Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                
Download as pdf or txt
Download as pdf or txt
You are on page 1of 21

AIR CONDITIONING

Daikin
Quick Selection Guide

High Ambient Series


INTRODUCTION
AIR CONDITIONING
MAKE YOUR WORLD A BETTER PLACE TABLE OF CONTENTS

PAGES

Product Range 4-5

DX DX SYSTEMS
DX Systems
DX
Split unit (Wall mounted, Cassette, Ducted)

AP AIR PURIFIER R-22 (Nominal Conditions)


R-22 (Actual Conditions)
8-9
10-11
R-410A / R-407C (Nominal Conditions) 12-13
R-410A / R-407C (Actual Conditions) 14-15
Roof Tops (Packaged Units) R-22 / R-410A 16-17
VRV VRV III SYSTEMS
Air Purifier 18-19
AP

AS APPLIED SYSTEMS
VRV III Systems
VRV
VRV-III Air Cooled Outdoor units 22-23
VRV-III Water Cooled Outdoor units 24
Ducted Indoor units 25
Cassette indoor units 26
Wall mounted units 27

Our mission, and the essence of our existence, is to identify and realise our customers’ future needs and dreams,
Applied Systems
even those that they themselves may not yet be aware of. We can accomplish this goal by paying careful attention to AS
changes in social trends and conducting extensive marketing to win the hearts and minds of customers. It is essential Air-Cooled Chillers 30-31-32-33
that we offer customers optimum convenience and comfort that are always one step ahead of our competitors Air Handling units 34
Fresh Air Handling units 35
by providing customers with the highest quality products, materials, and services for which we, as a manufacturer, will Chilled Water Fancoil units 36-37
be absolutely responsible. Moreover, we will continue offering products and services that provide customers with fresh
excitement and continued enjoyment.

In any era, in any business field, a company can grow and develop only if it possesses world-leading technologies.

As we continue developing our business operations in various fields, it is our mission to proactively develop
initiatives to respond to environmental issues. Incorporating environmental initiatives throughout our management
must be a priority for us.

In all aspects of our business operations, including product development, manufacturing and sales, we need to
formulate initiatives that sustain and improve the environment. Meanwhile, we need to promote the development of
new products and the innovation of technologies that will lead to a more environmentally healthy world.

Due to our policy of innovation some specifications may be changed without prior notification
Q U I C K S E L E C T I O N G U I D E
2 3
PRODUCT RANGE
AIR CONDITIONING
PRODUCT RANGE

Cooling Capacity Class (MBH) Water Cooled Chillers - Screw Product Picture [TR] 50 150 250 350 450 550 650
DX Indoor Unit Indoor Series Product Picture
9 12 18 24 30 36 48 56 60
ECOPLUS 46-171 TR
Wall Mounted FTD / FTS

Cassette Type FHC / FCRN / FFRN PFS 105-345 TR

Ducted Split FDM / FDMRN


WHS 95-430 TR
Ceiling Suspended / Convertible FL / FH / FLRN / FHRN

PROXIMUS 108-617 TR
Higher Cooling Capacity Class (MBH)
Product
Capacaity Dx Indoor Series
Picture
& Rooftop 60 75 100 115 125 150 200 225 250 300 320 400 500
Water Cooled
Product Picture [TR] 200 600 1000 1400 1800 2200 2600 3000 6200
Ducted Split - Centrifugal Chillers
FD / FDM / 2FD / 2FG / 4FG
Large Capacity
WSC 200-1250 TR
UAT
Roof Top
(Packaged Unit)
UATYQ WDC 400-2500 TR

Refrigerant R-410A Refrigerant R-22


WCC 1200-2700 TR

VRV III Air Product


Series 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
Cooled Picture
WCT 2500-6200 TR

Cooling Capacity (KW)1 15.5 22.4 28.0 33.5 40.0 45.0 49.0 55.9 61.5 67.0 71.4 77.0 82.5 89.0 94.0 98.0

Air Cooled Chillers Product Picture [TR] 50 150 250 350 450 550
Heating Capacity ( KW)2 18.0 25.0 31.5 37.5 45.0 50.0 56.5 62.5 69.0 75.0 81.5 88.0 94.0 102.0 107.0 113.0

RXYQ
Series - 50 ACZC 49-192 TR
HZ
Heat Pump
RXYMQ
Series
McEnergy 28-176 TR

VRV Indoor Unit Series Product Picture 15 20 25 32 40 50 63 71 80 100 125 140 200 250 AWS 184-571 TR

Cooling Capacity (KW) 1.7 2.2 2.8 3.6 4.5 5.6 7.1 8 9 11.2 14 16 22.4 28
Chilled Water Fan Coil Units Product Picture [CFM] 550 1000 1500 2000 2500 3000 3500 4000 4500
FXFQ
Ceiling WSC 180 - 1750 CFM
Mounted FXCQ
Cassette
FXKQ WDC 880 - 2500 CFM

FXDQ
WCC 2500 – 4600 CFM
Concealed
FXMQ
Ceiling Unit
WCT 200 – 1025 CFM
FXMQ - MA

Wall Mounted FXAQ


Air Handling Units Product Picture [CFM] 5,000 10,000 20,000 30,000 40,000 50,000 60,000 70,000 100,000

FXHQ
Ceiling Suspended DM (Malaysia) 700 – 42400 CFM
FXUQ

Easdale (UK/Italy) 700 – 73000 CFM


FXLQ
Floor Standing
FXNQ

Q U I C K S E L E C T I O N G U I D E
4 5
AIR CONDITIONING

DX Systems
DX
Split unit (Wall mounted, Cassette, Ducted)
R-22 (Nominal Conditions) 8-9
R-22 (Actual Conditions) 10-11
R-410A / R-407C (Nominal Conditions) 12-13
R-410A / R-407C (Actual Conditions) 14-15

Roof Tops (Packaged Units) R-22 / R-410A 16-17

7
DX SYSTEMS
AIR CONDITIONING
Nominal Conditions R-22

Cooling Power Indoor sound


Air Flow EER Power Pipe Size Dimensions (W/H/D) mm
Capacity Supply pressure
TYPE INDOOR OUTDOOR Input
Turbo / Hi / Med / (kW) Disch. Suction Turbo / Hi / Med /
TON kW W/W Btu/W V - PH - Hz Indoor Outdoor
Lo / Quiet (CFM) (Liquid) (Gas) Lo / Quiet (dBA)
FTD20JV1 RD20JV1 1.50 5.28 590/531/474/422/381 3.56 12.17 1.48 220-240/1/50 1/4” 5/8” 44/42/39/36/35 1065/310/228 885/651/328

FTD25JV1 RD25JV1 2.00 7.03 674/646/566/500/440 2.93 10.01 2.40 220-240/1/50 3/8” 5/8” 48/46/43/40/37 1065/310/228 855/753/328

FTD30JV1 RD30JEV1K 2.42 8.49 950/931/760/684/607 2.79 9.52 3.05 220-240/1/50 3/8” 5/8” 52/51/46/44/42 1289/310/240 855/753/328

FTD36JV1 RD40JEV1K 2.67 9.37 950/931/760/684/607 2.49 8.50 3.76 220-240/1/50 3/8” 3/4” 52/51/46/44/42 1289/310/240 1030/852/400
Wall Mounted
FTD36JV1 RD40JEY1K 2.67 9.37 950/931/760/684/607 2.49 8.50 3.76 220-240/1/50 3/8” 3/4” 52/51/46/44/42 1289/310/240 1030/852/400

FT18HEV1K R18HEV1K 1.62 5.70 460/383/324 2.71 9.27 2.10 220-240/1/50 1/4” 1/2” 49/45/41 940/298/200 913/680/378

FT24HEV1K R24HEV1K 1.84 6.45 471/412/354 2.69 9.18 2.40 220-240/1/50 1/4” 5/8” 46/43/40 1007/315/219 955/700/424

FT28HEV1K R28HEV1K 2.51 8.82 648 2.90 9.91 3.04 220-240/1/50 3/8” 5/8” 50/48/46 1178/326/227 950/412/840

FHC20JV1 RD20JV1 1.50 5.28 600/530/430/400 3.52 12.02 1.50 220-240/1/50 1/4” 5/8” 34/32/30/28 820/265/820 885/651/328

FHC25JV1 RD25JV1 2.00 7.03 680/600/530/430 2.81 9.60 2.50 220-240/1/50 3/8” 5/8” 37/34/33/32 820/265/820 855/753/328

FHC30JV1 RD30JV1 2.50 8.79 860/725/620/530 2.75 9.38 3.20 220-240/1/50 3/8” 5/8” 42/38/35/33 820/265/820 855/753/328
Cassette unit
FHC40JV1 RD40JV1 3.00 10.55 1030/860/740/620 3.10 10.60 3.40 220-240/1/50 3/8” 3/4” 47/44/40/36 820/300/820 1030/852/400

FHC40JV1 RD40JY1 3.00 10.55 1030/860/740/620 3.20 10.92 3.30 380-415/3/50 3/8” 3/4” 47/44/40/36 820/300/820 1030/852/400

FHC50JV1 RD50JY1 4.00 14.07 1200/1030/930/780 3.13 10.68 4.50 380-415/3/50 3/8” 3/4” 49/45/43/39 820/300/820 1030/852/400

FDM20JV1 RD20JV1 1.54 5.42 561/544/522 3.47 11.86 1.56 220-240/1/50 1/4” 5/8” 40/39/38 1065/261/411 885/651/328

FDM25JV1 RD25JV1 2.04 7.18 607/581/512 2.77 9.47 2.59 220-240/1/50 3/8” 5/8” 40/39/38 1200/261/411 855/753/328

FDM30JV1 RD30JV1 2.57 9.03 950/900/750 2.74 9.34 3.30 220-240/1/50 3/8” 5/8” 45/44/39 1228/292/420 855/753/328

FDM40JV1 RD40JV1 3.08 10.81 1000/950/880 2.92 9.98 3.70 220-240/1/50 3/8” 3/4” 46/45/44 1228/292/420 1030/852/400

FDM40JV1 RD40JY1 3.08 10.81 1000/950/880 3.02 10.31 3.58 380-415/3/50 3/8” 3/4” 46/45/44 1228/292/420 1030/852/400

FDM50JV1 RD50JY1 4.22 14.83 1950/1630/1420 2.83 9.66 5.24 380-415/3/50 3/8” 3/4” 55/53/52 1299/378/541 1030/852/400

FDM60JV1 RD60JY1 4.90 17.23 2060/1850/1590 2.90 9.90 5.94 380-415/3/50 1/2” 3/4” 58/56/54 1499/378/541 1030/852/400

FDM75DXV1 RC75DXY1 6.26 21.98 2420/2310/1930/1630 3.02 10.32 7.27 380-415/3/50 1/2” 1” 52/52/48/43 1370/430/710 981/1041/981

Ducted Split FDM100DXV1 RC100DXY1 8.30 29.18 3150/2950/2650/2150 2.71 9.21 10.82 380-415/3/50 5/8” 1 1/8” 55/54/52/48 1599/430/710 981/1041/981

FD125DXY1 RC125DXY1 10.60 37.24 3750 3.11 10.80 11.77 380-415/3/50 5/8” 1 3/8” 58 1694/710/775 1083/1041/1083

FD150DXY1 RC150DXY1 12.72 44.68 4500 2.78 9.64 15.83 380-415/3/50 5/8” 1 3/8” 59 1973/710/775 1083/1041/1083

2FD150DXY1 RC75DXY1 x 2 12.72 44.68 4500 3.16 10.96 13.92 380-415/3/50 1/2” 1” 59 1973/710/775 981/1041/981

2FD200DXY1 RC100DXY1 x 2 16.96 59.58 6000 2.67 9.28 21.93 380-415/3/50 5/8” 1 1/8” 60 1113/821/1064 981/1041/981x2

2FG250DXY1 RC125DXY1 x 2 21.19 74.47 7500 2.93 10.17 25.00 380-415/3/50 5/8” 1 3/8” 62 1202/922/1226 1083/1041/1083x2

2FG300DXY1 RC150DXY1 x 2 25.43 89.36 9000 2.65 9.20 33.18 380-415/3/50 5/8” 1 3/8” 65 1405/922/1226 1083/1142/1083x2

4FG400DXY1 RC100DXY1 x 4 33.91 119.14 12000 2.65 9.21 44.17 380-415/3/50 5/8” 1 1/8” 66 1596/1115/1462 981/1041/981x4

4FG500DXY1 RC125DXY1 x 4 42.38 148.93 15000 2.97 9.69 52.50 380-415/3/50 5/8” 1 3/8” 67 1952/1115/1462 1083/1142/1083x4

Selection based on Nominal Conditions: 80 / 67º F air on coil and 95º F ambient (27 / 19 º C and 35º C)

Q U I C K S E L E C T I O N G U I D E
8 9
DX SYSTEMS
AIR CONDITIONING
Actual Conditions R-22

Ambient 115° F (46°C), Air On Coil 80/67º F (27/19°C) Ambient 115° F (46°C), Air On Coil 76/63º F (24/16°C)
Medium Fan Speed Medium Fan Speed

TYPE INDOOR OUTDOOR TMBH SMBH T.kW S.kW CFM P.I. Kw TMBH SMBH T.kW S.kW CFM P.I. Kw
FTD20JV1 RD20JV1 14.89 10.65 4.36 3.12 475 1.70 13.52 11.78 3.96 3.45 475 1.70

FTD25JV1 RD25JV1 19.81 14.38 5.80 4.21 566 2.81 18.00 15.91 5.27 4.66 566 2.76

FTD30JV1 RD30JV1 TBA TBA TBA TBA TBA TBA TBA TBA TBA TBA TBA TBA

Wall Mounted FTD36JV1 RD36JV1 TBA TBA TBA TBA TBA TBA TBA TBA TBA TBA TBA TBA

FT18HEV1K R18HEV1K 17.55 11.58 5.14 3.39 384 2.57 17.11 11.51 5.01 3.37 384 2.54

FT24HEV1K R24HEV1K 19.84 13.11 5.81 3.84 413 2.93 19.36 13.01 5.67 3.81 413 2.91

FT28HEV1K R28HEV1K 27.15 17.93 7.95 5.25 649 3.73 26.47 17.79 7.75 5.21 649 3.69

FHC20JV1 RD20JV1 15.27 12.16 4.47 3.56 530 1.79 13.90 12.50 4.07 3.66 530 1.76

FHC25JV1 RD25JV1 19.29 14.55 5.65 4.26 600 2.98 17.55 14.92 5.14 4.37 600 2.93

FHC30JV1 RD30JV1 25.65 20.69 7.51 6.06 725 3.82 23.36 21.24 6.84 6.22 725 3.75
Cassette unit
FHC40JV1 RD40JV1 28.45 22.33 8.33 6.54 860 4.06 25.89 22.95 7.58 6.72 860 3.99

FHC40JV1 RD40JY1 28.45 22.33 8.33 6.54 861 3.94 25.89 22.95 7.58 6.72 861 3.87

FHC50JV1 RD50JY1 36.92 27.08 10.81 7.93 1,030 5.37 33.60 27.80 9.84 8.14 1,030 5.27

FDM20JV1 RD20JV1 15.88 11.99 4.65 3.51 544 1.86 14.90 11.58 4.36 3.39 544 1.84

FDM25JV1 RD25JV1 21.34 15.57 6.25 4.56 581 3.09 20.00 15.03 5.86 4.40 581 3.05

FDM30JV1 RD30JV1 26.50 23.32 7.76 6.83 900 3.93 24.83 22.54 7.27 6.60 900 3.89

FDM40JV1 RD40JV1 30.46 28.21 8.92 8.26 950 4.37 28.89 25.65 8.46 7.51 950 4.33

FDM40JV1 RD40JY1 31.73 24.31 9.29 7.12 950 4.27 29.74 23.50 8.71 6.88 950 4.22

FDM50JV1 RD50JY1 43.92 38.11 12.86 11.16 1,630 6.26 41.18 36.80 12.06 10.78 1,630 6.18

FDM60JV1 RD60JY1 51.67 44.87 15.13 13.14 1,850 7.09 48.42 43.30 14.18 12.68 1,850 7.00

FDM75DXV1 RC75DXY1 61.47 46.38 18.00 13.58 1,600 8.61 55.84 51.16 16.35 14.98 1,600 8.47

Ducted Split FDM100DXV1 RC100DXY1 81.98 59.28 24.01 17.36 2,100 12.82 74.45 65.43 21.80 19.16 2,100 12.60

FD125DXY1 RC125DXY1 104.81 82.98 30.69 24.30 3,750 13.98 95.14 89.23 27.86 26.13 3,750 13.70

FD150DXY1 RC150DXY1 125.74 93.30 36.82 27.32 4,500 18.80 114.13 101.43 33.42 29.70 4,500 18.42

FD150DXY1 RC75DXY1 x 2 125.74 96.95 36.82 28.39 4,500 18.80 114.13 104.26 33.42 30.53 4,500 18.42

2FD200DXY1 RC100DXY1 x 2 167.68 132.74 49.10 38.87 6,000 26.05 152.21 142.78 44.57 41.81 6,000 25.53

2FG250DXY1 RC125DXY1 x 2 209.61 165.93 61.38 48.59 7,500 29.69 190.25 178.47 55.71 52.26 7,500 29.10

2FG300DXY1 RC150DXY1 x 2 251.51 206.98 73.65 60.61 9,000 39.40 228.29 222.59 66.85 65.18 9,000 38.62

4FG400DXY1 RC100DXY1 x 4 335.35 265.48 98.20 77.74 12,000 52.45 304.38 285.53 89.13 83.61 12,000 51.41

4FG500DXY1 RC125DXY1 x 4 419.19 331.87 122.75 97.18 15,000 62.34 380.50 356.90 111.42 104.51 15,000 61.10

Q U I C K S E L E C T I O N G U I D E
10 11
DX SYSTEMS
AIR CONDITIONING
Nominal Conditions R-410A / R-407C

Cooling Power Indoor sound


Air Flow EER Power Pipe Size Dimensions (W/H/D) mm
Refrigerant Capacity Supply pressure
TYPE INDOOR OUTDOOR Input
Gas Turbo / Hi / Med / Disch. Suction Turbo / Hi / Med /
TON kW W/W Btu/W (kW) V - PH - Hz Indoor Outdoor
Lo / Quiet (CFM) (Liquid) (Gas) Lo / Quiet (dBA)
FTS20JV1 RS20JV1 1.50 5.28 594/531/474/422/381 3.24 11.06 1.63 220-240/1/50 1/4” 1/2” 44/42/39/36/35 1065/310/228 885/651/328
Wall Mounted
FTS25JV1 RS25JV1 2.00 7.03 674/646/566/500/440 3.29 11.22 2.14 220-240/1/50 1/4” 5/8” 48/46/43/40/37 1065/310/228 855/753/328

FCRN50EXV1 RN50CJXV1 1.53 5.36 600/530/430/400 3.08 10.52 1.74 220-240/1/50 1/4” 5/8” 34/32/30/28 1200/261/411 855/756/328

FCRN60EXV1 RN60CJXV1 1.85 6.51 680/600/530/430 3.36 11.46 1.94 220-240/1/50 3/8” 5/8” 37/34/33/32 1007/285/600 855/756/328

FCRN71EXV1 RR71CXV1 2.25 7.91 860/725/620/530 2.84 9.68 2.79 220-240/1/50 3/8” 5/8” 42/38/35/33 1302/305/638 1030/852/400
Cassette unit
FCRN100EXV1 RR90DXV1 2.44 8.56 1030/860/740/620 3.04 10.37 2.82 220-240/1/50 3/8” 5/8” 47/44/40/36 1302/305/638 1030/852/400

FCRN100EXV1 RR100DXY1 2.59 9.09 1030/860/740/620 2.37 8.08 3.84 380-415/3/50 3/8” 5/8” 47/44/40/36 1299/378/415 1030/852/1010

FCRN125EXV1 RR125DXY1 3.25 11.43 1200/1030/930/780 2.60 8.89 4.39 380-415/3/50 3/8” 3/4” 49/45/43/39 1499/378/541 1030/852/460

R-410A FDMRN25CXV1 RN25CXV1 0.79 2.78 250/235/210 2.89 9.88 0.96 220-240/1/50 1/4” 3/8” 33/30/26 765/261/411 700/540/250

FDMRN35CXV1 RN35CXV1 1.04 3.66 410/370/250 2.82 9.64 1.30 220-240/1/50 1/4” 1/2” 37/34/29 905/261/411 700/540/250

FDMRN50CXV1 RN50CXV1 1.50 5.28 570/558/480 3.01 10.26 1.76 220-240/1/50 1/4” 1/2” 38/36/34 1065/261/411 855/654/328

FDMRN60CXV1 RN60CXV1 1.75 6.16 690/660/535 3.08 10.50 2.00 220-240/1/50 1/4” 5/8” 40/39/36 1200/261/411 855/756/328

FDMRN71CXV1 RR71CXV1 2.18 7.65 850/810/770/710 2.65 9.03 2.89 220-240/1/50 3/8” 5/8” 44/41/38/34 1007/285/600 855/756/328

FDMRN100CXV1 RR90DXV1 2.70 9.49 1280/1160/1050/920 2.89 9.86 3.29 380-415/3/50 3/8” 5/8” 52/49/47/45 1302/305/638 1030/852/400

FDMRN100CXV1 RR100DXY1 3.29 11.57 1280/1160/1050/920 2.70 9.22 4.29 380-415/3/50 3/8” 5/8” 52/49/47/45 1302/305/638 1030/852/400

FDMRN125CXV1 RR125DXY1 3.81 13.38 1430/1320/1230/1130 2.91 9.93 4.60 380-415/3/50 3/8” 5/8” 54/53/52/51 1299/378/415 1030/852/1010

FDMRN140CXV1 RR140DXY1 4.64 16.31 1720/1550/1340/1170 3.04 10.39 5.36 380-415/3/50 3/8” 3/4” 54/52/50/46 1499/378/541 1030/852/460
Ducted Split
FDMP75DXV1 RCP75DXY1 6.26 21.98 2250/1950/1600/1250 2.72 9.29 8.08 380-415/3/50 1/2” 1” 52/52/48/43 1370/430/710 981/1041/981

FDMP100DXV1 RCP100DXY1 8.34 29.31 3000/2600/2100/1700 2.65 9.07 11.04 380-415/3/50 5/8” 1 1/8” 55/54/52/48 1599/430/710 981/1041/981

FDP125DXY1 RCP125DXY1 9.16 32.17 3750 2.61 9.08 12.10 380-415/3/50 5/8” 1 3/8” 58 1694/710/775 1083/1041/1083

FDP150DXY1 RCP150DXY1 12.29 43.19 4500 2.66 9.09 16.23 380-415/3/50 5/8” 1 3/8” 59 1973/710/775 1083/1142/1083

R-407C 2FDP200DXY1 RCP100DXY1 x 2 15.43 54.21 6000 2.38 8.28 22.37 380-415/3/50 5/8” 1 1/8” 60 1113/821/1064 981/1041/981x2

2FGP250DXY1 RCP125DXY1 x 2 18.31 64.34 7500 2.51 8.56 25.66 380-415/3/50 5/8” 1 3/8” 62 1202/922/1226 1083/1041/1083x2

2FGP300DXY1 RCP150DXY1 x 2 24.58 86.38 9000 2.54 8.68 33.99 380-415/3/50 5/8” 1 3/8” 65 1405/922/1226 1083/1142/1083x2

4FGP400DXY1 RCP100DXY1 x 4 30.85 108.42 12000 2.37 8.22 45.04 380-415/3/50 5/8” 1 1/8” 66 1596/1115/1462 981/1041/981x4

4FGP500DXY1 RCP125DXY1 x 4 36.62 128.68 15000 2.39 8.17 53.82 380-415/3/50 5/8” 1 3/8” 67 1952/1115/1462 1083/1142/1083x4

Q U I C K S E L E C T I O N G U I D E
12 13
DX SYSTEMS
AIR CONDITIONING
Actual Conditions R-410A / R-407C

Ambient 115° F (46°C), Air On Coil 80/67º F (27/19°C) Ambient 115° F (46°C), Air On Coil 76/63º F (24/16°C)
Medium Fan Speed Medium Fan Speed

TYPE Refrigerant INDOOR OUTDOOR TMBH SMBH T.kW S.kW CFM P.I. Kw TMBH SMBH T.kW S.kW CFM P.I. Kw
FTS20JV1 RS20JV1 14.72 11.13 4.31 3.26 474 1.91 13.66 12.57 4.00 3.68 474 1.87
Wall Mounted
FTS25JV1 RS25JV1 19.60 14.24 5.74 4.17 566 2.51 18.17 16.08 5.32 4.71 566 2.46

FCRN50EXV1 RN50CXV1 14.99 12.23 4.39 3.58 530 2.06 13.63 13.49 3.99 3.95 530 2.03

FCRN60EXV1 RN60CXV1 18.20 13.90 5.33 4.07 600 2.30 16.53 15.37 4.84 4.50 600 2.26

FCRN71EXV1 RR71CXV1 22.13 17.59 6.48 5.15 725 3.31 20.11 19.40 5.89 5.68 725 3.25
Cassette unit
FCRN100EXV1 RR90DXV1 23.94 19.77 7.01 5.79 860 3.34 21.75 21.75 6.37 6.37 860 3.29

FCRN100EXV1 RR100DXY1 31.90 22.74 9.34 6.66 860 4.64 28.96 25.10 8.48 7.35 860 4.57

FCRN125EXV1 RR125DXY1 35.24 26.23 10.32 7.68 1030 5.20 32.03 28.93 9.38 8.47 1030 5.11

R-410A FDMRN25CXV1 RN25CXV1 7.79 5.87 2.28 1.72 235 1.14 7.07 6.49 2.07 1.90 235 1.12

FDMRN35CXV1 RN35CXV1 10.25 7.62 3.00 2.23 370 1.54 9.29 8.40 2.72 2.46 370 1.51

FDMRN50CXV1 RN50CXV1 14.79 11.17 4.33 3.27 558 2.09 13.42 12.29 3.93 3.60 558 2.05

FDMRN60CXV1 RN60CXV1 17.25 12.98 5.05 3.80 660 2.37 15.64 14.31 4.58 4.19 660 2.33

FDMRN71CXV1 RR71CXV1 21.31 16.32 6.24 4.78 770 3.42 19.36 18.00 5.67 5.27 770 3.37

FDMRN100CXV1 RR90DXV1 26.26 18.71 7.69 5.48 1050 3.90 23.84 20.66 6.98 6.05 1050 3.83

FDMRN100CXV1 RR100DXY1 32.00 22.81 9.37 6.68 1050 5.08 29.06 25.17 8.51 7.37 1050 5.00

FDMRN125CXV1 RR125DXY1 36.92 26.33 10.81 7.71 1230 5.84 33.54 29.06 9.82 8.51 1230 5.74

FDMRN140CXV1 RR140DXY1 45.11 31.76 13.21 9.30 1340 6.82 40.98 35.04 12.00 10.26 1340 6.71

Ducted Split FDMP75DXV1 RCP75DXY1 61.50 48.25 18.01 14.13 1600 9.57 55.84 53.24 16.35 15.59 1600 9.41

FDMP100DXV1 RCP100DXY1 81.99 61.81 24.01 18.10 2100 13.08 74.48 68.23 21.81 19.98 2100 12.86

FDP125DXY1 RCP125DXY1 90.50 71.65 26.50 20.98 3750 14.37 82.16 77.08 24.06 22.57 3750 14.08

FDP150DXY1 RCP150DXY1 121.57 89.92 35.60 26.33 4500 19.28 110.34 96.71 32.31 28.32 4500 18.90

2FDP150DXY1 RCP75DXY1 x 2 122.39 98.18 35.84 28.75 4500 18.45 1101.44 105.59 322.53 30.92 4500 18.08
R-407C
2FDP200DXY1 RCP100DXY1 x 2 152.58 117.61 44.68 34.44 6000 26.56 138.51 126.49 40.56 37.04 6000 26.04

2FGP250DXY1 RCP125DXY1 x 2 181.10 143.40 53.03 41.99 7500 30.47 164.40 154.19 48.14 45.15 7500 29.86

2FGP300DXY1 RCP150DXY1 x 2 243.11 179.80 71.19 52.65 9000 40.37 220.68 193.39 64.62 56.63 9000 39.57

4FGP400DXY1 RCP100DXY1 x 4 305.16 235.23 89.36 68.88 12000 53.49 276.99 252.98 81.11 74.08 12000 52.42

4FGP500DXY1 RCP125DXY1 x 4 362.19 279.18 106.06 81.75 15000 63.91 328.73 300.25 96.26 87.92 15000 62.64

Q U I C K S E L E C T I O N G U I D E
14 15
DX SYSTEMS
AIR CONDITIONING
Roof Tops (Packaged units) - Nominal / Actual Conditions

Indoor
Nominal Ambient 35° C/ Air On Coil 80/67° F (27/19° C) Ambient 46° C/Air On Coil 80/67° F (27/19° C) Ambient 46° C/Air On Coil 76/63° F (24/16° C) Power
Air Flow Max. Sound
Capacity Medium Fan Speed Medium Fan Speed Medium Fan Speed Supply Dimensions
Ver/ Pressure
(W/H/D)
Model Total Sensible P.I. COP EER Total Sensible P.I. COP EER Total Sensible P.I. COP EER Tot. dBA
Refrigerant gas TON L/S CFM TMBH SMBH TMBH SMBH TMBH SMBH V - Ph. - Hz
Number (kW) (kW) (kW) W/W Btu/W (kW) (kW) (kW) W/W Btu/W (kW) (kW) (kW) W/W Btu/W H/M/L
380- 100
UAT180AMY1 4.85 850 1802 17,06 12,47 58,26 42,59 5,61 3,04 10,39 13,39 11,33 45,73 38,69 6,73 1,99 8,65 12,96 9,19 44,24 31,38 6,73 1,92 6,57 63 1100/1000/1530
415/3/50 Pa
380- 100
UAT240AMY1 6.57 1333 2826 23,10 16,69 78,90 56,98 8,10 2,85 9,74 17,24 13,13 58,86 44,85 9,72 1,77 8,12 17,01 10,20 58,07 34,84 9,72 1,75 5,97 65 1300/1000/1530
415/3/50 Pa
380- 100
UAT280AMY1 8.24 1667 3534 28,97 23,03 98,93 78,63 10,50 2,76 9,42 22,32 18,15 76,21 61,99 12,60 1,77 7,85 21,73 14,18 74,19 48,42 12,60 1,72 5,89 66 1300/1000/1530
415/3/50 Pa
380- 100
UAT320AMY1 9.57 1700 3604 33,64 25,80 114,86 88,12 11,56 2,91 9,94 24,31 22,83 83,03 77,98 13,87 1,75 8,28 24,24 17,63 82,78 60,19 13,87 1,75 5,97 68 1300/1000/1530
415/3/50 Pa
380- 125
UAT150CGXY1 12.51 2170 4600 43,96 32,53 150,12 111,09 13,07 3,36 11,49 39,21 30,19 133,90 103,10 15,45 1,95 9,72 35,70 31,27 121,92 106,79 15,11 2,36 8,07 66 1965/1390/1630
415/3/50 Pa
R-22 380- 150
UAT180CGXY1 16.04 3066 6500 56,36 41,71 192,47 142,44 16,92 3,33 11,38 50,85 38,65 173,65 131,99 20,32 1,90 9,47 46,30 41,65 158,11 142,23 19,87 2,33 7,96 68 1965/1390/1630
415/3/50 Pa
380- 200
UAT240CGXY1 21.27 3726,5 7900 74,74 57,55 255,24 196,53 23,00 3,25 11,10 67,41 50,56 230,21 172,66 28,27 1,79 9,03 61,38 54,48 209,61 186,05 27,64 2,22 7,58 68 1965/1690/1905
415/3/50 Pa
380- 250
UAT300CGXY1 26.22 4104 8700 92,12 66,33 314,59 226,52 28,36 3,25 11,09 83,47 62,60 285,05 213,78 33,40 1,87 9,42 76,01 67,47 259,57 230,41 32,66 2,33 7,95 73 2410/1650/2030
415/3/50 Pa
380- 300
UATC10AMY1 27.80 5200 11024 97,69 80,78 333,61 275,86 39,87 2,45 8,37 85,00 67,47 290,28 230,41 47,84 1,78 6,97 79,08 50,97 270,06 174,06 47,84 1,65 5,64 80 2252/1974/3180
415/3/50 Pa
380- 300
UATC12AMY1 34.10 5900 12508 119,82 93,64 409,18 319,77 46,80 2,56 8,74 92,10 75,59 314,51 258,15 56,16 1,64 7,29 89,64 58,47 306,13 199,66 56,16 1,60 5,45 80 2252/1974/3180
415/3/50 Pa
380- 150 Power
UATYQ250CY1 7.78 1557 3301 27,34 21,87 93,37 74,69 8,14 3,36 11,47 23,88 19,68 81,55 67,21 9,76 2,45 9,57 22,07 18,98 75,37 64,82 9,61 2,30 7,84 1638/1150/2063
415/3/50 Pa -82
380- 150 Power
UATYQ350CY1 10.13 2028 4299 35,58 28,82 121,51 98,42 10,78 3,30 11,27 31,08 25,94 106,14 88,59 12,63 2,46 9,62 28,72 25,05 98,08 85,55 12,44 2,31 7,88 2209/1028/2113
415/3/50 Pa -83
380- 150 Power
UATYQ450CY1 12.73 2665 5650 44,72 36,67 152,72 125,23 13,04 3,43 11,71 39,07 33,00 133,42 112,70 15,63 2,50 9,77 36,09 31,82 123,25 108,67 15,69 2,30 7,86 2209/1130/2113
415/3/50 Pa -83
R-410A 380- 200 Power
UATYQ550CY1 15.85 3160 6699 55,69 46,78 190,18 159,75 16,74 3,33 11,36 48,65 42,10 166,14 143,77 20,06 2,43 9,48 44,95 40,60 153,50 138,65 19,76 2,27 7,77 2209/1048/2670
415/3/50 Pa -87
380- 200 Power
UATYQ600CY1 19.02 3443 7299 66,82 52,79 228,19 180,28 19,65 3,40 11,61 58,37 47,51 199,33 162,25 23,55 2,48 9,69 53,93 45,81 184,17 156,44 23,20 2,32 7,94 2209/1302/2670
415/3/50 Pa -90
380- 200 Power
UATYQ700CY1 20.66 3443 7299 72,60 59,53 247,93 203,29 21,61 3,36 11,47 63,42 53,58 216,58 182,98 25,90 2,45 9,57 58,60 51,66 200,12 176,42 25,51 2,30 7,84 2209/1454/2670
415/3/50 Pa -90

Q U I C K S E L E C T I O N G U I D E
16 17
AIR CONDITIONING

You breathe 22,000 times a day.


What do you take in?
Main features of the Air Purifier:
Removes 99% virus and bacteria
Eliminates dust and sand particles
Destroys 99.6% of allergy
Odours neutralization
Ultra quiet operation (16dBA)
Portable (8.5 KG)
No need of installation
Easy maintenance
Economical
2

AP
MC70L
Applicable room area Up to 46 m 2

Power supply 1 phase 220-240 / 220-230 V

Color White

Dimensions HxWxD mm 576 x 403 x 241

Weight Kg 8.5

Convenient functions O timer, Child lock, display adjustment

Mode Quiet Low Normal High Turbo

Airflow (I/S) 15.1 36.6 58.3 79.9 116.6

Power consumption W 7.0 10.0 16.0 26.0 65.0

Sound pressure dB(A) 16.0 24.0 32.0 39.0 48.0

Sold separate Replacement pleated filter KAC017A4E Set of 5

19
AIR CONDITIONING

VRV III Systems


VRV
VRV-III Air Cooled Outdoor units 22-23
VRV-III Water Cooled Outdoor units 24
Ducted Indoor units 25
Cassette Indoor units 26
Wall Mounted units 27

21
VRV-III SYSTEMS
AIR CONDITIONING
Air Cooled Outdoor units
Power Supply: 3Phase / 50Hz / 380-415 Volt

Daikin High Ambient Units Daikin High Ambient Units with ECO Spray option Daikin High Ambient Units (Standard/w ECO Spray Option)
Daikin VRV Nom Cooling Capacity Cooling Capacity at 46º C Max. Power Input EER Cooling Capacity at 46º C Power Input EER Height Width Depth Sound Pressure* Weight
Outdoor model
RXYQ Series (kW) at 35º C (TR) at 35º C (kW) (TR) (kW) at 46º C at 35º C at 46º C (kW) (TR) (kW) (W/W) mm mm mm dBA Kg
8 HP 22.4 6.4 17.7 5.0 5.6 4.3 3.2 21.5 6.1 5.7 3.77 1680 930 765 60 187

10 HP 28 8.0 24.1 6.9 8.93 3.8 2.7 27.8 7.9 8.72 3.19 1680 1240 765 65 280

12 HP 33.5 9.5 27.2 7.7 9.93 3.8 2.7 33.3 9.5 10.43 3.19 1680 1240 765 65 281

16 HP 44.8 12.7 35.4 10.1 10.5 4.3 3.2 43 12.2 11.4 3.77 1680 930 + 930 765 63 374

18 HP 50.4 14.3 41.8 11.9 12.7 4.0 2.9 49.3 14.0 14.42 3.42 1680 930 + 1240 765 66 467

20 HP 55.9 15.9 44.9 12.8 14.2 3.9 2.9 53.2 15.1 17.1 3.11 1680 930 + 1240 765 66 468

22 HP 61.5 17.5 51.3 14.6 16.4 3.8 2.7 61.1 17.4 20.86 2.93 1680 1240 + 1240 765 68 561

24 HP 67 19.1 54.4 15.5 19.9 3.8 2.7 66.6 18.9 19.15 3.48 1680 1240 + 1240 765 68 562

26 HP 72.8 20.7 59.5 16.9 20.1 4.1 3.0 72.3 20.6 20.33 3.56 1680 930 + 1240 + 1240 765 67 561

28 HP 78.4 22.3 65.9 18.7 23.5 3.9 2.8 78.9 22.4 23.43 3.37 1680 930 + 1240 + 1240 765 69 747

30 HP 83.9 23.9 69 19.6 24.5 3.9 2.8 84.5 24.0 25.17 3.36 1680 930 + 1240 + 1240 765 69 748

32 HP 89.5 25.4 75.4 21.4 27.8 3.8 2.7 88.9 25.3 27.86 3.19 1680 1240 + 1240 + 1240 765 70 841

34 HP 95 27.0 78.5 22.3 28.8 3.8 2.7 96.6 27.5 30.01 3.22 1680 1240 + 1240 + 1240 765 70 842

36 HP 100.5 28.6 81.6 23.2 29.8 3.8 2.7 99.8 28.4 31.29 3.19 1680 1240 + 1240 + 1240 765 70 843

* Sound pressures are relative value, depending on the distance and acoustic environment values are measured in a semi-anechoic room.
The microphone is located 1m away and above the front side of the outdoor unit.

Q U I C K S E L E C T I O N G U I D E
22 23
VRV-III SYSTEMS
AIR CONDITIONING
Water Cooled Outdoor units Indoor units “M” series Ducted
Power Supply: 3Phase / 50Hz / 380-415 Volt Power Supply: 1 Phase / 50Hz / 220-240 Volt

Max. Cooling Capacity Power Airflow High Dimensions Sound Pressure*


Daikin VRV *Nom Cooling Sound Daikin VRV Weight
Power EER Height Width Depth Weight Input
Outdoor model Capacity Pressure* Ducted model at 27/19º C WB-nominal Low High Nominal High Height x Width x Depth Medium
Input
RWEY Series FXMQ Series
(kW) (TR) (kW) cfm cfm Pa Pa mm dBA Kg
(kW) (TR) (kW) (kW/kW) mm mm mm dBA Kg
20 2.2 0.6 0.049 230 318 50 100 300 x 550 x 700 31 28
8 HP 22.4 6.4 4.55 4.9 9.52 780 550 50 149
25 2.8 0.8 0.049 230 318 50 100 300 x 550 x 700 31 28
10 HP 26.7 7.6 6.03 4.1 9.52 780 550 52 150
32 3.6 1.0 0.053 247 335 50 100 300 x 550 x 700 32 28
16 HP 44.8 12.7 9.1 4.9 12.7 780 + 780 765 53 298
40 4.5 1.3 0.151 388 565 100 160 300 x 700 x 700 37 32
18 HP 49.1 14.0 10.6 4.6 15.9 780 + 780 765 54 299
50 5.6 1.6 0.11 530 636 100 200 300 x 1000 x 700 39 42
20 HP 53.4 15.2 12.1 4.4 15.9 780 + 780 765 55 300
63 7.1 2.0 0.12 565 689 100 200 300 x 1000 x 700 40 42
24 HP 67.2 19.1 13.7 4.9 15.9 780 + 780 + 780 765 55 447
80 9 2.6 0.171 706 883 100 200 300 x 1000 x 700 41 42
26 HP 71.5 20.3 15.1 4.7 19.1 780 + 780 + 780 765 55 448
100 11.2 3.2 0.176 812 1130 100 200 300 x 1400 x 700 41 54
28 HP 75.8 21.6 16.6 4.6 19.1 780 + 780 + 780 765 55 449
125 14 4.0 0.241 989 1377 100 200 300 x 1400 x 700 44 54
30 HP 80.1 22.8 18.1 4.4 19.1 780 + 780 + 780 765 56 450
140 16 4.5 0.461 1130 1624 100 140 300 x 1400 x 700 45 47
* Cooling capacities is based on : indoor temp 27 CDB, 19 WB; Inlet water temprature: 30º C, equivalent refrigerant piping 7.5m; level difference: 0m
200 22.4 6.4 1.294 1766 2048 132 221 400 x 1380 x 1100 48 137
* Sound pressures are relative value, depending on the distance and acoustic environment values are measured in a semi-anechoic room.
The microphone is located 1m away from the front side of the outdoor unit and at the height of 1.5m. 250 28 8.0 1.465 1766 2048 147 270 400 x 1380 x 1100 48 137

* Sound pressures are relative value, depending on the distance and acoustic environment values are measured in a semi-anechoic room.
The microphone is located 1.5m away from the unit.

Q U I C K S E L E C T I O N G U I D E
24 25
VRV-III SYSTEMS
AIR CONDITIONING
Indoor units “F” series Cassette Wall Mounted Units
Power Supply: 1 Phase / 50Hz / 220-240 Volt

Daikin VRV Cooling Capacity Power Airflow ESP Dimensions Sound Pressure* Sound
Cassette Weight Daikin VRV Cooling Capacity Power Airflow ESP Dimensions Sound
at 27º/19º C WB-nominal Input Low High Nom Height x Width x Depth Medium Pressure* Weight
model Cassette Input
FXFQ Series (kW) (TR) (kW) cfm cfm Pa mm dBA Kg model at 27º/19º C WB-nominal Low High Nom Height x Width x Depth Low High
FXFQ Series
25 2.8 0.8 0.033 353 459 - 246 x 840 x 840 28.5 19 (kW) (TR) (kW) cfm cfm Pa mm dBA dBA Kg
32 3.6 1.0 0.033 353 459 - 246 x 840 x 840 28.5 19 20 2.2 0.6 0.016 159 265 - 290 x 795 x 230 29 35 11

40 4.5 1.3 0.047 388 530 - 246 x 840 x 840 29 19 25 2.8 0.8 0.022 176 282 - 290 x 795 x 230 29 36 11

50 5.6 1.6 0.052 388 565 - 246 x 840 x 840 29.5 19 32 3.6 1.0 0.027 194 318 - 290 x 795 x 230 29 37 11

63 7.1 2.0 0.066 477 671 - 246 x 840 x 840 31 22 40 4.5 1.3 0.020 318 424 - 290 x 1050 x 230 34 39 14

80 9 2.6 0.093 530 742 - 246 x 840 x 840 33.5 22 50 5.6 1.6 0.027 424 529 - 290 x 1050 x 230 36 42 14

100 11.2 3.2 0.187 706 1130 - 288 x 840 x 840 39 25 63 7.1 2.0 0.050 494 671 - 290 x 1050 x 230 39 46 14

125 14 4.0 0.209 795 1165 - 288 x 840 x 840 39 25 * Sound pressures are relative value, depending on the distance and acoustic environment values are measured in a semi-anechoic room.
The microphone is located 1.5m away from the unit.
Decoration panel dimensions (HxWxD) shall be 50x950x950 mm.

Q U I C K S E L E C T I O N G U I D E
26 27
Air conditioning AIR CONDITIONING

Applied Systems
AS
Air-Cooled Chillers 30-31-32-33
Air Handling units 34
Fresh Air Handling units 35
Chilled Water Fancoil units 36-37

29
APPLIED SYSTEMS
Air conditioning AIR CONDITIONING
Air Cooled Chillers

Cooling Power Water Sound Operating


Water Flow Height x Width x Length
215 to Capacity Input Pressure Drop Pressure @ 1m Weight
Models EER ESEER IPLV
400 ton -
kW kW L/s kPa dBA mm kg
AWS.221.2.PR-ST 756 267 2.83 4.44 4.78 36.1 50 79.5 2540 x 2285 x 8885 8130
AWS.243.2.PR-ST 816 295 2.77 4.51 4.67 38.9 57 79.5 2540 x 2285 x 8885 8130
AWS.266.2.PR-ST 888 325 2.73 4.43 4.79 42.4 26 79.5 2540 x 2285 x 8885 8700
215 to AWS.290.2.PR-ST 978 358 2.73 4.52 4.69 46.7 51 80 2540 x 2285 x 9785 9330
400 ton
AWS.313.2.PR-ST 1050 392 2.68 4.38 4.73 50.1 58 80.5 2540 x 2285 x 9785 9590
(Premium
Efficiency) AWS.350.2.PR-ST 1158 432 2.68 4.46 4.68 55.3 50 80.4 2540 x 2285 x 11085 10380
AWS.378.2.PR-ST 1260 470 2.68 4.31 4.73 60.1 59 80.5 2540 x 2285 x 11985 10720
AWS.420.2.PR-ST 1334 508 2.63 4.33 4.73 63.6 67 80.8 2540 x 2285 x 11985 10720
AWS.444.2.PR-ST 1407 545 2.58 4.31 4.71 67.1 73 81.1 2540 x 2285 x 11985 10720
AWS.210.2.XE-ST 681 278 2.45 4.02 4.48 32.5 67 79.7 2540 x 2285 x 6185 6240
AWS.230.2.XE-ST 752 302 2.49 4.11 4.48 35.9 47 79.7 2540 x 2285 x 7085 6580
AWS.250.2.XE-ST 800 332 2.41 4.02 4.52 38.2 53 79.7 2540 x 2285 x 7085 6600
AWS.280.2.XE-ST 900 366 2.46 4.12 4.50 42.9 50 80.2 2540 x 2285 x 7985 7600
AWS.300.2.XE-ST 959 404 2.37 4.06 4.44 45.7 56 80.7 2540 x 2285 x 7985 7870
AWS.325.2.XE-ST 1082 434 2.49 4.15 4.50 51.6 38 80.2 2540 x 2285 x 9785 8610
AWS.360.2.XE-ST 1152 479 2.41 4.03 4.47 55 42 80.4 2540 x 2285 x 9785 8630
190 to AWS.385.2.XE-ST 1202 488 2.46 4.27 4.60 57.3 55 80.4 2540 x 2285 x 9785 9890
515 ton
AWS.402.2.XE-ST 1256 532 2.36 4.30 4.71 59.9 63 80.4 2540 x 2285 x 9785 9890
(High
Efficiency) AWS.434.2.XE-ST 1346 574 2.34 4.34 4.81 64.2 67 80.4 2540 x 2285 x 9785 9890
AWS.445.3.XE-ST 1431 603 2.37 4.21 4.58 68.3 51 80.9 2540 x 2285 x 11985 12430
AWS.470.3.XE-ST 1517 640 2.37 4.18 4.59 72.4 57 80.8 2540 x 2285 x 12885 12760
AWS.490.3.XE-ST 1595 673 2.37 4.16 4.51 76.1 56 81 2540 x 2285 x 13785 13140
AWS.515.3.XE-ST 1680 708 2.37 4.16 4.53 80.2 62 81 2540 x 2285 x 14685 13470
AWS.540.3.XE-ST 1723 744 2.32 4.15 4.57 82.2 33 81 2540 x 2285 x 14685 13470
AWS.555.3.XE-ST 1764 783 2.25 4.04 4.42 84.2 34 81 2540 x 2285 x 14685 13470
AWS.570.3.XE-ST 1809 822 2.20 4.02 4.47 86.3 36 81 2540 x 2285 x 14685 13470
AWS.183.2.HA-ST 600 273 2.19 3.77 4.10 28.6 33 81 2540 x 2285 x 5407 5610
AWS.211.2.HA-ST 671 317 2.12 3.94 4.19 32 48 79.5 2540 x 2285 x 5407 5990
AWS.236.2.HA-ST 745 358 2.08 3.91 4.16 35.5 40 79.5 2540 x 2285 x 5407 6010
AWS.260.2.HA-ST 820 382 2.14 3.82 4.22 39.1 49 80.4 2540 x 2285 x 6307 6530
AWS.275.2.HA-ST 875 421 2.08 3.77 4.15 41.7 53 80.6 2540 x 2285 x 6307 6810
AWS.288.2.HA-ST 916 431 2.12 3.85 4.21 43.7 33 80.6 2540 x 2285 x 6307 6810
AWS.303.2.HA-ST 965 454 2.13 3.88 4.16 46 50 80.6 2540 x 2285 x 7207 7250
170 to
490 ton AWS.327.2.HA-ST 1055 485 2.17 3.81 4.19 50.3 59 80.6 2540 x 2285 x 8107 7250
(Standard AWS.358.2.HA-ST 1144 520 2.20 3.97 4.33 54.6 72 80.7 2540 x 2285 x 9007 8280
Efficiency)
AWS.375.2.HA-ST 1200 533 2.25 4.06 4.42 57.3 43 80.7 2540 x 2285 x 9007 8280
AWS.405.2.HA-ST 1260 576 2.19 4.05 4.42 60.1 46 80.7 2540 x 2285 x 9007 8280
AWS.461.3.HA-ST 1433 683 2.10 3.83 4.15 68.4 52 81.1 2540 x 2285 x 11207 11110
AWS.487.3.HA-ST 1537 737 2.08 3.80 4.14 73.3 58 81.2 2540 x 2285 x 11207 11260
AWS.515.3.HA-ST 1609 810 1.99 3.82 4.24 76.8 28 81.5 2540 x 2285 x 11207 12110
AWS.535.3.HA-ST 1691 835 2.03 3.80 4.19 80.7 30 81.9 2540 x 2285 x 12107 12480
AWS.550.3.HA-ST 1735 881 1.97 3.80 4.21 82.8 32 81.9 2540 x 2285 x 12107 12480

Note: EER and ESEER are as per Eurovent guidelines.


Special Chiller selection with heat recovery option is available on request.

Chilled Water In: 12ºC Ambient Temp: 46ºC


Chilled Water OUT: 7ºC POWER SUPPLY 400V/3PH/50HZ

Q U I C K S E L E C T I O N G U I D E
30 31
APPLIED SYSTEMS
Air conditioning AIR CONDITIONING
Air Cooled Chillers

Cooling Power Water Water Sound Operating


Height x Width x Length
215 to Capacity Input Flow Pressure Drop Pressure @ 1m Weight
Models EER ESEER IPLV
400 ton -
kW kW L/s kPa dBA mm kg
McEng Evo.070.2.ClA-ST 228 96.8 2.36 3.6 3.98 10.9 42 77.5 2355 x 2234 x 3138 3000
McEng Evo.078.2.ClA-ST 257 107 2.41 3.64 4 12.3 40 77.5 2355 x 2234 x 4040 3400
McEng Evo.085.2.ClA-ST 281 115 2.44 3.67 4 13.4 43 77.5 2355 x 2234 x 4040 3400
McEng Evo.093.2.ClA-ST 302 126 2.39 3.89 4.08 14.4 40 77.5 2355 x 2234 x 4040 3400
65 to 160 Ton McEng Evo.101.2.ClA-ST 324 138 2.35 3.72 4.07 15.4 44 77.5 2355 x 2234 x 4040 3400
High
McEng Evo.107.2.ClA-ST 349 146 2.39 3.64 4.06 16.7 51 79 2355 x 2234 x 4040 3400
Efficiency
Screw McEng Evo.116.2.ClA-ST 373 155 2.41 3.66 3.98 17.8 56 79 2355 x 2234 x 4040 3400
McEng Evo.134.2.ClA-ST 404 186 2.18 3.88 4.16 19.3 36 79 2223 x 2234 x 4040 3780
McEng Evo.149.2.ClA-ST 471 208 2.26 4.1 4.83 22.5 52 79 2223 x 2234 x 4940 4940
McEng Evo.164.2.ClA-ST 512 227 2.25 4.09 4.83 24.4 46 79 2223 x 2234 x 4940 4940
McEng Evo.177.2.ClA-ST 552 247 2.24 3.88 4.61 26.4 31 79 2223 x 2234 x 4940 4940
McEng Evo.053.2.HA-ST 170 92.4 1.84 3.12 3.56 8.1 25 77 2223 x 2234 x 2239 2500
McEng Evo.057.2.HA-ST 183 90.3 2.02 3.24 3.74 8.7 19 77 2223 x 2234 x 2239 2500
McEng Evo.065.2.HA-ST 207 99.1 2.09 3.38 3.77 9.9 37 77 2223 x 2234 x 3339 2960
McEng Evo.071.2.HA-ST 227 109 2.08 3.24 3.66 10.8 42 77 2223 x 2234 x 3339 2960
McEng Evo.076.2.HA-ST 241 117 2.07 3.35 3.74 11.5 43 77 2223 x 2234 x 3339 2960
McEng Evo.081.2.HA-ST 255 125 2.05 3.33 3.73 12.2 48 77 2223 x 2234 x 3339 2960
50 to 157 Ton McEng Evo.088.2.HA-ST 270 135 2.01 3.33 3.72 12.9 52 77 2223 x 2234 x 3339 2960
Standard
McEng Evo.095.2.HA-ST 300 144 2.08 3.3 3.64 14.3 48 77 2223 x 2234 x 4040 3300
Efficinecy
Screw McEng Evo.107.2.HA-ST 355 156 2.28 3.66 3.99 17 62 79 2223 x 2234 x 4040 3300
McEng Evo.119.2.HA-ST 359 174 2.07 3.64 4 17.1 35 77 2223 x 2234 x 4040 3447
McEng Evo.128.2.HA-ST 389 185 2.1 3.73 4.05 18.5 41 77.5 2223 x 2234 x 4040 4112
McEng Evo.134.2.HA-ST 419 199 2.1 3.75 3.99 20 46 77.5 2223 x 2234 x 4940 4526
McEng Evo.149.2.HA-ST 445 215 2.07 3.7 4.1 21.2 39 77.5 2223 x 2234 x 4940 4526
McEng Evo.156.2.HA-ST 483 229 2.11 3.77 4.18 23.1 45 79 2223 x 2234 x 4940 4526
McEng Evo.167.2.HA-ST 526 245 2.15 3.85 4.5 25.1 43 79.5 2223 x 2234 x 4940 4526
ACZC.049.2.A.XE-ST 146 65.6 2.22 4.03 4.56 7 18 72.4 2271 x 1224 x 4413 1700
ACZC.055.2.A.XE-ST 167 75.3 2.21 4.25 4.76 8 19 74.4 2271 x 1224 x 4413 1973
ACZC.062.2.A.XE-ST 190 85.7 2.21 4.11 4.67 9 25 75 2271 x 1224 x 5313 2225
ACZC.070.2.A.XE-ST 211 94.4 2.23 4.28 4.7 10.1 31 75.5 2271 x 1224 x 5313 2353
ACZC.091.2.A.XE-ST 270 123 2.18 4.16 4.67 12.9 16 76 2271 x 1224 x 6213 2514
ACZC.101.2.A.XE-ST 303 140 2.16 4.17 4.64 14.4 17 76 2271 x 1224 x 6213 2672

40 to 165 Ton ACZC.093.2.A.XE-ST 270 123 2.18 4.43 4.6 12.9 16 76.8 2221 x 2258 x 3210 2514
Scroll ACZC.103.2.A.XE-ST 303 140 2.16 4.46 4.8 14.4 17 76.8 2221 x 2258 x 3210 2772
ACZC.114.2.A.XE-ST 345 156 2.21 4.39 4.72 16.4 22 77.9 2221 x 2258 x 4110 2784
ACZC.121.2.A.XE-ST 366 164 2.23 4.42 4.65 17.5 21 78.3 2221 x 2258 x 4110 2891
ACZC.129.2.A.XE-ST 389 175 2.22 4.37 4.6 18.5 21 78.6 2221 x 2258 x 4110 2907
ACZC.149.2.A.XE-ST 453 206 2.2 4.55 4.95 21.6 30 77.7 2221 x 2258 x 5010 3615
ACZC.173.2.A.XE-ST 517 238 2.17 4.5 4.82 24.7 32 78.7 2221 x 2258 x 5010 3727
ACZC.192.2.A.XE-ST 577 261 2.21 4.46 4.68 27.5 40 79.4 2221 x 2258 x 5910 4115

Note: EER and ESEER are as per Eurovent guidelines.


Special Chiller selection with heat recovery option is available on request.

Chilled Water In: 12ºC Ambient Temp: 46ºC


Chilled Water OUT: 7ºC POWER SUPPLY 400V/3PH/50HZ

MCQUAY participates in the ECC programme for Air Handling Unit; Check ongoing of certificte online: or use:

Q U I C K S E L E C T I O N G U I D E
32 33
APPLIED SYSTEMS
Air conditioning AIR CONDITIONING
Air Handling Units Fresh Air Handling Units

UNIT MODEL / GENERAL FAN COOLING COIL UNIT MODEL / GENERAL SUPPLY FAN EXTRACT FAN HEAT RECOVERY WHEEL COOLING COIL
Water Extract Extract Side Supply Side Water
Supply Motor Total Sensible Entering Leaving Air Water Supply Motor Motor Total Sensible Air On Air Water
Height x Width x Depth Weight ESP Pressure Air Height x Width x Depth Weight ESP ESP Pressure
Sl No Model Name Air Flow Power Capacity Capacity Air Temp Temp Flow Sl Model Air Flow Power Power Air On Air Air On Air Capacity Capacity DBT/WBT DBT/WBT Flow
Drop Flow Drop
No Name DBT/WBT DBT/WBT DBT/WBT DBT/WBT
m 3/hr mm kg Pa kW kW kW DB/WB (°C) DB/WB (°C) L/s kPa
m3/hr m3/hr mm kg Pa kW Pa kW ºC ºC ºC ºC kW kW ºC ºC L/s kPa
1 STD 3 2000 720 x 860 x 2340 160 500 1.1 8.7 7.8 24.4/17.2 13.0/12.5 0.23 37
1 STD 9 5000 4500 1760 x 1310 x 3530 585 500 3.0 500 2.2 24.0/17.1 41.3/25.8 46.0/29.0 30.5/22.4 48.7 29.7 30.5/22.4 13.0/13.0 1.29 44
2 STD 7 4000 840 x 1150 x 2660 233 500 2.2 17.4 15.5 24.4/17.2 13.0/12.5 0.46 46
2 STD 11 7000 6300 2100 x 1410 x 3875 771 500 4.0 500 3.0 24.0/17.1 40.6/25.2 46.0/29.0 31.1/23.0 73.3 43.3 31.1/23.0 13.0/13.0 1.94 37
3 STD 10 6000 1010 x 1410 x 2710 286 500 3.0 26.0 23.1 24.4/17.2 13.0/12.5 0.69 25
3 STD 12 9000 8100 2300 x 1510 x 3980 823 500 5.5 500 4.0 24.0/17.1 40.4/25.0 46.0/29.0 31.4/23.2 96.7 56.1 31.4/23.2 13.0/13.0 2.56 48
4 STD 12 8000 1150 x 1510 x 3000 374 500 4.0 35.2 31.0 24.4/17.2 13.0/12.4 0.93 31
4 STD 14 11000 9900 2620 x 1760 x 4335 1079 500 5.5 500 4.0 24.0/17.1 41.1/25.6 46.0/29.0 30.7/22.6 109.7 65.8 30.7/22.6 13.0/13.0 2.91 45
5 STD 13 10000 1220 x 1660 x 3070 420 500 5.5 43.6 38.8 24.4/17.2 13.0/12.5 1.16 34
5 STD 14 13000 11700 2800 x 1760 x 4415 1112 500 7.5 500 5.5 24.0/17.1 40.4/25.0 46.0/29.0 31.4/23.2 139.7 81.0 31.4/23.2 13.0/13.0 3.70 34
6 STD 14 12000 1400 x 1760 x 3140 488 500 5.5 53.3 46.4 24.4/17.2 13.0/12.4 1.41 36
6 STD 15 15000 13500 2920 x 2010 x 4640 1307 500 11.0 500 5.5 24.0/17.1 40.9/25.5 46.0/29.0 30.9/22.7 152.5 91.5 30.9/22.7 13.0/13.0 4.04 33
7 STD 14 14000 1400 x 1760 x 3240 507 500 7.5 61.0 54.3 24.4/17.2 13.0/12.5 1.62 46
7 STD 16 20000 18000 3170 x 2310 x 4860 1641 500 11.0 500 7.5 24.0/17.1 41.1/25.6 46.0/29.0 30.8/22.6 200.8 120.5 30.8/22.6 13.0/13.0 5.32 34
8 STD 15 16000 1520 x 2010 x 3310 590 500 7.5 70.8 61.6 24.4/17.2 13.0/12.4 1.88 36
8 STD 17 25000 22500 3430 x 2610 x 5210 2015 500 15.0 500 11.0 24.0/17.1 41.1/25.6 46.0/29.0 30.7/22.6 249.1 151.9 30.7/22.6 13.0/13.0 6.61 39
9 STD 16 18000 1520 x 2010 x 3560 632 500 11.0 78.6 69.9 24.4/17.2 13.0/12.5 2.08 44
9 STD 18 30000 27000 3680 x 2710 x 5630 2361 500 15.0 500 11.0 24.0/17.1 40.1/25.3 46.0/29.0 31.1/22.9 313.4 184.9 31.1/22.9 13.0/13.0 8.31 30
10 STD 16 20000 1650 x 2310 x 3560 738 500 11.0 89.1 77.5 24.4/17.2 13.0/12.4 2.36 41
10 STD 19 40000 36000 4180 x 3060 x 5990 3088 500 22.0 500 15.0 24.0/17.1 40.8/25.3 46.0/29.0 31.0/22.9 413.7 244.1 31.0/22.9 13.0/13.0 10.97 40
11 STD 17 25000 1780 x 2610 x 3760 885 500 11.0 111.3 96.9 24.4/17.2 13.0/12.4 2.95 48
11 STD 20 50000 45000 4440 x 3360 x 6700 4113 500 30.0 500 18.5 24.0/17.1 40.5/25.1 46.0/29.0 31.3/23.1 532.0 313.9 31.3/23.1 13.0/13.0 14.11 29
12 STD 18 30000 1900 x 2710 x 3980 1022 500 15.0 132.4 116.5 24.4/17.2 13.0/12.4 3.51 40
12 STD 23 70000 63000 4840 x 4550 x 6890 5882 500 37.0 500 22.0 24.0/17.1 40.7/25.6 46.0/29.0 31.1/22.6 704.2 429.6 31.1/22.6 13.0/13.0 18.68 41
13 STD 19 40000 2090 x 3060 x 4220 1380 500 18.5 171.9 154.8 24.4/17.2 13.0/12.5 4.56 23
13 STD 26 90000 81000 5490 x 5500 x 8480 8396 500 55.0 500 30.0 24.0/17.1 40.5/25.1 46.0/29.0 31.3/23.1 968.6 561.8 31.3/23.1 13.0/12.9 25.69 46
14 STD 21 55000 2410 x 3800 x 4470 1785 500 22.0 242.1 213.1 24.4/17.2 13.0/12.4 6.42 30
14 STD 26 100000 90000 5620 x 5500 x 8770 8650 500 55.0 500 37.0 24.0/17.1 40.0/24.7 46.0/29.0 31.7/23.4 1109.4 632.4 31.7/23.4 13.0/13.0 29.43 23
15 STD 23 70000 2430 x 4550 x 4970 2226 500 30.0 302.9 269.6 24.4/17.2 13.0/12.5 8.03 25

16 STD 25 80000 2680 x 5000 x 5480 2965 500 37.0 351.1 309.0 24.4/17.2 13.0/12.4 9.31 31 FAHU’s * Heat recovery options available on request
FAHU’s a) Plate heat Ex
17 STD 25 90000 2680 x 5000 x 5580 3016 500 37.0 389.6 346.7 24.4/17.2 13.0/12.5 10.33 28 Max face velocity 2.5 m/s b) Run around coil
Chilled water in/out temperature: 5.50 °C/14.50 °C c) Vertical heat pipe
18 STD 26 100000 2810 x 5500 x 6050 3750 500 45.0 437.8 385.3 24.4/17.2 13.0/12.4 11.61 35 Height indicative above does not include base frame 100mm
Power supply 400V/3Ph/50Hz
19 STD 26 110000 2810 x 5500 x 6150 3855 500 55.0 475.9 423.5 24.4/17.2 13.0/12.5 12.62 41
MECHANICAL CHARACTERISTIC (EN1886)
20 STD 27 120000 2890 x 6100 x 6150 4142 500 55.0 504.5 464.1 24.4/17.2 13.0/12.7 13.38 21
EUROVENT AHU Energy
Casing Strength Casing air leakage Thermal Transmit Thermal bridging
Efficiency Class
AHU’s
Max face velocity 2.5 m/s D1 L1/L1 T3 TB2 B
Chilled water in/out temperature: 5.50 °C/14.50 °C MCQUAY participates in the ECC programme for Air Handling Unit; Check ongoing of certificte online: or use:
Height indicative above does not include base frame 100mm
Power supply 400V/3Ph/50Hz
UNIT CONFIGURATION
MECHANICAL CHARACTERISTIC (EN1886)

EUROVENT AHU Energy


Casing Strength Casing air leakage Thermal Transmit Thermal bridging
Efficiency Class
U

D1 L1/L1 T3 TB2 A
MCQUAY participates in the ECC programme for Air Handling Unit; Check ongoing of certificte online: or use:

UNIT CONFIGURATION

Q U I C K S E L E C T I O N G U I D E
34 35
APPLIED SYSTEMS
Air conditioning AIR CONDITIONING
Fan Coil Units Fan Coil Units

Ceiling Concealed Chilled Water Fan Coil Units Ceiling Convertible Chilled Water Fan Coil Units

Power Speed ESP Air DB Air WB Water in Water out Power Speed ESP Air DB Air WB Water in Water out

220V/1PH/50HZ Medium 75 Pa 24.2°C 17.5°C 5.5°C 14.5°C 220V/1PH/50HZ Medium 0 Pa 24.2°C 17.5°C 5.5°C 14.5°C

Cooling Capacity Water Dimension Cooling Capacity Water Dimension


Water Water
Airflow Pressure Airflow Pressure
Flow Flow
Model Total Sensible Drop Length Width Height Model Total Sensible Drop Length Width Height

m3/hr kW kW m3/hr kPa mm mm mm m3/hr kW kW m3/hr kPa mm mm mm

MCW200DA 277 1.6 1.0 0.15 3 677 530 243 MCM20DW 858 4.6 3.4 0.44 24 1214 670 214

MCW300DA 359 2.2 1.5 0.21 5 827 530 243 MCM25DW 1053 5.2 3.7 0.50 25 1214 670 214

MCW400DA 538 3.1 2.1 0.29 12 927 530 243 MCM30DW 1167 6.3 4.6 0.61 21 1214 670 214

MCW500DA 715 3.6 2.7 0.34 5 997 530 243 MCM40DW 1543 7.8 6.4 0.74 10 1714 670 249

MCW600DA 773 4.1 3.0 0.39 7 1097 530 243 MCM50DW 1738 11.7 8.0 1.12 17 1714 670 249

MCW800DA 1166 6.2 4.7 0.59 9 1427 530 243

MCW900DA 1257 6.8 5.1 0.65 12 1537 530 243

MCW1000DA 1425 7.5 5.7 0.72 10 1727 530 243


Ceiling Convertible Chilled Water Fan Coil Units
MCW1200DA 1987 9.5 7.7 0.90 13 1427 600 297
Power Speed ESP Air DB Air WB Water in Water out
MCW1400DA 2143 10.1 8.3 0.97 15 1527 600 297
220V/1PH/50HZ Medium 0 Pa 27°C 19.5°C 5.5°C 14.5°C
MCW1600DA 2736 12.3 10.4 1.17 18 1827 600 297

Cooling Capacity Water Dimension


Water
Airflow Pressure
Flow
Ceiling Concealed Chilled Water Fan Coil Units Model Total Sensible Drop Length Width Height

m3/hr kW kW m3/hr kPa mm mm mm


Power Speed ESP Air DB Air WB Water in Water out
MCM20DW 858 5.6 3.9 0.54 28 1214 670 214

220V/1PH/50HZ Medium 75 Pa 27°C 19.5°C 5.5°C 14.5°C MCM25DW 1053 6.3 4.2 0.61 31 1214 670 214

Cooling Capacity Water Dimension MCM30DW 1167 7.7 5.2 0.73 26 1214 670 214
Water
Airflow Pressure MCM40DW 1543 9.9 7.4 0.95 14 1714 670 249
Flow
Model Total Sensible Drop Length Width Height
MCM50DW 1738 14.2 9.3 1.36 21 1714 670 249

m /hr
3
kW kW m /hr
3
kPa mm mm mm

MCW200DA 277 2.1 1.2 0.20 5 677 530 243

MCW300DA 359 2.9 1.7 0.27 9 827 530 243

MCW400DA 538 4.1 2.5 0.39 19 927 530 243

MCW500DA 715 4.8 3.2 0.45 9 997 530 243

MCW600DA 773 5.4 3.5 0.52 12 1097 530 243

MCW800DA 1166 8.3 5.5 0.79 15 1427 530 243

MCW900DA 1257 9.0 6.0 0.86 19 1537 530 243

MCW1000DA 1425 9.9 6.7 0.94 16 1727 530 243

MCW1200DA 1987 12.6 9.1 1.20 21 1427 600 297

MCW1400DA 2143 13.2 9.7 1.26 24 1527 600 297

MCW1600DA 2736 16.2 12.3 1.54 31 1827 600 297

Q U I C K S E L E C T I O N G U I D E
36 37
NOTES
AIR CONDITIONING

Q U I C K S E L E C T I O N G U I D E
38 39
www.daikinme.com
DAIKIN MCQUAY MIDDLE EAST
PO. Box 18674,
Jebel Ali Free Zone, Dubai - U.A.E. AIR CONDITIONING
Tel: +971 (0) 4 8110 300
Fax: +971 (0) 4 8110 311

DAME14-001

You might also like