DOCUMENT : BMS I/O SUMMARY FOR HVAC

I/O DETAILS CABLE DETAILS VENDORS CLIENT'S


Sl.NO PARTICULARS QTY
AI DI AO DO Soft Type Runs Tag From To Scope of Work Scope of Work
I HVAC
B AHU 07
BMS DDC shall provide potential free (N.O.) AHU panel shall accept potential free (N.O.)
1 On/Off Command 07 2 Core 07 AHU-ONOF-CMD DDC AHU Panel contact to AHU panel. contact from BMS DDC.
Supply, Installation, Testing & Commissionig of Provision of 8mm dia hole at suitable location for
2 Run Status 07 2 Core 07 AHU-RUN-STS Air DPS DDC Air Diff. Pressure Switch (DPS). pressure pickup tube installation.
BMS DDC shall accept potential free (N.O.) AHU panel shall provide potential free (N.O.)
3 Auto Manual status 07 AHU-A/M-STS AHU Panel DDC contact from AHU panel. contact to BMS DDC.
4 Core 07
BMS DDC shall accept potential free (N.O.) AHU panel shall provide potential free (N.O.)
4 Trip Status 07 AHU-TRIP-STS AHU Panel DDC contact from AHU panel. contact to BMS DDC.

Supply, Installation, Testing & Commissionig of Provision of 8mm dia hole at suitable location for
5 Filter status 14 2 Core 14 AHU-FLTR-STS Air DPS DDC Air Diff. Pressure Switch (DPS). pressure pickup tube installation.

Duct Temp Supply, Installation, Testing & Commissioning of Provision of 1/4" hole to be made on the side of
6 Supply Air Temperature & RH Monitoring 05 2 Core 05 AHU-SA-TEMP Sensor DDC Duct Temp Sensor. duct for Duct Temp Sensor probe insertion.
7 Return Air Temperature & RH Monitoring 05 2 Core 05 AHU-RA-TEMP Duct Temp Supply, Installation, Testing & Commissioning of Provision of 1/4" hole to be made on the side of
DDC
Sensor Duct Temp Sensor. duct for Duct Temp Sensor probe insertion.
BMS DDC shall provide 0-10 Vdc signal output
Valve Valve Actuator shall accept 0-10Vdc signal for 0-
8 Valve Modulation 0 4 Core 0 AHU-VLV-MOD DDC for 0-100% valve open to Valve Actuator. 24Vac
Actuator 100% valve open from BMS DDC.
supply to valve actuator.
BMS DDC shall provide 0-10 Vdc signal output AHU VFD shall accept 0-10Vdc signal for 0-
9 VFD control Signal 07 2 Core 07 AHU-VFD-CTR DDC AHU VFD for 0-100% speed to AHU VFD. 100% VFD speed from BMS DDC
VFD modulation using diff press transmitter
Supply, Installation, Testing & Commissioning of Provision of 8mm dia hole at suitable location for
10 (Location of Diff. pressure sensor to be in SA 07 4 Core 07 AHU-DP Air DPT DDC
Air Diff. Pressure Transmitter (DPT). pressure pickup tubes installation.
Duct within AHU room itself)
I/O DETAILS CABLE DETAILS VENDOR CLIENT'S
Sl.NO PARTICULARS QTY
Scope of Work Scope of Work
AI DI AO DO Soft Type Runs Tag From To
11 VFD soft integration 06
12 AHU's VFD Speed Feedback 07 Shall provide - 1) VFD Modbus RTU RS-485 wire
1) Supply, Installation, Testing &
Commissioning of Modbus RS485 Integrator. terminals.
13 AHU's VFD Frequency 07
1 (Daisy 2) VFD Modbus register mapping list.
2 Core VFD-COMM DDC AHU VFD 2) Communication Cable laying from integrator
14 AHU's VFD Current 07 Chain) 3) VFD Configuration as per site requirement.
to VFDs in daisy chain.
3) VFD point data mapping into BMS Software. 4) Demonstrate VFD communication in
15 AHU's VFD Voltage 07 open Modbus software like MODSCAN at
16 AHU's VFD Power 07 site.

17 AHU's VFD Run Time 07

Page 1 of 3
DOCUMENT : BMS I/O SUMMARY FOR HVAC

I/O DETAILS CABLE DETAILS HAIL'S CLIENT'S


Sl.NO PARTICULARS QTY
AI DI AO DO Soft Type Runs Tag From To Scope of Work Scope of Work
R SMDB UPS II 1
Incoming breaker 1
1 SMDB-UPS2-IC-ONOF- BMS DDC shall accept potential free (N.O.) Panel shall provide potential free (N.O.) contact
ON/OFF Status of each main incoming breaker 1 2 Core 1 STS Panel DDC contact from Panel. to BMS DDC.
S SMDB GYM 1
Incoming breaker 1
1 SMDB-GYM-IC-ONOF- BMS DDC shall accept potential free (N.O.) Panel shall provide potential free (N.O.) contact
ON/OFF Status of each main incoming breaker 1 2 Core 1 STS Panel DDC contact from Panel. to BMS DDC.
T SMDB F & B 1
Incoming breaker 1
1 SMDB-F&B-IC-ONOF- BMS DDC shall accept potential free (N.O.) Panel shall provide potential free (N.O.) contact
ON/OFF Status of each main incoming breaker 1 2 Core 1 STS Panel DDC contact from Panel. to BMS DDC.
U SMDB CF1 & CF2 2
Incoming breaker 2
1 SMDB-CFx-IC-ONOF- BMS DDC shall accept potential free (N.O.) Panel shall provide potential free (N.O.) contact
ON/OFF Status of each main incoming breaker 2 2 Core 2 STS Panel DDC contact from Panel. to BMS DDC.
V MCC FF 1
Incoming breaker 1
1 BMS DDC shall accept potential free (N.O.) Panel shall provide potential free (N.O.) contact
ON/OFF Status of each main incoming breaker 1 2 Core 1 MCC-FF-IC-ONOF-STS Panel DDC contact from Panel. to BMS DDC.
W FLOOR SMDBs 4

Incoming breaker 04
1 FLR-SMDBx-IC-ONOF- BMS DDC shall accept potential free (N.O.) Panel shall provide potential free (N.O.) contact
ON/OFF Status of each main incoming breaker 04 2 Core 04 STS Panel DDC contact from Panel. to BMS DDC.
X TENANT SMDBs 04
Incoming break 04
1 TENT-SMDBx-IC-ONOF- BMS DDC shall accept potential free (N.O.) Panel shall provide potential free (N.O.) contact
ON/OFF Status of each main incoming breaker 04 2 Core 04 STS Panel DDC contact from Panel. to BMS DDC.
Y TRANSFORMERS 0
BMS DDC shall accept 0-10 Vdc signal from Panel shall providde 0-10Vdc signal for BMS
1 Signals for monitoring 0 2 Core TX-SINGx-MTR Panel DDC panel interface with DDC.
BMS DDC shall accept potential free (N.O.) Panel shall provide potential free (N.O.) contact
2 Signals for monitoring 0 4 Core TX-SINGx-STS Panel DDC contact from Panel. to BMS DDC.
Z HT PANELS/BREAKERS 0
BMS DDC shall accept 0-10 Vdc signal from Panel shall providde 0-10Vdc signal for BMS
1 Signals for monitoring 2 Core HT-SINGx-MTR Panel DDC panel interface with DDC.
BMS DDC shall accept potential free (N.O.) Panel shall provide potential free (N.O.) contact
2 Signals for monitoring 4 Core HT-SINGx-STS Panel DDC contact from Panel. to BMS DDC.
AA LOAD MANAGERS INTEGRATION 103
1 Average Current 06
2 Voltage 06
3 Kilowatt 06 Shall provide - 1) EM Modbus RTU RS-485 wire
4 Run hour 06 1) Supply, Installation, Testing &
terminals.
5 Power Factor 06 Commissioning of Modbus RS485 Integrator.
1 (Daisy Load 2) EM Modbus register mapping list.
6 Forward Active Energy 06 2 Core EM-COMM DDC 2) Communication Cable laying from integrator
7 Power Factor Average 06 Chain) Manager 3) EM Configuration as per site requirement.
to EMs in daisy chain.
8 Line to Line Voltage Average 06 4) Demonstrate EM communication in
3) EM point data mapping into BMS Software.
9 Line to Line Neutral Average 06 open Modbus software like MODSCAN at
10 Frequency 06 site.
AB LIGHTING CONTROL
BMS DDC shall accept potential free (N.O.) Panel shall provide potential free (N.O.) contact
1 Circuit open/close status 0 LP-CKT-ONOF-STS Panel DDC contact from Panel. to BMS DDC.
4 Core 0
BMS DDC shall provide potential free (N.O.) Panel shall accept potential free (N.O.) contact
2 Circuit open/close command 0 LP-CKT-ONOF-CMD DDC Panel contact to Panel. from BMS DDC.
AC AIRCRAFT WARNING LIGHT 0
BMS DDC shall accept potential free (N.O.) Panel shall provide potential free (N.O.) contact
1 Circuit on/off status 1 AL-CKT-ONOF-STS Panel DDC contact from Panel. to BMS DDC.
4 Core 1
BMS DDC shall accept potential free (N.O.) Panel shall provide potential free (N.O.) contact
2 Circuit trip alarm 1 AL-CKT-TRIP-STS Panel DDC contact from Panel. to BMS DDC.

I/O DETAILS CABLE DETAILS HAIL'S CLIENT'S


Sl.NO PARTICULARS QTY
AI DI AO DO Soft Type Runs Tag From To Scope of Work Scope of Work

Page 2 of 3
DOCUMENT : BMS I/O SUMMARY FOR HVAC
AD UPS 0
1 O/P Voltage - R
2 O/P Voltage - Y
3 O/P Voltage - B Shall provide - 1) UPS Modbus RTU RS-485 wire
4 O/P Current - R 1) Supply, Installation, Testing &
terminals.
5 O/P Current - Y Commissioning of Modbus RS485 Integrator.
1 (Daisy 2) UPS Modbus register mapping list.
6 O/P Current - Y 2 Core UPS-COMM DDC UPS 2) Communication Cable laying from integrator
7 Battery Voltage Chain) 3) UPS Configuration as per site requirement.
to UPSs in daisy chain.
8 Battery Charge Remaining 4) Demonstrate UPS communication in
3) UPS point data mapping into BMS Software.
9 Frequency open Modbus software like MODSCAN at
10 Alarm Status site.

VII PA/BGM SYSTEM 1


1 Panel power ON status 1 PA-ONOF-STS Panel DDC PAS BY HAIL
2 Panel fault status 1 4 Core 1 PA-FAULT-STS Panel DDC PAS BY HAIL

VIII CCTV SYSTEM INTEGRATION DVM Interface

IX FIRE ALARM SYSTEM INTEGRATION Modbus Interface

X ACCESS CONTROL SYSTEM Tema Interface

TOTAL 482 1054 329 605 5961


10% Pseudo Points 843
TOTAL 9274