Ed43 441
Ed43 441
ENGINEERING DATA
Air Cooled
Single Packaged Air Conditioners
Roof Top Type
Series
UATY - K
Heat Pump
ED43-441
Air Cooled
Single Packaged
Roof Top Type
UATY06K
UATY08K
UATY09K
UATY10K
UATY06K
UATY12K
UATY15K
UATY18K
UATY21K
UATY08K
UATY09K
UATY10K
UATY12K
UATY15K
UATY18K
UATY21K
Remote Controller
KRC17-2B
ED43-441
1. Features ..................................................................................................3
1.1 Features ...................................................................................................3
3. Specifications ..........................................................................................7
3.1 50Hz .........................................................................................................7
3.2 60Hz .........................................................................................................9
4. Dimensions ...........................................................................................11
4.1 Dimensions / Service Space ..................................................................11
5. Piping Diagrams....................................................................................16
5.1 Piping Diagrams .....................................................................................16
6. Wiring Diagrams....................................................................................19
6.1 Y1, YAL Models......................................................................................19
6.2 TAL Models ............................................................................................22
9. Operation Limit......................................................................................44
9.1 Operation Limit .......................................................................................44
11.Electric Characteristics..........................................................................47
11.1 Electric Characteristics...........................................................................47
14.Installation .............................................................................................52
14.1 Installation Manual .................................................................................52
14.2 How to Install Pulley ...............................................................................62
14.3 Cautions .................................................................................................63
16.Wiring Modification................................................................................76
16.1 Wiring for Operating Signal and Alarm...................................................76
ED43-441
Features
1. Features
1.1
Features
Model Range
UATY06K~21K
Operation Range
(Outdoor Temp)
5CDB~52CDB Cooling
-10CWB~15.5CWB Heating
Capacity Range
Installation
Easy to install on rooftop or veranda, requiring only ducting, power line and drain piping.
Casing
The casing is made of paintable galvanized steel plate and treated against rust. Since the unit is installed
outdoors, the casing is completely weather-proof.
Scroll Compressor
Daikins innovative scroll compressor is 10% lighter and 30% smaller than equivalent conventional
reciprocating compressors. This makes this series among the industrys most lightweight and compact,
than previous models. Also, since the scroll compressor generates less vibration, this series has greatly
improved its durability and achieved the industrys lowest operation sound. Moreover, the installation of the
latest scroll compressor has further improved system efficiency. The recycling guard timer prevents
frequent ON/OFF switching, and protects the compressor against overloads due to short cycling.
<NEW>
Central Remote
Control with VRV
By adopting Central Control Adaptor Kit (DTA107A55), you can control UATY series using like VRV such
as Central Remote Controller (DCS302C61), Schedule Timer (DST301B61) and Unified ON/OFF
Controller (DCS301B61).
With these controller the following functions are available:
1. Operation and Monitoring ON/OFF
2. Setting and Monitoring of Operation Mode
3. Temperature Setting
4. Forced Shut Down
5. Group Control
6. Indication of Alarm
7. Setting of Timer
8. Setting and Cleaning Sign of Air Filter
9. ON/OFF Group Control
For the detail, refer to 15.4 Details of DTA107A55 (Central Control Adaptor Kit).
Features
ED43-441
Remote Controller
(Optional)
The Microcomputer
Type Deicer
The microcomputer type deicer is capable of sensing both refrigerant and outdoor temperature with its
highly sensible dual thermistors, and eliminates such waste as that defrosting is accomplished although the
outdoor coil is frosted only thinly when outdoor temperature is low.
Thus, the microcomputer type deicer not only saves unnecessary power, but also ensures constant
comfortable heating. In addition, the deicer is capable of selecting defrosting cycles, longer or shorter
depending on the volume of frost on the outdoor coil.
Evaporator and
Condenser
Efficient cross fin coils are used: the unique waffle louver fins*1 maximize heat exchange efficiency, while
the Hi-XA copper tube*2, featuring an inner spiral groove, fully exploits refrigerant turbulence to help
increase heat exchange efficiency. The result is substantial energy savings.
The fin of the heat exchanger is finished with special acrylic coating (PE fin), and highly resistant to
corrosion due to acid rain, sea breeze, etc.
Waffle louver fins
Hi-XA tube
U.S. PAT.
*1 : No.4,434,844
*2 : No.4,480,684
Heating Capacity at
Low Outdoor
Temperature
The heating capacities tabulated do not include capacity drop during frosting period and defrosting
operation.
Namely, the integrated heating capacities in consideration with capacity drop during frosting period and
defrosting operation are obtained from the following formula.
Integrated heating capacity = (Capacity tabulated) X
(Integrated correction factor during frosting period) (kcal/h)
Correction Factor
for Obtaining
Integrated Heating
Capacity
Note:
-6
-4
-2
0.95
0.93
0.87
0.81
0.83
0.89
1.00
Integrated heating capacity means that heating capacity during one cycle (between defrosting period and
defrosting period) as shown on Page 5, which is integrated and converted to heating capacity per hour.
ED43-441
Features
Note:
During defrosting in the zone marked with 1, the unit is under cooling operation, discharging the cool air
from the indoor side.
It is advisable to attach a duct heater on the spot to heat the air for constant heating or make heating
temperature higher.
Defrosting time changes depending on the outdoor air temperature. At normal conditions, it takes 6~8
minutes or at most 10 minutes before heating operation restarts.
In case the surface of the heat exchanger is covered with snow, heating capacity drops temporarily
although it differs with outdoor temperature (CWB), relative humidity (RH) and frosting volume.
Power Supply
ED43-441
2. Power Supply
2.1
Power Supply
Symbol
Y1
Model
UATY06KY1
UATY08KY1
Power Supply
3 380~415V 50Hz
(4 wires)
UATY09KY1
UATY10KY1
UATY15KY1
UATY18KY1
UATY21KY1
TAL
UATY06KTAL
UATY08KTAL
3 220V 60Hz
(3 wires)
UATY09KTAL
UATY12KTAL
UATY15KTAL
UATY18KTAL
UATY21KTAL
YAL
UATY06KYAL
UATY08KYAL
3 380V 60Hz
(4 wires)
UATY09KYAL
UATY12KYAL
UATY15KYAL
UATY18KYAL
UATY21KYAL
ED43-441
Specifications
3. Specifications
3.1
50Hz
Model
UATY06KY1
*1 Cooling Capacity
USRT
kW
Btu/h
kcal/h
kW
Btu/h
kW
Btu/h
kcal/h
%
UATY08KY1
UATY09KY1
UATY10KY1
6
7.5
9
22.0
26.4
31.4
75,000
90,000
107,200
18,900
22,700
27,000
*2 Cooling Capacity
(19.8)
(23.8)
(28.3)
(67,600)
(81,200)
(96,600)
*3 Heating Capacity
23.0
26.9
32.1
78,600
91,700
109,600
19,800
23,100
27,600
Capacity Steps
100-0
100-0
100-0
Connections Drain Piping
FPS3/4B
FPS3/4B
FPS3/4B
Ducting Return (HW)
mm
488917
488917
576952
Supply (HW)
mm
297878
297878
297878
Casing / Color
Paintable Galvanized Steel Plate / Ivory White
Indoor Coil
Type
Cross Fin Coil (Waffle Louver Fins and Hi-XA Tubes)
RowsStagesFin Pitch
2242.0
3222.0
3222.0
3262.0
Face Area
m
0.491
0.443
0.443
0.543
Indoor Fan
Type
Sirocco Fan
Drive
Belt Drive
Air Flow Rate
m/min
52
68
68
83
cfm
1,840
2,400
2,400
2,930
9
10
10
10
Ext. Static Pressure
mmH2O
Motor Output
kW
0.75
1.5
1.5
1.5
Compressor Type
Hermetically Sealed Scroll Type
Model
JT200B-YE
JT212D-P1YE
JT300D-P1YE
JT335D-P1YE
Motor Output
kW
4.5
5.5
7.5
9.0
Refrigerant
Model
R22
No. of Refrigerant Circuits
1
1
1
1
Charge
kg
3.2
4.4
4.4
5.5
Refrigerant
Model
SUNISO 4GSDID-K
Oil
Charge
L
1.6
2.7
2.7
2.7
Outdoor Coil Type
Cross Fin Coil (Waffle Louver Fins and Hi-XA Tubes)
RowsStagesFin Pitch
2502.0
2402.0
2402.0
2502.0
Face Area
m
1.26
1.57
1.57
1.97
Refrigerant Control
Capillary Tube
Outdoor Fan Type
Propeller
Model
P52H11S
P52H11S
P52H11S
P52H11S
Air Flow Rate
m/min
90
150
150
175
cfm
3,177
5,295
5,295
6,177
Motor Output
W
280
230+190
230+190
230+190
Safety Devices
Thermal Protector for Compressor and Outdoor Fan Motor. High Pressure Switch
Over Current Relay (Compressor and Indoor Fan Motor). Reverse Phase Protector. Fuse.
Dimensions HWD
mm
1,4906901,750
1,2701,6001,280
1,2701,6001,280
1,4901,6001,280
Weight
kg
230
326
329
344
Drawing No.
C : 4D014885
C : 4D014886
Note:
5
17.7
60,300
15,200
(15.5)
(52,900)
18.1
62,000
15,600
100-0
FPS3/4B
530932
270739
1. The above data marked with *1 are rated in accordance with 27CDB (80FDB) 19.5CWB (67FWB)
indoor temp. and 35CDB (95FDB) outdoor temp. at HI fan speed, 380V.
Above cooling capacities do not include indoor fan motor heat. (Gross)
2. The above data marked with *2 are rated in accordance with 29CDB (84FDB) 19CWB (66FWB) indoor
temp. and 46CDB (115FDB) outdoor temp. at HI fan speed, 380V.
3. The above data marked with *3 are rated in accordance with 20CDB (68FDB) indoor temp, and 7CDB /
6CWB (45FDB / 43FWB) outdoor temp.
Above heating capacities include indoor fan motor heat. (Net)
4. Operative up to 52C in cooling, down to -10C in heating.
5. The figures of *2 are reference value.
Conversion Formulae
kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3
Specifications
ED43-441
Model
UATY15KY1
*1 Cooling Capacity
USRT
kW
Btu/h
kcal/h
kW
Btu/h
kW
Btu/h
kcal/h
%
UATY18KY1
UATY21KY1
15
17.5
52.7
61.6
180,000
210,400
45,300
53,000
*2 Cooling Capacity
(47.5)
(55.5)
(162,100)
(189,400)
*3 Heating Capacity
54.2
62.8
185,000
214,400
46,600
54,000
Capacity Steps
100-50-0
100-50-0
Connections Drain Piping
FPS1B
FPS1B
Ducting Return (HW)
mm
5721,372
7481,372
Supply (HW)
mm
3431,042
3431,042
Casing / Color
Paintable Galvanized Steel Plate / Ivory White
Indoor Coil
Type
Cross Fin Coil (Waffle Louver Fins and Hi-XA Tubes)
RowsStagesFin Pitch
3262.0
3262.0
3342.0
Face Area
m
0.784
0.784
1.024
Indoor Fan
Type
Sirocco Fan
Drive
Belt Drive
Air Flow Rate
m/min
136
136
166
cfm
4,800
4,800
5,860
15
15
15
Ext. Static Pressure
mmH2O
Motor Output
kW
2.2
2.2
3.7
Compressor
Type
Hermetically Sealed Scroll Type
Model
2(JT212D-P1YE)
2(JT300D-P1YE)
2(JT335D-P1YE)
Motor Output
kW
25.5
27.5
29.0
Refrigerant
Model
R22
No. of Refrigerant Circuits
2
2
2
Charge
kg
24.7
24.7
26.0
Refrigerant
Model
SUNISO 4GSDID-K
Oil
Charge
L
22.7
22.7
22.7
Outdoor Coil Type
Cross Fin Coil (Waffle Louver Fins and Hi-XA Tubes)
RowsStagesFin Pitch
2(2402.0)
2(2402.0)
2(2502.0)
Face Area
m
21.57
21.57
21.97
Refrigerant Control
Capillary Tube
Outdoor Fan Type
Propeller
Model
P52H11S
P52H11S
P52H11S
Air Flow Rate
m/min
2150
2150
2175
cfm
25,295
25,295
26,177
Motor Output
W
2(230+190)
2(230+190)
2(230+190)
Safety Devices
Thermal Protector for Compressor and Outdoor Fan Motor. High Pressure Switch.
Over Current Relay (Compressor and Indoor Fan Motor). Reverse Phase Protector. Fuse.
Dimensions
HWD
mm
1,2701,9801,980
1,2701,9801,980
1,4901,9801,980
Weight
kg
650
656
686
Drawing No.
C : 4D014887
Note:
12.5
43.9
150,000
37,800
(39.6)
(135,200)
46.1
157,200
39,600
100-50-0
FPS1B
5721,372
3431,042
1. The above data marked with *1 are rated in accordance with 27CDB (80FDB) 19.5CWB (67FWB)
indoor temp. and 35CDB (95FDB) outdoor temp. at HI fan speed, 380V.
Above cooling capacities do not include indoor fan motor heat. (Gross)
2. The above data marked with *2 are rated in accordance with 29CDB (84FDB) 19CWB (66FWB) indoor
temp. and 46CDB (115FDB) outdoor temp. at HI fan speed, 380V.
3. The above data marked with *3 are rated in accordance with 20CDB (68FDB) indoor temp, and 7CDB /
6CWB (45FDB / 43FWB) outdoor temp.
Above heating capacities include indoor fan motor heat. (Net)
4. Operative up to 52C in cooling, down to -10C in heating.
5. The figures of *2 are reference value.
Conversion Formulae
kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3
ED43-441
3.2
Specifications
60Hz
Model
UATY06KTAL, YAL
*1 Cooling Capacity
USRT
kW
Btu/h
kcal/h
kW
Btu/h
kW
Btu/h
kcal/h
%
UATY08KTAL, YAL
UATY09KTAL, YAL
UATY12KTAL, YAL
6
7.5
10
22.0
26.4
35.1
75,000
90,000
120,000
18,900
22,700
30,200
*2 Cooling Capacity
(19.8)
(23.8)
(31.6)
(67,600)
(81,200)
(107,800)
*3 Heating Capacity
23.0
26.9
36.1
78,600
91,700
123,000
19,800
23,100
31,000
Capacity Steps
100-0
100-0
100-0
Connections Drain Piping
FPS3/4B
FPS3/4B
FPS3/4B
Ducting Return (HW)
mm
488917
488917
576952
Supply (HW)
mm
297878
297878
297878
Casing / Color
Paintable Galvanized Steel Plate / Ivory White
Indoor Coil
Type
Cross Fin Coil (Waffle Louver Fins and Hi-XA Tubes)
RowsStagesFin Pitch
2242.0
3222.0
3222.0
3262.0
Face Area
m
0.491
0.443
0.443
0.543
Indoor Fan
Type
Sirocco Fan
Drive
Belt Drive
Air Flow Rate
m/min
52
68
68
100
cfm
1,840
2,400
2,400
3,530
9
10
10
10
Ext. Static Pressure
mmH2O
Motor Output
kW
0.75
1.5
1.5
1.5
Compressor Type
Hermetically Sealed Scroll Type
Model
TAL
JT190B
JT190B
JT265D-P1
JT335D-P1
YAL
JT190B-YH
JT190B-YH
JT265D-P1YH
JT335D-P1YH
Motor Output
kW
4.5
4.5
7.5
9.0
Refrigerant
Model
R22
No. of Refrigerant Circuits
1
1
1
1
Charge
kg
3.2
4.4
4.4
5.5
Refrigerant
Model
SUNISO 4GSDID-K
Oil
Charge
L
1.6
2.7
2.7
2.7
Outdoor Coil Type
Cross Fin Coil (Waffle Louver Fins and Hi-XA Tubes)
RowsStagesFin Pitch
2502.0
2402.0
2402.0
2502.0
Face Area
m
1.26
1.57
1.57
1.97
Refrigerant Control
Capillary Tube
Outdoor Fan Type
Propeller
Model
P52H11S
P52H11S
P52H11S
P52H11S
Air Flow Rate
m/min
95
160
160
190
cfm
3,353
5,648
5,648
6,707
Motor Output
W
230
230+190
230+190
230+190
Safety Devices
Thermal Protector for Compressor and Outdoor Fan Motor. High Pressure Switch.
Over Current Relay (Compressor and Indoor Fan Motor). Reverse Phase Protector. Fuse.
Dimensions HWD
mm
1,4906901,750
1,2701,6001,280
1,2701,6001,280
1,4901,6001,280
Weight
kg
230
304
328
344
Drawing No.
TAL
C : 4D014888
C : 4D014889
YAL
C : 4D014891
C : 4D014892
Note:
5
17.7
60,300
15,200
(15.5)
(52,900)
18.1
62,000
15,600
100-0
FPS3/4B
530932
270739
1. The above data marked with *1 are rated in accordance with 27CDB (80FDB) 19.5CWB (67FWB)
indoor temp. and 35CDB (95FDB) outdoor temp. at HI fan speed, 380V.
Above cooling capacities do not include indoor fan motor heat. (Gross)
2. The above data marked with *2 are rated in accordance with 29CDB (84FDB) 19CWB (66FWB) indoor
temp. and 46CDB (115FDB) outdoor temp. at HI fan speed, 380V.
3. The above data marked with *3 are rated in accordance with 20CDB (68FDB) indoor temp, and 7CDB /
6CWB (45FDB / 43FWB) outdoor temp.
Above heating capacities include indoor fan motor heat. (Net)
4. Operative up to 52C in cooling, down to -10C in heating.
5. The figures of *2 are reference value.
Conversion Formulae
kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3
Specifications
ED43-441
Model
UATY15KTAL, YAL
*1 Cooling Capacity
USRT
kW
Btu/h
kcal/h
kW
Btu/h
kW
Btu/h
kcal/h
%
UATY18KTAL, YAL
UATY21KTAL, YAL
15
17.5
52.7
61.6
180,000
210,400
45,300
53,000
*2 Cooling Capacity
(47.5)
(55.5)
(162,100)
(189,400)
*3 Heating Capacity
54.2
62.8
185,000
214,400
46,600
54,000
Capacity Steps
100-50-0
100-50-0
Connections Drain Piping
FPS1B
FPS1B
Ducting Return (HW)
mm
5721,372
7481,372
Supply (HW)
mm
3431,042
3431,042
Casing / Color
Paintable Galvanized Steel Plate / Ivory White
Indoor Coil
Type
Cross Fin Coil (Waffle Louver Fins and Hi-XA Tubes)
RowsStagesFin Pitch
3262.0
3262.0
3342.0
Face Area
m
0.784
0.784
1.024
Indoor Fan
Type
Sirocco Fan
Drive
Belt Drive
Air Flow Rate
m/min
136
136
166
cfm
4,800
4,800
5,860
15
15
15
Ext. Static Pressure
mmH2O
Motor Output
kW
2.2
2.2
3.7
Compressor
Type
Hermetically Sealed Scroll Type
Model
TAL
2(JT190B)
2(JT265D-P1)
2(JT300D-P1)
YAL
2(JT190B-YH)
2(JT265D-P1YH)
2(JT300D-P1YH)
Motor Output
kW
24.5
27.5
27.5
Refrigerant
Model
R22
No. of Refrigerant Circuits
2
2
2
Charge
kg
24.7
24.7
26.0
Refrigerant
Model
SUNISO 4GSDID-K
Oil
Charge
L
21.6
22.7
22.7
Outdoor Coil Type
Cross Fin Coil (Waffle Louver Fins and Hi-XA Tubes)
RowsStagesFin Pitch
2(2402.0)
2(2402.0)
2(2502.0)
Face Area
m
21.57
21.57
21.97
Refrigerant Control
Capillary Tube
Outdoor Fan Type
Propeller
Model
P52H11S
P52H11S
P52H11S
Air Flow Rate
m/min
2160
2160
2190
cfm
25,648
25,648
26,707
Motor Output
W
2(230+190)
2(230+190)
2(230+190)
Safety Devices
Thermal Protector for Compressor and Outdoor Fan Motor. High Pressure Switch.
Over Current Relay (Compressor and Indoor Fan Motor). Reverse Phase Protector. Fuse.
Dimensions
HWD
mm
1,2701,9801,980
1,2701,9801,980
1,4901,9801,980
Weight
kg
605
654
686
Drawing No.
TAL
C : 4D014890
YAL
C : 4D014893
Note:
10
12.5
43.9
150,000
37,800
(39.6)
(135,200)
46.1
157,200
39,600
100-50-0
FPS1B
5721,372
3431,042
1. The above data marked with *1 are rated in accordance with 27CDB (80FDB) 19.5CWB (67FWB)
indoor temp. and 35CDB (95FDB) outdoor temp. at HI fan speed, 380V.
Above cooling capacities do not include indoor fan motor heat. (Gross)
2. The above data marked with *2 are rated in accordance with 29CDB (84FDB) 19CWB (66FWB) indoor
temp. and 46CDB (115FDB) outdoor temp. at HI fan speed, 380V.
3. The above data marked with *3 are rated in accordance with 20CDB (68FDB) indoor temp, and 7CDB /
6CWB (45FDB / 43FWB) outdoor temp.
Above heating capacities include indoor fan motor heat. (Net)
4. Operative up to 52C in cooling, down to -10C in heating.
5. The figures of *2 are reference value.
Conversion Formulae
kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3
ED43-441
Dimensions
4. Dimensions
4.1
3D013699A
Unit (mm)
UATY06K
11
Dimensions
ED43-441
12
3D013700A
Unit (mm)
UATY08K
UATY09K
ED43-441
Dimensions
3D013701A
Unit (mm)
UATY10K
UATY12K
13
Dimensions
ED43-441
14
3D014563
Unit (mm)
UATY15K
UATY18K
ED43-441
Dimensions
3D014564
Unit (mm)
UATY21K
15
Piping Diagrams
ED43-441
5. Piping Diagrams
5.1
Piping Diagrams
3D014923A
UATY06K
16
ED43-441
Piping Diagrams
3D014924B
UATY08K
UATY09K
UATY10K
UATY12K
17
Piping Diagrams
ED43-441
3D014925B
UATY15K
UATY18K
UATY21K
18
ED43-441
Wiring Diagrams
6. Wiring Diagrams
6.1
3D014476
UATY06KY1
UATY06KYAL
19
Wiring Diagrams
ED43-441
3D014478
UATY08KY1
UATY08KYAL
UATY09KY1
UATY09KYAL
UATY10KY1
UATY12KYAL
20
ED43-441
Wiring Diagrams
2D014383
UATY15KY1
UATY15KYAL
UATY18KY1
UATY18KYAL
UATY21KY1
UATY21KYAL
21
Wiring Diagrams
6.2
ED43-441
TAL Models
3D014477A
UATY06KTAL
22
ED43-441
Wiring Diagrams
3D014479A
UATY08KTAL
UATY09KTAL
23
Wiring Diagrams
ED43-441
3D014480A
UATY12KTAL
24
ED43-441
Wiring Diagrams
2D014414A
UATY15KTAL
UATY18KTAL
UATY21KTAL
25
Capacity Tables
ED43-441
7. Capacity Tables
7.1
UATY06KY1
Indoor air
AFR(BF) EWB(C) EDB(C)
14.0 20.0
16.0 22.0
18.0 25.0
47
(0.15) 19.0 27.0
19.5 27.0
22.0 30.0
24.0 32.0
14.0 20.0
16.0 22.0
18.0 25.0
52
(0.16) 19.0 27.0
19.5 27.0
22.0 30.0
24.0 32.0
14.0 20.0
16.0 22.0
18.0 25.0
62
(0.18) 19.0 27.0
19.5 27.0
22.0 30.0
24.0 32.0
TC
15.9
16.9
18.0
18.5
18.8
20.3
21.6
16.2
17.2
18.3
18.9
19.2
20.7
21.9
16.6
17.8
18.8
19.4
19.7
21.3
22.6
25
SHC
12.0
12.1
12.8
13.4
13.1
13.4
13.3
12.5
12.5
13.3
14.0
13.6
14.0
13.9
13.3
13.4
14.2
15.0
14.6
15.0
14.9
Symbols:
AFR : Air flow rate
BF : Bypass factor
EWB : Entering wet bulb temp.
EDB : Entering dry bulb temp.
TC : Total cooling capacity
SHC : Sensible heat capacity
: Power input
PI
(Comp.+outdoor fan motor).
PI
4.6
4.7
4.8
4.8
4.8
5.0
5.1
4.6
4.7
4.8
4.8
4.9
5.0
5.2
4.6
4.7
4.8
4.9
4.9
5.1
5.2
TC
15.2
16.3
17.3
17.8
18.1
19.6
20.8
15.5
16.5
17.6
18.2
18.4
19.9
21.1
16.0
17.0
18.1
18.7
19.0
20.4
21.7
(m/min.)
(CWB)
(CDB)
(kW)
(kW)
(kW)
30
SHC
11.7
11.7
12.4
13.1
12.7
13.0
13.0
12.1
12.2
12.9
13.6
13.3
13.6
13.5
12.9
13.0
13.8
14.6
14.2
14.6
14.6
PI
5.0
5.1
5.2
5.2
5.3
5.4
5.6
5.0
5.1
5.2
5.3
5.3
5.5
5.6
5.0
5.2
5.3
5.3
5.4
5.5
5.7
TC
14.6
15.6
16.6
17.1
17.4
18.8
19.9
14.8
15.8
16.9
17.4
17.7
19.1
20.3
15.3
16.3
17.3
17.9
18.1
19.6
20.8
35
SHC
11.3
11.3
12.0
12.7
12.4
12.7
12.6
11.7
11.8
12.5
13.2
12.9
13.2
13.2
12.5
12.6
13.4
14.2
13.8
14.2
14.2
PI
5.4
5.6
5.7
5.8
5.8
5.9
6.1
5.5
5.6
5.7
5.8
5.8
6.0
6.1
5.5
5.6
5.8
5.8
5.9
6.0
6.2
45
SHC
10.5
10.5
11.2
11.9
11.6
11.9
11.8
10.8
10.9
11.7
12.4
12.1
12.4
12.4
11.6
11.7
12.5
13.3
12.9
13.4
13.3
PI
6.5
6.7
6.8
6.9
6.9
7.1
7.2
6.6
6.7
6.8
6.9
6.9
7.1
7.3
6.6
6.7
6.9
7.0
7.0
7.2
7.3
TC
12.4
13.3
14.1
14.6
14.9
16.1
12.6
13.5
14.4
14.8
15.1
16.4
12.9
13.8
14.7
15.2
15.4
16.7
50
SHC
10.0
10.1
10.8
11.5
11.1
11.5
10.4
10.5
11.2
12.0
11.6
12.0
11.1
11.2
12.0
12.8
12.5
12.9
PI
7.2
7.3
7.4
7.5
7.5
7.7
7.2
7.3
7.5
7.5
7.6
7.8
7.2
7.4
7.5
7.6
7.6
7.8
TC
12.4
13.3
14.1
14.6
14.9
16.1
12.6
13.5
14.4
14.8
15.1
16.4
12.9
13.8
14.7
15.2
15.4
16.7
52
SHC
10.0
10.1
10.8
11.5
11.1
11.5
10.4
10.5
11.2
12.0
11.6
12.0
11.1
11.2
12.0
12.8
12.5
12.9
PI
7.2
7.3
7.4
7.5
7.5
7.7
7.2
7.3
7.5
7.5
7.6
7.8
7.2
7.4
7.5
7.6
7.6
7.8
Notes:
1. Direct interpolation is permissible.
Do not extrapolate beyond the Operation Limits.
2.
shows nominal capacities.
3. SHC is based on each EWB and EDB.
SHC*=SHC correction for other dry bulb. (DB*)
=0.02AFR(1-BF)(DB*-EDB)
Add SHC* to SHC.
4. Above cooling capacities do not include indoor fan motor heat.
3D014894A
UATY08KY1
Symbols:
AFR : Air flow rate
BF : Bypass factor
EWB : Entering wet bulb temp.
EDB : Entering dry bulb temp.
TC : Total cooling capacity
SHC : Sensible heat capacity
: Power input
PI
(Comp.+outdoor fan motor).
(m/min.)
(CWB)
(CDB)
(kW)
(kW)
(kW)
Notes:
1. Direct interpolation is permissible.
Do not extrapolate beyond the Operation Limits.
2.
shows nominal capacities.
3. SHC is based on each EWB and EDB.
SHC*=SHC correction for other dry bulb. (DB*)
=0.02AFR(1-BF)(DB*-EDB)
Add SHC* to SHC.
4. Above cooling capacities do not include indoor fan motor heat.
3D014898A
26
ED43-441
Capacity Tables
UATY09KY1
Symbols:
AFR : Air flow rate
BF : Bypass factor
EWB : Entering wet bulb temp.
EDB : Entering dry bulb temp.
TC : Total cooling capacity
SHC : Sensible heat capacity
: Power input
PI
(Comp.+outdoor fan motor).
(m/min.)
(CWB)
(CDB)
(kW)
(kW)
(kW)
Notes:
1. Direct interpolation is permissible.
Do not extrapolate beyond the Operation Limits.
2.
shows nominal capacities.
3. SHC is based on each EWB and EDB.
SHC*=SHC correction for other dry bulb. (DB*)
=0.02AFR(1-BF)(DB*-EDB)
Add SHC* to SHC.
4. Above cooling capacities do not include indoor fan motor heat.
3D014902A
UATY10KY1
Symbols:
AFR : Air flow rate
BF : Bypass factor
EWB : Entering wet bulb temp.
EDB : Entering dry bulb temp.
TC : Total cooling capacity
SHC : Sensible heat capacity
: Power input
PI
(Comp.+outdoor fan motor).
(m/min.)
(CWB)
(CDB)
(kW)
(kW)
(kW)
Notes:
1. Direct interpolation is permissible.
Do not extrapolate beyond the Operation Limits.
2.
shows nominal capacities.
3. SHC is based on each EWB and EDB.
SHC*=SHC correction for other dry bulb. (DB*)
=0.02AFR(1-BF)(DB*-EDB)
Add SHC* to SHC.
4. Above cooling capacities do not include indoor fan motor heat.
3D014906A
27
Capacity Tables
ED43-441
UATY15KY1
Symbols:
AFR : Air flow rate
BF : Bypass factor
EWB : Entering wet bulb temp.
EDB : Entering dry bulb temp.
TC : Total cooling capacity
SHC : Sensible heat capacity
: Power input
PI
(Comp.+outdoor fan motor).
(m/min.)
(CWB)
(CDB)
(kW)
(kW)
(kW)
Notes:
1. Direct interpolation is permissible.
Do not extrapolate beyond the Operation Limits.
2.
shows nominal capacities.
3. SHC is based on each EWB and EDB.
SHC*=SHC correction for other dry bulb. (DB*)
=0.02AFR(1-BF)(DB*-EDB)
Add SHC* to SHC.
4. Above cooling capacities do not include indoor fan motor heat.
3D014910A
UATY18KY1
Symbols:
AFR : Air flow rate
BF : Bypass factor
EWB : Entering wet bulb temp.
EDB : Entering dry bulb temp.
TC : Total cooling capacity
SHC : Sensible heat capacity
: Power input
PI
(Comp.+outdoor fan motor).
(m/min.)
(CWB)
(CDB)
(kW)
(kW)
(kW)
Notes:
1. Direct interpolation is permissible.
Do not extrapolate beyond the Operation Limits.
2.
shows nominal capacities.
3. SHC is based on each EWB and EDB.
SHC*=SHC correction for other dry bulb. (DB*)
=0.02AFR(1-BF)(DB*-EDB)
Add SHC* to SHC.
4. Above cooling capacities do not include indoor fan motor heat.
3D014914A
28
ED43-441
Capacity Tables
UATY21KY1
Symbols:
AFR : Air flow rate
BF : Bypass factor
EWB : Entering wet bulb temp.
EDB : Entering dry bulb temp.
TC : Total cooling capacity
SHC : Sensible heat capacity
: Power input
PI
(Comp.+outdoor fan motor).
(m/min.)
(CWB)
(CDB)
(kW)
(kW)
(kW)
Notes:
1. Direct interpolation is permissible.
Do not extrapolate beyond the Operation Limits.
2.
shows nominal capacities.
3. SHC is based on each EWB and EDB.
SHC*=SHC correction for other dry bulb. (DB*)
=0.02AFR(1-BF)(DB*-EDB)
Add SHC* to SHC.
4. Above cooling capacities do not include indoor fan motor heat.
3D014918A
29
Capacity Tables
7.2
ED43-441
UATY06KY1
Indoor air
-5
AFR EDB(C)
16.0
18.0
20.0
47
21.0
22.0
24.0
16.0
18.0
20.0
52
21.0
22.0
24.0
16.0
18.0
20.0
62
21.0
22.0
24.0
TC
13.8
13.7
13.7
13.7
13.7
13.7
13.8
13.8
13.7
13.7
13.7
13.7
13.8
13.8
13.7
13.7
13.7
13.7
0
PI
4.4
4.5
4.7
4.8
4.9
5.1
4.3
4.4
4.6
4.7
4.8
5.0
4.2
4.3
4.5
4.5
4.6
4.8
TC
16.7
16.7
16.6
16.6
16.6
16.5
16.7
16.7
16.6
16.6
16.6
16.5
16.8
16.7
16.7
16.7
16.6
16.3
Symbols:
AFR : Air flow rate
EDB : Entering dry bulb temp.
TC : Total heating capacity
: Power input
PI
(Comp.+outdoor fan motor).
(m/min.)
(CDB)
(kW)
(kW)
15
TC
22.8
22.8
22.7
22.6
22.9
22.9
22.8
22.7
23.1
23.1
23.0
22.9
PI
6.2
6.3
6.4
6.6
6.0
6.1
6.2
6.4
5.7
5.8
5.9
6.1
Notes:
1. Direct interpolation is permissible.
Do not extrapolate beyond the Operation Limits.
2.
shows nominal capacities.
3. Capacities are based on the following conditions.
Outdoor air : 85% RH. However, the condition on nominal capacity is
7CDB/6CWB.
4. Above heating capacities include indoor fan motor heat.
3D014896A
UATY08KY1
Symbols:
AFR : Air flow rate
EDB : Entering dry bulb temp.
TC : Total heating capacity
: Power input
PI
(Comp.+outdoor fan motor).
(m/min.)
(CDB)
(kW)
(kW)
Notes:
1. Direct interpolation is permissible.
Do not extrapolate beyond the Operation Limits.
2.
shows nominal capacities.
3. Capacities are based on the following conditions.
Outdoor air : 85% RH. However, the condition on nominal capacity is
7CDB/6CWB.
4. Above heating capacities include indoor fan motor heat.
3D014900A
30
ED43-441
Capacity Tables
UATY09KY1
Symbols:
AFR : Air flow rate
EDB : Entering dry bulb temp.
TC : Total heating capacity
: Power input
PI
(Comp.+outdoor fan motor).
(m/min.)
(CDB)
(kW)
(kW)
Notes:
1. Direct interpolation is permissible.
Do not extrapolate beyond the Operation Limits.
2.
shows nominal capacities.
3. Capacities are based on the following conditions.
Outdoor air : 85% RH. However, the condition on nominal capacity is
7CDB/6CWB.
4. Above heating capacities include indoor fan motor heat.
3D014904A
UATY10KY1
Symbols:
AFR : Air flow rate
EDB : Entering dry bulb temp.
TC : Total heating capacity
: Power input
PI
(Comp.+outdoor fan motor).
(m/min.)
(CDB)
(kW)
(kW)
Notes:
1. Direct interpolation is permissible.
Do not extrapolate beyond the Operation Limits.
2.
shows nominal capacities.
3. Capacities are based on the following conditions.
Outdoor air : 85% RH. However, the condition on nominal capacity is
7CDB/6CWB.
4. Above heating capacities include indoor fan motor heat.
3D014908A
31
Capacity Tables
ED43-441
UATY15KY1
Symbols:
AFR : Air flow rate
EDB : Entering dry bulb temp.
TC : Total heating capacity
: Power input
PI
(Comp.+outdoor fan motor).
(m/min.)
(CDB)
(kW)
(kW)
Notes:
1. Direct interpolation is permissible.
Do not extrapolate beyond the Operation Limits.
2.
shows nominal capacities.
3. Capacities are based on the following conditions.
Outdoor air : 85% RH. However, the condition on nominal capacity is
7CDB/6CWB.
4. Above heating capacities include indoor fan motor heat.
3D014912A
UATY18KY1
Symbols:
AFR : Air flow rate
EDB : Entering dry bulb temp.
TC : Total heating capacity
: Power input
PI
(Comp.+outdoor fan motor).
(m/min.)
(CDB)
(kW)
(kW)
Notes:
1. Direct interpolation is permissible.
Do not extrapolate beyond the Operation Limits.
2.
shows nominal capacities.
3. Capacities are based on the following conditions.
Outdoor air : 85% RH. However, the condition on nominal capacity is
7CDB/6CWB.
4. Above heating capacities include indoor fan motor heat.
3D014916A
32
ED43-441
Capacity Tables
UATY21KY1
Symbols:
AFR : Air flow rate
EDB : Entering dry bulb temp.
TC : Total heating capacity
: Power input
PI
(Comp.+outdoor fan motor).
(m/min.)
(CDB)
(kW)
(kW)
Notes:
1. Direct interpolation is permissible.
Do not extrapolate beyond the Operation Limits.
2.
shows nominal capacities.
3. Capacities are based on the following conditions.
Outdoor air : 85% RH. However, the condition on nominal capacity is
7CDB/6CWB.
4. Above heating capacities include indoor fan motor heat.
3D014920A
33
Capacity Tables
7.3
ED43-441
UATY06KTAL
UATY06KYAL
Indoor air
AFR(BF) EWB(C) EDB(C)
14.0 20.0
16.0 22.0
18.0 25.0
47
(0.15) 19.0 27.0
19.5 27.0
22.0 30.0
24.0 32.0
14.0 20.0
16.0 22.0
18.0 25.0
52
(0.16) 19.0 27.0
19.5 27.0
22.0 30.0
24.0 32.0
14.0 20.0
16.0 22.0
18.0 25.0
62
(0.18) 19.0 27.0
19.5 27.0
22.0 30.0
24.0 32.0
TC
15.8
16.9
17.9
18.5
18.8
20.3
21.5
16.1
17.2
18.3
18.9
19.2
20.7
21.9
16.6
17.7
18.9
19.4
19.7
21.3
22.6
25
SHC
11.8
11.9
12.6
13.2
12.9
13.1
13.1
12.3
12.4
13.1
13.8
13.4
13.7
13.6
13.1
13.2
14.0
14.7
14.4
14.7
14.7
Symbols:
AFR : Air flow rate
BF : Bypass factor
EWB : Entering wet bulb temp.
EDB : Entering dry bulb temp.
TC : Total cooling capacity
SHC : Sensible heat capacity
: Power input
PI
(Comp.+outdoor fan motor).
PI
5.4
5.5
5.6
5.7
5.7
5.9
6.1
5.4
5.6
5.7
5.8
5.8
6.0
6.1
5.5
5.6
5.8
5.8
5.9
6.0
6.2
TC
15.2
16.2
17.3
17.8
18.1
19.5
20.7
15.5
16.5
17.6
18.1
18.4
19.9
21.1
16.0
17.0
18.1
18.7
19.0
20.4
21.7
(m/min.)
(CWB)
(CDB)
(kW)
(kW)
(kW)
30
SHC
11.5
11.5
12.2
12.8
12.5
12.8
12.7
11.9
12.0
12.7
13.4
13.0
13.3
13.2
12.7
12.8
13.5
14.3
14.0
14.3
14.3
PI
5.9
6.0
6.1
6.2
6.2
6.4
6.6
5.9
6.0
6.2
6.2
6.3
6.5
6.6
6.0
6.1
6.2
6.3
6.4
6.5
6.7
TC
14.6
15.6
16.6
17.1
17.4
18.8
19.9
14.9
15.9
16.9
17.4
17.7
19.1
20.2
15.3
16.3
17.4
17.9
18.2
19.6
20.8
35
SHC
11.1
11.2
11.8
13.0
12.1
12.4
12.4
11.6
11.6
12.3
13.0
12.6
13.0
12.9
12.3
12.4
13.2
13.9
13.6
13.9
13.9
PI
6.4
6.5
6.7
6.7
6.8
7.0
7.1
6.4
6.6
6.7
6.8
6.8
7.0
7.2
6.5
6.6
6.8
6.8
6.9
7.1
7.2
45
SHC
10.3
10.3
11.0
11.6
11.3
11.6
11.5
10.7
10.7
11.4
12.1
11.8
12.1
12.1
11.4
11.5
12.3
13.0
12.6
13.0
13.0
PI
7.5
7.7
7.8
7.9
7.9
8.1
8.3
7.5
7.7
7.8
7.9
8.0
8.2
8.3
7.6
7.8
7.9
8.0
8.0
8.2
8.4
TC
12.4
13.2
14.1
14.6
14.8
16.0
12.6
13.4
14.3
14.8
15.0
16.2
12.9
13.8
14.7
15.1
15.4
16.6
50
SHC
9.8
9.9
10.5
11.2
10.9
11.2
10.2
10.3
11.0
11.6
11.3
11.7
10.9
11.0
11.7
12.5
12.1
12.5
PI
8.1
8.3
8.4
8.5
8.6
8.8
8.2
8.3
8.5
8.6
8.6
8.8
8.2
8.4
8.5
8.6
8.7
8.9
TC
12.0
12.9
13.7
14.1
14.4
15.6
12.2
13.1
13.9
14.4
14.6
15.8
12.5
13.4
14.3
14.7
15.0
16.2
52
SHC
9.6
9.7
10.3
11.0
10.7
11.0
10.0
10.1
10.8
11.4
11.1
11.5
10.7
11.0
11.5
12.3
11.9
12.3
PI
8.4
8.5
8.7
8.8
8.9
9.0
8.4
8.6
8.7
8.8
8.9
9.1
8.5
8.6
8.8
8.9
8.9
9.1
Notes:
1. Direct interpolation is permissible.
Do not extrapolate beyond the Operation Limits.
2.
shows nominal capacities.
3. SHC is based on each EWB and EDB.
SHC*=SHC correction for other dry bulb. (DB*)
=0.02AFR(1-BF)(DB*-EDB)
Add SHC* to SHC.
4. Above cooling capacities do not include indoor fan motor heat.
3D014895A
UATY08KTAL
UATY08KYAL
Symbols:
AFR : Air flow rate
BF : Bypass factor
EWB : Entering wet bulb temp.
EDB : Entering dry bulb temp.
TC : Total cooling capacity
SHC : Sensible heat capacity
: Power input
PI
(Comp.+outdoor fan motor).
(m/min.)
(CWB)
(CDB)
(kW)
(kW)
(kW)
Notes:
1. Direct interpolation is permissible.
Do not extrapolate beyond the Operation Limits.
2.
shows nominal capacities.
3. SHC is based on each EWB and EDB.
SHC*=SHC correction for other dry bulb. (DB*)
=0.02AFR(1-BF)(DB*-EDB)
Add SHC* to SHC.
4. Above cooling capacities do not include indoor fan motor heat.
3D014899A
34
ED43-441
Capacity Tables
UATY09KTAL
UATY09KYAL
Symbols:
AFR : Air flow rate
BF : Bypass factor
EWB : Entering wet bulb temp.
EDB : Entering dry bulb temp.
TC : Total cooling capacity
SHC : Sensible heat capacity
: Power input
PI
(Comp.+outdoor fan motor).
(m/min.)
(CWB)
(CDB)
(kW)
(kW)
(kW)
Notes:
1. Direct interpolation is permissible.
Do not extrapolate beyond the Operation Limits.
2.
shows nominal capacities.
3. SHC is based on each EWB and EDB.
SHC*=SHC correction for other dry bulb. (DB*)
=0.02AFR(1-BF)(DB*-EDB)
Add SHC* to SHC.
4. Above cooling capacities do not include indoor fan motor heat.
3D014903A
UATY12KTAL
UATY12KYAL
Symbols:
AFR : Air flow rate
BF : Bypass factor
EWB : Entering wet bulb temp.
EDB : Entering dry bulb temp.
TC : Total cooling capacity
SHC : Sensible heat capacity
: Power input
PI
(Comp.+outdoor fan motor).
(m/min.)
(CWB)
(CDB)
(kW)
(kW)
(kW)
Notes:
1. Direct interpolation is permissible.
Do not extrapolate beyond the Operation Limits.
2.
shows nominal capacities.
3. SHC is based on each EWB and EDB.
SHC*=SHC correction for other dry bulb. (DB*)
=0.02AFR(1-BF)(DB*-EDB)
Add SHC* to SHC.
4. Above cooling capacities do not include indoor fan motor heat.
3D014907A
35
Capacity Tables
ED43-441
UATY15KTAL
UATY15KYAL
Symbols:
AFR : Air flow rate
BF : Bypass factor
EWB : Entering wet bulb temp.
EDB : Entering dry bulb temp.
TC : Total cooling capacity
SHC : Sensible heat capacity
: Power input
PI
(Comp.+outdoor fan motor).
(m/min.)
(CWB)
(CDB)
(kW)
(kW)
(kW)
Notes:
1. Direct interpolation is permissible.
Do not extrapolate beyond the Operation Limits.
2.
shows nominal capacities.
3. SHC is based on each EWB and EDB.
SHC*=SHC correction for other dry bulb. (DB*)
=0.02AFR(1-BF)(DB*-EDB)
Add SHC* to SHC.
4. Above cooling capacities do not include indoor fan motor heat.
3D014911A
UATY18KTAL
UATY18KYAL
Symbols:
AFR : Air flow rate
BF : Bypass factor
EWB : Entering wet bulb temp.
EDB : Entering dry bulb temp.
TC : Total cooling capacity
SHC : Sensible heat capacity
: Power input
PI
(Comp.+outdoor fan motor).
(m/min.)
(CWB)
(CDB)
(kW)
(kW)
(kW)
Notes:
1. Direct interpolation is permissible.
Do not extrapolate beyond the Operation Limits.
2.
shows nominal capacities.
3. SHC is based on each EWB and EDB.
SHC*=SHC correction for other dry bulb. (DB*)
=0.02AFR(1-BF)(DB*-EDB)
Add SHC* to SHC.
4. Above cooling capacities do not include indoor fan motor heat.
3D014915A
36
ED43-441
Capacity Tables
UATY21KTAL
UATY21KYAL
Symbols:
AFR : Air flow rate
BF : Bypass factor
EWB : Entering wet bulb temp.
EDB : Entering dry bulb temp.
TC : Total cooling capacity
SHC : Sensible heat capacity
: Power input
PI
(Comp.+outdoor fan motor).
(m/min.)
(CWB)
(CDB)
(kW)
(kW)
(kW)
Notes:
1. Direct interpolation is permissible.
Do not extrapolate beyond the Operation Limits.
2.
shows nominal capacities.
3. SHC is based on each EWB and EDB.
SHC*=SHC correction for other dry bulb. (DB*)
=0.02AFR(1-BF)(DB*-EDB)
Add SHC* to SHC.
4. Above cooling capacities do not include indoor fan motor heat.
3D014919A
37
Capacity Tables
7.4
ED43-441
UATY06KTAL
UATY06KYAL
Indoor air
-5
AFR EDB(C)
16.0
18.0
20.0
47
21.0
22.0
24.0
16.0
18.0
20.0
52
21.0
22.0
24.0
16.0
18.0
20.0
62
21.0
22.0
24.0
TC
13.5
13.5
13.5
13.6
13.6
13.6
13.5
13.5
13.5
13.5
13.5
13.6
13.6
13.5
13.5
13.5
13.5
13.5
0
PI
5.0
5.2
5.4
5.5
5.6
5.7
4.9
5.1
5.3
5.4
5.4
5.6
4.8
4.9
5.1
5.2
5.3
5.5
TC
15.5
15.5
15.5
15.5
15.5
15.5
15.6
15.6
15.5
15.5
15.5
15.5
15.6
15.6
15.6
15.5
15.5
15.5
Symbols:
AFR : Air flow rate
EDB : Entering dry bulb temp.
TC : Total heating capacity
: Power input
PI
(Comp.+outdoor fan motor).
(m/min.)
(CDB)
(kW)
(kW)
15
TC
22.7
22.6
22.5
22.4
22.8
23.0
22.7
22.6
23.0
22.9
22.9
22.7
PI
7.2
7.3
7.4
7.7
7.0
7.1
7.2
7.4
6.7
6.8
6.9
7.1
Notes:
1. Direct interpolation is permissible.
Do not extrapolate beyond the Operation Limits.
2.
shows nominal capacities.
3. Capacities are based on the following conditions.
Outdoor air : 85% RH. However, the condition on nominal capacity is
7CDB/6CWB.
4. Above heating capacities include indoor fan motor heat.
3D014897A
UATY08KTAL
UATY08KYAL
Symbols:
AFR : Air flow rate
EDB : Entering dry bulb temp.
TC : Total heating capacity
: Power input
PI
(Comp.+outdoor fan motor).
(m/min.)
(CDB)
(kW)
(kW)
Notes:
1. Direct interpolation is permissible.
Do not extrapolate beyond the Operation Limits.
2.
shows nominal capacities.
3. Capacities are based on the following conditions.
Outdoor air : 85% RH. However, the condition on nominal capacity is
7CDB/6CWB.
4. Above heating capacities include indoor fan motor heat.
3D014901A
38
ED43-441
Capacity Tables
UATY09KTAL
UATY09KYAL
Symbols:
AFR : Air flow rate
EDB : Entering dry bulb temp.
TC : Total heating capacity
: Power input
PI
(Comp.+outdoor fan motor).
(m/min.)
(CDB)
(kW)
(kW)
Notes:
1. Direct interpolation is permissible.
Do not extrapolate beyond the Operation Limits.
2.
shows nominal capacities.
3. Capacities are based on the following conditions.
Outdoor air : 85% RH. However, the condition on nominal capacity is
7CDB/6CWB.
4. Above heating capacities include indoor fan motor heat.
3D014905A
UATY12KTAL
UATY12KYAL
Symbols:
AFR : Air flow rate
EDB : Entering dry bulb temp.
TC : Total heating capacity
: Power input
PI
(Comp.+outdoor fan motor).
(m/min.)
(CDB)
(kW)
(kW)
Notes:
1. Direct interpolation is permissible.
Do not extrapolate beyond the Operation Limits.
2.
shows nominal capacities.
3. Capacities are based on the following conditions.
Outdoor air : 85% RH. However, the condition on nominal capacity is
7CDB/6CWB.
4. Above heating capacities include indoor fan motor heat.
3D014909A
39
Capacity Tables
ED43-441
UATY15KTAL
UATY15KYAL
Symbols:
AFR : Air flow rate
EDB : Entering dry bulb temp.
TC : Total heating capacity
: Power input
PI
(Comp.+outdoor fan motor).
(m/min.)
(CDB)
(kW)
(kW)
Notes:
1. Direct interpolation is permissible.
Do not extrapolate beyond the Operation Limits.
2.
shows nominal capacities.
3. Capacities are based on the following conditions.
Outdoor air : 85% RH. However, the condition on nominal capacity is
7CDB/6CWB.
4. Above heating capacities include indoor fan motor heat.
3D014913A
UATY18KTAL
UATY18KYAL
Symbols:
AFR : Air flow rate
EDB : Entering dry bulb temp.
TC : Total heating capacity
: Power input
PI
(Comp.+outdoor fan motor).
(m/min.)
(CDB)
(kW)
(kW)
Notes:
1. Direct interpolation is permissible.
Do not extrapolate beyond the Operation Limits.
2.
shows nominal capacities.
3. Capacities are based on the following conditions.
Outdoor air : 85% RH. However, the condition on nominal capacity is
7CDB/6CWB.
4. Above heating capacities include indoor fan motor heat.
3D014917A
40
ED43-441
Capacity Tables
UATY21KTAL
UATY21KYAL
Symbols:
AFR : Air flow rate
EDB : Entering dry bulb temp.
TC : Total heating capacity
: Power input
PI
(Comp.+outdoor fan motor).
(m/min.)
(CDB)
(kW)
(kW)
Notes:
1. Direct interpolation is permissible.
Do not extrapolate beyond the Operation Limits.
2.
shows nominal capacities.
3. Capacities are based on the following conditions.
Outdoor air : 85% RH. However, the condition on nominal capacity is
7CDB/6CWB.
4. Above heating capacities include indoor fan motor heat.
3D014921A
41
Fan Performance
ED43-441
8. Fan Performance
8.1
3D014926C
42
ED43-441
8.2
Fan Performance
Y1 TAL
YAL
Y1 TAL
YAL
Y1 TAL
YAL
Y1 TAL
YAL
Y1
5.5
0.75
1.5
2.2
3.7
19
24
28
28
38
Shaft Length :
Q (mm)
40
50
60
60
80
Keyway Width :
W (mm)
10
Keyway Depth :
U (mm)
3.5
B
10
Insulation Class :
Key Width :
b (mm)
Key Height :
h (mm)
d (mm)
19
24
28
28
38
Keyway :
B (mm)
10
Keyway Height :
H (mm)
21.5
27
31
31
41
Motor Pulley have to be changed when Air Flow Rate and the External Static Pressure are different from
factory setting.
8.3
D2
N2
N1
D1
D2
N1
N2
Relation between outer diameter and pitch diameter of each Pulley are as follows:
A type ( Pitch Diameter) = Outer Diameter of Pulley - 9mm
B type ( Pitch Diameter) = Outer Diameter of Pulley - 11mm
D1
Lp = 2C + 1.57( D1 + D2 ) +
Model Name
UATY06K
UATY08/09/10/12K
UATY15/18K
UATY21K
( D1 - D2 ) 2
4C
43
Operation Limit
ED43-441
9. Operation Limit
9.1
Operation Limit
4D014922
44
ED43-441
Sound Level
50/60Hz
UATY06K
62
UATY08K
63
UATY09K
UATY10K
64
UATY12K
UATY15K
66
UATY18K
UATY21K
67
4D013870
Note:
45
Sound Level
10.2
ED43-441
UATY06K
UATY08K
UATY09K
4D013868
4D013867
UATY10K
UATY12K
UATY15K
UATY18K
4D013870
4D013869
UATY21K
: 50Hz
: 60Hz
4D013871
46
ED43-441
Electric Characteristics
Electric Characteristics
3D014570A-1
47
Electric Characteristics
ED43-441
3D014570A-2
48
ED43-441
Field Wiring
Field Wiring
C : 4D014928
49
Center of Gravity
ED43-441
Center of Gravity
UATY06K
4D013704
UATY08K
UATY09K
UATY10K
UATY12K
4D013705B
50
ED43-441
Center of Gravity
UATY15K
UATY18K
UATY21K
3D013864B
51
Installation
ED43-441
14. Installation
14.1
52
Installation Manual
ED43-441
Installation
53
Installation
54
ED43-441
ED43-441
Installation
INSTALLATION
(1) Before starting the installation, confirm that the foundation is strong enough so that the unit will not make noise or
vibrations.
Secure the unit to the foundation with foundation bolts.
20mm
(Prepare 4 sets of M12 foundation bolts with the proper nuts and washers.)
The foundation bolts should extend 20 mm from the surface of the base. (See right Fig.)
Place more than three antivibration pads under a unit per one side.
Model
650
1460
1230
1200
1930
1080
UAT06K(A)
UATY06K
UAT08~12K(A)
UATY08~12K
UAT15~21K(A)
UATY15~21K
Compressor
CAUTION
(2) Remove the yellow packing brace from the
compressor as shown in the figure at the right.
Retighten the installation bolts for the compressor.
Two packing braces are attached to the front of
each compressor.
Packing brace
(Yellow)
Bolt
CAUTION
Carry out the specified installation work after taking into account strong winds, typhoons or earthquakes.
Improper installation work may result in the equipment falling and causing an accident.
Make sure that the drainage of the unit will not inconvenience neighbors or harm the environment. Construct a
drainage ditch if necessary.
If the unit is to be installed on a rooftop, make certain that it will be capable of withstanding the weight of the
unit and that measures have been taken to ensure watertightness.
1PN02530D-4
55
Installation
ED43-441
3VA08895
56
ED43-441
Installation
57
Installation
58
ED43-441
ED43-441
Installation
59
Installation
60
ED43-441
ED43-441
Installation
61
Installation
14.2
ED43-441
UATY06K
UATY08K
UATY09K
UATY10K
UATY12K
UATY06K
L = 5mm
UATY08K
UATY09K
UATY10K
L = 6mm
UATY12K
UATY15K
UATY18K
UATY21K
UATY15K
UATY18K
UATY21K
62
L = 4mm
L = 8mm
ED43-441
14.3
Installation
Cautions
Normal
Operation (1) Normal Operation
63
Optional Accessories
ED43-441
Option List
Option
Remote Controller
Remark
Kit Name
KRC17-2B (Note 1)
{ (Note 2)
KRC47-5
{ (Note 2)
KTA19A1
DTA107A55
Mechanical Type
Digital Type
3 Minutes Timer
Central Control Adaptor Kit
UATY06-12K UATY15-21K
{
C : 3D014927A
Note:
15.2
2. Holder
10mm
4mm
4.5mm
83mm
4.5mm
325
165
80
15
4-6HOLE
310
70
345
(P0007)
4. Wire Cable
Cable length : 4m (8m or 15m will be available on request.)
Connecting cable between 1. Digital Remote Controller and 3. Control Board (Box).
64
ED43-441
15.3
Optional Accessories
65
Optional Accessories
15.4
ED43-441
15.4.1 Features
66
ED43-441
Optional Accessories
Kit
Unified ON/OFF
(P0020)
Down
Control 1
Alarm
2
3
Schedule Timer
128
DCS301B61
1
8
16
128
Using the Schedule Timer with the Central Remote Controller makes it possible to set ON/OFF time four times a day.
Four times of ON/OFF time can be set up per day, because two settings of ON/OFF time are possible to one
Schedule Timer, and two Schedule Timers can be registered into a Central Remote Controller.
(P0021)
67
Optional Accessories
ED43-441
15.4.4 Dimension
3D019850
68
ED43-441
Optional Accessories
3D019866
UATY06KY1,YAL + DTA107A55
69
Optional Accessories
ED43-441
3D019867A
UATY06KTAL + DTA107A55
70
ED43-441
Optional Accessories
3D019868
71
Optional Accessories
ED43-441
3D019869A
UATY08KTAL + DTA107A55
UATY09KTAL + DTA107A55
72
ED43-441
Optional Accessories
3D019870A
UATY12KTAL + DTA107A55
73
Optional Accessories
ED43-441
3D019871
74
ED43-441
Optional Accessories
3D019872A
UATY15KTAL + DTA107A55
UATY18KTAL + DTA107A55
UATY21KTAL + DTA107A55
75
Wiring Modification
ED43-441
Note : For wiring, an electric component box (Field supplied) is required since the wires do not fit in the unit.
3VA08858
UATY06KY1
76
Note : For wiring, an electric component box (Field supplied) is required since the wires do not fit in the unit.
3VA08861
ED43-441
UATY08KY1
UATY09KY1
UATY10KY1
77
Note : For wiring, an electric component box (Field supplied) is required since the wires do not fit in the unit.
3VA08865
Wiring Modification
78
ED43-441
UATY15KY1
UATY18KY1
UATY21KY1
Note : For wiring, an electric component box (Field supplied) is required since the wires do not fit in the unit.
3VA08859
ED43-441
UATY06KTAL
79
Note : For wiring, an electric component box (Field supplied) is required since the wires do not fit in the unit.
3VA08862
Wiring Modification
80
ED43-441
UATY08KTAL
UATY09KTAL
Note : For wiring, an electric component box (Field supplied) is required since the wires do not fit in the unit.
3VA08864
ED43-441
UATY12KTAL
81
Note : For wiring, an electric component box (Field supplied) is required since the wires do not fit in the unit.
3VA08866
Wiring Modification
82
ED43-441
UATY15KTAL
UATY18KTAL
UATY21KTAL
Note : For wiring, an electric component box (Field supplied) is required since the wires do not fit in the unit.
3VA08860
ED43-441
UATY06KYAL
83
Note : For wiring, an electric component box (Field supplied) is required since the wires do not fit in the unit.
3VA08863
Wiring Modification
84
ED43-441
UATY08KYAL
UATY09KYAL
UATY12KYAL
Note : For wiring, an electric component box (Field supplied) is required since the wires do not fit in the unit.
3VA08867
ED43-441
UATY15KYAL
UATY18KYAL
UATY21KYAL
85
Certificate Number.
Dealer
Head Office:
Umeda Center Bldg., 4-12, Nakazaki-Nishi
2-chome, Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:
JR Shinagawa East Bldg., 18-1, Konan
2-chome, Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/global/
c All rights reserved
The specifications, designs, and information in this brochure are subject to change without notice.
ED 43-441
Printed in Japan 07/2004 FS