Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                
Download as pdf or txt
Download as pdf or txt
You are on page 1of 32

1 2 3 4 5 6 7 8

D
C
Client :
M/S: HYUNDAI ENGINEERING
Project :
B
TOWER PROJECT
TYPICAL PANEL QTY
Panel Reference : Standard Equipment Type:
1 PLOT-C MDB-1 1
2 PLOT-D MDB-1 1
TEMPORARY MDB-1 PANEL -
-
Item No. :_1_ 02
Quantity :______
ENTEQ Trading & Contracting CO. W.L.L Revision Mark
A
0 25/02/2020 FOR APPROVAL ES OE FY GE Scale : Order No. : Drawing No. : Sheet No. :
IND DATE NATURE OF MODIFICATION Drawn By Designed By Checked By Approved By NTS ENT-12/220/ MDB1-C 01
GENERAL DATA
LOCATION OUTDOOR WALL
MOUNTING SURFACE FLUSH
D Q TECHNICAL DATA
CABLE ENTRY & ACCESS INCOMING OUTGOING
F F FUSE
TOP ENTRY
BOTTOM ENTRY
A A FRONT ACCESS
ELERTRICAL DATA
V V
RATED SERVICE VOLTAGE 415V
RATED CURRENT 1250A
Hz V RATED FREQUENCY 50Hz
C
CUBICLE DATA
SS
CUBICLE SYSTEM SCHNEIDER
STANDARD IEC 61439-1, 2 & 3
PMU
L1
L2
L3
DEGREE OF PROTECTION IP-54
FORM OF CONSTRUCTION FORM-2B
RYB
ACCESS CLOSING FRONT ROVER WITH DOOR
PAINT FINISH RAL 7035
CT1-3
p2 s2
p2
p1

s1 p1

MAIN BUSBARS 36 kA 1 Sec


B
COPPER PAN ASSEMBLY STANDARD NEUTRAL LINK & EARTH LINK
CONSTRUCTION DATA
EXTERNAL CABLE CONNECTION DIRECT ON DEVICE TERMINAL
WIRING IDENTIFICATION RED,YELLOW,BLUE,BLACK,YELLOW/GREEN
EQUIPMENT MOUNTING FIXED INCOMING & OUTGOINGS
LABELS ARE WHITE BARKGROUND PVC ADHESIVE
BLACK LETTERS IN ENGLISH.
A
PROJECT : PANEL ID: DRAWING NO. :
TOWER PROJECT TEMPORARY MDB-1 PANEL SHEET NO:
ENTEQ ENT-12/220/ MDB1-C 02
25/02/2020
0 FOR APPROVAL CONTRACTOR : TITLE : Trading & Contracting
IND DATE NATURE OF MODIFICATION IND DATE NATURE OF MODIFICATION
HYUNDAI ENGINEERING GENERAL ARRANGEMENT
INDEX
D
R Y B
R-PHASE Y-PHASE B-PHASE
HEALTHY HEALTHY HEALTHY
PMU
L1
L2
L3
C
B
400
800 1200 800
A
PROJECT : PANEL ID: DRAWING NO. :
TOWER PROJECT TEMPORARY MDB-1 PANEL SHEET NO:
ENTEQ ENT-12/220/ MDB1-C 03
25/02/2020
0 FOR APPROVAL CONTRACTOR : TITLE : Trading & Contracting
IND DATE NATURE OF MODIFICATION IND DATE NATURE OF MODIFICATION
HYUNDAI ENGINEERING GENERAL ARRANGEMENT
INDEX
D
TRANSPARENT DEAD FRONT COVER
C
B
Gland Plate
A
PROJECT : PANEL ID: DRAWING NO. :
TOWER PROJECT TEMPORARY MDB-1 PANEL SHEET NO:
ENTEQ ENT-12/220/ MDB1-C 04
25/02/2020
0 FOR APPROVAL CONTRACTOR : TITLE : Trading & Contracting
IND DATE NATURE OF MODIFICATION IND DATE NATURE OF MODIFICATION
HYUNDAI ENGINEERING COMPONENT LAYOUT
INDEX
1250A, TPN 36 kA 1 sec Busbar 2x50x10
PE
D
N
R,Y,B
PMU
p2 s2

L1
CT1-3
p2

L2
L3
p1

s1 p1

1250/5A
MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB
C 1250A 800A 400A 400A 400A 400A 400A 400A 400A
TP TP TP TP TP TP TP TP TP
B
Y
R
B
FEEDER REF Q Q1 Q2 Q3 Q4 Q5 Q6 Q7 Q8
BREAKER RATING 1250 A MCCB 800 A MCCB 400 A MCCB 400 A MCCB 400 A MCCB 400 A MCCB 400 A MCCB 400 A MCCB 400 A MCCB
DESIGNATION INCOMER
FEEDER SMDB-1 SMDB-3 SMDB-5 SMDB-6 SMDB-7 SMDB-8 SMDB-9 SMDB-10
FROM QC-GEN-1
CABLER SIZE 2x4Cx120 mm² 4Cx120 mm² 4Cx120 mm² 4Cx120 mm² 4Cx120 mm² 4Cx120 mm² 4Cx120 mm² 4Cx120 mm² 4Cx120 mm²
1Cx120 mm² 1Cx70 mm² 1Cx70 mm² 1Cx70 mm² 1Cx70 mm² 1Cx70 mm² 1Cx70 mm² 1Cx70 mm² 1Cx70 mm²
A
LOAD IN KW - - - - - - - - -
PROJECT : PANEL ID: DRAWING NO. :
TOWER PROJECT TEMPORARY MDB-1 PANEL SHEET NO:
ENTEQ ENT-12/220/ MDB1-C 05
25/02/2020
0 FOR APPROVAL CONTRACTOR : TITLE : Trading & Contracting
IND DATE NATURE OF MODIFICATION IND DATE NATURE OF MODIFICATION
HYUNDAI ENGINEERING POWERLINE DRAWING
INDEX
PE
D
N
R,Y,B
MCCB MCCB MCCB MCCB
C 400A 400A 200A 200A
TP TP TP TP
B
FEEDER REF Q9 Q10 Q11 Q12
BREAKER RATING 400 A MCCB 400 A MCCB 200 A MCCB 200 A MCCB
DESIGNATION
FEEDER SPARE SPARE SPARE SPARE
CABLER SIZE - - - -
- - - -
A
LOAD IN KW - - - -
PROJECT : PANEL ID: DRAWING NO. :
TOWER PROJECT TEMPORARY MDB-1 PANEL SHEET NO:
ENTEQ ENT-12/220/ MDB1-C 06
25/02/2020
0 FOR APPROVAL CONTRACTOR : TITLE : Trading & Contracting
IND DATE NATURE OF MODIFICATION IND DATE NATURE OF MODIFICATION
HYUNDAI ENGINEERING POWERLINE DIAGRAM
INDEX
1 2 3 4 5 6 7 8
D
C
Client :
M/S: HYUNDAI ENGINEERING
Project :
B
TOWER PROJECT
TYPICAL PANEL QTY
Panel Reference : Standard Equipment Type:
1 PLOT-C MDB-2 1
2 PLOT-D MDB-2 1
-
TEMPORARY MDB-2 PANEL -
Item No. :_1_ Quantity :___02__
ENTEQ Trading & Contracting CO. W.L.L Revision Mark
A
0 25/02/2020 FOR APPROVAL ES OE FY GE Scale : Order No. : Drawing No. : Sheet No. :
IND DATE NATURE OF MODIFICATION Drawn By Designed By Checked By Approved By NTS ENT-12/220/ MDB2-C 01
GENERAL DATA
LOCATION OUTDOOR WALL
MOUNTING SURFACE FLUSH
D Q TECHNICAL DATA
CABLE ENTRY & ACCESS INCOMING OUTGOING
F F FUSE
TOP ENTRY
BOTTOM ENTRY
A A FRONT ACCESS
ELERTRICAL DATA
V V
RATED SERVICE VOLTAGE 415V
RATED CURRENT 1250A
Hz V RATED FREQUENCY 50Hz
C
CUBICLE DATA
SS
CUBICLE SYSTEM SCHNEIDER
STANDARD IEC 61439-1, 2 & 3
PMU
L1
L2
L3
DEGREE OF PROTECTION IP-54
FORM OF CONSTRUCTION FORM-2B
RYB
ACCESS CLOSING FRONT ROVER WITH DOOR
PAINT FINISH RAL 7035
CT1-3
p2 s2
p2
p1

s1 p1

MAIN BUSBARS 36 kA 1 Sec


B
COPPER PAN ASSEMBLY STANDARD NEUTRAL LINK & EARTH LINK
CONSTRUCTION DATA
EXTERNAL CABLE CONNECTION DIRECT ON DEVICE TERMINAL
WIRING IDENTIFICATION RED,YELLOW,BLUE,BLACK,YELLOW/GREEN
EQUIPMENT MOUNTING FIXED INCOMING & OUTGOINGS
LABELS ARE WHITE BARKGROUND PVC ADHESIVE
BLACK LETTERS IN ENGLISH.
A
PROJECT : PANEL ID: DRAWING NO. :
TOWER PROJECT TEMPORARY MDB-2 PANEL SHEET NO:
ENTEQ ENT-12/220/ MDB2-C 02
25/02/2020
0 FOR APPROVAL CONTRACTOR : TITLE : Trading & Contracting
IND DATE NATURE OF MODIFICATION IND DATE NATURE OF MODIFICATION
HYUNDAI ENGINEERING GENERAL ARRANGEMENT
INDEX
D
R Y B
R-PHASE Y-PHASE B-PHASE
HEALTHY HEALTHY HEALTHY
PMU
L1
L2
L3
C
1600
B
400
800 1200 800
TYPICAL PANEL QTY
1 PLOT-C MDB-2 1
2 PLOT-D MDB-2 1
A
PROJECT : PANEL ID: DRAWING NO. :
TOWER PROJECT TEMPORARY MDB-2 PANEL SHEET NO:
ENTEQ ENT-12/220/ MDB2-C 03
25/02/2020
0 FOR APPROVAL CONTRACTOR : TITLE : Trading & Contracting
IND DATE NATURE OF MODIFICATION IND DATE NATURE OF MODIFICATION
HYUNDAI ENGINEERING GENERAL ARRANGEMENT
INDEX
D
TRANSPARENT DEAD FRONT COVER
C
B
Gland Plate
A
PROJECT : PANEL ID: DRAWING NO. :
TOWER PROJECT TEMPORARY MDB-2 PANEL SHEET NO:
ENTEQ ENT-12/220/ MDB2-C 04
25/02/2020
0 FOR APPROVAL CONTRACTOR : TITLE : Trading & Contracting
IND DATE NATURE OF MODIFICATION IND DATE NATURE OF MODIFICATION
HYUNDAI ENGINEERING COMPONENT LAYOUT
INDEX
1250A, TPN 36 kA 1 sec Busbar 2x50x10
PE
D
N
R,Y,B
PMU
p2 s2

L1
CT1-3
p2

L2
L3
p1

s1 p1

1250/5A
MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB
C 1250A 800A 400A 400A 400A 400A 400A 200A 200A
TP TP TP TP TP TP TP TP TP
B
Y
R
B
FEEDER REF Q Q1 Q2 Q3 Q4 Q5 Q6 Q7 Q8
BREAKER RATING 1250 A MCCB 800 A MCCB 400 A MCCB 400 A MCCB 400 A MCCB 400 A MCCB 400 A MCCB 200 A MCCB 200 A MCCB
DESIGNATION INCOMER
FEEDER FROM QC-GEN-01 (PLOT-C) SMDB-2 SMDB-4 SPARE SPARE SPARE SPARE SPARE SPARE
CABLER SIZE 2x4Cx120 mm² 4Cx120 mm² 4Cx120 mm² 4Cx120 mm² 4Cx120 mm² 4Cx120 mm² 4Cx120 mm² 4Cx120 mm² 4Cx120 mm²
1Cx120 mm² 1Cx70 mm² 1Cx70 mm² 1Cx70 mm² 1Cx70 mm² 1Cx70 mm² 1Cx70 mm² 1Cx70 mm² 1Cx70 mm²
A
LOAD IN KW - - - - - - - - -
PROJECT : PANEL ID: DRAWING NO. :
TOWER PROJECT TEMPORARY MDB-2 PANEL SHEET NO:
ENTEQ ENT-12/220/ MDB2-C 05
25/02/2020
0 FOR APPROVAL CONTRACTOR : TITLE : Trading & Contracting
IND DATE NATURE OF MODIFICATION IND DATE NATURE OF MODIFICATION
HYUNDAI ENGINEERING POWERLINE DRAWING
INDEX
PE
D
N
R,Y,B
MCCB MCCB MCCB MCCB
C 200A 200A 150A 150A
TP TP TP TP
B
FEEDER REF Q9 Q10 Q11 Q12
BREAKER RATING 200 A MCCB 200 A MCCB 150 A MCCB 150 A MCCB
DESIGNATION
FEEDER SPARE SPARE SPARE SPARE
CABLER SIZE - - - -
- - - -
A
LOAD IN KW - - - -
PROJECT : PANEL ID: DRAWING NO. :
TOWER PROJECT TEMPORARY MDB-2 PANEL SHEET NO:
ENTEQ ENT-12/220/ MDB2-C 06
25/02/2020
0 FOR APPROVAL CONTRACTOR : TITLE : Trading & Contracting
IND DATE NATURE OF MODIFICATION IND DATE NATURE OF MODIFICATION
HYUNDAI ENGINEERING POWERLINE DIAGRAM
INDEX
1 2 3 4 5 6 7 8
D
C
Client :
M/S: HYUNDAI ENGINEERING
Project :
B
TOWER PROJECT
TYPICAL PANEL QTY
Panel Reference : Standard Equipment Type:
1 PLOT-C SMDB-1 1
2 PLOT-D SMDB-1 1
-
SMDB-1 -
Item No. :_1_ 02
Quantity :______
ENTEQ Trading & Contracting CO. W.L.L Revision Mark
A
0 25/02/2020 FOR APPROVAL ES OE FY GE Scale : Order No. : Drawing No. : Sheet No. :
IND DATE NATURE OF MODIFICATION Drawn By Designed By Checked By Approved By NTS ENT-12/220/ SMDB1-C 01
GENERAL DATA
LOCATION OUTDOOR WALL
MOUNTING SURFACE FLUSH
D Q TECHNICAL DATA
CABLE ENTRY & ACCESS INCOMING OUTGOING
F F FUSE
TOP ENTRY
BOTTOM ENTRY
A A FRONT ACCESS
ELERTRICAL DATA
V V
RATED SERVICE VOLTAGE 415V
RATED CURRENT 800A
Hz V RATED FREQUENCY 50Hz
C
CUBICLE DATA
SS
CUBICLE SYSTEM SCHNEIDER
STANDARD IEC 61439-1, 2 & 3
PMU
L1
L2
L3
DEGREE OF PROTECTION IP-54
FORM OF CONSTRUCTION FORM-2B
RYB
ACCESS CLOSING FRONT ROVER WITH DOOR
PAINT FINISH RAL 7035
CT1-3
p2 s2
p2
p1

s1 p1

MAIN BUSBARS 36 kA 1 Sec


B
COPPER PAN ASSEMBLY STANDARD NEUTRAL LINK & EARTH LINK
CONSTRUCTION DATA
EXTERNAL CABLE CONNECTION DIRECT ON DEVICE TERMINAL
WIRING IDENTIFICATION RED,YELLOW,BLUE,BLACK,YELLOW/GREEN
EQUIPMENT MOUNTING FIXED INCOMING & OUTGOINGS
LABELS ARE WHITE BARKGROUND PVC ADHESIVE
BLACK LETTERS IN ENGLISH.
A
PROJECT : PANEL ID: DRAWING NO. :
TOWER PROJECT SMDB-1 SHEET NO:
ENTEQ ENT-12/220/ SMDB1-C 02
25/02/2020
0 FOR APPROVAL CONTRACTOR : TITLE : Trading & Contracting
IND DATE NATURE OF MODIFICATION IND DATE NATURE OF MODIFICATION
HYUNDAI ENGINEERING GENERAL ARRANGEMENT
INDEX
400
D
R
R-PHASE

Y
Y-PHASE

B
B-PHASE
HEALTHY HEALTHY HEALTHY
PMU
L1
L2
L3
C
1600
B
1200
TYPICAL PANEL QTY
1 PLOT-C SMDB-1 1
A 2 PLOT-D SMDB-1 1
PROJECT : PANEL ID: DRAWING NO. :
TOWER PROJECT SMDB-1 SHEET NO:
ENTEQ ENT-12/220/ SMDB1-C 03
25/02/2020
0 FOR APPROVAL CONTRACTOR : TITLE : Trading & Contracting
IND DATE NATURE OF MODIFICATION IND DATE NATURE OF MODIFICATION
HYUNDAI ENGINEERING GENERAL ARRANGEMENT
INDEX
800A, TPN 36 kA 1 sec Busbar 1x50x10
PE
D
N
R,Y,B
PMU
p2 s2

L1
CT1-3
p2

L2
L3
p1

s1 p1

800/5A
MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB
C 800A 400A 400A 400A 400A 100A 200A 100A 100A
TP TP TP TP TP TP TP TP TP
B
Y
R
B
FEEDER REF Q Q1 Q2 Q3 Q4 Q5 Q6 Q7 Q8
BREAKER RATING 800 A MCCB 400 A MCCB 400 A MCCB 400 A MCCB 400 A MCCB 100 A MCCB 200 A MCCB 100 A MCCB 100 A MCCB
DESIGNATION
FEEDER INCOMER (FROM MDB-1) TC-1 TC-2 TC-3 TC-4 QC-DB-1 to QC-DB-4 HOIST HOIST QC-DB-5 to QC-DB-8
CABLER SIZE 1x4Cx120 mm² 1x4Cx120 mm² 1x4Cx120 mm² 1x4Cx120 mm² 1x4Cx120 mm² 1x4Cx70 mm² 1x4Cx95 mm² 1x4Cx70 mm² 1x4Cx70 mm²
1Cx70 mm² 1Cx35 mm² 1Cx70 mm² 1Cx70 mm² 1Cx70 mm² 1Cx35 mm² 1Cx50 mm² 1Cx35 mm² 1Cx35 mm²
A
LOAD IN KW - - - - - - - - -
PROJECT : PANEL ID: DRAWING NO. :
TOWER PROJECT SMDB-1 SHEET NO:
ENTEQ ENT-12/220/ SMDB1-C 04
25/02/2020
0 FOR APPROVAL CONTRACTOR : TITLE : Trading & Contracting
IND DATE NATURE OF MODIFICATION IND DATE NATURE OF MODIFICATION
HYUNDAI ENGINEERING POWERLINE DRAWING
INDEX
PE
D
N
R,Y,B
MCCB MCCB MCCB MCCB
C 100A 100A 100A 100A
TP TP TP TP
B
FEEDER REF Q9 Q10 Q11 Q12
BREAKER RATING 100 A MCCB 100 A MCCB 100 A MCCB 100 A MCCB
DESIGNATION
FEEDER QC-DB-9 to QC-DB-12 QC-DB-25 to QC-DB-28 SPARE SPARE
CABLER SIZE 1x4Cx70 mm² 1x4Cx70 mm² - -
1Cx35 mm² 1Cx35 mm² - -
A
LOAD IN KW - - - -
PROJECT : PANEL ID: DRAWING NO. :
TOWER PROJECT SMDB-1 SHEET NO:
ENTEQ ENT-12/220/ SMDB1-C 05
25/02/2020
0 FOR APPROVAL CONTRACTOR : TITLE : Trading & Contracting
IND DATE NATURE OF MODIFICATION IND DATE NATURE OF MODIFICATION
HYUNDAI ENGINEERING POWERLINE DIAGRAM
INDEX
1 2 3 4 5 6 7 8
D
C
Client :
M/S: HYUNDAI ENGINEERING
Project :
B
TOWER PROJECT
TYPICAL PANEL QTY
Panel Reference : Standard Equipment Type:
1 PLOT-C SMDB-2 1
2 PLOT-D SMDB-2 1
-
SMDB-2 -
Item No. :_1_ 01
Quantity :______
ENTEQ Trading & Contracting CO. W.L.L Revision Mark
A
0 25/02/2020 FOR APPROVAL ES OE FY GE Scale : Order No. : Drawing No. : Sheet No. :
IND DATE NATURE OF MODIFICATION Drawn By Designed By Checked By Approved By NTS ENT-12/220/ SMDB2-C 01
GENERAL DATA
LOCATION OUTDOOR WALL
MOUNTING SURFACE FLUSH
D Q TECHNICAL DATA
CABLE ENTRY & ACCESS INCOMING OUTGOING
F F FUSE
TOP ENTRY
BOTTOM ENTRY
A A FRONT ACCESS
ELERTRICAL DATA
V V
RATED SERVICE VOLTAGE 415V
RATED CURRENT 800A
Hz V RATED FREQUENCY 50Hz
C
CUBICLE DATA
SS
CUBICLE SYSTEM SCHNEIDER
STANDARD IEC 61439-1, 2 & 3
PMU
L1
L2
L3
DEGREE OF PROTECTION IP-54
FORM OF CONSTRUCTION FORM-2B
RYB
ACCESS CLOSING FRONT ROVER WITH DOOR
PAINT FINISH RAL 7035
CT1-3
p2 s2
p2
p1

s1 p1

MAIN BUSBARS 36 kA 1 Sec


B
COPPER PAN ASSEMBLY STANDARD NEUTRAL LINK & EARTH LINK
CONSTRUCTION DATA
EXTERNAL CABLE CONNECTION DIRECT ON DEVICE TERMINAL
WIRING IDENTIFICATION RED,YELLOW,BLUE,BLACK,YELLOW/GREEN
EQUIPMENT MOUNTING FIXED INCOMING & OUTGOINGS
LABELS ARE WHITE BARKGROUND PVC ADHESIVE
BLACK LETTERS IN ENGLISH.
A
PROJECT : PANEL ID: DRAWING NO. :
TOWER PROJECT SMDB-2 SHEET NO:
ENTEQ ENT-12/220/ SMDB2-C 02
25/02/2020
0 FOR APPROVAL CONTRACTOR : TITLE : Trading & Contracting
IND DATE NATURE OF MODIFICATION IND DATE NATURE OF MODIFICATION
HYUNDAI ENGINEERING GENERAL ARRANGEMENT
INDEX
400
D
R
R-PHASE

Y
Y-PHASE

B
B-PHASE
HEALTHY HEALTHY HEALTHY
PMU
L1
L2
L3
C
1600
B
1200
TYPICAL PANEL QTY
1 PLOT-C SMDB-2 1
2 PLOT-D SMDB-2 1
A
PROJECT : PANEL ID: DRAWING NO. :
TOWER PROJECT SMDB-2 SHEET NO:
ENTEQ ENT-12/220/ SMDB2-C 03
25/02/2020
0 FOR APPROVAL CONTRACTOR : TITLE : Trading & Contracting
IND DATE NATURE OF MODIFICATION IND DATE NATURE OF MODIFICATION
HYUNDAI ENGINEERING GENERAL ARRANGEMENT
INDEX
800A, TPN 36 kA 1 sec Busbar 1x50x10
PE
D
N
R,Y,B
PMU
p2 s2

L1
CT1-3
p2

L2
L3
p1

s1 p1

800/5A
MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB
C 800A 400A 400A 400A 400A 100A 100A 100A 100A
TP TP TP TP TP TP TP TP TP
B
Y
R
B
FEEDER REF Q Q1 Q2 Q3 Q4 Q5 Q6 Q7 Q8
BREAKER RATING 800 A MCCB 400 A MCCB 400 A MCCB 400 A MCCB 400 A MCCB 100 A MCCB 100 A MCCB 100 A MCCB 100 A MCCB
DESIGNATION
FEEDER INCOMER (FROM MDB-2) TC-5 TC-6 TC-7 TC-8 QC-DB-13 to QC-DB-16 QC-DB-17 to QC-DB-20 QC-DB-21 to QC-DB-24 QC-DB-65 to QC-DB-68
CABLER SIZE 1x4Cx120 mm² 1x4Cx120 mm² 1x4Cx120 mm² 1x4Cx120 mm² 1x4Cx120 mm² 1x4Cx70 mm² 1x4Cx70 mm² 1x4Cx70 mm² 1x4Cx70 mm²
1Cx70 mm² 1Cx35 mm² 1Cx70 mm² 1Cx70 mm² 1Cx70 mm² 1Cx35 mm² 1Cx35 mm² 1Cx35 mm² 1Cx35 mm²
A
LOAD IN KW - - - - - - - - -
PROJECT : PANEL ID: DRAWING NO. :
TOWER PROJECT SMDB-2 SHEET NO:
ENTEQ ENT-12/220/ SMDB2-C 04
25/02/2020
0 FOR APPROVAL CONTRACTOR : TITLE : Trading & Contracting
IND DATE NATURE OF MODIFICATION IND DATE NATURE OF MODIFICATION
HYUNDAI ENGINEERING POWERLINE DRAWING
INDEX
PE
D
N
R,Y,B
MCCB MCCB MCCB MCCB
C 100A 100A 100A 100A
TP TP TP TP
B
FEEDER REF Q9 Q10 Q11 Q12
BREAKER RATING 100 A MCCB 100 A MCCB 100 A MCCB 100 A MCCB
DESIGNATION
FEEDER SPARE SPARE SPARE SPARE
CABLER SIZE - - - -
- - - -
A
LOAD IN KW - - - -
PROJECT : PANEL ID: DRAWING NO. :
TOWER PROJECT SMDB-2 SHEET NO:
ENTEQ ENT-12/220/ SMDB2-C 05
25/02/2020
0 FOR APPROVAL CONTRACTOR : TITLE : Trading & Contracting
IND DATE NATURE OF MODIFICATION IND DATE NATURE OF MODIFICATION
HYUNDAI ENGINEERING POWERLINE DIAGRAM
INDEX
1 2 3 4 5 6 7 8
D
C
Client :
M/S: HYUNDAI ENGINEERING
Project :
B
TOWER PROJECT
TYPICAL PANEL QTY
Panel Reference : Standard Equipment Type:
1 PLOT-C SMDB-3 1
2 PLOT-D SMDB-3 1
-
SMDB-3 -
Item No. :_1_ 01
Quantity :______
ENTEQ Trading & Contracting CO. W.L.L Revision Mark
A
0 25/02/2020 FOR APPROVAL ES OE FY GE Scale : Order No. : Drawing No. : Sheet No. :
IND DATE NATURE OF MODIFICATION Drawn By Designed By Checked By Approved By NTS ENT-12/220/ SMDB3-C 01
GENERAL DATA
LOCATION OUTDOOR WALL
MOUNTING SURFACE FLUSH
D Q TECHNICAL DATA
CABLE ENTRY & ACCESS INCOMING OUTGOING
F F FUSE
TOP ENTRY
BOTTOM ENTRY
A A FRONT ACCESS
ELERTRICAL DATA
V V
RATED SERVICE VOLTAGE 415V
RATED CURRENT 400A
Hz V RATED FREQUENCY 50Hz
C
CUBICLE DATA
SS
CUBICLE SYSTEM SCHNEIDER
STANDARD IEC 61439-1, 2 & 3
PMU
L1
L2
L3
DEGREE OF PROTECTION IP-54
FORM OF CONSTRUCTION FORM-2B
RYB
ACCESS CLOSING FRONT ROVER WITH DOOR
PAINT FINISH RAL 7035
CT1-3
p2 s2
p2
p1

s1 p1

MAIN BUSBARS 36 kA 1 Sec


B
COPPER PAN ASSEMBLY STANDARD NEUTRAL LINK & EARTH LINK
CONSTRUCTION DATA
EXTERNAL CABLE CONNECTION DIRECT ON DEVICE TERMINAL
WIRING IDENTIFICATION RED,YELLOW,BLUE,BLACK,YELLOW/GREEN
EQUIPMENT MOUNTING FIXED INCOMING & OUTGOINGS
LABELS ARE WHITE BARKGROUND PVC ADHESIVE
BLACK LETTERS IN ENGLISH.
A
PROJECT : PANEL ID: DRAWING NO. :
TOWER PROJECT SMDB-3 SHEET NO:
ENTEQ ENT-12/220/ SMDB3-C 02
25/02/2020
0 FOR APPROVAL CONTRACTOR : TITLE : Trading & Contracting
IND DATE NATURE OF MODIFICATION IND DATE NATURE OF MODIFICATION
HYUNDAI ENGINEERING GENERAL ARRANGEMENT
INDEX
0
30
D
R
R-PHASE

Y
Y-PHASE

B
B-PHASE
HEALTHY HEALTHY HEALTHY
PMU
L1
L2
L3
C
1400
B
800
TYPICAL PANEL QTY
1 PLOT-C SMDB-3 1
2 PLOT-D SMDB-3 1
A
PROJECT : PANEL ID: DRAWING NO. :
TOWER PROJECT SMDB-3 SHEET NO:
ENTEQ ENT-12/220/ SMDB3-C 03
25/02/2020
0 FOR APPROVAL CONTRACTOR : TITLE : Trading & Contracting
IND DATE NATURE OF MODIFICATION IND DATE NATURE OF MODIFICATION
HYUNDAI ENGINEERING GENERAL ARRANGEMENT
INDEX
400A, TPN 36 kA 3 sec Busbar 1x30x10
PE
D
N
R,Y,B
PMU
p2 s2

L1
CT1-3
p2

L2
L3
p1

s1 p1

400/5A
MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB
C 400A 100A 100A 100A 200A 100A 100A 100A 100A
TP TP TP TP TP TP TP TP TP
B
Y
R
B
FEEDER REF Q Q1 Q2 Q3 Q4 Q5 Q6 Q7 Q8
BREAKER RATING 400 A MCCB 100 A MCCB 100 A MCCB 100 A MCCB 200 A MCCB 100 A MCCB 100 A MCCB 100 A MCCB 100 A MCCB
DESIGNATION EXTERNAL DB'S EXTERNAL DB'S
FEEDER INCOMER (FROM MDB-1) QC-DB-29 to QC-DB-32 HOIST QC-DB-41 to QC-DB-44 QC-DB-45 to QC-DB-48 QC-DB-48 to QC-DB-52 QC-DB-53 to QC-DB-56
QC-DB-37 to QC-DB-40 QC-DB-33 to QC-DB-36
CABLER SIZE 1x4Cx120 mm² 1x4Cx70 mm² 1x4Cx70 mm² 1x4Cx70 mm² 1x4Cx95 mm² 1x4Cx70 mm² 1x4Cx70 mm² 1x4Cx70 mm² 1x4Cx70 mm²
1Cx70 mm² 1Cx35 mm² 1Cx35 mm² 1Cx35 mm² 1Cx50 mm² 1Cx35 mm² 1Cx35 mm² 1Cx35 mm² 1Cx35 mm²
A
LOAD IN KW - - - - - - - - -
PROJECT : PANEL ID: DRAWING NO. :
TOWER PROJECT SMDB-3 SHEET NO:
ENTEQ ENT-12/220/ SMDB3-C 04
25/02/2020
0 FOR APPROVAL CONTRACTOR : TITLE : Trading & Contracting
IND DATE NATURE OF MODIFICATION IND DATE NATURE OF MODIFICATION
HYUNDAI ENGINEERING POWERLINE DRAWING
INDEX
PE
D
N
R,Y,B
MCCB MCCB MCCB MCCB
C 100A 100A 100A 100A
TP TP TP TP
B
FEEDER REF Q9 Q10 Q11 Q12
BREAKER RATING 100 A MCCB 100 A MCCB 100 A MCCB 100 A MCCB
DESIGNATION
FEEDER QC-DB-57 to QC-DB-60 QC-DB-61 to QC-DB-64 SPARE SPARE
CABLER SIZE 1x4Cx70 mm² 1x4Cx70 mm² - -
1Cx35 mm² 1Cx35 mm² - -
A
LOAD IN KW - - - -
PROJECT : PANEL ID: DRAWING NO. :
TOWER PROJECT SMDB-3 SHEET NO:
ENTEQ ENT-12/220/ SMDB3-C 05
25/02/2020
0 FOR APPROVAL CONTRACTOR : TITLE : Trading & Contracting
IND DATE NATURE OF MODIFICATION IND DATE NATURE OF MODIFICATION
HYUNDAI ENGINEERING POWERLINE DIAGRAM
INDEX
1 2 3 4 5 6 7 8
D
C
Client :
M/S: HYUNDAI ENGINEERING
Project :
B
TOWER PROJECT
TYPICAL PANEL QTY
Panel Reference : Standard Equipment Type:
1 PLOT-C SMDB-4 to 10 7
2 PLOT-C SMDB-4 to 10 7
TYPICAL SMDB'S
-
SMDB-4 to SMDB-10 -
Item No. :_1_ 14
Quantity :______
ENTEQ Trading & Contracting CO. W.L.L Revision Mark
A
0 25/02/2020 FOR APPROVAL ES OE FY GE Scale : Order No. : Drawing No. : Sheet No. :
IND DATE NATURE OF MODIFICATION Drawn By Designed By Checked By Approved By NTS ENT-12/220/ SMDB4/10 01
GENERAL DATA
LOCATION OUTDOOR WALL
MOUNTING SURFACE FLUSH
D Q TECHNICAL DATA
CABLE ENTRY & ACCESS INCOMING OUTGOING
F F FUSE
TOP ENTRY
BOTTOM ENTRY
A A FRONT ACCESS
ELERTRICAL DATA
V V
RATED SERVICE VOLTAGE 415V
RATED CURRENT 400A
Hz V RATED FREQUENCY 50Hz
C
CUBICLE DATA
SS
CUBICLE SYSTEM SCHNEIDER
STANDARD IEC 61439-1, 2 & 3
PMU
L1
L2
L3
DEGREE OF PROTECTION IP-54
FORM OF CONSTRUCTION FORM-2B
RYB
ACCESS CLOSING FRONT ROVER WITH DOOR
PAINT FINISH RAL 7035
CT1-3
p2 s2
p2
p1

s1 p1

MAIN BUSBARS 36 kA 1 Sec


B
COPPER PAN ASSEMBLY STANDARD NEUTRAL LINK & EARTH LINK
CONSTRUCTION DATA
EXTERNAL CABLE CONNECTION DIRECT ON DEVICE TERMINAL
WIRING IDENTIFICATION RED,YELLOW,BLUE,BLACK,YELLOW/GREEN
EQUIPMENT MOUNTING FIXED INCOMING & OUTGOINGS
LABELS ARE WHITE BARKGROUND PVC ADHESIVE
BLACK LETTERS IN ENGLISH.
A
PROJECT : PANEL ID: DRAWING NO. :
TOWER PROJECT SMDB-4 to SMDB-10 SHEET NO:
ENTEQ ENT-12/220/ SMDB4/10 02
25/02/2020
0 FOR APPROVAL CONTRACTOR : TITLE : Trading & Contracting
IND DATE NATURE OF MODIFICATION IND DATE NATURE OF MODIFICATION
HYUNDAI ENGINEERING GENERAL ARRANGEMENT
INDEX
0
30
D
R
R-PHASE

Y
Y-PHASE

B
B-PHASE
HEALTHY HEALTHY HEALTHY
PMU
L1
L2
L3
C
1400
B
TYPICAL PANEL QTY 800
1 PLOT-C SMDB-4 to 10 7
2 PLOT-C SMDB-4 to 10 7
A
PROJECT : PANEL ID: DRAWING NO. :
TOWER PROJECT SMDB-4 to SMDB-10 SHEET NO:
ENTEQ ENT-12/220/ SMDB4/10 03
25/02/2020
0 FOR APPROVAL CONTRACTOR : TITLE : Trading & Contracting
IND DATE NATURE OF MODIFICATION IND DATE NATURE OF MODIFICATION
HYUNDAI ENGINEERING GENERAL ARRANGEMENT
INDEX
400A, TPN 36 kA 3 sec Busbar 1x30x10
PE
D
N
R,Y,B
PMU
p2 s2

L1
CT1-3
p2

L2
L3
p1

s1 p1

400/5A
MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB
C 400A 100A 100A 100A 200A 100A 100A 100A 100A
TP TP TP TP TP TP TP TP TP
B
Y
R
B
FEEDER REF Q Q1 Q2 Q3 Q4 Q5 Q6 Q7 Q8
BREAKER RATING 400 A MCCB 100 A MCCB 100 A MCCB 100 A MCCB 200 A MCCB 100 A MCCB 100 A MCCB 100 A MCCB 100 A MCCB
DESIGNATION EXTERNAL DB'S EXTERNAL DB'S
FEEDER INCOMER QC-DB-29 to QC-DB-32 HOIST QC-DB-41 to QC-DB-44 QC-DB-45 to QC-DB-48 QC-DB-48 to QC-DB-52 QC-DB-53 to QC-DB-56
QC-DB-37 to QC-DB-40 QC-DB-33 to QC-DB-36
CABLER SIZE 1x4Cx120 mm² 1x4Cx70 mm² 1x4Cx70 mm² 1x4Cx70 mm² 1x4Cx95 mm² 1x4Cx70 mm² 1x4Cx70 mm² 1x4Cx70 mm² 1x4Cx70 mm²
1Cx70 mm² 1Cx35 mm² 1Cx35 mm² 1Cx35 mm² 1Cx50 mm² 1Cx35 mm² 1Cx35 mm² 1Cx35 mm² 1Cx35 mm²
A
LOAD IN KW - - - - - - - - -
PROJECT : PANEL ID: DRAWING NO. :
TOWER PROJECT SMDB-4 to SMDB-10 SHEET NO:
ENTEQ ENT-12/220/ SMDB4/10 04
25/02/2020
0 FOR APPROVAL CONTRACTOR : TITLE : Trading & Contracting
IND DATE NATURE OF MODIFICATION IND DATE NATURE OF MODIFICATION
HYUNDAI ENGINEERING POWERLINE DRAWING
INDEX
PE
D
N
R,Y,B
MCCB MCCB MCCB MCCB
C 100A 100A 100A 100A
TP TP TP TP
B
FEEDER REF Q9 Q10 Q11 Q12
BREAKER RATING 100 A MCCB 100 A MCCB 100 A MCCB 100 A MCCB
DESIGNATION
FEEDER QC-DB-57 to QC-DB-60 QC-DB-61 to QC-DB-64 SPARE SPARE
CABLER SIZE 1x4Cx70 mm² 1x4Cx70 mm² - -
1Cx35 mm² 1Cx35 mm² - -
A
LOAD IN KW - - - -
PROJECT : PANEL ID: DRAWING NO. :
TOWER PROJECT SMDB-4 to SMDB-10 SHEET NO:
ENTEQ ENT-12/220/ SMDB4/10 05
25/02/2020
0 FOR APPROVAL CONTRACTOR : TITLE : Trading & Contracting
IND DATE NATURE OF MODIFICATION IND DATE NATURE OF MODIFICATION
HYUNDAI ENGINEERING POWERLINE DIAGRAM
INDEX