Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

IG NTC BB Datasheet - 1

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

InteliGen NTC

BaseBox

Order code: IG-NTC-BB

Gen-set Controller
Datasheet
Product description
Comprehensive paralleling gen-set controller Extensive built-in protection functions
Parallel operation up to 32 gen-sets Standard protections
High level control for complex systems User configurable protection
CHP and gas engine controller Extendable with ComAp's extension modules
True RMS (TRMS) is used with Voltage, Current
Key features
and Power measurement
Load sharing and VAr sharing via CAN
Virtual shared inputs and outputs via CAN Application overview
Support of wide range of applications
Single or multiple gen-sets in parallel to mains
operation with automatic back up function, multiple
island operation
Advanced power management function
Customizable load control in parallel to mains
Wide range of ECU support
Extended communication capabilities
Built-in web server
Full Modbus slave support
GPS and AirGate support and more
Highly configurable
Timers,Internal PLC , Force values and more
Compatible with ComAp's InteliVision displays
Active e-mail messaging and SMS

| InteliGen NTC BaseBox Datasheet | Related HW ver: 2.0 | Related SW ver: 3.3.0 | Date of issue: 9/19/2019
Technical data
Power supply Binary outputs
Power supply Number 16, non-isolated
8-36 V DC
range Max current 0.5 A (2 A per group)
0.4 A / 8 VDC Switching to Negative/positive supply terminal
Power consumption 0.15 A / 24 VDC
0.1 A / 36 VDC Analog inputs
10 years Number 3, non-isolated
RTC battery
(replaceable by official service) Switchable (Voltage, Resistance,
Type
Fusing 2 A (without BOUT consumption) Current)
Max. Power Resolution 10 bits, max 4 decimals
16 W
Dissipation Range 0-5 V DC / 0-2500 Ω / 0-20 mA

Operating conditions Input impedance >100 kΩ / >100 kΩ / 180 Ω


±1 % of meas. value ±5 mV
Operating
-40 ˚C to +70 ˚C Accuracy ±2 % of meas value ±2 Ω
temperature
±1 % of meas value ±0.5 mA
Storage temperature -40 ˚C to +80 ˚C
2000 m above sea level Magnetic pick-up
Max.operating
4000 m above sea level for Voltage input range 2 Vpk-pk to 50 Veff
altitude
max Ph-Ph voltage 400V AC
Frequency input
Operating humidity 95 % w/o condensation 4 Hz to 15 kHz
range
5-25 Hz, ±1.6 mm Frequency
Vibration
25-100 Hz, a = 4 g measurement 0.2 %
Shocks a=200 m/s2 tolerance
Heat radiation 16 W
Voltage regulator output
Voltage measurement 5 V TTL PWM / ±10 V DC with IG-
Type
Measurement 3 ph-n Gen voltage AVRi interface
inputs 3 ph-n Mains voltage/Bus voltage
Speed governor output
Measurement range 110V / 277V
Voltage output ±10 V DC / max. 10 mA
Max allowed
125 % ph-n Voltage output via ±10 V DC via 10 kΩ resistor / max . 1
voltage
resistor mA
Accuracy 1 % of 110V / 277V
PWM 500÷3000 Hz / 5 V / max. 10 mA
40-70 Hz (accuracy 0.1 Hz)
Frequency range
45-55 Hz (accuracy <0.01 Hz) Communications
Input impedance 0.6 MΩ ph-ph, 0.3 MΩ ph-n RS232 Direct / Modbus, non-isolated
RS485 Direct / Modbus, isolated
Current measurement
Non-isolated RS485, only terminal
3 ph Gen current Display port
Measurement connection
1 ph Mains current
inputs USB port Direct, Isolated
galvanically isolated
Measurement range 1A/5A galvanically isolated
Ethernet port LAN/Internet, Modbus TCP,
Max allowed
200 % / 200 % SNMP, WebServer, AirGate
continuous current
Accuracy 2 % of 1 A / 5 A External modules, 250 kbps, max
CAN1
200 m, Isolated
Input impedance < 0.1 Ω
Intercontroller and comm
Binary inputs CAN2 extensions, 250 / 50 kbps, max 200
/ 1000 m, Isolated
Number 16, non-isolated

Input resistance 4.7 kΩ

Close/Open 0-2 V DC close contact


indication >4 V DC open contact

InteliGen NTC BaseBox Datasheet 2


Dimensions, terminals and mounting

Panel door mounting DIN-rail mounting Panel door mounting


with InteliVision 5 with InteliVision 8

① InteliVision5
② InteliGenNTC-BaseBox
③ DIN-rail
④ InteliVision 8

Note: InteliGenNTC BaseBox can be mounted on a standard DIN rail or, in combination with InteliVision 5 or
InteliVision 8, it can be door mounted. InteliVision 5 features mounting rail for direct mounting. Mounting in
combination with InteliVision 8 uses four screws provided in the InteliGenNTC BaseBox package.

InteliGen NTC BaseBox Datasheet 3


Available Extension modules
Product Description Order code
8 Binary inputs, 8 Binary outputs and 2 Analog outputs in a small unit (HW switchable to IO16/0) I-IO8/8
Inteli IO8/8
HW switchableto IO16/0 - 16 Binary inputs packed in a small unit I-IO8/8
Inteli AIN8 8 Analog inputs (R, I, V) and 1 pulse/frequency input in a small unit I-AIN8
Inteli AIN8TC 8 Thermocouple Analog inputs in a small unit I-AIN8TC
Inteli AIO9/1 9 Analog inputs (4x DC, 4x thermocouples, 1x R) in a small unit I-AIO9/1
IS-AIN8 8 Analog inputs packed in a rugged metal unit IS-AIN8
IGS-PTM 8 Binary inputs, 8 Binary outputs, 4 Analog inputs and 1 Analog output in a unit IGS-PTM
IGL-RA15 15 Binary LED output (3 colors) packed in a rugged metal unit IGL-RA15
I-AOUT8 8 Analog outputs packed in a rugged metal unit I-AOUT8
I-LB+ Direct connection (PC) to all controllers on CAN2 or RS485 I-LB+
IB-NT Communication Module with Cellular/Ethernet Connection IB-NT

Related products
Product Description Order code
InteliVision 5 Color 5.6" display for monitoring and control INTELIVISION 5
InteliVision 8 Color 8" display for advanced monitoring, control & trending, USB capable INTELIVISION 8
InteliVision 12Touch Color 12" touch display for advanced monitoring, control & trending, USB capable RD1IV12TBZH
Color 18“ touchscreen display designed for complete monitoring and control of multiple
InteliVision 18Touch RD31840PBIE
controllers or cogeneration installation.
ECON-4 Digital speed governor dedicated for speed control of gas or diesel engines. ECON-4

Functions and protections


The product fully supports functions and protections as defined by ANSI (American National Standards
Institute). Examples are bellow. Other functions can be found in the IGS-NT Reference guide.

ANSI ANSI ANSI ANSI


Description Description Description Description
code code code code
Synchronism
25 Excitation loss 40 Overcurrent (IDMT) 51 AC reclosing 79
check
Current Earth fault current
Undervoltage 27 46 51N+64 Overfrequency 81H
unbalance IDMT

Certificates and standards


EN 60068-2-6 EN 60068-2-64
ed.2:2008 EN 61010-1:2003
EN 60068-2-27
ed.2:2010
EN 60068-2-30,
May 2000
List of standards is available on: https://webstore.iec.ch/

Manufacturer:
ComAp a.s.
Czech Republic E-mail: info@comap-control.com
Phone: +420 246 012 111 Web: www.comap-control.com

© ComAp. Features and specification are subject to change without prior notice.

You might also like