Altivar Machine 320: Variable Speed Drive For Asynchronous and Synchronous Motors PROFIBUS DP Manual - VW3A3607
Altivar Machine 320: Variable Speed Drive For Asynchronous and Synchronous Motors PROFIBUS DP Manual - VW3A3607
Altivar Machine 320: Variable Speed Drive For Asynchronous and Synchronous Motors PROFIBUS DP Manual - VW3A3607
NVE41310 04/2016
www.schneider-electric.com
The information provided in this documentation contains general descriptions and/or technical character-
istics of the performance of the products contained herein. This documentation is not intended as a
substitute for and is not to be used for determining suitability or reliability of these products for specific user
applications. It is the duty of any such user or integrator to perform the appropriate and complete risk
analysis, evaluation and testing of the products with respect to the relevant specific application or use
thereof. Neither Schneider Electric nor any of its affiliates or subsidiaries shall be responsible or liable for
misuse of the information contained herein. If you have any suggestions for improvements or amendments
or have found errors in this publication, please notify us.
No part of this document may be reproduced in any form or by any means, electronic or mechanical,
including photocopying, without express written permission of Schneider Electric.
All pertinent state, regional, and local safety regulations must be observed when installing and using this
product. For reasons of safety and to help ensure compliance with documented system data, only the
manufacturer should perform repairs to components.
When devices are used for applications with technical safety requirements, the relevant instructions must
be followed.
Failure to use Schneider Electric software or approved software with our hardware products may result in
injury, harm, or improper operating results.
Failure to observe this information can result in injury or equipment damage.
© 2016 Schneider Electric. All rights reserved.
2 NVE41310 04/2016
Table of Contents
Safety Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Chapter 1 Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Hardware Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Software Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Chapter 2 Basics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.2 Common Additional Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Identification and Maintenance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
I&M Record . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
2.3 PROFIdrive Parameters Channel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
PROFIdrive Profile. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Parameter Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
PROFIdrive Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
PROFIdrive Parameter Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Chapter 3 Hardware Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Hardware Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Firmware and Description File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Installation of the Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Electrical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Cable Routing Practices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Chapter 4 Software Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
4.1 Basic Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
[Address] AdrC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
[Data rate used] bdrU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
[PPO profile used] PrFL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
[DP Master Active] dPMA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
4.2 Communication Profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Definition of a Profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Functional Profiles Supported by the Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Functional Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
CIA402 Operating State Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Description of Operating States. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Cmd Register CMd . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Stop Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Assigning Control Word Bits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
[CIA402 State Reg] EtA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Starting Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Sequence for a Drive Powered by the Power Stage Supply . . . . . . . . . . . . . . . . . . . . . . . . . 55
Sequence for a Drive with Separate Control Stage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Sequence for a Drive with Mains Contactor Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Telegram 100, 101, 102 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Configuring Drive with a Siemens© S7-300 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Configuration of Drive with the Telegram 100 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Configuring a Drive with the Telegram 101, 102 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Parameters Management with the Telegram 100, 101, 102 . . . . . . . . . . . . . . . . . . . . . . . . . 66
NVE41310 04/2016 3
Telegram 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
State Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Command Word and Operating State Word . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Reference Frequency. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
4.3 Fieldbus Integration Tutorial. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Fieldbus Integration Tutorial. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Chapter 5 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
5.1 Operating States . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Configuring Communication Error Response. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
5.2 Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Configuring the Control Channel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Configuration of the Drive for Operation in I/O Profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Configuration of the Drive for Operation with CiA 402 Profile in Combined Mode. . . . . . . . . 86
Configuration of the Drive for Operation with CiA 402 Profile in Separate Mode. . . . . . . . . . 87
Chapter 6 Diagnostic and Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Fieldbus Status LEDs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Connection for Fieldbus Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Fieldbus Function Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Communication Interruption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Monitoring of Communication Channel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Control-Signal Diagnostics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
4 NVE41310 04/2016
Safety Information
Important Information
NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device before
trying to install, operate, service, or maintain it. The following special messages may appear throughout
this documentation or on the equipment to warn of potential hazards or to call attention to information that
clarifies or simplifies a procedure.
PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this
material.
A qualified person is one who has skills and knowledge related to the construction and operation of
electrical equipment and its installation, and has received safety training to recognize and avoid the
hazards involved.
Qualification Of Personnel
Only appropriately trained persons who are familiar with and understand the contents of this manual and
all other pertinent product documentation are authorized to work on and with this product. In addition, these
persons must have received safety training to recognize and avoid hazards involved. These persons must
have sufficient technical training, knowledge and experience and be able to foresee and detect potential
hazards that may be caused by using the product, by changing the settings and by the mechanical,
electrical and electronic equipment of the entire system in which the product is used. All persons working
on and with the product must be fully familiar with all applicable standards, directives, and accident
prevention regulations when performing such work.
NVE41310 04/2016 5
Intended Use
This product is a drive for three-phase asynchronous motors and intended for industrial use according to
this manual.The product may only be used in compliance with all applicable safety standard and local
regulations and directives, the specified requirements and the technical data. The product must be
installed outside the hazardous ATEX zone. Prior to using the product, you must perform a risk assessment
in view of the planned application. Based on the results, the appropriate safety measures must be
implemented.Since the product is used as a component in an entire system, you must ensure the safety
of persons by means of the design of this entire system (for example, machine design). Any use other than
the use explicitly permitted is prohibited and can result in hazards. Electrical equipment should be installed,
operated, serviced, and maintained only by qualified personnel.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Only appropriately trained persons who are familiar with and understand the contents of this manual
and all other pertinent product documentation and who have received safety training to recognize and
avoid hazards involved are authorized to work on and with this drive system. Installation, adjustment,
repair and maintenance must be performed by qualified personnel.
The system integrator is responsible for compliance with all local and national electrical code
requirements as well as all other applicable regulations with respect to grounding of all equipment.
Many components of the product, including the printed circuit boards, operate with mains voltage. Do
not touch. Use only electrically insulated tools.
Do not touch unshielded components or terminals with voltage present.
Motors can generate voltage when the shaft is rotated. Prior to performing any type of work on the
drive system, block the motor shaft to prevent rotation.
AC voltage can couple voltage to unused conductors in the motor cable. Insulate both ends of unused
conductors of the motor cable.
Do not short across the DC bus terminals or the DC bus capacitors or the braking resistor terminals.
Before performing work on the drive system:
Disconnect all power, including external control power that may be present.
Place a Do Not Turn On label on all power switches.
Lock all power switches in the open position.
Wait 15 minutes to allow the DC bus capacitors to discharge. The DC bus LED is not an indicator
of the absence of DC bus voltage that can exceed 800 Vdc.
Measure the voltage on the DC bus between the DC bus terminals (PA/+, PC/-) using a properly
rated voltmeter to verify that the voltage is <42 Vdc
If the DC bus capacitors do not discharge properly, contact your local Schneider Electric represen-
tative. Do not repair or operate the product.
Install and close all covers before applying voltage.
Failure to follow these instructions will result in death or serious injury.
Drive systems may perform unexpected movements because of incorrect wiring, incorrect settings,
incorrect data or other errors.
WARNING
UNANTICIPATED EQUIPMENT OPERATION
Carefully install the wiring in accordance with the EMC requirements.
Do not operate the product with unknown or unsuitable settings or data.
Perform a comprehensive commissioning test.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Damaged products or accessories may cause electric shock or unanticipated equipment operation.
6 NVE41310 04/2016
DANGER
ELECTRIC SHOCK OR UNANTICIPATED EQUIPMENT OPERATION
Do not use damaged products or accessories.
Failure to follow these instructions will result in death or serious injury.
Contact your local Schneider Electric sales office if you detect any damage whatsoever.
WARNING
LOSS OF CONTROL
The designer of any control scheme must consider the potential failure modes of control paths and,
for critical control functions, provide a means to achieve a safe state during and after a path failure.
Examples of critical control functions are emergency stop, overtravel stop, power outage and restart.
Separate or redundant control paths must be provided for critical control functions.
System control paths may include communication links. Consideration must be given to the
implications of unanticipated transmission delays or failures of the link.
Observe all accident prevention regulations and local safety guidelines (1).
Each implementation of the product must be individually and thoroughly tested for proper operation
before being placed into service.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
(1) For USA: Additional information, refer to NEMA ICS 1.1 (latest edition), Safety Guidelines for the
Application, Installation, and Maintenance of Solid State Control and to NEMA ICS 7.1 (latest edition),
Safety Standards for Construction and Guide for Selection, Installation and Operation of Adjustable-Speed
Drive Systems.
NOTICE
DESTRUCTION DUE TO INCORRECT MAINS VOLTAGE
Before switching on and configuring the product, verify that it is approved for the mains voltage
Failure to follow these instructions can result in equipment damage.
The temperature of the products described in this manual may exceed 80 °C (176 °F) during operation.
WARNING
HOT SURFACES
Ensure that any contact with hot surfaces is avoided.
Do not allow flammable or heat-sensitive parts in the immediate vicinity of hot surfaces.
Verify that the product has sufficiently cooled down before handling it.
Verify that the heat dissipation is sufficient by performing a test run under maximum load conditions.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
The product is not approved for use in hazardous areas (explosive atmospheres).
WARNING
EXPLOSION HAZARD
Only use this device outside of hazardous areas (explosive atmospheres).
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Machines, controllers, and related equipment are usually integrated into networks. Unauthorized persons
and malware may gain access to the machine as well as to other devices on the network/fieldbus of the
machine and connected networks via insufficiently secure access to software and networks.
NVE41310 04/2016 7
WARNING
UNAUTHORIZED ACCESS TO THE MACHINE VIA SOFTWARE AND NETWORKS
In your hazard and risk analysis, consider all hazards that result from access to and operation on the
network/fieldbus and develop an appropriate cyber security concept.
Verify that the hardware infrastructure and the software infrastructure into which the machine is
integrated as well as all organizational measures and rules covering access to this infrastructure
consider the results of the hazard and risk analysis and are implemented according to best practices
and standards covering IT security and cyber security (such as: ISO/IEC 27000 series, Common
Criteria for Information Technology Security Evaluation, ISO/ IEC 15408, IEC 62351, ISA/IEC 62443,
NIST Cybersecurity Framework, Information Security Forum - Standard of Good Practice for
Information Security).
Verify the effectiveness of your IT security and cyber security systems using appropriate, proven
methods.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
8 NVE41310 04/2016
About the Book
At a Glance
Document Scope
The purpose of this document is to:
Show you how to install the PROFIBUS DP fieldbus module on the drive.
Show you how to configure the drive to use PROFIBUS DP fieldbus.
NOTE: Read and understand this document and all related documents (see below) before installing,
operating, or maintaining the drive.
Validity Note
This documentation is valid for the Altivar Machine drives.
The technical characteristics of the devices described in this document also appear online. To access this
information online:
Step Action
1 Go to the Schneider Electric home page www.schneider-electric.com.
2 In the Search box type the reference of a product or the name of a product range.
Do not include blank spaces in the reference or product range.
To get information on grouping similar modules, use asterisks (*).
3 If you entered a reference, go to the Product Datasheets search results and click on the
reference that interests you.
If you entered the name of a product range, go to the Product Ranges search results and click
on the product range that interests you.
4 If more than one reference appears in the Products search results, click on the reference that
interests you.
5 Depending on the size of your screen, you may need to scroll down to see the data sheet.
6 To save or print a data sheet as a .pdf file, click Download XXX product datasheet.
The characteristics that are presented in this manual should be the same as those characteristics that
appear online. In line with our policy of constant improvement, we may revise content over time to improve
clarity and accuracy. If you see a difference between the manual and online information, use the online
information as your reference.
NVE41310 04/2016 9
Related Documents
Use your tablet or your PC to quickly access detailed and comprehensive information on all our products
on www.schneider-electric.com
The internet site provides the information you need for products and solutions
The whole catalog for detailed characteristics and selection guides
The CAD files to help design your installation, available in over 20 different file formats
All software and firmware to maintain your installation up to date
A large quantity of White Papers, Environment documents, Application solutions, Specifications... to
gain a better understanding of our electrical systems and equipment or automation
And finally all the User Guides related to your drive, listed below:
You can download these technical publications and other technical information from our website at
http://download.schneider-electric.com
Terminology
The technical terms, terminology, and the corresponding descriptions in this manual normally use the
terms or definitions in the relevant standards.
In the area of drive systems this includes, but is not limited to, terms such as error, error message, failure,
fault, fault reset, protection, safe state, safety function, warning, warning message, and so on.
Among others, these standards include:
IEC 61800 series: Adjustable speed electrical power drive systems
IEC 61508 Ed.2 series: Functional safety of electrical/electronic/programmable electronic safety-related
EN 954-1 Safety of machinery - Safety related parts of control systems
EN ISO 13849-1 & 2 Safety of machinery - Safety related parts of control systems.
IEC 61158 series: Industrial communication networks - Fieldbus specifications
IEC 61784 series: Industrial communication networks - Profiles
IEC 60204-1: Safety of machinery - Electrical equipment of machines – Part 1: General requirements
In addition, the term zone of operation is used in conjunction with the description of specific hazards, and
is defined as it is for a hazard zone or danger zone in the EC Machinery Directive (2006/42/EC) and in ISO
12100-1.
Also see the glossary at the end of this manual.
10 NVE41310 04/2016
Altivar Machine 320
Presentation
NVE41310 04/2016
Chapter 1
Presentation
Presentation
NVE41310 04/2016 11
Presentation
Hardware Overview
General
The VW3A3607 is a PROFIBUS DP fieldbus module that can be used in a PROFIBUS DP industrial
fieldbus. The module has a 9-pin female Sub-D connector for connection to the PROFIBUS DP network.
The figure shows the hardware presentation of the VW3A3607 PROFIBUS DP fieldbus module:
12 NVE41310 04/2016
Presentation
Software Overview
Compatibility
The VW3A3607 communication module enables the integration of a variable speed drive into a PROFIBUS
DP fieldbus. This module offers the possibility to control its host drive in native profile or with the
PROFIdrive profile.
Profile Telegrams
Native drive profile (CiA®402) 100,101,102
I/O profile 100,101,102
PROFIdrive 1
NVE41310 04/2016 13
Presentation
14 NVE41310 04/2016
Altivar Machine 320
Basics
NVE41310 04/2016
Chapter 2
Basics
Basics
NVE41310 04/2016 15
Basics
Section 2.1
Introduction
Introduction
Introduction
PROFIBUS
PROFIBUS DP is the fast PROFIBUS version which is specially designed for communication in production
processes and for building automation. Features of PROFIBUS DP includes simple connection of new
devices in the bus and high transmission rates.
Device Identification
A master device uses the Ident number to identify the device class of the connected slave. The Ident
number is a unique number assigned to each device class by the PNO.
Slave Address
Each device on the network must be assigned a unique address from 1 to 126.
The master (normally address 0 ... 2) can communicate with each slave via this address.
PROFIBUS DP V1 Communication
PROFIBUS DP-V1 allows cyclic and acyclic communication between master and slave. Acyclic
communication is slower than cyclic communication, however it enables the modification of parameters
during operation.
The product supports acyclic communication as per PROFIBUS specification for MS0 communication.
The product supports acyclic communication for DP-V1 as per PROFIBUS specification for MS1 and MS2
communication.
The following services are available for acyclic communication:
16 NVE41310 04/2016
Basics
Section 2.2
Common Additional Features
NVE41310 04/2016 17
Basics
Overview
Identification & maintenance (I&M) is established through PNO
Supports the user during various scenarios of the device life cycle, such as:
Configuration
Commissioning
Repair and update
Operation and visualization
18 NVE41310 04/2016
Basics
I&M Record
Description
The table provides the details of I&M record:
NVE41310 04/2016 19
Basics
Section 2.3
PROFIdrive Parameters Channel
20 NVE41310 04/2016
Basics
PROFIdrive Profile
Overview
When operated with the PROFIdrive profile, the drive parameters are organized as defined by PNU
numbering and addressing modes. However, for people who are familiar with the Altivar parameters, this
addressing mode keeps the native structure of the device (based on Modbus addressing). PNU is
numbered from 0...65535 and each PNU represents a parameter (from single type as words to complex
data structure or arrays). PROFIdrive parameters from PNU 900 ...PNU 999 are standardized, they are
described below. All others PNUs are manufacturer-specific.
In the case of this drive, parameters can be separated in two groups:
Standardized PNUs (900...999)
Drive parameters which are gathered in a single PNU entry point: PNU1000 and Modbus address as
subindex. It is also possible to access the parameters using the Modbus address as PNU for each
parameter (1001...59999) and 0 as subindex.
NVE41310 04/2016 21
Basics
Parameter Structure
PROFIdrive Telegram
The table describes the PROFIdrive header:
DU Byte Nr Request
Function code 0 −
Slot_num 1 0: global parameters
Index 2 47: Reserved for PROFIdrive
Length 3 Length of PROFIdrive parameter channel frame
Data 4...5 PROFIdrive parameter channel frame: check
The access to the 3 different areas of a parameter is specified by the attribute field of the parameter
request.
The following diagram summarizes the parameter model (For more information, refer to the profile drive
technology V4 standard).
The parameters and their sub parts are identified as follows:
22 NVE41310 04/2016
Basics
Drive Parameters
Each drive parameter can be represented according to the PNU standard structure. Drive parameters are
part of the PNU 1000 or can be accessed using the Modbus address as PNU number.
The table provides the possible values of a parameter according to the PNU properties:
NVE41310 04/2016 23
Basics
PROFIdrive Parameters
24 NVE41310 04/2016
Basics
Parameters Requests
There are 2 types of request:
Request parameter (parameters are PNU number, attribute, and sub index)
Change parameter (parameters are PNU number, attribute, and sub index)
These requests are able to manage one or more parameters or several attributes of one parameter. In
order to access to a specific attribute of a parameter, the request header contains: the PNU, the sub index,
and an attribute. This attribute defines whether the request mentions the value, the description area, or the
text area.
Parameter Reading
Request
Response
NOTE: byte 41 hex, word 42 hex, standard integer 03 hex, double word 43 hex.
Parameter Writing
Request
Response
NVE41310 04/2016 25
Basics
With the sub index in addition to the detected error value, the total length of the answer is 10 bytes.
26 NVE41310 04/2016
Altivar Machine 320
Hardware Setup
NVE41310 04/2016
Chapter 3
Hardware Setup
Hardware Setup
NVE41310 04/2016 27
Hardware Setup
Hardware Presentation
1 Sub-D 9 connector
28 NVE41310 04/2016
Hardware Setup
Compatibility
The VW3A3607 fieldbus module version 1.CIE04 and higher is compliant with all Altivar Machine product
range.
The associated GSD is named as the following example:
SCHN0F85.GSD
The files are available on www.schneider-electric.com.
NVE41310 04/2016 29
Hardware Setup
Before Starting
Verify that the catalog number printed on the label corresponds to the purchase order.
Remove the fieldbus module from its packaging and check that it has not been damaged in transit.
DANGER
ELECTRIC SHOCK OR UNANTICIPATED EQUIPMENT OPERATION
Do not use damaged products or accessories.
Failure to follow these instructions will result in death or serious injury.
Step Action
1 Ensure that the power is off.
2 Locate the fieldbus module slot (A) on the bottom of the control part.
3 Insert the module.
4 Check that the module is correctly inserted and locked mechanically in the drive.
1 Slot A
Step Action
1 Ensure that the power is off.
2 Press the strip.
3 Remove the module while maintaining the strip pressed,
30 NVE41310 04/2016
Hardware Setup
Electrical Installation
Pin Layout
The VW3A3607 fieldbus module is equipped with a sub-D 9 female connector for the PROFIBUS DP
connection.
Use only validated PROFIBUS connectors. The PROFIBUS connectors are suitable for connecting the
fieldbus signal.
Connect the PROFIBUS signals.
If the device is at the end of the network, use a PROFIBUS connector with a terminating resistor.
Fasten the cables to the cable guide. The cable guide is not a strain relief.
The table provides the pin out details of the sub-D 9 connector:
Cable Specification
Cable specifications are as follows:
Use equipotential bonding conductors.
Use pre-assembled cables to reduce the wiring mistakes.
Shield: both end grounded.
Twisted-pair cable.
Verify that wiring, cables, and connected interfaces meet the PELV requirements.
The maximum cable length depends on the baud rate and the signal propagation delay, that is, shorter
bus cable for higher baud rate.
Data rate (kbps) 9.6 19.2 93.75 187.5 500 1500 3000 6000 12000
Distance m (ft.) 1200 1200 1200 1000 400 200 100 100 100
(4000) (4000) (4000) (3300) (1300) (650) (330) (330) (330)
NVE41310 04/2016 31
Hardware Setup
Terminating Resistor
Both ends of the entire PROFIBUS DP network must be terminated with a terminating resistor. Use
PROFIBUS connectors with integrated terminating resistors at both ends of the network.
The schematic diagram shows the terminating resistor combination:
32 NVE41310 04/2016
Hardware Setup
Installation Topology
The following figure shows an example of a wiring solution between a master and slaves using VW3A3607
fieldbus modules. The connector and cable for connection to the PROFIBUS DP network must be ordered
separately.
NVE41310 04/2016 33
Hardware Setup
34 NVE41310 04/2016
Altivar Machine 320
Software Setup
NVE41310 04/2016
Chapter 4
Software Setup
Software Setup
NVE41310 04/2016 35
Software Setup
Section 4.1
Basic Settings
Basic Settings
36 NVE41310 04/2016
Software Setup
Introduction
Overview
The parameters are described according to the graphic display terminal.
NVE41310 04/2016 37
Software Setup
[Address] AdrC
Access
The parameter is accessible in the [COMMUNICATION] COM/[COMMUNICATION CARD] Cbd-menu.
The parameter number is 6601
Possible Settings
38 NVE41310 04/2016
Software Setup
Access
The parameter is accessible in the [COMMUNICATION] COM-/[COMMUNICATION CARD] Cbd-
menu.
This is a read-only parameter
The parameter number is 6660
Possible Settings
NVE41310 04/2016 39
Software Setup
Access
The parameter is accessible in the [COMMUNICATION] COM-/[COMMUNICATION CARD] Cbd-
menu.
This is a read parameter.
The parameter number is 6665.
Possible Settings
The table presents the parameter settings:
40 NVE41310 04/2016
Software Setup
Access
The parameter is accessible in the [COMMUNICATION] COM-/[COMMUNICATION CARD] Cbd-
menu.
This is a read-only parameter
The parameter number is 6666
Possible Settings
NVE41310 04/2016 41
Software Setup
Section 4.2
Communication Profile
Communication Profile
42 NVE41310 04/2016
Software Setup
Definition of a Profile
Types of Profiles
There are 3 types of profile:
Communication profiles
Functional profiles
Application profiles
Communication Profile
A communication profile describes the characteristics of a bus or network:
Cables
Connectors
Electrical characteristics
Access protocol
Addressing system
Periodic exchange service
Messaging service
...
A communication profile is unique to a type of fieldbus (such as Modbus, PROFIBUS DP, and so on) and
is used by different types of devices.
Functional Profile
A functional profile describes the behavior of a type of device:
Functions
Parameters (such as name, format, unit, type, and so on.)
Periodic I/O variables
State chart
...
A functional profile is common to all members of a device family (such as variable speed drives, encoders,
I/O modules, displays, and so on).
They can feature common or similar parts. The standardized (IEC 61800-7) functional profiles of variable
speed drives are:
CiA402
PROFIDRIVE
CIP AC Drive
CiA402 device profile for drives and motion control represents the next stage of this standard development
and is now part of the IEC 61800-7 standard.
Application Profile
Application profile defines the services to be provided by the devices on a machine. For example, CiA DSP
417-2 V 1.01 part 2: CANopen application profile for lift control systems - virtual device definitions.
Interchangeability
The aim of communication and functional profiles is to achieve interchangeability of the devices connected
via the fieldbus.
NVE41310 04/2016 43
Software Setup
I/O Profile
Using the I/O profile simplifies PLC programming.
The I/O profile mirrors the use of the terminal strip for control by utilizing 1 bit to control a function.
The I/O profile for the drive can also be used when controlling via a fieldbus.The drive starts up as soon as
the run command is sent.15 bits of the control word (bits 1...15) can be assigned to a specific function.
This profile can be developed for simultaneous control of the drive via:
The terminals
The Modbus control word
The fieldbus module control word
The I/O profile is supported by the drive itself and therefore in turn by all the communication ports
(integrated Modbus, PROFIBUS DP ,PROFINET, EtherCAT, and DeviceNet fieldbus modules).
CiA402 Profile
The drive only starts up following a command sequence.
The control word is standardized.
5 bits of the control word (bits 11...15) can be assigned to a function.
The CiA402 profile is supported by the drive itself and therefore by all the communication ports.
The drive supports the velocity mode of CiA402 profile.
In the CiA402 profile, there are two modes that are specific to the drive and characterize commands and
references value management:
Separate [Separate] SEP
Not separate [Not separ.] SIm,
44 NVE41310 04/2016
Software Setup
Functional Description
Introduction
Drive operation involves two main functions, which are illustrated in the diagrams below.
CiA402
The main parameters are shown with their CiA402 name and their CiA402/Drivecom index (the values in
brackets are the CANopen addresses of the parameter).
The following figure shows the control diagram for drive operation:
Altivar Drive
These diagrams translate as follows for the Altivar drive.
The following figure shows the control diagram for drive operation:
NVE41310 04/2016 45
Software Setup
State Diagram
After switching on and when an operating mode is started, the product goes through a number of operating
states.
The state diagram (state machine) shows the relationships between the operating states and the state
transitions. The operating states are internally monitored and influenced by monitoring functions.
The following figure shows the CIA402 state diagram:
46 NVE41310 04/2016
Software Setup
NVE41310 04/2016 47
Software Setup
48 NVE41310 04/2016
Software Setup
Summary
Operating State Power Stage Supply for Power Supplied to Motor Modification of Configuration
Separate Control Stage Parameters
1 - Not ready to Not required No Yes
switch on
2 - Switch on Not required No Yes
disabled
3 - Ready to Not required No Yes
switch on
4 - Switched on Required No Yes, return to 2 - Switch on
disabled operating state
5 - Operation Required Yes No
enabled
6 - Quick stop Required Yes, during fast stop No
active
7 - Fault reaction Depends on error response Depends on error −
active configuration response configuration
8 - Fault Not required No Yes
NVE41310 04/2016 49
Software Setup
50 NVE41310 04/2016
Software Setup
Stop Commands
Halt Command
The Halt command enables movement to be interrupted without having to leave the 5 - Operation
enabled state. The stop is performed in accordance with the [Type of stop] Stt parameter.
If the Halt command is active, no power is supplied to the motor and no torque is applied.
Regardless of the assignment of the [Type of stop] Stt parameter [Fast stop Assign] FSt, [Ramp stop]
rMP, [Freewheel Stop] nSt, or [DC Injection Assign] dCI, the drive remains in the 5 - Operation
enabled state.
Freewheel Command
A Freewheel Stop command using a digital input of the terminal or a bit of the control word assigned
to Freewheel Stop causes a change to operating state 2 - Switch on disabled.
NVE41310 04/2016 51
Software Setup
Function Codes
In the CiA402 profile, fixed assignment of a function input is possible using the following codes:
For example, to assign the DC injection braking to bit13 of a fieldbus module, simply configure the [ DC
Injection Assign] dCI parameter with the [C313] C313 value.
Bit 11 is assigned by default to the operating direction command [Reverse Assign] rrS.
52 NVE41310 04/2016
Software Setup
Operating Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 ETA Masked
State Switch On Quick Voltage Fault Operation Switched Ready to by 006F H (1)
Disabled Stop Enabled Enabled On Switch On
1 -Not 0 X X 0 0 0 0 −
ready to
switch on
2 -Switch 1 X X 0 0 0 0 0040 hex
on
disabled
3 -Ready 0 1 X 0 0 0 1 0021 hex
to switch
on
4 - 0 1 1 0 0 1 1 0023 hex
Switched
on
5 - 0 1 11 0 1 1 1 0027 hex
Operation
enabled
6 -Quick 0 0 0 1 1 1 0007 hex
stop
active
7 -Fault 0 X X 1 1 1 1 −
reaction
active
8 -Fault 0 X X 1 0 0 0 0008 hex(2)..
.0028 hex
(1)
This mask can be used by the PLC program to test the diagram state.
(2)detected error following operating state 6 - Quick stop active.
X: In this state, the value of the bit can be 0 or 1.
NVE41310 04/2016 53
Software Setup
Starting Sequence
Description
The command sequence in the state diagram depends on how power is being supplied to the drive.
There are 3 possible scenarios:
54 NVE41310 04/2016
Software Setup
Description
Both the power and control stages are powered by the power stage supply.
If power is supplied to the control stage, it has to be supplied to the power stage as well.
The following sequence must be applied:
Step 1
Apply the 2 - Shut down command
Step 2
Check that the drive is in the operating state 3 - Ready to switch on.
Then apply the 4 - Enable operation command.
The motor can be controlled (send a reference value not equal to zero).
NOTE: It is possible, but not necessary to apply the 3 - Switch on command followed by the 4 -
Enable Operation command to switch successively into the operating states 3 - Ready to Switch
on, 4 - Switched on and then 5 - Operation Enabled. The 4 - Enable operation command
is sufficient.
NVE41310 04/2016 55
Software Setup
Description
Power is supplied separately to the power and control stages.
If power is supplied to the control stage, it does not have to be supplied to the power stage as well.
The following sequence must be applied:
Step 1
The power stage supply is not necessarily present.
Apply the 2 - Shut down command
Step 2
Check that the drive is in the operating state 3 - Ready to switch on.
Check that the power stage supply is present (Voltage enabled of the status word).
56 NVE41310 04/2016
Software Setup
Step 3
Check that the drive is in the operating state 4 - Switched on.
Then apply the 4 - Enable operation command.
The motor can be controlled (send a reference value not equal to zero).
If the power stage supply is still not present in the operating state 4 - Switched on after a time delay
[Mains V. time out] LCt, the drive triggers an error [Input Contactor] LCF.
NVE41310 04/2016 57
Software Setup
Description
Power is supplied separately to the power and control stages.
If power is supplied to the control stage, it does not have to be supplied to the power stage as well. The
drive controls the mains contactor.
The following sequence must be applied:
Step 1
The power stage supply is not present as the mains contactor is not being controlled.
Apply the 2 - Shutdown command.
Step 2
Check that the drive is in the operating state 3 - Ready to switch on.
Apply the 3 - Switch on command, which closes the mains contactor and switch on the power stage
supply.
58 NVE41310 04/2016
Software Setup
Overview
The following diagram shows the native modes for telegram 100:
The native mode of the PROFIBUS DP VW3A3607 is used when telegram 100 is used.
The PKW area of telegram 100, which is used for a simple parameter management, is compliant with the
PKW mechanism used with the PROFIBUS DP fieldbus module of the Altivar 32, 320, 61, 71.
NOTE: After switching from one telegram to another, the drive shall be restarted to validate the new
configuration.
The following diagram shows the native modes for telegram 101:
NVE41310 04/2016 59
Software Setup
The following diagram shows the native modes for telegram 102:
Periodic Exchanges
The following table provides the details of telegram 100, 101, and 102
The configuration of the cyclic data is made with the PROFIBUS DP master configuration tool. The Modbus
address of the parameter linked to each cyclic data must be defined as in the following example with the
HW configuration software:
Input cyclic data 1/2 and output cyclic data 1/2 are already preconfigured to (CMd) (8501) and (LFrd)
(8602); (EtA) (3201) and (rFrd) (8604).
If a null address Modbus is entered, no link between the related cyclic data and the drive is established. In
any case, the 6 cyclic data are not disabled and the 6 cyclic data takes place in the I/O memory image of
the controller.
60 NVE41310 04/2016
Software Setup
NVE41310 04/2016 61
Software Setup
GSD Installation
First download, and install the GSD file of the drive in the hardware configuration tool of the SIMATIC
STEP7® software.
You can find the GSD file and its associated picture on www.schneider-electric.com.
From the menu > Options > Install GSD File...
Once installed you can see the drive, in the library, as follow:
62 NVE41310 04/2016
Software Setup
Description
With this telegram, the drive is controlled with two process data.
Configure master PLC and its PROFIBUS DP network. Then select and place the drive from the library to
the bus:
Define the addresses of the cyclic data and PKW data in the PLC periphery:
By default, the process data are linked to (CMd), (LFrd), (EtA) and (rFrd) (native CiA 402 profile
of the drive).
NVE41310 04/2016 63
Software Setup
You can check that the exchanges are working properly with the Monitor/Modify function of the
configuration tool:
64 NVE41310 04/2016
Software Setup
New parameters are added or modified by entering the drive Modbus address.
For example: OMA3 is configured to read the value of ACC, which Modbus address is 9001.
NVE41310 04/2016 65
Software Setup
Description
In native modes several accesses to the drive parameters are possible:
The standard acyclic requests from PROFIdrive, for more information see PROFIdrive Parameters
Channel (see page 20).
PKW mechanisms.
The table lists the drive-to-controller parameters in the output PKW area:
66 NVE41310 04/2016
Software Setup
DU Byte - nr
Function code 0
Slot_num 1
Index 2
Length 3
Data 4-5
Step 2:
NVE41310 04/2016 67
Software Setup
68 NVE41310 04/2016
Software Setup
NVE41310 04/2016 69
Software Setup
Telegram 1
Overview
The following diagram shows the operating modes:
The following section describes how the VW3A3607 is operated when configured in PROFIdrive mode
(telegram 1).
The selection of this mode is done while configuring the slave device with the PROFIBUS DP network
configuration tool. It is out of the scope of this document to describe how to use such tool. However, you
can find in the examples (see Configuring the Drive With a Siemens© S7-300 ) how to configure the
module for the Schneider PLCs and for the SIMATIC® S7 PLCs.
Periodic Exchanges
The periodic exchanges, with PROFIdrive application class 1 profile consists of:
16-bit command word (STW1) and 16-bit reference word (NSOLL_A),
16-bit operating state word (ZSW1) and 16-bit actual velocity word (NIST_A).
The mapping of these words is automatically done when you select telegram 1 during the configuration of
the device.
NOTE: After switching from one telegram to another, restart the controller to validate the new configuration.
70 NVE41310 04/2016
Software Setup
State Diagram
Description
The following state diagram shows the PROFIdrive state machine for the application class 1. The diagram
also describes the command word and operating state word.
NVE41310 04/2016 71
Software Setup
Overview
The table lists the command wording from PROFIdrive application profile class 1:
STW1
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Fault reset − − − Enable Quick stop Coast stop ON/OFF
operation
The table lists the status from PROFIdrive application profile class 1:
ZSW1
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Warning Switching Quick stop Coast stop Error Operation Ready to Ready to
inhibited not activated not activated detected enabled operate switch ON
72 NVE41310 04/2016
Software Setup
STW1
Bit 0 ON 1 Switched on operating state; voltage at the power converters, indicates that
the power voltage is enabled.
OFF 0 The drive is ramped-down along the ramp (RFG) or along the current limit or
(OFF 1) along the voltage limit of the d.c. Link if standstill is detected and power is
disabled when deceleration bit 1 of ZSW1 is still set.
An OFF command is interruptible (the drive returns to the
ready for switching on operating state).
Bit 1 No coast stop 1 Coast Stop (OFF2) not active.
Coast stop (OFF 2) 0 Power voltage disabled..
The drive goes into the Switching On Inhibited Power voltage is
disabled; the motor coasts down to a standstill.
Bit 2 No quick stop 1 Quick Stop (OFF3) not active.
Quick stop (OFF 3) 0 Quick stop; if required, withdraw the operating enable, the drive is decelerated
as fast as possible. For example, along the current limit or at the voltage limit of
the d.c. Link, at n / f = 0; if the rectifier pulses are disabled, the power voltage
is disabled (the contact is opened) and the drive goes into the
Switching On Inhibited operating state.
A Quick Stop command is not interruptible.
Bit 3 Enable operation 1 Enable electronics and pulses.
The drive then runs-up to the reference frequency.
Disable operation 0 The drive coasts down to a standstill (ramp-function generator to 0 or tracking)
and goes into the Switched on operating state (refer to control word 1, bit 0).
Bit 4 Reserved
Bit 5 Reserved
Bit 6 Not used
Bit 7 Fault reset 1 The fault reset function is active with a positive edge; the drive error response
depends on the type of detected error. If the error response has isolated the
voltage, the drive then goes into the Switching On Inhibited operating
state.
Bit 8 Not used
Bit 9 Not used
Bit 10 Control by fieldbus 1 Channel for the reference frequency and the command from the bus are active.
No control by 0 Channel for the reference frequency and the command from the bus are not
fieldbus active.
Bit 11 Reserved
Bit 12 Reserved
Bit 13 Reserved
Bit 14 Reserved
Bit 15 Reserved
NVE41310 04/2016 73
Software Setup
ZSW1
Bit 0 Ready to switch 1 Mains power supply is switched on, electronics are initialized, pulses are
ON inhibited.
Not ready to switch 0 −
ON
Bit 1 Ready to operate 1 Refer to control word 1, bit 0.
Not ready to 0 −
operate
Bit 2 Operation enabled 1 Drive follows a reference frequency. This means that:
The electronic and the power stages are enabled (Refer to control word 1, bit
3),
The drive is in running state.
Operation disabled 0 Either the power stage is disabled or the drive does not follow the reference
frequency.
Bit 3 Error detected 1 An error has been detected. The drive error response depends on the type of
detected error. The Fault Reset function may only be successfully used if the
detected error cause has disappeared or has been removed. If the detected
error response has disabled the power stage, the drive goes into the
Switching On Inhibited operating state, otherwise the drive returns to
Operation operating state.
No error detected 0 −
Bit 4 Coast stop not 1 −
activated
Coast stop 0 Coast stop (OFF 2) command is present.
activated
Bit 5 Quick stop not 1 −
activated
Quick stop 0 Quick Stop (OFF 3) command is present.
activated
Bit 6 Switching inhibited 1 The drive is in Switching on inhibited operating state.
Switching not 0 −
inhibited
Bit 7 Warning present 1 Warning information present in the service/maintenance parameter;
acknowledgement required.
No warning 0 −
Bit 8 Speed feedback 1 Actual value is within a tolerance band; dynamic speed discrepancies are
within tolerance permissible.
range
Speed feedback 0 −
out of tolerance
range
Bit 9 Control requested 1 The automation system controls the drive.
No control 0 Control by the automation system is not possible, only possible at the device
requested level, by another interface or the drive is controlled from a supervisor (Master
class 2).
Bit 10 Reference 1 Actual output frequency ≥ reference frequency which may be set via the
frequency reached parameter number.
or exceeded
Reference 0 −
frequency not
reached
Bit 11 Reserved
Bit 12 Reserved
Bit 13 Reserved
Bit 14 Reserved
Bit 15 Reserved
74 NVE41310 04/2016
Software Setup
Reference Frequency
NVE41310 04/2016 75
Software Setup
Section 4.3
Fieldbus Integration Tutorial
76 NVE41310 04/2016
Software Setup
NVE41310 04/2016 77
Software Setup
78 NVE41310 04/2016
Software Setup
NVE41310 04/2016 79
Software Setup
80 NVE41310 04/2016
Altivar Machine 320
Operation
NVE41310 04/2016
Chapter 5
Operation
Operation
NVE41310 04/2016 81
Operation
Section 5.1
Operating States
Operating States
Description
The response of the drive in the event of communication interruption can be configured. Configuration can
be performed using the display terminal from the [FULL] FULL, [FAULT MANAGEMENT] FLt-menu,
[COM.FAULT.MANAGEMENT] CLL- submenu, via the [Network fault mgt] CLL parameter.
The values of the [Network fault mgt] CLL parameter, which triggers a transition to the operating state
fault are:
Value Meaning
[Freewheel Stop] YES Freewheel stop (factory setting)
[Ramp stop] rMP Stop on ramp
[Fast stop] FSt Fast stop
[DC injection] dCI DC injection stop
The values of the [Network fault mgt] CLL parameter, which does not trigger a transition to the operating
state fault are:
Value Meaning
[Ignore] nO Detected error ignored
[Per STT] Stt Stop according to configuration of [Type of stop] Stt
[Fallback Speed] LFF Change to fallback speed, maintained as long as the detected error persists
and the run command has not been removed
[Speed maintained] rLS The drive maintains the speed at the time the detected error occurred, as
long as the detected error persists, and the run command has not been
removed
The fallback speed can be configured in the [FULL] FULL, [FAULT MANAGEMENT] FLt- menu,
[Fallback speed] LFF- submenu, using the [FallbackSpeed] LFF parameter.
WARNING
LOSS OF CONTROL
If this parameter is set to nO, fieldbus communication monitoring is disabled.
Only use this setting after a thorough risk assessment in compliance with all regulations and standards
that apply to the device and to the application.
Only use this setting for tests during commissioning.
Verify that communication monitoring has been re-enabled before completing the commissioning
procedure and performing the final commissioning test.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
82 NVE41310 04/2016
Operation
Section 5.2
Operating Modes
Operating Modes
NVE41310 04/2016 83
Operation
Overview
This chapter explains how to configure the drive for operation from the communication network through
three following examples.
I/O mode - a simple command word (based on forward, reverse, and reset binary commands).
Combined mode (with native profile CiA 402) - Both reference value and command word come from the
communication network.
Separate (with native profile CiA 402) - reference value and command word come from separate
sources: for example, the command word (in CiA 402) comes from the communication network and the
reference value from the HMI.
84 NVE41310 04/2016
Operation
Description
For the I/O profile, here is a simple example, which can be extended with additional features. The
command word is made of run forward (bit 0 of CMd), run reverse (bit 1 of CMd), and the function fault
reset (bit 7 of CMd). The reference frequency value is given by Graphic Display Terminal.
In the [FAULT MANAGEMENT] FLt- menu, [Fault reset] rSt- submenu, configure:
NVE41310 04/2016 85
Operation
Configuration of the Drive for Operation with CiA 402 Profile in Combined Mode
Description
This section describes how to configure the settings of the drive if it is controlled in CiA 402 mode. The
example focuses on the not separate mode. Additional modes are detailed in the drive programming
manual.
In the [COMMAND] CtL- menu:
[Ref Freq 1 Config] Fr1: is set on according to the communication source you can choose in the
following table:
[Freq Switch Assign] rFC is set to default value [Ref Freq 1 Config] Fr1.
[Control Mode] CHCF: defines if the drive operates in combined mode (reference and command from
the same channel).
For the current example, [Control Mode] CHCF is adjusted to [Not separ.] SIM as reference and control
are originated from the communication network:
86 NVE41310 04/2016
Operation
Configuration of the Drive for Operation with CiA 402 Profile in Separate Mode
Description
Alternate combinations are possible, see the drive programming manual for the list of possible settings.
For example:
The drive is controlled from the fieldbus (PROFIBUS DP) but the reference value is adjusted on the
controller terminal. The control word comes from the controller and is written according to CiA 402 profile.
The settings are as shown in the table:
NVE41310 04/2016 87
Operation
88 NVE41310 04/2016
Altivar Machine 320
Diagnostic and Troubleshooting
NVE41310 04/2016
Chapter 6
Diagnostic and Troubleshooting
NVE41310 04/2016 89
Diagnostic and Troubleshooting
LED Indicators
The following figure describes the LEDs status module:
LED Description
Module Status
This LED indicates the module status:
90 NVE41310 04/2016
Diagnostic and Troubleshooting
Description
If the product cannot be addressed via the fieldbus, first check the connections. The product manual
contains the technical data of the device and information on network and device installation. Check the
following:
Power connections to the device
Fieldbus cable and fieldbus wiring
Network connection to the device
NVE41310 04/2016 91
Diagnostic and Troubleshooting
Description
If the connections are correct, check the settings for the fieldbus addresses. After correct configuration of
the transmission data, test the fieldbus mode.
In addition to the controller that knows the device via the data in the GSD file and its address, a bus monitor
should be installed. As a passive device, it can display messages.
Switch off or on the supply voltage of the drive system.
Observe the network messages shortly after switching on the drive system. A bus monitor can be used
to record the elapsed time between telegrams and the relevant information in the telegram.
92 NVE41310 04/2016
Diagnostic and Troubleshooting
Communication Interruption
Description
The drive triggers an error [Internal Link Error] ILF when the following events occur:
Hardware error is detected on the PROFIBUS DP module
Communication interruption between the PROFIBUS DP module and the drive
The response of the drive in the event of an [Internal Link Error] ILF error cannot be configured, and the
drive stops in freewheel. This detected error requires a power reset.
The diagnostic parameter can be used to obtain more detailed information about the origin of the [Internal
Link Error] ILF .
The [InterCom Error1] ILF1 parameter can be accessed on the graphic display terminal in the
[COMUNICATION CARD] CMM- menu
This data report and gives an indication on the drive status when the diagnostic event was triggered
Byte Description
1...6 Reserved
7 Ext_Diag_Data External diagnostic data length = 6
8 IF ETA.bit 3 = 1: ADL LFT LSB
Otherwise: 0
9 ADL ETA LSB
10 ADL ETA MSB
11 LSB of the last value of the output speed
12 MSB of the last value of the output speed
NVE41310 04/2016 93
Diagnostic and Troubleshooting
Enabling Diagnostics
By default, extended diagnostics are disabled. They can be activated during the configuration phase as
shown below:
94 NVE41310 04/2016
Diagnostic and Troubleshooting
NVE41310 04/2016 95
Diagnostic and Troubleshooting
96 NVE41310 04/2016
Diagnostic and Troubleshooting
Control-Signal Diagnostics
Introduction
On the display terminal, the [MONITORING] MON-, [Communication map] CMM- submenu can be
used to display control-signal diagnostic information between the drive and the controller:
Active command channel [Command Channel] CMdC
Value of the control word [Cmd Register] CMd from the active command channel [Command Channel]
CMdC
Active reference frequency channel [Ref Freq Channel] rFCC
Value of the reference frequency [Pre-Ramp Ref Freq] FrH from the active target channel [Ref Freq
Channel] rFCC
Value of the operating state word [CIA402 State Reg] EtA
Specific data for all available fieldbus are in dedicated submenus.
In the [Command word image] CWI- submenu: control words from all channels
In the [Freq. ref. word map] rWI- submenu: reference frequency values produced by all channels
Bit Description
DRIVECOM Status word
Bit0 = 1 Ready to switch on
Bit1 = 1 Switched on
Bit2 = 1 Operation enabled
Bit3 = 1 Operating state fault
Bit4 = 1 Power stage is switched on
Bit5 = 0 Quick stop
Bit6 = 1 Switch on disabled
Bit7 = 1 Warning
Bit8 = 1 Drivecom reserved
Bit9 = 0 Forced local mode in progress
Bit10 = 1 Reference value reached (steady state)
Bit11 = 1 Reference value exceeded (< LSP or > HSP)
Bit12 Reserved
Bit13 Reserved
Bit14 = 1 Stop imposed via STOP key
Bit15 = 0 Motor rotation in forward direction (or stopped)
NVE41310 04/2016 97
Diagnostic and Troubleshooting
98 NVE41310 04/2016
Altivar Machine 320
Glossary
NVE41310 04/2016
Glossary
A
Abbreviations
Req. = Required
Opt. = Optional
C
CAN
Controller Area Network is an internally standardized serial bus system
COB
Communication Object. A unit of transportation in a CAN network. Data must be sent across a CAN
Network inside a COB. There are 2048 different COB's in a CAN network. A COB can contain at most
8 bytes of data.
COB ID
Each COB is uniquely identified in a CAN network by a number called the COB Identifier (COB-ID).
D
Display terminal
The display terminal menus are shown in square brackets.
For example: [Communication]
The codes are shown in round brackets.
For example: COM-
Parameter names are displayed on the display terminal in square brackets.
For example: [Fallback Speed]
Parameter codes are displayed in round brackets.
For example: LFF
E
Error
Discrepancy between a detected (computed, measured, or signaled) value or condition and the specified
or theoretically correct value or condition.
F
Factory setting
Default configuration of the product.
Fault
Fault is an operating state. If the monitoring functions detect an error, a transition to this operating state is
triggered, depending on the error class. A "Fault reset" is required to exit this operating state after the
cause of the detected error has been removed. Further information can be found in the pertinent standards
such as IEC 61800-7, ODVA Common Industrial Protocol (CIP).
Fault Reset
A function used to restore the drive to an operational state after a detected error is cleared by removing
the cause of the error so that the error is no longer active.
L
LSB
Least Significant Byte
NVE41310 04/2016 99
Glossary
M
Monitoring function
Monitoring functions acquire a value continuously or cyclically (for example, by measuring) in order to
check whether it is within permissible limits. Monitoring functions are used for error detection.
MSB
Most Significant Byte
N
NMT
Network Management. One of the service elements of the application layer in the CAN Reference Model.
The NMT serves to configure, initialize, and handle detected errors in a CAN network.
P
Parameter
Device data and values that can be read and set (to a certain extent) by the user.
PDO
Process Data Object
PELV
Protective Extra Low Voltage, low voltage with isolation. For more information: IEC 60364-4-41
PLC
Programmable logic controller
Power stage
The power stage controls the motor. The power stage generates current for controlling the motor.
Q
Quick Stop
The quick Stop function can be used for fast deceleration of a movement as a response to a detected error
or via a command.
R
RPDO
Receive PDO
S
SYNC
Synchronization Object
T
TPDO
Transmit PDO
W
Warning
If the term is used outside the context of safety instructions, a warning alerts to a potential problem that
was detected by a monitoring function. A warning does not cause a transition of the operating state.
Z
Zone of operation
This term is used in conjunction with the description of specific hazards, and is defined as it is for a hazard
zone or danger zone in the EC Machinery Directive (2006/42/EC) and in ISO 12100-1.
04/2016