Fiche Technique Unité Roof Top
Fiche Technique Unité Roof Top
Fiche Technique Unité Roof Top
Product Data
4TCY4024 through 4TCY4060
Single Packaged Convertible Cooling
14 SEER
2 - 5 Ton
R-410A
2
Contents
Optional Equipment Listing 4
General Data 5
Heater Data 8
SPEK Data 9
Performance Data
Indoor Fan 12
Typical Wiring 15
Optional Equipment 18
Dimensional Data 23
Mechanical Specifications 29
3
Optional Equipment
OPTIONAL EQUIPMENT FOR PACKAGED UNITS (check mark [3] indicates accessories included)
NOTES: 1 Must use internal filter frame when economizer or fresh air kit is used.
2 Dry bulb control standard with economizer.
3 Ships knocked down.
4 Downflow only.
5 Low Ambient cooling requires crankcase heater (BAYCCHT----B).
6 It is the responsibility of the installing dealer to properly size the ductwork for each specific application.
7 BAYCOVR112,118A will not cover BAYSQRD002A applications.
8 See table on page 8 for matching kit with units and heaters.
‡ = A or B
4
General Data
MODEL 4TCY4024A1000B 4TCY4030A1000B 4TCY4036B1000B
RATED Volts/PH/Hz 208-230/1/60 208-230/1/60 208-230/1/60
Performance Cooling BTUH 23400 30000 38000
Indoor Airflow (CFM) 780 900 1195
Power Input (KW) 1.99 2.5 3.17
EER/SEER (BTU/Watt-Hr.) 12 / 14.0 12.0 / 14.0 12.0 / 14.2
Sound Power Rating [dB(A)] 68 71 69
POWER CONN.—V/Ph/Hz 208-230/1/60 208-230/1/60 208-230/1/60
Min. Brch. Cir. Ampacity 16.5 19.1 26.3
Fuse Size — Max. (amps) 25 30 40
Fuse Size — Recmd. (amps) 25 30 40
COMPRESSOR RECIPROCATING RECIPROCATING SCROLL
Volts/Ph/Hz 200-230/1/60 208-230/1/60 208-230/1/60
R.L. Amps — L.R. Amps 8.3 / 57.8 11.1 / 63 16.7 / 69
OUTDOOR COIL — TYPE SPINE-FIN SPINE-FIN SPINE-FIN
Rows/F.P.I. 2 / 24 2 / 24 2 / 24
Face Area (sq.ft.) 13.32 13.32 15.49
Tube Size (in.) 3/8 3/8 3/8
INDOOR COIL — TYPE PLATE FIN PLATE FIN PLATE FIN
Rows/F.P.I. 3 / 15 3 / 15 4 / 15
Face Area (sq.ft.) 3.54 3.54 3.54
Tube Size (in.) 3/8 3/8 3/8
Refrigerant Control EXPANSION VALVE EXPANSION VALVE EXPANSION VALVE
Drain Conn. Size (in.) 3/4 FEMALE NPT 3/4 FEMALE NPT 3/4 FEMALE NPT
OUTDOOR FAN — TYPE PROPELLER PROPELLER PROPELLER
Dia. (in.) 23.4 23.4 23.4
Drive/No. Speeds DIRECT / 1 DIRECT / 1 DIRECT / 1
CFM @ 0.0 in. w.g. 2560 2550 3300
Motor — HP/R.P.M. 1/12 / 810 1/6 / 830 1/5 / 830
Volts/Ph/Hz 230/1/60 208-230/1/60 230/1/60
F.L. Amps/L.R. Amps 0.54 / 0.95 0.9 / 1.7 1.1 / 1.9
INDOOR FAN — TYPE CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL
Dia x Width (in.) 10 X 10 10 X 10 10 X 10
Drive/No. Speeds DIRECT / VARIABLE DIRECT / VARIABLE DIRECT / VARIABLE
CFM @ 0.0 in. w.g. SEE FAN PERFORMANCE TABLE SEE FAN PERFORMANCE TABLE SEE FAN PERFORMANCE TABLE
Motor — HP/R.P.M. 1/2 / VARIABLE 1/2 / VARIABLE 1/2 / VARIABLE
Volts/Ph/Hz 200-230/1/60 208-230/1/60 200-230/1/60
F.L. Amps/L.R. Amps 4.3 / 4.3 4.3 / 4.3 4.3 / 4.3
FILTER / FURNISHED NO NO NO
Type Recommended THROWAWAY THROWAWAY THROWAWAY
Recmd. Face Area (sq. ft.) 4.0 4.0 4
REFRIGERANT R410A R410A R410A
Charge (lbs.) 6.0 6.30 7.80
DIMENSIONS HXWXL HXWXL HXWXL
Crated (in.) 45.86 / 44.5 / 52.03 45.86 / 44.5 / 52.03 47.86 / 44.5 / 52.03
WEIGHT
Shipping (lbs.) / Net (lbs.) 444 / 348 444 / 348 450 / 354
5
General Data
MODEL 4TCY4036B3000A 4TCY4042B1000B 4TCY4048B1000B
RATED Volts/PH/Hz 208-230/3/60 208-230/1/60 208-230/1/60
Performance Cooling BTUH 37000 42000 48500
Indoor Airflow (CFM) 1195 1420 1605
Power Input (KW) 3.17 3.5 4.041
EER/SEER (BTU/Watt-Hr.) 12.0 / 14.2 12.0 / 14.25 12 / 14.2
Sound Power Rating [dB(A)] 69 74 72
POWER CONN.—V/Ph/Hz 208-230/3/60 208-230/1/60 208-230/1/60
Min. Brch. Cir. Ampacity 18.4 30.7 35.5
Fuse Size — Max. (amps) 25 45 50
Fuse Size — Recmd. (amps) 25 45 50
COMPRESSOR SCROLL SCROLL SCROLL
Volts/Ph/Hz 208-230/3/60 208-230/1/60 208-230/1/60
R.L. Amps — L.R. Amps 10.4 / 73 17.9 / 112 21.8 / 117
OUTDOOR COIL — TYPE SPINE-FIN SPINE-FIN SPINE-FIN
Rows/F.P.I. 2 / 24 2 / 24 2 / 24
Face Area (sq.ft.) 15.49 18.01 18.01
Tube Size (in.) 3/8 3/8 3/8
INDOOR COIL — TYPE PLATE FIN PLATE FIN PLATE FIN
Rows/F.P.I. 4 / 15 3 / 15 3 / 15
Face Area (sq.ft.) 3.54 5 5.0
Tube Size (in.) 3/8 3/8 3/8
Refrigerant Control EXPANSION VALVE EXPANSION VALVE EXPANSION VALVE
Drain Conn. Size (in.) 3/4 FEMALE NPT 3/4 FEMALE NPT 3/4 FEMALE NPT
OUTDOOR FAN — TYPE PROPELLER PROPELLER PROPELLER
Dia. (in.) 23.4 28.2 28.2
Drive/No. Speeds DIRECT / 1 DIRECT / 1 DIRECT / 1
CFM @ 0.0 in. w.g. 3260 4460 4460
Motor — HP/R.P.M. 1/5 / 830 1/4 / 825 1/4 / 825
Volts/Ph/Hz 230/1/60 208-230/1/60 230/1/60
F.L. Amps/L.R. Amps 1.1 / 1.9 1.4 / 3.4 1.4 / 3.37
INDOOR FAN — TYPE CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL
Dia x Width (in.) 10 X 10 11 X 10 10 X 10
Drive/No. Speeds DIRECT / VARIABLE DIRECT / VARIABLE DIRECT / VARIABLE
CFM @ 0.0 in. w.g. SEE FAN PERFORMANCE TABLE SEE FAN PERFORMANCE TABLE SEE FAN PERFORMANCE TABLE
Motor — HP/R.P.M. 1/2 / VARIABLE 3/4 / VARIABLE 3/4 / VARIABLE
Volts/Ph/Hz 200-230/1/60 208-230/1/60 200-230/1/60
F.L. Amps/L.R. Amps 4.3 / 4.3 6.8 / 6.8 6.8 / 6.8
FILTER / FURNISHED NO NO NO
Type Recommended THROWAWAY THROWAWAY THROWAWAY
Recmd. Face Area (sq. ft.) 4 5.3 5.3
REFRIGERANT R410A R410A R410A
Charge (lbs.) 7.80 7.00 8.30
DIMENSIONS HXWXL HXWXL HXWXL
Crated (in.) 47.86 / 44.5 / 52.03 47.86 / 47.4 / 61.75 47.86 / 47.4 / 61.75
WEIGHT
Shipping (lbs.) / Net (lbs.) 450 / 354 607 / 479 623 / 495
6
General Data
MODEL 4TCY4048B3000A 4TCY4060A1000B 4TCY4060A3000B
RATED Volts/PH/Hz 208-230/3/60 208-230/1/60 208-230/3/60
Performance Cooling BTUH 48500 60000 60000
Indoor Airflow (CFM) 1605 1800 1800
Power Input (KW) 4.041 4.93 4.93
EER/SEER (BTU/Watt-Hr.) 12.0 / 14.2 12.0 / 14.0 12.0 / 14.0
Sound Power Rating [dB(A)] 72 76 76
POWER CONN.—V/Ph/Hz 208-230/3/60 208-230/1/60 208-230/3/60
Min. Brch. Cir. Ampacity 25.3 41.6 28.6
Fuse Size — Max. (amps) 35 60 40
Fuse Size — Recmd. (amps) 35 60 40
COMPRESSOR SCROLL SCROLL SCROLL
Volts/Ph/Hz 208-230/3/60 208-230/1/60 208-230/3/60
R.L. Amps — L.R. Amps 13.7 / 83.1 26.4 / 134 16.0 / 110
OUTDOOR COIL — TYPE SPINE-FIN SPINE-FIN SPINE-FIN
Rows/F.P.I. 2 / 24 2 / 24 2 / 24
Face Area (sq.ft.) 18.01 23.57 23.57
Tube Size (in.) 3/8 3/8 3/8
INDOOR COIL — TYPE PLATE FIN PLATE FIN PLATE FIN
Rows/F.P.I. 3 / 15 4 / 15 4 / 15
Face Area (sq.ft.) 5.0 5.0 5.0
Tube Size (in.) 3/8 3/8 3/8
Refrigerant Control EXPANSION VALVE EXPANSION VALVE EXPANSION VALVE
Drain Conn. Size (in.) 3/4 FEMALE NPT 3/4 FEMALE NPT 3/4 FEMALE NPT
OUTDOOR FAN — TYPE PROPELLER PROPELLER PROPELLER
Dia. (in.) 28.2 28.2 28.2
Drive/No. Speeds DIRECT / 1 DIRECT / 1 DIRECT / 1
CFM @ 0.0 in. w.g. 4460 5720 5720
Motor — HP/R.P.M. 1/4 / 825 1/3 / 825 1/3 / 825
Volts/Ph/Hz 230/1/60 230/1/60 230/1/60
F.L. Amps/L.R. Amps 1.4 / 3.37 1.7 / 3.5 1.7 / 3.5
INDOOR FAN — TYPE CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL
Dia x Width (in.) 10 X 10 11 X 10 11 X 10
Drive/No. Speeds DIRECT / VARIABLE DIRECT / VARIABLE DIRECT / VARIABLE
CFM @ 0.0 in. w.g. SEE FAN PERFORMANCE TABLE SEE FAN PERFORMANCE TABLE SEE FAN PERFORMANCE TABLE
Motor — HP/R.P.M. 3/4 / VARIABLE 1 / VARIABLE 1 / VARIABLE
Volts/Ph/Hz 200-230/1/60 208-230/1/60 208-230/1/60
F.L. Amps/L.R. Amps 6.8 / 6.8 6.9 / 6.9 6.9 / 6.9
FILTER / FURNISHED NO NO NO
Type Recommended THROWAWAY THROWAWAY THROWAWAY
Recmd. Face Area (sq. ft.) 5.3 5.3 5.3
REFRIGERANT R410A R410A R410A
Charge (lbs.) 8.30 10.10 10.10
DIMENSIONS HXWXL HXWXL HXWXL
Crated (in.) 47.86 / 47.4 / 61.75 51.86 / 47.4 / 61.75 51.86 / 47.4 / 61.75
WEIGHT
Shipping (lbs.) / Net (lbs.) 607 / 479 612 / 484 612 / 484
7
Heater Data
4TCY4024 to 4TCY4060 Heater Data
^W/TC*3018-060‡1
^W/TCY4024-060‡1 BAYHTRV105E 208/240 1 18/21 3.76/5.0 12800/17100 1 3.76/5.0 23/26 25/30 25/30
^WCZ6036-060‡1
^W/TC*3018-060‡1
^W/TCY4024-060‡1 BAYHTRV108E 208/240 1 29/33 6.0/8.0 20500/27300 1 6.0/8.0 36/41 40/45 40/45
^WCZ6036-060‡1
^W/TC*3024-060‡1
^W/TCY4024-060‡1 BAYHTRV110E 208/240 1 36/42 7.5/10.0 25600/34100 1 7.5/10.0 45/52 45/60 45/60
^WCZ6036-060‡1
^W/TC*3030-060‡1
^W/TCY4030-060‡1 BAYHTRV115E# 208/240 1 54/63 11.27/15.0 38500/51200 2 7.5/10.0 3.76/5.0 68/78 70/80 70/80
^WCZ6036-060‡1
^W/TC*3042-060‡1
^W/TCY4042-060‡1 BAYHTRV120E# 208/240 1 72/83 15.0/20.0 51200/68300 2 7.5/10.0 7.5/10.0 90/104 90/110 90/110
^WCZ6048-060‡1
4WC*3042‡1
^W/TC*3060‡1
BAYHTRV125E# 208/240 1 90/104 18.78/25.0 64100/85300 2 11.26/15.0 7.5/10.0 113/130 125/150 125/150
^W/TCY4042-060‡1
^WCZ6048-060‡1
^W/TC*3036-060‡3
^W/TCY4036-060‡3 BAYHTRV305E 208/240 3 10/12 3.76/5.0 12800/17100 1 3.76/5.0 13/15 15/15 15/15
^WCZ6036-060‡3
^W/TC*3036-060‡3
^W/TCY4036-060‡3 BAYHTRV308E 208/240 3 17/19 6.0/8.0 20500/27300 1 6.0/8.0 21/24 25/25 25/25
^WCZ6036-060‡3
^W/TC*3036-060‡3
^W/TCY4036-060‡3 BAYHTRV310E 208/240 3 21/24 7.5/10.0 25600/34100 1 7.5/10.0 26/30 30/30 30/30
^WCZ6036-060‡3
^W/TC*3036-060‡3
^W/TCY4036-060‡3 BAYHTRV315E 208/240 3 31/36 11.27/15.0 38500/51200 2 7.5/10.0 3.76/5.0 39/45 40/45 40/45
^WCZ6036-060‡3
^W/TC*3048-060‡3
^W/TCY4048-060‡3 BAYHTRV320E 208/240 3 42/48 15.0/20.0 51200/68300 2 7.5/10.0 7.5/10.0 52/60 60/60 60/60
^WCZ6048-060‡3
^W/TC*3060‡3
^W/TCY4048-060‡3 BAYHTRV325E# 208/240 3 52/60 18.78/25.0 64100/85300 2 11.26/15.0 7.5/10.0 65/75 70/80 70/80
^WCZ6048-060‡3
^W/TC*3036-060‡4
BAYHTRV405E 480 3 6 5.0 17100 1 5.0 8 15 15
^WCZ6036-060‡4
^W/TC*3036-060‡4
BAYHTRV408E 480 3 10 8.0 27300 1 8.0 13 15 15
^WCZ6036-060‡4
^W/TC*3036-060‡4
BAYHTRV410E 480 3 12 10.0 34100 1 10.0 15 15 15
^WCZ6036-060‡4
^W/TC*3036-060‡4
BAYHTRV415E 480 3 18 15.0 51200 2 10.0 5.0 23 25 25
^WCZ6036-060‡4
^W/TC*3048-060‡4
BAYHTRV420E 480 3 24 20.0 68300 2 10.0 10.0 30 30 30
^WCZ6048-060‡4
^W/TC*3060‡4
BAYHTRV425E 480 3 30 25.0 85300 2 15.0 10.0 38 40 40
^WCZ6048-060‡4
8
Single Power Entry Kit Data
Notes:
* = C or X
‡ = A or B
9
Single Power Entry Kit Data
Notes:
* = C or X
‡ = A or B
10
Single Power Entry Kit Data
Notes:
* = C or X
‡ = A or B
11
Indoor Blower Performance
Indoor Fan Performance (230v) 4TCY4024 (230vperformance)
Horizontal Airflow
4TCY4024-HOR DIPSWITCH SETTINGS External Static Pressure (in. wg)
AIRFLOW SETTING 1 2 3 4 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
AIRFLOW SETTING 1 2 3 4 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
AIRFLOW SETTING 1 2 3 4 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Down Airflow
4TCY4030-DOWN DIPSWITCH SETTINGS External Static Pressure (in. wg)
AIRFLOW SETTING 1 2 3 4 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
12
Indoor Blower Performance
Indoor Fan Performance (230v) 4TCY4036 (230vperformance)
Horizontal Airflow
4TCY4036-HOR DIPSWITCH SETTINGS External Static Pressure (in. wg)
AIRFLOW SETTING 1 2 3 4 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Watts 162 173 197 226 256 285 313 343 360 - -
350 CFM/TON OFF OFF OFF ON
CFM 1058 1062 1063 1063 1062 1060 1057 1053 1010 - -
Watts 179 230 265 296 329 366 403 431 436 - -
400 CFM/TON* OFF OFF OFF OFF
CFM 1179 1196 1204 1206 1205 1203 1199 1194 1185 - -
Watts 318 336 365 399 435 469 502 533 - - -
450 CFM/TON OFF OFF ON OFF
CFM 1390 1376 1370 1366 1361 1354 1349 1351 - - -
Down Airflow
4TCY4036-DOWN DIPSWITCH SETTINGS External Static Pressure (in. wg)
AIRFLOW SETTING 1 2 3 4 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Watts 169 182 210 243 273 301 331 370 433 - -
350 CFM/TON OFF OFF OFF ON
CFM 1025 1062 1068 1063 1060 1061 1064 1055 1015 - -
Watts 225 253 283 315 348 381 414 449 484 - -
400 CFM/TON* OFF OFF OFF OFF
CFM 1187 1201 1203 1201 1198 1197 1194 1184 1157 - -
Watts 339 357 390 424 455 483 516 571 - - -
450 CFM/TON OFF OFF ON OFF
CFM 1391 1377 1377 1375 1366 1352 1344 1360 - -
Down Airflow
4TCY4042-DOWN DIPSWITCH SETTINGS External Static Pressure (in. wg)
AIRFLOW SETTING 1 2 3 4 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
OFF OFF OFF ON Watts - 195 229 258 283 308 335 362 390 415 -
350 CFM/TON
CFM - 1240 1244 1245 1243 1238 1229 1217 1203 1189 -
OFF OFF OFF OFF Watts - 289 312 341 371 402 432 461 491 523 -
400 CFM/TON*
CFM - 1433 1422 1415 1411 1405 1399 1392 1383 1377 -
OFF OFF ON OFF Watts - 385 422 457 491 527 563 600 636 670 -
450 CFM/TON
CFM - 1604 1602 1600 1598 1596 1593 1590 1585 1578
13
Indoor Blower Performance
Indoor Fan Performance (230v) 4TCY4048 (230vperformance)
Horizontal Airflow
4TCY4048-HOR DIPSWITCH SETTINGS External Static Pressure (in. wg)
AIRFLOW SETTING 1 2 3 4 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Watts 187 232 264 291 318 347 379 413 446 472 -
350 CFM/TON OFF OFF OFF ON
CFM 1355 1387 1396 1392 1382 1370 1360 1351 1341 1326 -
Watts 315 324 352 389 428 464 498 529 563 606 -
400 CFM/TON* OFF OFF OFF OFF
CFM 1603 1581 1577 1580 1583 1583 1577 1567 1558 1556 -
Watts 301 431 507 552 584 615 651 694 739 779 -
450 CFM/TON OFF OFF ON OFF
CFM 1752 1794 1812 1816 1812 1806 1800 1797 1793 1785
Down Airflow
4TCY4048-DOWN DIPSWITCH SETTINGS External Static Pressure (in. wg)
AIRFLOW SETTING 1 2 3 4 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Watts 208 254 284 312 343 379 414 437 460 490 -
350 CFM/TON OFF OFF OFF ON
CFM 1337 1393 1398 1388 1383 1390 1399 1384 1380 1370 -
Watts 302 349 386 423 465 509 552 583 599 628 -
400 CFM/TON* OFF OFF OFF OFF
CFM 1574 1580 1585 1589 1594 1598 1601 1597 1584 1556 -
Watts 501 523 555 592 631 672 714 760 800 845 -
450 CFM/TON OFF OFF ON OFF
CFM 1847 1823 1817 1818 1820 1819 1817 1820 1815 1810
Horizontal Airflow
4TCY4060A-HOR DIPSWITCH SETTINGS External Static Pressure (in. wg)
AIRFLOW SETTING 1 2 3 4 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
Watts 394 427 464 504 548 591 633 668 - - -
350 CFM/TON OFF OFF OFF ON
CFM 1673 1772 1799 1793 1779 1771 1767 1756 - - -
Watts 695 642 660 710 764 811 849 893 966 1108 -
400 CFM/TON* OFF OFF OFF OFF
CFM 2054 2036 2031 2032 2033 2031 2023 2012 2002 2000 -
Down Airflow
4TCY4060A-DOWN DIPSWITCH SETTINGS External Static Pressure (in. wg)
AIRFLOW SETTING 1 2 3 4 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
Watts 443 461 493 532 571 607 642 680 - - -
350 CFM/TON OFF OFF OFF ON
CFM 1796 1741 1726 1725 1722 1712 1698 1692 - - -
Watts 740 697 715 763 819 866 892 894 872 835 -
400 CFM/TON* OFF OFF OFF OFF
CFM 2010 1987 1979 1977 1976 1969 1950 1913 1852 1759 -
14
Indoor Blower Performance
4TCY4024 AIRFLOW WITH AUXILIARY HEAT (CFM)
COOLING FAN DELAY OPTIONS
SWITCH SETTINGS SELECTION NOMINAL AIRFLOW
7-OFF 8-OFF LOW 700 CFM NOMINAL
7-ON 8-OFF HIGH 800 CFM SWITCH SETTINGS DELAY AIRFLOW
7-OFF 8-ON HIGH 800 CFM 5-OFF 6-OFF NONE 100%
7-ON 8-ON HIGH 800 CFM 5-ON 6-OFF 45 SEC 100%
5-OFF 6-ON 90 SEC 50%
5-ON 6-ON ** 50-100%
4TCY4030 AIRFLOW WITH AUXILIARY HEAT (CFM)
** This ENHANCED MODE selection provides a
SWITCH SETTINGS SELECTION NOMINAL AIRFLOW ramping up and ramping down of the indoor blower
7-OFF 8-OFF LOW 1050 CFM speed to provide improved comfort, quietness, and
7-ON 8-OFF HIGH 1200 CFM potential energy savings. The Graph below shows
7-OFF 8-ON HIGH 1200 CFM the ramping process
7-ON 8-ON HIGH 1200 CFM 100% if necessary
as required
4TCY4042 AIRFLOW WITH AUXILIARY HEAT (CFM) 1 7.5 3
minute minutes minutes
SWITCH SETTINGS SELECTION NOMINAL AIRFLOW COMPRESSOR OPERATION ON OFF
7-OFF 8-OFF LOW 1400 CFM
7-ON 8-OFF HIGH 1600 CFM
7-OFF 8-ON HIGH 1600 CFM
7-ON 8-ON HIGH 1600 CFM
15
Typical Wiring
16
Typical Wiring
17
Optional Equipment
BAYCURB050A FULL PERIMETER ROOF MOUNTING CURB FOR *****024-036
17 7/8
46 3/8
3
3 5/8
19 1/2 14”
2 3/16
19 1/2
15
38 7/8
14
The drawings on this page are prepared by
1 1/2 the manufacturer in order to provide detail
regarding job layout only. These drawings
are not intended to be used as a basis to
construct, build or modify the items de-
picted in the drawings. The manufacturer is
not responsible for the unauthorized use of
these drawings and expressly disclaims any
liability for damages resulting from such
unauthorized use.
43 3/8
35 7/8
18
Optional Equipment
BAYCURB051A Full Perimeter Roof Mounting Curb for *****042-060
15 7/8
56 1/8
3
1 1/2
10 7/8
19 1/2
20 4 3/4
19 1/2
41 7/8
14
38 7/8 53 1/8
19
Optional Equipment
BAYECON101,102A Down Discharge Economizer and Rain Hood
(Mounts Over Horizontal Return Air Opening)
HVAC Unit
Economizer
rain hood
Economizer Unit Application Models A
4TC*,WC*,YC*,DC*
Outside air BAYECON101A 20.125"
dampers *018-036
Return
air damp- Required
4TC*,WC*,YC*, DC*
ers filter kit, order
BAYECON102A 24.375"
separately *042-060
Mist elimi-
nator
Relief
damper Return
Roofcurb Duct
Economizer A B C D E F
20
Optional Equipment
BAYOSAH001,002A, 25% Outside Air Damper
(Replaces Filter/Coil Access Panel)
FULLY
B CLOSED
B
C
4YC,WC3018-036
4TC*3018-036,
BAYDMPR101A 15 13/16"" 11 13/16"" 10 1/4"" 11 1/2"" 12 1/4""
4W/T/Y/DCY4024-036,
4W/Y/DCZ6036
4YC,WC3042-060,
4TC*3042-060,
BAYDMPR102A 18 3/16"" 15 1/8"" 10 1/4"" 11 1/2"" 12 1/4""
4W/T/Y/DCY4042-060,
4W/Y/DCZ6048-060
21
Optional Equipment
BAYFLTR101, 201B, 1" - 2" Filter Rack
(Mounts in Filter/Coil Section)
Filter
The drawings on this page are prepared by the manufacturer in order to provide detail regarding job layout only. These drawings are not
intended to be used as a basis to construct, build or modify the items depicted in the drawings. The manufacturer is not responsible for the
unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use.
22
Dimensional Data and Weights
23
Dimensional Data and Weights
24
Dimensional Data and Weights
25
Dimensional Data and Weights
26
Dimensional Data and Weight
27
Dimensional Data and Weight
28
Mechanical Specifications
General Condenser Coil Single Source Power Entry
The units shall be horizontal airflow as The Spine Fin™condenser coil shall be This accessory, when used with electric
shipped and convertible to downflow. All continuously wrapped, corrosion resis- heat accessory, shall allow single source
units shall be factory assembled, piped, in- tant all aluminum with minimum brazed power connection to unit and heater com-
ternally wired and fully charged with R‑22. joints. This coil is 3/8 inch O.D. seamless bination. Single source power entry kits
All units shall be factory run tested to check aluminum tubing glued to a continuous shall have specific matching heater(s). Kit
cooling operation, fan and blower rotation aluminum fin. Coils are lab tested to shall include high voltage terminal blocks,
and control sequence. Units shall be designed withstand 2,000 pounds of pressure per fuse blocks and fuses, cut‑to‑length in-
to operate at ambient temperatures between terconnecting wiring, and junction box (if
square inch. The outdoor coil provides
55°F and 115°F in cooling as manufactured. required) to provide power sources with
low airflow resistance and efficient heat fuse protection as required for both the
Cooling performance shall be rated in accor-
transfer. The coil is protected on all four unit and accessory heater. Kit components
dance with A.H.R.I. standards.
sides by louvered panels. shall install within the heater cabinet in the
Unit Casing Indoor Air Fan heater access section. Single source branch
All panels shall be heavy gauge steel, gas- Direct-drive, forward-curved, centrifugal power circuit shall be protected and wired
keted and insulated. Foil-faced fiber insula- wheel in a Composite Vortica® Blower in accordance with local codes.
tion shall be in the heater section. Foil-faced housing. Motor shall have thermal overload
fiber insulation shall be in the evaporator protection and permanently lubricated Fully Modulating Economizer
section. Base pan shall be heavy gauge steel. motor bearings. Motor/blower assembly This accessory shall be field installed and be
WEATHERGUARD™exteriorcorrosionresistant isolated from unit with rubber mounts. composed of the following items: 0‑100% fresh
screws shall be used for added resistance to air damper, damper drive motor, fixed dry bulb
rust and corrosion. Outdoor Fan enthalpy control, and low voltage pigtails for
One direct‑drive, statically and dynami- electrical connections. Solid state enthalpy
Compressor cally balanced propeller fan shall be used in or differential enthalpy control is optional.
The compressor shall be a hermetically a drawthrough configuration. Permanently Economizer operations shall be controlled by
sealed, high efficiency Climatuff® com- lubricated weather proof motor shall have the preset position of the enthalpy control.
pressor. Internal overcurrent and over built‑in thermal overload protection. A barometic relief damper shall be standard
temperature protection, internal pressure with the downflow economizer and provide a
relief shall be standard. Other features System Controls pressure operated damper that shall be gravity
include, centrifugal oil pump and low vibra- System controls include condenser fan, closing and prohibit entrance of outside air on
tion and noise. evaporator fan and compressor contactors. equipment “off” cycle.
Trane Trane has a policy of continuous product and product data improvement and it reserves the right to change design
6200 Troup Highway and specifications without notice.
Tyler, TX 75707-9010
29