InteliSysNTC

BaseBox

Order code: IS-NTC-BB

Gen-set controller
Datasheet
Product description
Comprehensive paralleling gen-set controller Compatible with ComAp's InteliVision displays
Parallel operation up to 32 gen-sets Active e-mail messaging and SMS
High level control for complex systems Extensive built-in protection functions
CHP and gas engine controller Standard protections
User configurable protection
Key features
Extendable with ComAp's extension modules
Load sharing and VAr sharing via CAN
True RMS (TRMS) is used with Voltage, Current
Virtual shared inputs and outputs via CAN
and Power measurement
Support of wide range of applications
Single or multiple gen-sets in parallel to mains Application overview
operation with automatic back up function,
multiple island operation
Advanced power management function
Customizable load control in parallel to mains
Wide range of ECU support
Extended communication capabilities
Built-in web server
Full Modbus slave support
GPS and AirGate support and more
Highly configurable
Timers,Extended internal PLC , Force values
and more

| InteliSys NTC BaseBox Datasheet | Related HW ver: 2.0 | Related SW ver: 3.3.0 | Date of issue: 9/19/2019
Technical data
Power supply Binary outputs
Power supply range 8-36 VDC Number 16 non-isolated
0.4 A / 8 VDC Max current 0.5 A (2 A per group)
Power consumption 0.15 A / 24 VDC Switching to negative/positive supply terminal
0.1 A / 36 VDC
10 years (replaceable by official Analog inputs
RTC battery
service) Number 4 non-isolated
Fusing 2 A (without BOUT consumption) Switchable (Voltage, Resistance,
Type
Current)
Operating conditions
Resolution 10 bits, max 4 decimals
Operating temperature -40°C to +70°C
Range 0-5 VDC/0-2500 Ω/0-20 mA
Storage temperature -40°C to +80°C
Input impedance >100 kΩ/>100 kΩ/180 Ω
2000 m above sea level for
±1 % of meas. value ±1 mV
max 480 V
Max. operating altitude Accuracy ±2 % of meas value ±2 Ω
4000 m above sea level for ±1 % of meas value ±0.5 mA
max 400 V
Operating humidity 95% w/o condensation Analog outputs
5-25 Hz, ±1.6 mm Number 1
Vibration
25-100 Hz, a=4 g
Type Switchable (Voltage, Current)
Shocks a=200 m/s2
Range 0-10 VDC/0-20 mA

Voltage measurement Max current/load 5 mA/500 Ω


±0.5 % of output value ±20 mV
Measurement 3 ph-n Gen voltage Accuracy
±0.5 % of output value ±100 μA
inputs 3 ph-n Mains/Bus voltage
Measurement
110V / 277V ph-n
Magnetic pick-up
range
Voltage input range 2 Vpk-pk to 50 Veff
Max allowed
125 % ph-n Frequency input range 4 Hz to 15 kHz
voltage
Frequency measurement tolerance 0.2 %
Accuracy 1 % of 110V / 277V
Frequency range 40-70 Hz (at accy 0.1 Hz) Voltage regulator output
0.6 MΩ ph-ph
Input impedance Type 5 V TTL PWM / ± 10 VDC with IG-AVRi interface
0.3 MΩ ph-n

Current measurement Speed governor output


Voltage output ± 10 VDC / max.15 mA
3 ph Gen current
1 ph Mains current Voltage output via
Measurement inputs ± 10 VDC via 10 kΩ resistor / max . 1 mA
resistor
galvanically isolated
PWM 500÷3000 Hz / 5V / max. 10mA
Measurement range 1A/5A
Max allowed continuous
200 % / 200 % Communications
current
RS232 Direct/Modbus, non-isolated
Accuracy 2 % of 1 A / 5 A
RS485 Direct/Modbus, isolated
Input impedance <0.1 Ω
non-isolated RS485, only terminal
Display port
Binary inputs connection
USB port Direct, isolated
Number 16 non-isolated
galvanically isolated
Input resistance 4.7 kΩ
Ethernet port LAN/Internet, Modbus TCP, SNMP,
0-2 VDC close contact
Close/Open indication WebServer, AirGate
>4 VDC open contact
External modules
CAN1
250 kbps, max 200 m, Isolated
Intercontroller and comm extensions
CAN2
250/50 kbps, max 200/1000 m, Isolated

InteliSys NTC BaseBox Datasheet 2


Dimensions, terminals and mounting

Panel door mounting DIN-rail mounting Panel door mounting


with InteliVision 5 with InteliVision 8

① InteliVision5
② InteliSysNTC BaseBox
③ DIN-rail
④ InteliVision 8

Note: InteliSysNTC BaseBox can be mounted on a standard DIN rail or, in combination with InteliVision 5 or
InteliVision 8, it can be door mounted. InteliVision 5 features mounting rail for direct mounting. Mounting in
combination with InteliVision 8 uses four screws provided in the InteliSysNTC BaseBox package.

InteliSys NTC BaseBox Datasheet 3


Available extension modules
Product Description Order code
Inteli IO8/8 8 Binary inputs, 8 Binary outputs and 2 Analog outputs packed in a small unit (HW switchable to IO16/0) I-IO8/8
Inteli IO8/8 HW switchableto IO16/0 - 16 Binary inputs packed in a small unit I-IO8/8
Inteli AIN8 8 Analog inputs (R, I, V) and 1 pulse/frequency input in a small unit I-AIN8
Inteli AIN8TC 8 Thermocouple Analog inputs in a small unit I-AIN8TC
Inteli AIO9/1 9 Analog inputs (4x DC, 4x thermocouples, 1x R) in a small unit I-AIO9/1
IS-AIN8 8 Analog inputs packed in a rugged metal unit IS-AIN8
IGS-PTM 8 Binary inputs, 8 Binary outputs, 4 Analog inputs and 1 Analog output in a unit IGS-PTM
IGL-RA15 15 Binary LED output (3 colors) packed in a rugged metal unit IGL-RA15
I-AOUT8 8 Analog outputs packed in a rugged metal unit I-AOUT8
InternetBridge-NT Multiple Internet connections (PC and Modbus) to all controllers on CAN2 or RS485 IB-NT
I-LB+ Direct connection (PC) to all controllers on CAN2 or RS485 I-LB+

Related products
Product Description Order code
InteliVision 5 Color 5.6" display for monitoring and control INTELIVISION 5
InteliVision 8 Color 8" display for advanced monitoring, control & trending, USB capable INTELIVISION 8
InteliVision 12Touch Color 12" touch display for advanced monitoring, control & trending, USB capable RD1IV12TBZH
Color 17“ touchscreen display designed for complete monitoring and control of multiple
InteliVision 17Touch IV17T2
controllers or cogeneration installation.
ECON-4 Digital speed governor dedicated for speed control of gas or diesel engines. ECON-4

Functions and protections


The described product fully supports the following functions and protections as defined by ANSI (American National
Standards Institute):

Description ANSI code Description ANSI code


Synchronism check 25 Overcurrent (IDMT) 51
Undervoltage 27 Earth fault current IDMT 51N+64
Overload 32 Power factor 55
Load shedding 32P Overvoltage 59
Reverse power 32R Gas (fuel) level 71
Undercurrent 37 Vector shift 78
Excitation loss 40 AC reclosing 79
Current unbalance 46 Overfrequency 81H
Temperature monitoring 49T Underfrequency 81L
Generator overcurrent 50 ROCOF 81R
Earth fault current 50N+64

Certificates and standards


This product is CE compliant.

EN 60068-2-6 ed.2:2008; EN 60068-2-27 ed.2:2010; EN 60068-2-30, May 2000