contactor
Run Time 1 BMS
Common Alarm 1 Dry contact - Pump panel Fire - BMS
Contractor contactor

Sprinkler Jockey Pump 1


Pump on off status 1 Dry contact - Pump panel Fire - BMS
Contractor contactor
Pump trip alarm 1 Dry contact - Pump panel Fire - BMS
Contractor contactor
Auto manual status 1 Dry contact - Pump panel Fire - BMS
Contractor contactor
Running Hours 1 BMS

Splrinkler Header 1
Line Pressure 1 2-10V/4-20mA - Pump panel BMS - BMS
contactor
Flow Status 1 Flow Switch - Pump panel BMS - BMS
contactor

Sprinkler Priming Tank 1


Low Level 1 Dry Contact Gen: Supplier

Hydrant Pumps 1
MCC Panel Power On 1 Dry contact Pump panel Fire BMS
Contractor contactor
Pump on off status 1 Dry contact - Pump panel Fire - BMS
Contractor contactor
Pump trip alarm 1 Dry contact - Pump panel Fire - BMS
Contractor contactor
Pump power failure 1 Dry contact - Pump panel Fire - BMS
Contractor contactor
Auto manual status 1 Dry contact - Pump panel Fire - BMS
Contractor contactor
Running Hours 1 BMS

Motor Driven Hydrant Pumps 1


Diesel Engine Auto/Manual/Off 3 Dry contact Pump panel Fire BMS
Contractor contactor
Diesel Engine Run Stop status 1 Dry contact - Pump panel Fire - BMS
Contractor contactor
DC Power Fail 1 Dry contact - Pump panel Fire - BMS
Contractor contactor
Battery Charger Fail 1 Dry contact - Pump panel Fire - BMS
Contractor contactor
Overspeed shut down 1 Dry contact - Pump panel Fire - BMS
Contractor contactor
Fail to Start 1 Dry contact - Pump panel Fire - BMS
Contractor contactor
Run Time 1 BMS
Common Alarm 1 Dry contact - Pump panel Fire - BMS
Contractor contactor

Hydrant Jockey Pump 1


Pump on off status 1 Dry contact - Pump panel Pool - BMS
Contractor contactor
Pump trip alarm 1 Dry contact - Pump panel Pool - BMS
Contractor contactor
Auto manual status 1 Dry contact - Pump panel Pool - BMS
Contractor contactor
Running Hours 1 BMS

Hydrant Header 1
Line Pressure 1 2-10V/4-20mA - Pump panel BMS - BMS
contactor
Flow Status 1 Flow Switch - Pump panel BMS - BMS
contactor

Hydrant Priming Tank 1


Low Level 1 Dry Contact Gen: Supplier

Fire Pump Fuel Tank 1


Low Level 1 Dry Contact Gen: Supplier
Mid Level 1 Dry Contact Gen: Supplier
High Level 1 Dry Contact Gen: Supplier

8 Cold Room
Garbage Cold Room 1
Garbage Room Temperature 1 pt 100 10K RTD/4-20mA - Garbage Cold BMS BMS BMS
Room contactor contactor contactor
MCC Panel Power On 1 Dry contact Cold Room MVAC BMS
panel Contractor contactor
AC on off status 1 Dry contact - Cold Room MVAC - BMS
panel Contractor contactor
AC trip alarm 1 Dry contact - Cold Room MVAC - BMS
panel Contractor contactor
AC power failure 1 Dry contact - Cold Room MVAC - BMS
panel Contractor contactor
Auto manual status 1 Dry contact - Cold Room MVAC - BMS
panel Contractor contactor
Running Hours 1 BMS

9 High level third party systems

1 Generator 2 24 BACnet IP/ Modbus IP - Gen plant Gen supplier - BMS


room contractor

2 Fire Detection system 1 BACnet IP/ Modbus IP - Fire control Fire system - BMS
room supplier contractor
Fire Alarm Status 300 Highlevel Interface Fire system BMS
supplier contractor

3 CCTV system 1 BACnet IP/ Modbus IP - CCTV control CCTV system - BMS
room supplier contractor
System On/Off status 1 Dry contact CCTV system
supplier
System Fault 1 Dry contact CCTV system
supplier
Power Failure 1 Dry contact CCTV system
supplier

4 EACS system 1 BACnet IP/ Modbus IP - Access Access - BMS


control room control contractor
system
supplier
System On/Off status 1 Dry contact EACS system
supplier
System Fault 1 Dry contact EACS system
supplier
Power Failure 1 Dry contact EACS system
supplier

5 V.B system 1 BACnet IP/ Modbus IP - Access Access - BMS


control room control contractor
system
supplier
System On/Off status 1 Dry contact EACS system
supplier
System Fault 1 Dry contact EACS system
supplier
Power Failure 1 Dry contact EACS system
supplier

6 Car Park Management system 1 BACnet IP/ Modbus IP - Access Access - BMS
control room control contractor
system
supplier
System On/Off status 1 Dry contact EACS system
supplier
System Fault 1 Dry contact EACS system
supplier
Power Failure 1 Dry contact EACS system
supplier

7 PA system 1 BACnet IP/ Modbus IP - FCC Room PAV system - BMS


supplier contractor
System On/Off status 1 Dry contact PAV system
supplier
System Fault 1 Dry contact PAV system
supplier
Power Failure 1 Dry contact PAV system
supplier
Water Leakage Detection 1 Dry contact BMS BMS
contractor

8 Telephone and Intercom System 1 BACnet IP/ Modbus IP - Data/Tel Data/Tel - BMS
System system contractor
supplier
System Fault 1 Dry contact Data/Tel BMS
system contractor
supplier
Space Temperature/Humidity 2 pt 100 10K RTD Immersion BMS BMS BMS
temperature contactor contactor contactor
Water Leakage Detection 1 Dry contact BMS BMS
contractor

9 UPS for ELV systems 30


ON/OFF 30 Dry contact ELV panel

Total points 321 47 23 2 1066