Flex Power Guide 1.3.2
Flex Power Guide 1.3.2
Flex Power Guide 1.3.2
World Wide
Version: 1.3.2
Date: August 27, 2013
The user of this document is responsible for obtaining the latest copy prior to use. Obsolete copies may be
archived and used for reference purposes only. The latest version of this document is located at:
http://www.ibm.com/support/techdocs/atsmastr.nsf/WebIndex/WP102111
Revision History
Contributors:
Doug Evans – IBM System x Development
dougevan@us.ibm.com
Notices:
This paper is intended to provide information regarding powering IBM Flex System Enterprise Chassis solutions. It presents findings based on
configurations that were created and tested under laboratory conditions. These findings may not be realized in all customer environments, and
implementation in such environments may require additional steps, configurations and performance analysis. The information herein is
provided “AS IS” with no warranties, express or implied. This information does not constitute a specification or form part of the warranty for any
IBM or non-IBM products.
Information in this document was developed in conjunction with the use of the equipment specified and is limited in application to those
specific hardware and software products and levels.
The information contained in this document has not been submitted to any formal IBM test and is distributed as is. The use of this information
or the implementation of these techniques is a customer responsibility and depends on the customer’s ability to evaluate and integrate them
into the customer’s operational environment. While each item may have been reviewed by IBM for accuracy in a specific situation, there is no
guarantee that the same or similar results will be obtained elsewhere. Customers attempting to adapt these techniques to their own
environments do so at their own risk.
IBM may not officially support techniques mentioned in this document. For questions regarding officially supported techniques, please refer to
the product documentation, announcement letters or contact the IBM Support Line at 1-800-IBM-SERV.
This document makes references to vendor-acquired applications or utilities. It is the customer responsibility to obtain licenses of these utilities
prior to their usage.
© Copyright International Business Machines Corporation 2012, 2013. All rights reserved. U.S. Government Users Restricted Rights –
Use, duplication or disclosure restricted by GSA ADP Schedule Contract with IBM Corp.
Table of Contents
INTRODUCTION ............................................................................................................................................................... 7
HOW TO USE THIS GUIDE ............................................................................................................................................................... 7
IBM FLEX POWER OVERVIEW ........................................................................................................................................... 8
IBM FLEX SYSTEM POWER SUPPLY UNIT (PSU) ................................................................................................................................. 8
2500W PSU – Rating & Part Number Information ............................................................................................................... 8
2100W PSU – Rating & Part Number Information ............................................................................................................... 8
PSU Compatibility Matrix ..................................................................................................................................................... 9
2500W PSU – Half Wide Nodes Minimum PSU Required For N+N..................................................................................... 10
2100W PSU – Half Wide Nodes Minimum PSU Required For N+N..................................................................................... 10
2500W PSU – Full Wide Nodes Minimum PSU Required For N+N ..................................................................................... 11
2100W PSU – Full Wide Nodes Minimum PSU Required For N+N ..................................................................................... 11
2500W PSU – Half Wide Nodes Minimum PSU Required For N+1 ..................................................................................... 12
2100W PSU – Half Wide Nodes Minimum PSU Required For N+1 ..................................................................................... 12
2500W PSU – Full Wide Nodes Minimum PSU Required For N+1 ...................................................................................... 13
2100W PSU – Full Wide Nodes Minimum PSU Required For N+1 ...................................................................................... 13
IBM FLEX SYSTEM ZONE COOLING ................................................................................................................................................. 14
IBM FLEX SYSTEM POWER CORDS ................................................................................................................................................. 14
IBM System x Worldwide Power Cords .............................................................................................................................. 14
IBM System x North American Power Cords ...................................................................................................................... 15
IBM System x International Power Cords ........................................................................................................................... 16
IBM Power Systems Worldwide Power Cords .................................................................................................................... 17
IBM Power Systems North American Power Cords ............................................................................................................ 17
PDU CONFIGURATIONS (6X PSU / FLEX) – NORTH AMERICA ........................................................................................... 18
2X FLEX (6X PSU) ON 60A@208V 3PH PDUS – NORTH AMERICA .................................................................................................... 18
2X FLEX (6X PSU) ON 30A@200-240V 1PH PDUS – NORTH AMERICA ............................................................................................. 22
1X FLEX (6X PSU) ON 50A@208V 3PH PDUS – NORTH AMERICA .................................................................................................... 23
1X FLEX (6X PSU) ON 30A@208V 3PH PDUS – NORTH AMERICA .................................................................................................... 25
1X FLEX (6X PSU) ON 60A@200-240V 1PH PDUS – NORTH AMERICA ............................................................................................. 27
1X FLEX (6X PSU) ON 30A@200-240V 1PH PDUS – NORTH AMERICA ............................................................................................. 29
PDU CONFIGURATIONS (5X PSU / FLEX) – NORTH AMERICA ........................................................................................... 31
1X FLEX (5X PSU) ON 60A@208V 3PH PDUS – NORTH AMERICA .................................................................................................... 31
1X FLEX (5X PSU) ON 50A@208V 3PH PDUS – NORTH AMERICA .................................................................................................... 33
1X FLEX (5X PSU) ON 30A@208V 3PH PDUS – NORTH AMERICA .................................................................................................... 35
1X FLEX (5X PSU) ON 60A@200-240V 1PH PDUS – NORTH AMERICA ............................................................................................. 37
1X FLEX (5X PSU) ON 5X 30A@200-240V 1PH PDUS – NORTH AMERICA ......................................................................................... 39
PDU CONFIGURATIONS (4X PSU / FLEX) – NORTH AMERICA ........................................................................................... 41
3X FLEX (4X PSU) ON 60A@208V 3PH PDUS – NORTH AMERICA .................................................................................................... 41
3X FLEX (4X PSU) ON 50A@208V 3PH PDUS – NORTH AMERICA .................................................................................................... 44
3X FLEX (4X PSU) ON 30A@208V 3PH PDUS – NORTH AMERICA .................................................................................................... 46
3X FLEX (4X PSU) ON 60A@200-240V 1PH PDUS – NORTH AMERICA ............................................................................................. 48
1X FLEX (4X PSU) ON 60A@208V 3PH PDUS – NORTH AMERICA .................................................................................................... 50
1X FLEX (4X PSU) ON 50A@208V 3PH PDUS – NORTH AMERICA .................................................................................................... 52
1X FLEX (4X PSU) ON 30A@208V 3PH PDUS – NORTH AMERICA .................................................................................................... 54
1X FLEX (4X PSU) ON 60A@200-240V 1PH PDUS – NORTH AMERICA ............................................................................................. 56
1X FLEX (4X PSU) ON 30A@200-240V 1PH PDUS – NORTH AMERICA ............................................................................................. 58
PDU CONFIGURATIONS (3X PSU / FLEX) – NORTH AMERICA ........................................................................................... 60
2X FLEX (3X PSU) ON 60A@208V 3PH PDUS – NORTH AMERICA .................................................................................................... 60
1X FLEX (3X PSU) ON 50A@208V 3PH PDUS – NORTH AMERICA .................................................................................................... 62
Introduction
The IBM Flex System Enterprise Chassis covered in this guide is currently marketed worldwide. The intent of this
guide is to provide power information for installation planning of IBM Flex System Enterprise Chassis. The guide
contains examples of the IBM Flex System Enterprise Chassis connected to various PDUs and circuits.
This guide is best used in softcopy form since it contains hyperlinks for navigation. This document can still be
used in hardcopy as reference only. You can obtain the latest copy of this document from this web page:
http://www.ibm.com/support/techdocs/atsmastr.nsf/WebIndex/PRS4401
Power connections to the IBM Flex chassis must be wired to comply with local and/or national electrical codes.
Consult your local AHJ (Authority Having Jurisdiction) to ensure compliance.
Important Notice: All wiring examples provided in this document are based on nameplate label ratings for the
systems.
Each example covered in this guide gives System x PDU options information (if available), along with information
on Flex power policies.
Example Configuration:
Power
Management
Policies
Wiring Diagram
Required Flex
Line Cord
System x PDU
Options
IBM Power Configurator for System x, BladeCenter, and Flex System tool link:
http://www.ibm.com/systems/bladecenter/resources/powerconfig.html
PSU 6
PSU 3
CMM
6 Bay
PSU Nominal Input Voltage Range = 200-208, 220-240V AC @ 50-60 Hz. Fan
Bay
5
4
Fan
Bay
PSU 5
PSU 2
Power
Supply
Bays
6 3
5 2
4 1
Fan
Bays
Fan Fan
Bay Bay
TX/ RX
PSU 4
PSU 1
Fan Fan
Bay Bay
CMM1
12.2V
System System
Personality Card
IO Bay
IO Bay
IO Bay
IO Bay
System System
1 Full Wide Node or 2 Half Nodes
Fan Fan
(80mm) (80mm)
1 Full Wide Node or 2 Half Nodes
2500W PSU – Half Wide Nodes Minimum PSU Required For N+N
# of Half Wide 500 W ITE 600 W ITE 700 W ITE
Nodes # of PSU1 Fault # of PSU 1
Fault # of PSU1 Fault
14 6 408 6 408 Not Supported
13 6 444 6 440 Not Supported
12 6 476 6 476 6 476
11 6 500 6 520 6 520
10 4 329 6 572 6 572
9 4 374 4 374 6 644
8 4 431 4 431 6 700
7 4 493 4 493 4 493
6 4 500 4 575 4 575
5 4 500 4 600 4 700
4 2 296 4 600 4 700
3 2 395 2 395 2 395
2 2 500 2 593 2 593
1 2 500 2 600 2 700
1 – Theoretical number that may require unrealistic throttle levels.
Note: When a fault occurs, all Nodes in the chassis must throttle to the average power, in watts, indicated in
the “Fault” column. For more information on N+N and N+1 redundancy see “What is N+N and N+1
Redundancy” section on page 187 in this document.
2100W PSU – Half Wide Nodes Minimum PSU Required For N+N
# of Half Wide 500 W ITE 600 W ITE 700 W ITE
Nodes # of PSU1 Fault # of PSU1 Fault # of PSU1 Fault
14 Not Supported Not Supported Not Supported
13 6 347 Not Supported Not Supported
12 6 376 Not Supported Not Supported
11 6 410 6 410 Not Supported
10 6 451 6 451 Not Supported
9 6 500 6 510 6 510
8 4 331 6 584 6 584
7 4 378 4 378 6 667
6 4 441 4 441 4 441
5 4 500 4 546 4 546
4 500 4 600 4 700
3 2 261 4 600 4 700
2 2 392 2 392 2 392
1 2 500 2 600 2 700
1 – Theoretical number that may require unrealistic throttle levels.
Note: When a fault occurs, all Nodes in the chassis must throttle to the average power, in watts, indicated in
the “Fault” column. For more information on N+N and N+1 redundancy see “What is N+N and N+1
Redundancy” section on page 187 in this document.
2500W PSU – Full Wide Nodes Minimum PSU Required For N+N
# of Full Wide 1000 W ITE 1200 W ITE 1400 W ITE
Nodes # of PSU1 Fault # of PSU 1
Fault # of PSU1 Fault
7 6 816 6 816 Not Supported
6 6 953 6 953 6 953
5 4 658 6 1143 6 1143
4 4 863 4 863 6 1400
3 4 1000 4 1150 4 1150
2 2 593 4 1200 4 1400
1 2 1000 2 1185 2 1185
1 – Theoretical number that may require unrealistic throttle levels.
Note: When a fault occurs, all Nodes in the chassis must throttle to the average power, in watts, indicated in
the “Fault” column. For more information on N+N and N+1 redundancy see “What is N+N and N+1
Redundancy” section on page 187 in this document.
2100W PSU – Full Wide Nodes Minimum PSU Required For N+N
# of Full Wide 1000 W ITE 1200 W ITE 1400 W ITE
Nodes # of PSU1 Fault # of PSU 1
Fault # of PSU1 Fault
7 6 645 Not Supported Not Supported
6 6 752 Not Supported Not Supported
5 6 902 6 902 6 902
4 4 662 6 1168 6 1168
3 4 883 4 883 4 883
2 4 1000 4 1200 4 1400
1 2 784 2 784 2 784
1 – Theoretical number that may require unrealistic throttle levels.
Note: When a fault occurs, all Nodes in the chassis must throttle to the average power, in watts, indicated in
the “Fault” column. For more information on N+N and N+1 redundancy see “What is N+N and N+1
Redundancy” section on page 187 in this document.
2500W PSU – Half Wide Nodes Minimum PSU Required For N+1
# of Half Wide 500 W ITE 600 W ITE 700 W ITE
Nodes # of PSU1 Fault # of PSU 1
Fault # of PSU1 Fault
14 4 414 4 414 5 590
13 4 446 4 446 5 635
12 4 483 4 483 4 483
11 4 500 4 527 4 527
10 3 333 4 580 4 580
9 3 379 3 379 4 653
8 3 436 3 436 4 700
7 3 499 3 499 3 499
6 3 500 3 582 3 582
5 3 500 3 600 3 700
4 2 296 3 600 3 700
3 2 395 2 395 2 395
2 2 500 2 593 2 593
1 2 500 2 600 2 700
1 – Theoretical number that may require unrealistic throttle levels.
Note: When a fault occurs, all Nodes in the chassis must throttle to the average power, in watts, indicated in
the “Fault” column. For more information on N+N and N+1 redundancy see “What is N+N and N+1
Redundancy” section on page 187 in this document.
2100W PSU – Half Wide Nodes Minimum PSU Required For N+1
Note: When a fault occurs, all Nodes in the chassis must throttle to the average power, in watts, indicated in
the “Fault” column. For more information on N+N and N+1 redundancy see “What is N+N and N+1
Redundancy” section on page 187 in this document.
2500W PSU – Full Wide Nodes Minimum PSU Required For N+1
Note: When a fault occurs, all Nodes in the chassis must throttle to the average power, in watts, indicated in
the “Fault” column. For more information on N+N and N+1 redundancy see “What is N+N and N+1
Redundancy” section on page 187 in this document.
2100W PSU – Full Wide Nodes Minimum PSU Required For N+1
Note: When a fault occurs, all Nodes in the chassis must throttle to the average power, in watts, indicated in
the “Fault” column. For more information on N+N and N+1 redundancy see “What is N+N and N+1
Redundancy” section on page 187 in this document.
Quantity of 80mm Fans required per number of Nodes installed to maintain cooling redundancy of N+1.
Zone 2 Zone 1
# of 80mm # of Nodes # of 80mm # of Nodes
Fans Required Installed Fans Required Installed
2 1-2 2 1-2
3 3-4 3 3-4
4 5-7 4 5-7
CMM
6 Bay
4
Fan Fan
Bay Bay
Fan 9 Fan 4
Power Fan Power Fan
200-240V Supply
IN OUT Bay 200-240V Supply
IN OUT Bay
13,8A Bay 13,8A Bay
50/60Hz 50/60Hz
Fan 8 6
5
Power
Supply
Bays
3
2
Fan 3
4 1
Fan
Bays
10 5
9 4
8 3
7 2
6 1
Fan Fan
Bay Bay
TX/ RX
Power
200-240V Supply
IN OUT
13,8A Bay
50/60Hz
Fan 7 Power
200-240V Supply
IN OUT
13,8A Bay
50/60Hz
Fan 2 LINK
Fan Fan
Bay Bay
Fan 6 2
1
Fan 1
CMM1
1 6 3 2 1 4
IEC 320
C19
IEC 320
C19
L3 L2
N L1
IEC 320
G
C19
IEC 320
C19
IEC 320
C19
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex System Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 60A@208V 3 phase PDUs IBM Switched & Monitored 60A@208V 3 phase PDU
P/N: 39Y8923 or FC: 6061 P/N: 46M4003 or FC: 5897
P/N: 71763NU or FC: 6051
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 60A@208V 3 phase Configuration
See the “IBM Power Systems PDU Information North America” section on page 168 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 60A@208V 3 phase PDUs IBM Switched & Monitored 60A@208V 3 phase
P/N: 39Y8923 or FC: 6061 PDU
P/N: 71763NU or FC: 6051 P/N: 46M4003 or FC: 5897
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 60A@208V 3 phase Configuration
See the “IBM Power Systems PDU Information North America” section on page 168 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 60A@208V 3 phase PDUs IBM Switched & Monitored 60A@208V 3 phase PDU
P/N: 39Y8923 or FC: 6061 P/N: 46M4003 or FC: 5897
P/N: 71763NU or FC: 6051
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 60A@208V 3 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 60A@208V 3 phase PDUs IBM Switched & Monitored 60A@208V 3 phase
P/N: 39Y8923 or FC: 6061 PDU
P/N: 71763NU or FC: 6051 P/N: 46M4003 or FC: 5897
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 60A@208V 3 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex System Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 60A@208V 3 phase PDUs IBM Switched & Monitored 60A@208V 3 phase PDU
P/N: 39Y8923 or FC: 6061 P/N: 46M4003 or FC: 5897
P/N: 71763NU or FC: 6051
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 60A@208V 3 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 50A@208V 3 phase PDUs IBM Switched & Monitored 50A@208V 3 phase PDU
P/N: 46M4140 or FC: 5926 P/N: 46M4134 or FC: 5931
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 50A@208V 3 phase Configuration
Currently IBM Power Systems does not have an available PDU to support this configuration. A suitable IBM System x
PDU from the list above or a third party PDU will need to be used to implement this configuration.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 50A@208V 3 phase PDUs IBM Switched & Monitored 50A@208V 3 phase PDU
P/N: 46M4140 or FC: 5926 P/N: 46M4134 or FC: 5931
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 50A@208V 3 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 30A@208V 3 phase Configuration
Currently IBM Power Systems does not have an available PDU to support this configuration. A suitable IBM System x
PDU from the list above or a third party PDU will need to be used to implement this configuration.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 30A@208V 3 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 60A@200-240V 1 phase PDUs IBM Switched & Monitored 60A@200-240V 1 phase PDU
P/N: 39Y8940 or FC: A11U P/N: 46M4002 + input line cord P/N: 40K9615 = FC: 5902
P/N: 39Y8948 + input line cord P/N: 40K9615 = FC: 6063
P/N: 71762NX + input line cord P/N: 40K9615 = FC: 6501
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 60A@200-240V 1 phase Configuration
See the “IBM Power Systems PDU Information North America” section on page 168 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 60A@200-240V 1 phase PDUs IBM Switched & Monitored 60A@200-240V 1 phase PDU
P/N: 39Y8940 or FC: A11U P/N: 46M4002 + input line cord P/N: 40K9615 = FC: 5902
P/N: 39Y8948 + input line cord P/N: 40K9615 = FC: 6063
P/N: 71762NX + input line cord P/N: 40K9615 = FC: 6501
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 60A@200-240V 1 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 30A@200-240V 1 phase PDUs IBM Switched & Monitored 30A@200-240V 1 phase PDU
P/N: 39Y8939 or FC: A11T P/N: 46M4002 + input line cord P/N: 40K9614 = FC: 5901
P/N: 39Y8948 + input line cord P/N: 40K9614 = FC: 6062
P/N: 71762NX + input line cord P/N: 40K9614 = FC: 6500
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 30A@200-240V 1 phase Configuration
See the “IBM Power Systems PDU Information North America” section on page 168 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 30A@200-240V 1 phase PDUs IBM Switched & Monitored 30A@200-240V 1 phase PDU
P/N: 39Y8939 or FC: A11T P/N: 46M4002 + input line cord P/N: 40K9614 = FC: 5901
P/N: 39Y8948 + input line cord P/N: 40K9614 = FC: 6062
P/N: 71762NX + input line cord P/N: 40K9614 = FC: 6500
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 30A@200-240V 1 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 30A@200-240V 1 phase PDUs IBM Switched & Monitored 30A@200-240V 1 phase PDU
P/N: 39Y8939 or FC: A11T P/N: 46M4002 + input line cord P/N: 40K9614 = FC: 5901
P/N: 39Y8948 + input line cord P/N: 40K9614 = FC: 6062
P/N: 71762NX + input line cord P/N: 40K9614 = FC: 6500
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 30A@200-240V 1 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 60A@208V 3 phase PDUs IBM Switched & Monitored 60A@208V 3 phase PDU
P/N: 39Y8923 or FC: 6061 P/N: 46M4003 or FC: 5897
P/N: 71763NU or FC: 6051
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 60A@208V 3 phase Configuration
See the “IBM Power Systems PDU Information North America” section on page 168 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 60A@208V 3 phase PDUs IBM Switched & Monitored 60A@208V 3 phase PDU
P/N: 39Y8923 or FC: 6061 P/N: 46M4003 or FC: 5897
P/N: 71763NU or FC: 6051
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 60A@208V 3 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 50A@208V 3 phase PDUs IBM Switched & Monitored 50A@208V 3 phase PDU
P/N: 46M4140 or FC: 5926 P/N: 46M4134 or FC: 5931
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 50A@208V 3 phase Configuration
Currently IBM Power Systems does not have an available PDU to support this configuration. A suitable IBM System x
PDU from the list above or a third party PDU will need to be used to implement this configuration.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 50A@208V 3 phase PDUs IBM Switched & Monitored 50A@208V 3 phase PDU
P/N: 46M4140 or FC: 5926 P/N: 46M4134 or FC: 5931
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 50A@208V 3 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 30A@208V 3 phase Configuration
Currently IBM Power Systems does not have an available PDU to support this configuration. A suitable IBM System x
PDU from the list above or a third party PDU will need to be used to implement this configuration.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 30A@208V 3 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 60A@200-240V 1 phase PDUs IBM Switched & Monitored 60A@200-240V 1 phase PDU
P/N: 39Y8940 or FC: A11U P/N: 46M4002 + input line cord P/N: 40K9615 = FC: 5902
P/N: 39Y8948 + input line cord P/N: 40K9615 = FC: 6063
P/N: 71762NX + input line cord P/N: 40K9615 = FC: 6501
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 60A@200-240V 1 phase Configuration
See the “IBM Power Systems PDU Information North America” section on page 168 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 60A@200-240V 1 phase PDUs IBM Switched & Monitored 60A@200-240V 1 phase PDU
P/N: 39Y8940 or FC: A11U P/N: 46M4002 + input line cord P/N: 40K9615 = FC: 5902
P/N: 39Y8948 + input line cord P/N: 40K9615 = FC: 6063
P/N: 71762NX + input line cord P/N: 40K9615 = FC: 6501
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 60A@200-240V 1 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 30A@200-240V 1 phase PDUs IBM Switched & Monitored 30A@200-240V 1 phase PDU
P/N: 39Y8939 or FC: A11T P/N: 46M4002 + input line cord P/N: 40K9614 = FC: 5901
P/N: 39Y8948 + input line cord P/N: 40K9614 = FC: 6062
P/N: 71762NX + input line cord P/N: 40K9614 = FC: 6500
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 30A@200-240V 1 phase Configuration
See the “IBM Power Systems PDU Information North America” section on page 168 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 30A@200-240V 1 phase PDUs IBM Switched & Monitored 30A@200-240V 1 phase PDU
P/N: 39Y8939 or FC: A11T P/N: 46M4002 + input line cord P/N: 40K9614 = FC: 5901
P/N: 39Y8948 + input line cord P/N: 40K9614 = FC: 6062
P/N: 71762NX + input line cord P/N: 40K9614 = FC: 6500
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 30A@200-240V 1 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 60A@208V 3 phase PDUs IBM Switched & Monitored 60A@208V 3 phase PDU
P/N: 39Y8923 or FC: 6061 P/N: 46M4003 or FC: 5897
P/N: 71763NU or FC: 6051
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 60A@208V 3 phase Configuration
See the “IBM Power Systems PDU Information North America” section on page 168 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 60A@208V 3 phase PDUs IBM Switched & Monitored 60A@208V 3 phase PDU
P/N: 39Y8923 or FC: 6061 P/N: 46M4003 or FC: 5897
P/N: 71763NU or FC: 6051
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 60A@208V 3 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 50A@208V 3 phase PDUs IBM Switched & Monitored 50A@208V 3 phase PDU
P/N: 46M4140 or FC: 5926 P/N: 46M4134 or FC: 5931
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 50A@208V 3 phase Configuration
Currently IBM Power Systems does not have an available PDU to support this configuration. A suitable IBM System x
PDU from the list above or a third party PDU will need to be used to implement this configuration.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 50A@208V 3 phase PDUs IBM Switched & Monitored 50A@208V 3 phase PDU
P/N: 46M4140 or FC: 5926 P/N: 46M4134 or FC: 5931
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 50A@208V 3 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 30A@208V 3 phase Configuration
Currently IBM Power Systems does not have an available PDU to support this configuration. A suitable IBM System x
PDU from the list above or a third party PDU will need to be used to implement this configuration.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 30A@208V 3 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 60A@200-240V 1 phase PDUs IBM Switched & Monitored 60A@200-240V 1 phase PDU
P/N: 39Y8940 or FC: A11U P/N: 46M4002 + input line cord P/N: 40K9615 = FC: 5902
P/N: 39Y8948 + input line cord P/N: 40K9615 = FC: 6063
P/N: 71762NX + input line cord P/N: 40K9615 = FC: 6501
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 60A@200-240V 1 phase Configuration
See the “IBM Power Systems PDU Information North America” section on page 168 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 60A@200-240V 1 phase PDUs IBM Switched & Monitored 60A@200-240V 1 phase PDU
P/N: 39Y8940 or FC: A11U P/N: 46M4002 + input line cord P/N: 40K9615 = FC: 5902
P/N: 39Y8948 + input line cord P/N: 40K9615 = FC: 6063
P/N: 71762NX + input line cord P/N: 40K9615 = FC: 6501
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 60A@200-240V 1 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 60A@208V 3 phase PDUs IBM Switched & Monitored 60A@208V 3 phase PDU
P/N: 39Y8923 or FC: 6061 P/N: 46M4003 or FC: 5897
P/N: 71763NU or FC: 6051
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 60A@208V 3 phase Configuration
See the “IBM Power Systems PDU Information North America” section on page 168 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 60A@208V 3 phase PDUs IBM Switched & Monitored 60A@208V 3 phase PDU
P/N: 39Y8923 or FC: 6061 P/N: 46M4003 or FC: 5897
P/N: 71763NU or FC: 6051
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 60A@208V 3 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 50A@208V 3 phase PDUs IBM Switched & Monitored 50A@208V 3 phase PDU
P/N: 46M4140 or FC: 5926 P/N: 46M4134 or FC: 5931
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 50A@208V 3 phase Configuration
Currently IBM Power Systems does not have an available PDU to support this configuration. A suitable IBM System x
PDU from the list above or a third party PDU will need to be used to implement this configuration.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 50A@208V 3 phase PDUs IBM Switched & Monitored 50A@208V 3 phase PDU
P/N: 46M4140 or FC: 5926 P/N: 46M4134 or FC: 5931
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 50A@208V 3 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 30A@208V 3 phase Configuration
Currently IBM Power Systems does not have an available PDU to support this configuration. A suitable IBM System x
PDU from the list above or a third party PDU will need to be used to implement this configuration.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 30A@208V 3 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 60A@200-240V 1 phase PDUs IBM Switched & Monitored 60A@200-240V 1 phase PDU
P/N: 39Y8940 or FC: A11U P/N: 46M4002 + input line cord P/N: 40K9615 = FC: 5902
P/N: 39Y8948 + input line cord P/N: 40K9615 = FC: 6063
P/N: 71762NX + input line cord P/N: 40K9615 = FC: 6501
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 60A@200-240V 1 phase Configuration
See the “IBM Power Systems PDU Information North America” section on page 168 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 60A@200-240V 1 phase PDUs IBM Switched & Monitored 60A@200-240V 1 phase PDU
P/N: 39Y8940 or FC: A11U P/N: 46M4002 + input line cord P/N: 40K9615 = FC: 5902
P/N: 39Y8948 + input line cord P/N: 40K9615 = FC: 6063
P/N: 71762NX + input line cord P/N: 40K9615 = FC: 6501
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 60A@200-240V 1 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 30A@200-240V 1 phase PDUs IBM Switched & Monitored 30A@200-240V 1 phase PDU
P/N: 39Y8939 or FC: A11T P/N: 46M4002 + input line cord P/N: 40K9614 = FC: 5901
P/N: 39Y8948 + input line cord P/N: 40K9614 = FC: 6062
P/N: 71762NX + input line cord P/N: 40K9614 = FC: 6500
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 30A@200-240V 1 phase Configuration
See the “IBM Power Systems PDU Information North America” section on page 168 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 30A@200-240V 1 phase PDUs IBM Switched & Monitored 30A@200-240V 1 phase PDU
P/N: 39Y8939 or FC: A11T P/N: 46M4002 + input line cord P/N: 40K9614 = FC: 5901
P/N: 39Y8948 + input line cord P/N: 40K9614 = FC: 6062
P/N: 71762NX + input line cord P/N: 40K9614 = FC: 6500
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 30A@200-240V 1 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 60A@208V 3 phase PDUs IBM Switched & Monitored 60A@208V 3 phase PDU
P/N: 39Y8923 or FC: 6061 P/N: 46M4003 or FC: 5897
P/N: 71763NU or FC: 6051
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 60A@208V 3 phase Configuration
See the “IBM Power Systems PDU Information North America” section on page 168 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 60A@208V 3 phase PDUs IBM Switched & Monitored 60A@208V 3 phase PDU
P/N: 39Y8923 or FC: 6061 P/N: 46M4003 or FC: 5897
P/N: 71763NU or FC: 6051
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 60A@208V 3 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 50A@208V 3 phase PDUs IBM Switched & Monitored 50A@208V 3 phase PDU
P/N: 46M4140 or FC: 5926 P/N: 46M4134 or FC: 5931
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 50A@208V 3 phase Configuration
Currently IBM Power Systems does not have an available PDU to support this configuration. A suitable IBM System x
PDU from the list above or a third party PDU will need to be used to implement this configuration.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 50A@208V 3 phase PDUs IBM Switched & Monitored 50A@208V 3 phase PDU
P/N: 46M4140 or FC: 5926 P/N: 46M4134 or FC: 5931
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 50A@208V 3 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 30A@208V 3 phase Configuration
Currently IBM Power Systems does not have an available PDU to support this configuration. A suitable IBM System x
PDU from the list above or a third party PDU will need to be used to implement this configuration.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 30A@208V 3 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 60A@200-240V 1 phase PDUs IBM Switched & Monitored 60A@200-240V 1 phase PDU
P/N: 39Y8940 or FC: A11U P/N: 46M4002 + input line cord P/N: 40K9615 = FC: 5902
P/N: 39Y8948 + input line cord P/N: 40K9615 = FC: 6063
P/N: 71762NX + input line cord P/N: 40K9615 = FC: 6501
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 60A@200-240V 1 phase Configuration
See the “IBM Power Systems PDU Information North America” section on page 168 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 60A@200-240V 1 phase PDUs IBM Switched & Monitored 60A@200-240V 1 phase PDU
P/N: 39Y8940 or FC: A11U P/N: 46M4002 + input line cord P/N: 40K9615 = FC: 5902
P/N: 39Y8948 + input line cord P/N: 40K9615 = FC: 6063
P/N: 71762NX + input line cord P/N: 40K9615 = FC: 6501
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 60A@200-240V 1 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 30A@200-240V 1 phase PDUs IBM Switched & Monitored 30A@200-240V 1 phase PDU
P/N: 39Y8939 or FC: A11T P/N: 46M4002 + input line cord P/N: 40K9614 = FC: 5901
P/N: 39Y8948 + input line cord P/N: 40K9614 = FC: 6062
P/N: 71762NX + input line cord P/N: 40K9614 = FC: 6500
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 30A@200-240V 1 phase Configuration
See the “IBM Power Systems PDU Information North America” section on page 168 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 30A@200-240V 1 phase PDUs IBM Switched & Monitored 30A@200-240V 1 phase PDU
P/N: 39Y8939 or FC: A11T P/N: 46M4002 + input line cord P/N: 40K9614 = FC: 5901
P/N: 39Y8948 + input line cord P/N: 40K9614 = FC: 6062
P/N: 71762NX + input line cord P/N: 40K9614 = FC: 6500
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 30A@200-240V 1 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 60A@208V 3 phase PDUs IBM Switched & Monitored 60A@208V 3 phase PDU
P/N: 39Y8923 or FC: 6061 P/N: 46M4003 or FC: 5897
P/N: 71763NU or FC: 6051
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 60A@208V 3 phase Configuration
See the “IBM Power Systems PDU Information North America” section on page 168 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 60A@208V 3 phase PDUs IBM Switched & Monitored 60A@208V 3 phase PDU
P/N: 39Y8923 or FC: 6061 P/N: 46M4003 or FC: 5897
P/N: 71763NU or FC: 6051
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 60A@208V 3 phase Configuration
See the “IBM Power Systems PDU Information North America” section on page 168 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 60A@208V 3 phase PDUs IBM Switched & Monitored 60A@208V 3 phase PDU
P/N: 39Y8923 or FC: 6061 P/N: 46M4003 or FC: 5897
P/N: 71763NU or FC: 6051
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 60A@208V 3 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 60A@208V 3 phase PDUs IBM Switched & Monitored 60A@208V 3 phase PDU
P/N: 39Y8923 or FC: 6061 P/N: 46M4003 or FC: 5897
P/N: 71763NU or FC: 6051
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 60A@208V 3 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 50A@208V 3 phase PDUs IBM Switched & Monitored 50A@208V 3 phase PDU
P/N: 46M4140 or FC: 5926 P/N: 46M4134 or FC: 5931
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 50A@208V 3 phase Configuration
Currently IBM Power Systems does not have an available PDU to support this configuration. A suitable IBM System x
PDU from the list above or a third party PDU will need to be used to implement this configuration.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 50A@208V 3 phase PDUs IBM Switched & Monitored 50A@208V 3 phase PDU
P/N: 46M4140 or FC: 5926 P/N: 46M4134 or FC: 5931
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 50A@208V 3 phase Configuration
Currently IBM Power Systems does not have an available PDU to support this configuration. A suitable IBM System x
PDU from the list above or a third party PDU will need to be used to implement this configuration.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 50A@208V 3 phase PDUs IBM Switched & Monitored 50A@208V 3 phase PDU
P/N: 46M4140 or FC: 5926 P/N: 46M4134 or FC: 5931
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 50A@208V 3 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 50A@208V 3 phase PDUs IBM Switched & Monitored 50A@208V 3 phase PDU
P/N: 46M4140 or FC: 5926 P/N: 46M4134 or FC: 5931
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 50A@208V 3 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 30A@208V 3 phase Configuration
Currently IBM Power Systems does not have an available PDU to support this configuration. A suitable IBM System x
PDU from the list above or a third party PDU will need to be used to implement this configuration.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 30A@208V 3 phase Configuration
Currently IBM Power Systems does not have an available PDU to support this configuration. A suitable IBM System x
PDU from the list above or a third party PDU will need to be used to implement this configuration.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 30A@208V 3 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 30A@208V 3 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 60A@200-240V 1 phase PDUs IBM Switched & Monitored 60A@200-240V 1 phase PDU
P/N: 39Y8940 or FC: A11U P/N: 46M4002 + input line cord P/N: 40K9615 = FC: 5902
P/N: 39Y8948 + input line cord P/N: 40K9615 = FC: 6063
P/N: 71762NX + input line cord P/N: 40K9615 = FC: 6501
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 60A@200-240V 1 phase Configuration
See the “IBM Power Systems PDU Information North America” section on page 168 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 60A@200-240V 1 phase PDUs IBM Switched & Monitored 60A@200-240V 1 phase PDU
P/N: 39Y8940 or FC: A11U P/N: 46M4002 + input line cord P/N: 40K9615 = FC: 5902
P/N: 39Y8948 + input line cord P/N: 40K9615 = FC: 6063
P/N: 71762NX + input line cord P/N: 40K9615 = FC: 6501
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 60A@200-240V 1 phase Configuration
See the “IBM Power Systems PDU Information North America” section on page 168 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 60A@200-240V 1 phase PDUs IBM Switched & Monitored 60A@200-240V 1 phase PDU
P/N: 39Y8940 or FC: A11U P/N: 46M4002 + input line cord P/N: 40K9615 = FC: 5902
P/N: 39Y8948 + input line cord P/N: 40K9615 = FC: 6063
P/N: 71762NX + input line cord P/N: 40K9615 = FC: 6501
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 60A@200-240V 1 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 60A@200-240V 1 phase PDUs IBM Switched & Monitored 60A@200-240V 1 phase PDU
P/N: 39Y8940 or FC: A11U P/N: 46M4002 + input line cord P/N: 40K9615 = FC: 5902
P/N: 39Y8948 + input line cord P/N: 40K9615 = FC: 6063
P/N: 71762NX + input line cord P/N: 40K9615 = FC: 6501
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 60A@200-240V 1 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 30A@200-240V 1 phase PDUs IBM Switched & Monitored 30A@200-240V 1 phase PDU
P/N: 39Y8939 or FC: A11T P/N: 46M4002 + input line cord P/N: 40K9614 = FC: 5901
P/N: 39Y8948 + input line cord P/N: 40K9614 = FC: 6062
P/N: 71762NX + input line cord P/N: 40K9614 = FC: 6500
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 30A@200-240V 1 phase Configuration
See the “IBM Power Systems PDU Information North America” section on page 168 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 30A@200-240V 1 phase PDUs IBM Switched & Monitored 30A@200-240V 1 phase PDU
P/N: 39Y8939 or FC: A11T P/N: 46M4002 + input line cord P/N: 40K9614 = FC: 5901
P/N: 39Y8948 + input line cord P/N: 40K9614 = FC: 6062
P/N: 71762NX + input line cord P/N: 40K9614 = FC: 6500
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 30A@200-240V 1 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 30A@200-240V 1 phase PDUs IBM Switched & Monitored 30A@200-240V 1 phase PDU
P/N: 39Y8939 or FC: A11T P/N: 46M4002 + input line cord P/N: 40K9614 = FC: 5901
P/N: 39Y8948 + input line cord P/N: 40K9614 = FC: 6062
P/N: 71762NX + input line cord P/N: 40K9614 = FC: 6500
See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 30A@200-240V 1 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
IBM Basic 32A@380-415V 3 phase PDUs IBM Switched & Monitored 32A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 40K9611 = FC: 6066 P/N: 46M4002 + input line cord P/N: 40K9611 = FC: 5905
P/N: 46M4143 or FC: 5927 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9611 = FC: 6504
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 32A@380-415V 3 phase Configuration
See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 32A@380-415V 3 phase PDUs IBM Switched & Monitored 32A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 40K9611 = FC: 6066 P/N: 46M4002 + input line cord P/N: 40K9611 = FC: 5905
P/N: 46M4143 or FC: 5927 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9611 = FC: 6504
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 32A@380-415V 3 phase Configuration
See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.
IBM Basic 32A@380-415V 3 phase PDUs IBM Switched & Monitored 32A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 40K9611 = FC: 6066 P/N: 46M4002 + input line cord P/N: 40K9611 = FC: 5905
P/N: 46M4143 or FC: 5927 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9611 = FC: 6504
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 32A@380-415V 3 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 32A@380-415V 3 phase PDUs IBM Switched & Monitored 32A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 40K9611 = FC: 6066 P/N: 46M4002 + input line cord P/N: 40K9611 = FC: 5905
P/N: 46M4143 or FC: 5927 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9611 = FC: 6504
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 32A@380-415V 3 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 16A@380-415V 3 phase PDUs IBM Switched & Monitored 16A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 47C2495 = FC: A3T3 P/N: 46M4002 + input line cord P/N: 47C2495 = FC: A3T4
P/N: 71762NX + input line cord P/N: 47C2495 = FC: A3TC
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 16A@380-415V 3 phase Configuration
See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 16A@380-415V 3 phase PDUs IBM Switched & Monitored 16A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 47C2495 = FC: A3T3 P/N: 46M4002 + input line cord P/N: 47C2495 = FC: A3T4
P/N: 71762NX + input line cord P/N: 47C2495 = FC: A3TC
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 16A@380-415V 3 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.
IBM Basic 63A@220-240V 1 phase PDUs IBM Switched & Monitored 63A@220-240V 1 phase PDU
P/N: 39Y8935 or FC: A11W P/N: 46M4002 + input line cord P/N: 40K9613 = FC: 5904
P/N: 39Y8948 + input line cord P/N: 40K9613 = FC: 6065 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9613 = FC: 6503
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
2500W PSU N+N & N+1 Wiring Diagram for Derated International Power Systems Single Phase
PDUs
Requires Flex System power cord IBM Power Systems FC: 4558 | See “IBM Flex Power Cords” section for further details.
IBM Power Systems PDU Options for This 63A@220-240V 1 phase Configuration
Note: IBM Power Systems international single phase PDUs are derated to 24A for 32A single phase PDUs and 48A for
63A single phase PDUs.
See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.
IBM Basic 63A@220-240V 1 phase PDUs IBM Switched & Monitored 63A@220-240V 1 phase PDU
P/N: 39Y8935 or FC: A11W P/N: 46M4002 + input line cord P/N: 40K9613 = FC: 5904
P/N: 39Y8948 + input line cord P/N: 40K9613 = FC: 6065 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9613 = FC: 6503
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 63A@220-240V 1 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.
IBM Basic 32A@220-240V 1 phase PDUs IBM Switched & Monitored 32A@220-240V 1 phase
P/N: 39Y8934 (32A IEC 309 P+N+G) or FC: A11V PDU
P/N: 39Y8936 (30A KSC 8305) or FC: A11Y P/N: 46M4004 + input line cord A = FC: 5910
P/N: 39Y8937 (32A AUS/NZ 3112) or FC: A11X P/N: 46M4004 + input line cord B = FC: 5913
P/N: 39Y8948 + input line cord A = FC: 6064 P/N: 46M4004 + input line cord C = FC: 5914
P/N: 39Y8948 + input line cord B = FC: 6067
P/N: 39Y8948 + input line cord C = FC: 6068 PDU Input Line Cords
P/N: 71762NX + input line cord A = FC: 6502 A – P/N: 40K9612 (IEC 309 P+N+G)
P/N: 71762NX + input line cord B = FC: 6505 B – P/N: 40K9617 (AUS/NZ 3112 32A)
P/N: 71762NX + input line cord C = FC: 6506 C – P/N: 40K9618 (KSC 8305 30A)
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
2500W PSU N+N & N+1 Wiring Diagram for Derated International Power Systems Single Phase
PDUs
Requires Flex System power cord IBM Power Systems FC: 4558 | See “IBM Flex Power Cords” section for further details.
IBM Power Systems PDU Options for This 32A@220-240V 1 phase Configuration
IBM Power Systems international single phase PDUs are derated to 24A for 32A single phase PDUs and 48A for 63A
single phase PDUs.
See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.
IBM Basic 32A@220-240V 1 phase PDUs IBM Switched & Monitored 32A@220-240V 1 phase
P/N: 39Y8934 (32A IEC 309 P+N+G) or FC: A11V PDU
P/N: 39Y8936 (30A KSC 8305) or FC: A11Y P/N: 46M4004 + input line cord A = FC: 5910
P/N: 39Y8937 (32A AUS/NZ 3112) or FC: A11X P/N: 46M4004 + input line cord B = FC: 5913
P/N: 39Y8948 + input line cord A = FC: 6064 P/N: 46M4004 + input line cord C = FC: 5914
P/N: 39Y8948 + input line cord B = FC: 6067
P/N: 39Y8948 + input line cord C = FC: 6068 PDU Input Line Cords
P/N: 71762NX + input line cord A = FC: 6502 A – P/N: 40K9612 (IEC 309 P+N+G)
P/N: 71762NX + input line cord B = FC: 6505 B – P/N: 40K9617 (AUS/NZ 3112 32A)
P/N: 71762NX + input line cord C = FC: 6506 C – P/N: 40K9618 (KSC 8305 30A)
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 32A@220-240V 1 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 32A@380-415V 3 phase PDUs IBM Switched & Monitored 32A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 40K9611 = FC: 6066 P/N: 46M4002 + input line cord P/N: 40K9611 = FC: 5905
P/N: 46M4143 or FC: 5927 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9611 = FC: 6504
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 32A@380-415V 3 phase Configuration
See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 32A@380-415V 3 phase PDUs IBM Switched & Monitored 32A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 40K9611 = FC: 6066 P/N: 46M4002 + input line cord P/N: 40K9611 = FC: 5905
P/N: 46M4143 or FC: 5927 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9611 = FC: 6504
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 32A@380-415V 3 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 16A@380-415V 3 phase PDUs IBM Switched & Monitored 16A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 47C2495 = FC: A3T3 P/N: 46M4002 + input line cord P/N: 47C2495 = FC: A3T4
P/N: 71762NX + input line cord P/N: 47C2495 = FC: A3TC
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 16A@380-415V 3 phase Configuration
See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 16A@380-415V 3 phase PDUs IBM Switched & Monitored 16A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 47C2495 = FC: A3T3 P/N: 46M4002 + input line cord P/N: 47C2495 = FC: A3T4
P/N: 71762NX + input line cord P/N: 47C2495 = FC: A3TC
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 16A@380-415V 3 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.
IBM Basic 63A@220-240V 1 phase PDUs IBM Switched & Monitored 63A@220-240V 1 phase PDU
P/N: 39Y8935 or FC: A11W P/N: 46M4002 + input line cord P/N: 40K9613 = FC: 5904
P/N: 39Y8948 + input line cord P/N: 40K9613 = FC: 6065 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9613 = FC: 6503
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
2500W PSU N+1 Wiring Diagram for Derated International Power Systems Single Phase PDUs
Requires Flex System power cord IBM Power Systems FC: 4558 | See “IBM Flex Power Cords” section for further details.
IBM Power Systems PDU Options for This 63A@220-240V 1 phase Configuration
Note: IBM Power Systems international single phase PDUs are derated to 24A for 32A single phase PDUs and 48A for
63A single phase PDUs.
See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.
IBM Basic 63A@220-240V 1 phase PDUs IBM Switched & Monitored 63A@220-240V 1 phase PDU
P/N: 39Y8935 or FC: A11W P/N: 46M4002 + input line cord P/N: 40K9613 = FC: 5904
P/N: 39Y8948 + input line cord P/N: 40K9613 = FC: 6065 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9613 = FC: 6503
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 63A@220-240V 1 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.
IBM System x PDU Options for This 32A@220-240V 1 phase Configuration
IBM Basic 32A@220-240V 1 phase PDUs IBM Switched & Monitored 32A@220-240V 1 phase
P/N: 39Y8934 (32A IEC 309 P+N+G) or FC: A11V PDU
P/N: 39Y8936 (30A KSC 8305) or FC: A11Y P/N: 46M4004 + input line cord A = FC: 5910
P/N: 39Y8937 (32A AUS/NZ 3112) or FC: A11X P/N: 46M4004 + input line cord B = FC: 5913
P/N: 39Y8948 + input line cord A = FC: 6064 P/N: 46M4004 + input line cord C = FC: 5914
P/N: 39Y8948 + input line cord B = FC: 6067
P/N: 39Y8948 + input line cord C = FC: 6068 PDU Input Line Cords
P/N: 71762NX + input line cord A = FC: 6502 A – P/N: 40K9612 (IEC 309 P+N+G)
P/N: 71762NX + input line cord B = FC: 6505 B – P/N: 40K9617 (AUS/NZ 3112 32A)
P/N: 71762NX + input line cord C = FC: 6506 C – P/N: 40K9618 (KSC 8305 30A)
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
2500W PSU N+1 Wiring Diagram for Derated International Power Systems Single Phase PDUs
Requires Flex System power cord IBM Power Systems FC: 4558 | See “IBM Flex Power Cords” section for further details.
IBM Power Systems PDU Options for This 32A@220-240V 1 phase Configuration
IBM Power Systems international single phase PDUs are derated to 24A for 32A single phase PDUs and 48A for 63A
single phase PDUs.
See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.
IBM Basic 32A@220-240V 1 phase PDUs IBM Switched & Monitored 32A@220-240V 1 phase
P/N: 39Y8934 (32A IEC 309 P+N+G) or FC: A11V PDU
P/N: 39Y8936 (30A KSC 8305) or FC: A11Y P/N: 46M4004 + input line cord A = FC: 5910
P/N: 39Y8937 (32A AUS/NZ 3112) or FC: A11X P/N: 46M4004 + input line cord B = FC: 5913
P/N: 39Y8948 + input line cord A = FC: 6064 P/N: 46M4004 + input line cord C = FC: 5914
P/N: 39Y8948 + input line cord B = FC: 6067
P/N: 39Y8948 + input line cord C = FC: 6068 PDU Input Line Cords
P/N: 71762NX + input line cord A = FC: 6502 A – P/N: 40K9612 (IEC 309 P+N+G)
P/N: 71762NX + input line cord B = FC: 6505 B – P/N: 40K9617 (AUS/NZ 3112 32A)
P/N: 71762NX + input line cord C = FC: 6506 C – P/N: 40K9618 (KSC 8305 30A)
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 32A@220-240V 1 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 32A@380-415V 3 phase PDUs IBM Switched & Monitored 32A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 40K9611 = FC: 6066 P/N: 46M4002 + input line cord P/N: 40K9611 = FC: 5905
P/N: 46M4143 or FC: 5927 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9611 = FC: 6504
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 32A@380-415V 3 phase Configuration
See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM System x PDU Options for This 32A@380-415V 3 phase Configuration
IBM Basic 32A@380-415V 3 phase PDUs IBM Switched & Monitored 32A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 40K9611 = FC: 6066 P/N: 46M4002 + input line cord P/N: 40K9611 = FC: 5905
P/N: 46M4143 or FC: 5927 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9611 = FC: 6504
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 32A@380-415V 3 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 16A@380-415V 3 phase PDUs IBM Switched & Monitored 16A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 47C2495 = FC: A3T3 P/N: 46M4002 + input line cord P/N: 47C2495 = FC: A3T4
P/N: 71762NX + input line cord P/N: 47C2495 = FC: A3TC
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 16A@380-415V 3 phase Configuration
See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 16A@380-415V 3 phase PDUs IBM Switched & Monitored 16A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 47C2495 = FC: A3T3 P/N: 46M4002 + input line cord P/N: 47C2495 = FC: A3T4
P/N: 71762NX + input line cord P/N: 47C2495 = FC: A3TC
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 16A@380-415V 3 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.
IBM Basic 63A@220-240V 1 phase PDUs IBM Switched & Monitored 63A@220-240V 1 phase PDU
P/N: 39Y8935 or FC: A11W P/N: 46M4002 + input line cord P/N: 40K9613 = FC: 5904
P/N: 39Y8948 + input line cord P/N: 40K9613 = FC: 6065 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9613 = FC: 6503
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDUs are not supported with this configuration due to IBM Power Systems single phase PDUs derating.
Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.
IBM Basic 63A@220-240V 1 phase PDUs IBM Switched & Monitored 63A@220-240V 1 phase PDU
P/N: 39Y8935 or FC: A11W P/N: 46M4002 + input line cord P/N: 40K9613 = FC: 5904
P/N: 39Y8948 + input line cord P/N: 40K9613 = FC: 6065 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9613 = FC: 6503
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 63A@220-240V 1 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 32A@380-415V 3 phase PDUs IBM Switched & Monitored 32A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 40K9611 = FC: 6066 P/N: 46M4002 + input line cord P/N: 40K9611 = FC: 5905
P/N: 46M4143 or FC: 5927 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9611 = FC: 6504
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 32A@380-415V 3 phase Configuration
See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 32A@380-415V 3 phase PDUs IBM Switched & Monitored 32A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 40K9611 = FC: 6066 P/N: 46M4002 + input line cord P/N: 40K9611 = FC: 5905
P/N: 46M4143 or FC: 5927 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9611 = FC: 6504
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 32A@380-415V 3 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 16A@380-415V 3 phase PDUs IBM Switched & Monitored 16A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 47C2495 = FC: A3T3 P/N: 46M4002 + input line cord P/N: 47C2495 = FC: A3T4
P/N: 71762NX + input line cord P/N: 47C2495 = FC: A3TC
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 16A@380-415V 3 phase Configuration
See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 16A@380-415V 3 phase PDUs IBM Switched & Monitored 16A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 47C2495 = FC: A3T3 P/N: 46M4002 + input line cord P/N: 47C2495 = FC: A3T4
P/N: 71762NX + input line cord P/N: 47C2495 = FC: A3TC
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 16A@380-415V 3 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.
IBM Basic 63A@220-240V 1 phase PDUs IBM Switched & Monitored 63A@220-240V 1 phase PDU
P/N: 39Y8935 or FC: A11W P/N: 46M4002 + input line cord P/N: 40K9613 = FC: 5904
P/N: 39Y8948 + input line cord P/N: 40K9613 = FC: 6065 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9613 = FC: 6503
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
2500W PSU N+N & N+1 Wiring Diagram for Derated International Power Systems Single Phase
PDUs
Requires Flex System power cord IBM Power Systems FC: 4558 | See “IBM Flex Power Cords” section for further details.
IBM Power Systems PDU Options for This 63A@220-240V 1 phase Configuration
Note: IBM Power Systems international single phase PDUs are derated to 24A for 32A single phase PDUs and 48A for
63A single phase PDUs.
See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.
IBM Basic 63A@220-240V 1 phase PDUs IBM Switched & Monitored 63A@220-240V 1 phase PDU
P/N: 39Y8935 or FC: A11W P/N: 46M4002 + input line cord P/N: 40K9613 = FC: 5904
P/N: 39Y8948 + input line cord P/N: 40K9613 = FC: 6065 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9613 = FC: 6503
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 63A@220-240V 1 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.
IBM Basic 32A@220-240V 1 phase PDUs IBM Switched & Monitored 32A@220-240V 1 phase
P/N: 39Y8934 (32A IEC 309 P+N+G) or FC: A11V PDU
P/N: 39Y8936 (30A KSC 8305) or FC: A11Y P/N: 46M4004 + input line cord A = FC: 5910
P/N: 39Y8937 (32A AUS/NZ 3112) or FC: A11X P/N: 46M4004 + input line cord B = FC: 5913
P/N: 39Y8948 + input line cord A = FC: 6064 P/N: 46M4004 + input line cord C = FC: 5914
P/N: 39Y8948 + input line cord B = FC: 6067
P/N: 39Y8948 + input line cord C = FC: 6068 PDU Input Line Cords
P/N: 71762NX + input line cord A = FC: 6502 A – P/N: 40K9612 (IEC 309 P+N+G)
P/N: 71762NX + input line cord B = FC: 6505 B – P/N: 40K9617 (AUS/NZ 3112 32A)
P/N: 71762NX + input line cord C = FC: 6506 C – P/N: 40K9618 (KSC 8305 30A)
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
2500W PSU N+N & N+1 Wiring Diagram for Derated International Power Systems Single Phase
PDUs
Requires Flex System power cord IBM Power Systems FC: 4558 | See “IBM Flex Power Cords” section for further details.
IBM Power Systems PDU Options for This 32A@220-240V 1 phase Configuration
IBM Power Systems international single phase PDUs are derated to 24A for 32A single phase PDUs and 48A for 63A
single phase PDUs.
See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.
IBM Basic 32A@220-240V 1 phase PDUs IBM Switched & Monitored 32A@220-240V 1 phase
P/N: 39Y8934 (32A IEC 309 P+N+G) or FC: A11V PDU
P/N: 39Y8936 (30A KSC 8305) or FC: A11Y P/N: 46M4004 + input line cord A = FC: 5910
P/N: 39Y8937 (32A AUS/NZ 3112) or FC: A11X P/N: 46M4004 + input line cord B = FC: 5913
P/N: 39Y8948 + input line cord A = FC: 6064 P/N: 46M4004 + input line cord C = FC: 5914
P/N: 39Y8948 + input line cord B = FC: 6067
P/N: 39Y8948 + input line cord C = FC: 6068 PDU Input Line Cords
P/N: 71762NX + input line cord A = FC: 6502 A – P/N: 40K9612 (IEC 309 P+N+G)
P/N: 71762NX + input line cord B = FC: 6505 B – P/N: 40K9617 (AUS/NZ 3112 32A)
P/N: 71762NX + input line cord C = FC: 6506 C – P/N: 40K9618 (KSC 8305 30A)
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 32A@220-240V 1 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 32A@380-415V 3 phase PDUs IBM Switched & Monitored 32A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 40K9611 = FC: 6066 P/N: 46M4002 + input line cord P/N: 40K9611 = FC: 5905
P/N: 46M4143 or FC: 5927 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9611 = FC: 6504
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 32A@380-415V 3 phase Configuration
See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 32A@380-415V 3 phase PDUs IBM Switched & Monitored 32A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 40K9611 = FC: 6066 P/N: 46M4002 + input line cord P/N: 40K9611 = FC: 5905
P/N: 46M4143 or FC: 5927 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9611 = FC: 6504
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 32A@380-415V 3 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 16A@380-415V 3 phase PDUs IBM Switched & Monitored 16A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 47C2495 = FC: A3T3 P/N: 46M4002 + input line cord P/N: 47C2495 = FC: A3T4
P/N: 71762NX + input line cord P/N: 47C2495 = FC: A3TC
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 16A@380-415V 3 phase Configuration
See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 16A@380-415V 3 phase PDUs IBM Switched & Monitored 16A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 47C2495 = FC: A3T3 P/N: 46M4002 + input line cord P/N: 47C2495 = FC: A3T4
P/N: 71762NX + input line cord P/N: 47C2495 = FC: A3TC
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 16A@380-415V 3 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.
IBM Basic 63A@220-240V 1 phase PDUs IBM Switched & Monitored 63A@220-240V 1 phase PDU
P/N: 39Y8935 or FC: A11W P/N: 46M4002 + input line cord P/N: 40K9613 = FC: 5904
P/N: 39Y8948 + input line cord P/N: 40K9613 = FC: 6065 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9613 = FC: 6503
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
2500W PSU N+1 Wiring Diagram for Derated International Power Systems Single Phase PDUs
Requires Flex System power cord IBM Power Systems FC: 4558 | See “IBM Flex Power Cords” section for further details.
IBM Power Systems PDU Options for This 63A@220-240V 1 phase Configuration
Note: IBM Power Systems international single phase PDUs are derated to 24A for 32A single phase PDUs and 48A for
63A single phase PDUs.
See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.
IBM Basic 63A@220-240V 1 phase PDUs IBM Switched & Monitored 63A@220-240V 1 phase PDU
P/N: 39Y8935 or FC: A11W P/N: 46M4002 + input line cord P/N: 40K9613 = FC: 5904
P/N: 39Y8948 + input line cord P/N: 40K9613 = FC: 6065 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9613 = FC: 6503
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 63A@220-240V 1 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.
IBM Basic 32A@220-240V 1 phase PDUs IBM Switched & Monitored 32A@220-240V 1 phase
P/N: 39Y8934 (32A IEC 309 P+N+G) or FC: A11V PDU
P/N: 39Y8936 (30A KSC 8305) or FC: A11Y P/N: 46M4004 + input line cord A = FC: 5910
P/N: 39Y8937 (32A AUS/NZ 3112) or FC: A11X P/N: 46M4004 + input line cord B = FC: 5913
P/N: 39Y8948 + input line cord A = FC: 6064 P/N: 46M4004 + input line cord C = FC: 5914
P/N: 39Y8948 + input line cord B = FC: 6067
P/N: 39Y8948 + input line cord C = FC: 6068 PDU Input Line Cords
P/N: 71762NX + input line cord A = FC: 6502 A – P/N: 40K9612 (IEC 309 P+N+G)
P/N: 71762NX + input line cord B = FC: 6505 B – P/N: 40K9617 (AUS/NZ 3112 32A)
P/N: 71762NX + input line cord C = FC: 6506 C – P/N: 40K9618 (KSC 8305 30A)
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
2500W PSU N+1 Wiring Diagram for Derated International Power Systems Single Phase PDUs
Requires Flex System power cord IBM Power Systems FC: 4558 | See “IBM Flex Power Cords” section for further details.
IBM Power Systems PDU Options for This 32A@220-240V 1 phase Configuration
IBM Power Systems international single phase PDUs are derated to 24A for 32A single phase PDUs and 48A for 63A
single phase PDUs.
See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.
IBM Basic 32A@220-240V 1 phase PDUs IBM Switched & Monitored 32A@220-240V 1 phase
P/N: 39Y8934 (32A IEC 309 P+N+G) or FC: A11V PDU
P/N: 39Y8936 (30A KSC 8305) or FC: A11Y P/N: 46M4004 + input line cord A = FC: 5910
P/N: 39Y8937 (32A AUS/NZ 3112) or FC: A11X P/N: 46M4004 + input line cord B = FC: 5913
P/N: 39Y8948 + input line cord A = FC: 6064 P/N: 46M4004 + input line cord C = FC: 5914
P/N: 39Y8948 + input line cord B = FC: 6067
P/N: 39Y8948 + input line cord C = FC: 6068 PDU Input Line Cords
P/N: 71762NX + input line cord A = FC: 6502 A – P/N: 40K9612 (IEC 309 P+N+G)
P/N: 71762NX + input line cord B = FC: 6505 B – P/N: 40K9617 (AUS/NZ 3112 32A)
P/N: 71762NX + input line cord C = FC: 6506 C – P/N: 40K9618 (KSC 8305 30A)
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 32A@220-240V 1 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 32A@380-415V 3 phase PDUs IBM Switched & Monitored 32A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 40K9611 = FC: 6066 P/N: 46M4002 + input line cord P/N: 40K9611 = FC: 5905
P/N: 46M4143 or FC: 5927 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9611 = FC: 6504
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 32A@380-415V 3 phase Configuration
See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 32A@380-415V 3 phase PDUs IBM Switched & Monitored 32A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 40K9611 = FC: 6066 P/N: 46M4002 + input line cord P/N: 40K9611 = FC: 5905
P/N: 46M4143 or FC: 5927 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9611 = FC: 6504
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 32A@380-415V 3 phase Configuration
See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 32A@380-415V 3 phase PDUs IBM Switched & Monitored 32A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 40K9611 = FC: 6066 P/N: 46M4002 + input line cord P/N: 40K9611 = FC: 5905
P/N: 46M4143 or FC: 5927 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9611 = FC: 6504
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 32A@380-415V 3 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 32A@380-415V 3 phase PDUs IBM Switched & Monitored 32A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 40K9611 = FC: 6066 P/N: 46M4002 + input line cord P/N: 40K9611 = FC: 5905
P/N: 46M4143 or FC: 5927 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9611 = FC: 6504
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 32A@380-415V 3 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 16A@380-415V 3 phase PDUs IBM Switched & Monitored 16A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 47C2495 = FC: A3T3 P/N: 46M4002 + input line cord P/N: 47C2495 = FC: A3T4
P/N: 71762NX + input line cord P/N: 47C2495 = FC: A3TC
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 16A@380-415V 3 phase Configuration
See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 16A@380-415V 3 phase PDUs IBM Switched & Monitored 16A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 47C2495 = FC: A3T3 P/N: 46M4002 + input line cord P/N: 47C2495 = FC: A3T4
P/N: 71762NX + input line cord P/N: 47C2495 = FC: A3TC
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 16A@380-415V 3 phase Configuration
IBM Monitored 16A@380-415V 3 phase PDU
P/N: 42R8743 or FC: 7189 + input line cord P/N: 39M5412 or FC: 6653
See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 16A@380-415V 3 phase PDUs IBM Switched & Monitored 16A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 47C2495 = FC: A3T3 P/N: 46M4002 + input line cord P/N: 47C2495 = FC: A3T4
P/N: 71762NX + input line cord P/N: 47C2495 = FC: A3TC
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 16A@380-415V 3 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM Basic 16A@380-415V 3 phase PDUs IBM Switched & Monitored 16A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 47C2495 = FC: A3T3 P/N: 46M4002 + input line cord P/N: 47C2495 = FC: A3T4
P/N: 71762NX + input line cord P/N: 47C2495 = FC: A3TC
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 16A@380-415V 3 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.
IBM Basic 63A@220-240V 1 phase PDUs IBM Switched & Monitored 63A@220-240V 1 phase PDU
P/N: 39Y8935 or FC: A11W P/N: 46M4002 + input line cord P/N: 40K9613 = FC: 5904
P/N: 39Y8948 + input line cord P/N: 40K9613 = FC: 6065 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9613 = FC: 6503
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
2500W PSU N+N & N+1 Wiring Diagram for Derated International Power Systems Single Phase
PDUs
Requires Flex System power cord IBM Power Systems FC: 4558 | See “IBM Flex Power Cords” section for further details.
IBM Power Systems PDU Options for This 63A@220-240V 1 phase Configuration
Note: IBM Power Systems international single phase PDUs are derated to 24A for 32A single phase PDUs and 48A for
63A single phase PDUs.
See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.
IBM Basic 63A@220-240V 1 phase PDUs IBM Switched & Monitored 63A@220-240V 1 phase PDU
P/N: 39Y8935 or FC: A11W P/N: 46M4002 + input line cord P/N: 40K9613 = FC: 5904
P/N: 39Y8948 + input line cord P/N: 40K9613 = FC: 6065 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9613 = FC: 6503
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
2500W PSU N+1 Wiring Diagram for Derated International Power Systems Single Phase PDUs
Requires Flex System power cord IBM Power Systems FC: 4558 | See “IBM Flex Power Cords” section for further details.
IBM Power Systems PDU Options for This 63A@220-240V 1 phase Configuration
Note: IBM Power Systems international single phase PDUs are derated to 24A for 32A single phase PDUs and 48A for
63A single phase PDUs.
See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.
IBM Basic 63A@220-240V 1 phase PDUs IBM Switched & Monitored 63A@220-240V 1 phase PDU
P/N: 39Y8935 or FC: A11W P/N: 46M4002 + input line cord P/N: 40K9613 = FC: 5904
P/N: 39Y8948 + input line cord P/N: 40K9613 = FC: 6065 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9613 = FC: 6503
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 63A@220-240V 1 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.
IBM Basic 63A@220-240V 1 phase PDUs IBM Switched & Monitored 63A@220-240V 1 phase PDU
P/N: 39Y8935 or FC: A11W P/N: 46M4002 + input line cord P/N: 40K9613 = FC: 5904
P/N: 39Y8948 + input line cord P/N: 40K9613 = FC: 6065 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9613 = FC: 6503
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 63A@220-240V 1 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.
IBM Basic 32A@220-240V 1 phase PDUs IBM Switched & Monitored 32A@220-240V 1 phase
P/N: 39Y8934 (32A IEC 309 P+N+G) or FC: A11V PDU
P/N: 39Y8936 (30A KSC 8305) or FC: A11Y P/N: 46M4004 + input line cord A = FC: 5910
P/N: 39Y8937 (32A AUS/NZ 3112) or FC: A11X P/N: 46M4004 + input line cord B = FC: 5913
P/N: 39Y8948 + input line cord A = FC: 6064 P/N: 46M4004 + input line cord C = FC: 5914
P/N: 39Y8948 + input line cord B = FC: 6067
P/N: 39Y8948 + input line cord C = FC: 6068 PDU Input Line Cords
P/N: 71762NX + input line cord A = FC: 6502 A – P/N: 40K9612 (IEC 309 P+N+G)
P/N: 71762NX + input line cord B = FC: 6505 B – P/N: 40K9617 (AUS/NZ 3112 32A)
P/N: 71762NX + input line cord C = FC: 6506 C – P/N: 40K9618 (KSC 8305 30A)
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
2500W PSU N+N & N+1 Wiring Diagram for Derated International Power Systems Single Phase
PDUs
Requires Flex System power cord IBM Power Systems FC: 4558 | See “IBM Flex Power Cords” section for further details.
IBM Power Systems PDU Options for This 32A@220-240V 1 phase Configuration
IBM Power Systems international single phase PDUs are derated to 24A for 32A single phase PDUs and 48A for 63A
single phase PDUs.
See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.
Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.
IBM Basic 32A@220-240V 1 phase PDUs IBM Switched & Monitored 32A@220-240V 1 phase
P/N: 39Y8934 (32A IEC 309 P+N+G) or FC: A11V PDU
P/N: 39Y8936 (30A KSC 8305) or FC: A11Y P/N: 46M4004 + input line cord A = FC: 5910
P/N: 39Y8937 (32A AUS/NZ 3112) or FC: A11X P/N: 46M4004 + input line cord B = FC: 5913
P/N: 39Y8948 + input line cord A = FC: 6064 P/N: 46M4004 + input line cord C = FC: 5914
P/N: 39Y8948 + input line cord B = FC: 6067
P/N: 39Y8948 + input line cord C = FC: 6068 PDU Input Line Cords
P/N: 71762NX + input line cord A = FC: 6502 A – P/N: 40K9612 (IEC 309 P+N+G)
P/N: 71762NX + input line cord B = FC: 6505 B – P/N: 40K9617 (AUS/NZ 3112 32A)
P/N: 71762NX + input line cord C = FC: 6506 C – P/N: 40K9618 (KSC 8305 30A)
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDUs are not supported with this configuration due to IBM Power Systems single phase PDUs derating.
Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.
IBM Basic 32A@220-240V 1 phase PDUs IBM Switched & Monitored 32A@220-240V 1 phase
P/N: 39Y8934 (32A IEC 309 P+N+G) or FC: A11V PDU
P/N: 39Y8936 (30A KSC 8305) or FC: A11Y P/N: 46M4004 + input line cord A = FC: 5910
P/N: 39Y8937 (32A AUS/NZ 3112) or FC: A11X P/N: 46M4004 + input line cord B = FC: 5913
P/N: 39Y8948 + input line cord A = FC: 6064 P/N: 46M4004 + input line cord C = FC: 5914
P/N: 39Y8948 + input line cord B = FC: 6067
P/N: 39Y8948 + input line cord C = FC: 6068 PDU Input Line Cords
P/N: 71762NX + input line cord A = FC: 6502 A – P/N: 40K9612 (IEC 309 P+N+G)
P/N: 71762NX + input line cord B = FC: 6505 B – P/N: 40K9617 (AUS/NZ 3112 32A)
P/N: 71762NX + input line cord C = FC: 6506 C – P/N: 40K9618 (KSC 8305 30A)
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 32A@220-240V 1 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.
IBM Basic 32A@220-240V 1 phase PDUs IBM Switched & Monitored 32A@220-240V 1 phase
P/N: 39Y8934 (32A IEC 309 P+N+G) or FC: A11V PDU
P/N: 39Y8936 (30A KSC 8305) or FC: A11Y P/N: 46M4004 + input line cord A = FC: 5910
P/N: 39Y8937 (32A AUS/NZ 3112) or FC: A11X P/N: 46M4004 + input line cord B = FC: 5913
P/N: 39Y8948 + input line cord A = FC: 6064 P/N: 46M4004 + input line cord C = FC: 5914
P/N: 39Y8948 + input line cord B = FC: 6067
P/N: 39Y8948 + input line cord C = FC: 6068 PDU Input Line Cords
P/N: 71762NX + input line cord A = FC: 6502 A – P/N: 40K9612 (IEC 309 P+N+G)
P/N: 71762NX + input line cord B = FC: 6505 B – P/N: 40K9617 (AUS/NZ 3112 32A)
P/N: 71762NX + input line cord C = FC: 6506 C – P/N: 40K9618 (KSC 8305 30A)
See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.
IBM Power Systems PDU Options for This 32A@220-240V 1 phase Configuration
Currently IBM Power Systems does not support the Flex System 2100W PSU.
UPS Configurations
1x Flex (6x PSU) on 2x IBM UPS11000 – World Wide
This configuration will consume 20U in rack (Flex = 10U, two IBM UPS11000 = 10U). This means a maximum of
two of this configuration can be installed in a 42U rack.
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex power cord FC: 6252 or 6292 | See “IBM Flex Power Cords” section for further details.
IBM UPS11000 P/N: 53959KX & EBM P/N: 69Y1986 FC: 5735
See the IBM System x Uninterruptible Power Supply (UPS) Guide for further details on the IBM UPS6000:
http://www.ibm.com/support/techdocs/atsmastr.nsf/WebIndex/WP101655
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex power cord FC: 6252 or 6292 | See “IBM Flex Power Cords” section for further details.
IBM UPS6000 P/N: 53956KX & EBM P/N: 69Y1984 FC: 5734
See the IBM System x Uninterruptible Power Supply (UPS) Guide for further details on the IBM UPS6000:
http://www.ibm.com/support/techdocs/atsmastr.nsf/WebIndex/WP101655
Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.
Requires Flex power cord FC: 6252 or 6292 | See “IBM Flex Power Cords” section for further details.
IBM UPS6000 P/N: 53956AX & EBM P/N: 69Y1984 FC: 5734
See the IBM System x Uninterruptible Power Supply (UPS) Guide for further details on the IBM UPS6000:
http://www.ibm.com/support/techdocs/atsmastr.nsf/WebIndex/WP101655
PureFlex Systems is a pre-configured, pre-integrated infrastructure with integrated management and cloud
capabilities, factory tuned from IBM with x86 and Power hybrid solution.
Flex Systems allows you to build and tune a custom configuration based on the most advanced blade server
in the market with maximum x86 EP compute and memory performance.
This section will cover some of the predefined PureFlex configurations examples available through Systems x.
Below is a link to the IBM System x and Cluster Solutions Configurator (x-config) used to create PureFlex
configurations for System x orders.
https://www.ibm.com/products/hardware/configurator/americas/bhui/asit/index.html
Below are some quick links to the PureFlex Systems x-config Configuration Examples in this section:
3x Flex Chassis w/ 4x ToR Switches – 3 Phase 60A@208V & 32A@380-415V – Page 146
3x Flex Chassis w/ 6x ToR Switches – 3 Phase 60A@208V & 32A@380-415V – Page 147
3x Flex Chassis w/ 6x ToR Switches – 1 Phase 60A@200-240V & 63A@220-240V – Page 149
2x Flex Chassis w/ 6x ToR Switches – 3 Phase 60A@208V & 32A@380-415V – Page 150
2x Flex Chassis w/ 6x ToR Switches – 1 Phase 60A@200-240V & 63A@220-240V – Page 152
2x Flex Chassis w/ 6x ToR Switches – 1 Phase 20A@200-240V & 30A@200-240V– Page 153
This PureFlex configuration is not supported internationally. It is only supported in North America and countries
that use the NEMA type electric plugs and outlets.
PureFlex Systems is a pre-configured, pre-integrated infrastructure with integrated management and cloud
capabilities, factory tuned from IBM with x86 and Power hybrid solution.
Flex Systems allows you to build and tune a custom configuration based on the most advanced blade server
in the market with maximum x86 EP compute and memory performance.
This section will cover some of the predefined PureFlex configurations examples available through IBM Power
Systems. Below is a link to the IBM Configurator for e-Business (e-config) used to create PureFlex
configurations for IBM Power Systems orders.
http://www.ibm.com/services/econfig/announce/index.htm
Below are some quick links to the PureFlex Systems e-config Configuration Examples in this section:
3x PureFlex Chassis w/ 6x ToR Switches & 2x V7000 – 3ph 60A@208V & 32A@380-415V – Page 155
3x PureFlex Chassis w/ 6x ToR Switches & 2x V7000 – 1ph 60A@200-240V & 63A@220-240V – Page 157
2x PureFlex Chassis w/ 6x ToR Switches & 7x V7000 – 3ph 60A@208V & 32A@380-415V – Page 159
2x PureFlex Chassis w/ 6x ToR Switches & 7x V7000 – 1ph 60A@200-240V & 63A@220-240V – Page 161
2x Flex Chassis w/ 6x ToR Switches & 7x V7000 – 1 Phase 20A@200-240V & 30A@200-240V – Page 163
1x PureFlex Chassis w/ 6x ToR Switches & 12x V7000 – 3ph 60A@208V & 32A@380-415V – Page 164
1x PureFlex Chassis w/ 6x ToR Switches & 12x V7000 – 1ph 60A@200-240V & 63A@220-240V– Page 166
This PureFlex configuration is not supported internationally. It is only supported in North America and countries
that use the NEMA type electric plugs and outlets.
1x PureFlex Chassis w/ 6x ToR Switches & 12x V7000 – 3ph 60A@208V &
32A@380-415V – e-config Example
IBM System x & Power Systems North American PDUs Input Line Cords
NEMA L6-30
NEMA L6-30P (4.3m) 30A (24A Derated) @ 200V-240V Single Phase
200-240V 100-120V
100-120V
G
X
EQUIP.
GR. Y
G
NEMA L6-30
Used with:
IBM System x PDU Information North America
Only a receptacle or a connector is needed to mate with the plug on the PDU input line cord. See section
“IEC 309 Pin & Sleeve Plug Decode” on page 188 in this document for further details on IEC309.
Matching receptacle listing 360R6W IP-67 HUBBELL, Hubbell receptacle P/N HBL360R6W
Matching connector listing 360C6W IP-67 HUBBELL, Hubbell connector P/N HBL360C6W
Used with:
IBM System x PDU Information North America
NEMA L21-30
Attached 3.0 meter line cord with NEMA L21-30P Plug
30A (13.85A / Phase Derated) @ 200V-240V Three Phase Delta
41.55A Total Derated Circuit Capacity
L21-30 Z
X 120V 208V
Y
N
Y 208V
G
Z
120V 208V
N
120V
X SYS.
GR.
G
EQUIP.
GR.
Used with:
IBM System x PDUs
Only a receptacle or a connector is needed to mate with the plug on the PDU input line cord.
Matching receptacle listing CS8369
Matching connector listing CS8364
Used with:
46M4140 – 0U 12 C19/12 C13 PDU Basic
46M4134 – 0U 12 C19/12 C13 Switched and Monitored
Female Male Z
208V 208V 120V
X X
Y Y Y
208V 120V
Z Z
G G X
120V
G
EQUIP.
GR.
Used with:
IBM System x PDU Information North America
Only a receptacle or a connector is needed to mate with the plug on the PDU input line cord. See section
“IEC 309 Pin & Sleeve Plug Decode” on page 188 in this document for further details on IEC309.
Matching receptacle listing 460R9W IP-67 HUBBELL, Hubbell receptacle P/N HBL460R9W
Matching connector listing 460C9W IP-67 HUBBELL, Hubbell connector P/N HBL460C9W
EQUIP.
GR.
Used with:
IBM System x PDU Information North America
IBM System x & Power Systems International PDUs Input Line Cords
IEC 309 P+N+G – 32A@220-240V 1ph
IEC 309 P+N+G (4.3m) - 32A / 220-240V Single Phase
Only a receptacle or a connector is needed to mate with the plug on the PDU input line cord. See section
“IEC 309 Pin & Sleeve Plug Decode” on page 188 in this document for further details on IEC309.
Matching receptacle listing 332R6W IP-67 HUBBELL, Hubbell receptacle P/N HBL332R6W
Matching connector listing 332C6W IP-67 HUBBELL, Hubbell connector P/N HBL332C6W
EQUIP.
GR.
Used with:
IBM System x PDU Information International
PDU + Number /
PDU Part Line Cord Line Type of Form
PDU Name Number Part Number Cord FC Outlet Factor
Front End Basic 39Y8934 Comes with PDU A11V 3 / C19 Front ½U
Enterprise C13 Basic 39Y8941 40K9612 6014 12 / C13 Front 1U
DPI Enterprise Basic 39Y8948 40K9612 6064 6 / C19 Front 1U
9 / C19 Front
DPI Ultra Density Enterprise Basic 71762NX 40K9612 6502 1U
3 / C13 Back
0U 24 C13 Basic 46M4131 Attached 5925 24 / C13 Front 0U
Enterprise + - C13 Monitored 39M2816 40K9612 6034 12 / C13 Front 1U
1U 12 C13 Switched & Monitored 46M4004 40K9612 5910 12 / C13 Front 1U
9 / C19 Front
1U 9 C19 / 3 C13 Switched & Monitored 46M4002 40K9612 5903 1U
3 / C13 Back
0U 24 C13U Switched & Monitored 46M4119 Attached 5930 24 / C13 Front 0U
G G G
EQUIP.
GR.
Used with:
IBM System x PDU Information International
PDU + Number /
PDU Part Line Cord Line Type of Form
PDU Name Number Part Number Cord FC Outlet Factor
Front End Basic 39Y8936 Comes with PDU A11Y 3 / C19 Front ½U
Enterprise C13 Basic 39Y8941 40K9617 6017 12 / C13 Front 1U
DPI Enterprise Basic 39Y8948 40K9617 6067 6 / C19 Front 1U
9 / C19 Front
DPI Ultra Density Enterprise Basic 71762NX 40K9617 6505 1U
3 / C13 Back
Enterprise + - C13 Monitored 39M2816 40K9617 6037 12 / C13 Front 1U
1U 12 C13 Switched & Monitored 46M4004 40K9617 5913 12 / C13 Front 1U
9 / C19 Front
1U 9 C19 / 3 C13 Switched & Monitored 46M4002 40K9617 5906 1U
3 / C13 Back
N L L N 220V 220V
N
G G
G
EQUIP.
GR.
Used with:
IBM System x PDU Information International
PDU + Number /
PDU Part Line Cord Line Type of Form
PDU Name Number Part Number Cord FC Outlet Factor
Front End Basic 39Y8937 Comes with PDU A11X 3 / C19 Front ½U
Enterprise C13 Basic 39Y8941 40K9618 6018 12 / C13 Front 1U
DPI Enterprise Basic 39Y8948 40K9618 6068 6 / C19 Front 1U
9 / C19 Front
DPI Ultra Density Enterprise Basic 71762NX 40K9618 6506 1U
3 / C13 Back
Enterprise + - C13 Monitored 39M2816 40K9618 6038 12 / C13 Front 1U
1U 12 C13 Switched & Monitored 46M4004 40K9618 5914 12 / C13 Front 1U
9 / C19 Front
1U 9 C19 / 3 C13 Switched & Monitored 46M4002 40K9618 5907 1U
3 / C13 Back
Only a receptacle or a connector is needed to mate with the plug on the PDU input line cord. See section
“IEC 309 Pin & Sleeve Plug Decode” on page 188 in this document for further details on IEC309.
Matching receptacle listing 363R6W IP-67 HUBBELL, Hubbell receptacle P/N HBL363R6W
Matching connector listing 363C6W IP-67 HUBBELL, Hubbell connector P/N HBL363C6W
EQUIP.
GR.
Used with:
IBM System x PDU Information International
PDU + Number /
PDU Part Line Cord Line Type of Form
PDU Name Number Part Number Cord FC Outlet Factor
Front End Basic 39Y8935 Comes with PDU A11W 3 / C19 Front ½U
Enterprise C13 Basic 39Y8941 40K9613 6015 12 / C13 Front 1U
DPI Enterprise Basic 39Y8948 40K9613 6065 6 / C19 Front 1U
9 / C19 Front
DPI Ultra Density Enterprise Basic 71762NX 40K9613 6503 1U
3 / C13 Back
Enterprise + - C13 Monitored 39M2816 40K9613 6035 12 / C13 Front 1U
1U 12 C13 Switched & Monitored 46M4004 40K9613 5911 12 / C13 Front 1U
9 / C19 Front
1U 9 C19 / 3 C13 Switched & Monitored 46M4002 40K9613 5904 1U
3 / C13 Back
Only a receptacle or a connector is needed to mate with the plug on the PDU input line cord. See section
“IEC 309 Pin & Sleeve Plug Decode” on page 188 in this document for further details on IEC309.
Matching receptacle listing 516R6W IP-67 HUBBELL, Hubbell receptacle P/N HBL516R6W
Matching connector listing 516C6W IP-67 HUBBELL, Hubbell connector P/N HBL516C6W
EQUIP.
GR.
Used with:
IBM System x PDU Information International
Earth
GR.
Used with:
IBM System x PDU Information International
Currently IBM System x does not have an available PDU to support this outlet. A suitable IBM Power
Systems PDU from the list below or a third party PDU will need to be used to connect this outlet.
Only a receptacle or a connector is needed to mate with the plug on the PDU input line cord. See section
“IEC 309 Pin & Sleeve Plug Decode” on page 188 in this document for further details on IEC309.
Matching receptacle listing 532R6W IP-67 HUBBELL, Hubbell receptacle P/N HBL532R6W
Matching connector listing 532C6W IP-67 HUBBELL, Hubbell connector P/N HBL532C6W
EQUIP.
GR.
Used with:
IBM System x PDU Information International
Rack & Rear Door Heat eXchanger (RDHx) – IBM System x PureFlex Part Numbers
9363-4CX IBM PureFlex System 42U Rack
9363-4DX IBM PureFlex System 42U Expansion Rack
44X3132 IBM PureFlex System Rack Door Kit
1756-42X IBM Rear Door Heat eXchanger
IBM Power Systems Flex System Power & Cooling Part Numbers
v7000 Rack & Rear Door Heat eXchanger (RDHx)
G8264R PDUs North America
G8052R PDUs International
Flex System Enterprise Chassis
FC: 6671 2.7m (9ft) 100-240V 10A C13 to C14 World Wide
FC: 6672 1.5m (5) 100-240V 10A C13 to C14 World Wide
FC: 6680 2.7m (9ft) 250V 10A C13 to AS3112-1964 and NZS 198 wall plug #6
* - For this feature, IBM Manufacturing chooses the optimum cord length when assembling systems into a
rack - 1.5m (5 ft), 2.7m (9 ft), or 4.2m (13.8 ft)
* - For this feature, IBM Manufacturing chooses the optimum cord length when assembling systems into a
rack - 1.5m (5 ft), 2.7m (9 ft), or 4.2m (13.8 ft)
Flex System Enterprise Chassis – IBM Power Systems PureFlex Part Numbers
7893-92X Flex System Enterprise Chassis
FC: 3590 Additional 1x 2500W PSU (1x to 4x)
FC: 9059 Base 2500W PSUs (includes 2x PSUs)
FC: 7805 Additional 2x 80mmFans
FC: 9038 Base 4x 80mm Fans
FC: 1452 4.3m (14ft) 200-240V 15A C19 to NEMA 6-15P US
FC: 3733 2.5m (8.2ft) 200-240V 15A C19 to NEMA 6-15P US
FC: 4558 2.5m (8.2ft) 200-240V 16A C19 to C20 World Wide
FC: 4560 4.3m (14ft) 200-240V 20A C19 to NEMA L6-20P US
Rack & Rear Door Heat eXchanger (RDHx) – IBM Power Systems PureFlex Part Numbers
7953-94X IBM PureFlex System 42U
FC: EC01 Rack Front Door (Black)
FC: EC02 Rack Rear Door
FC: EC03 Rack Side Cover
FC: EC04 Rack Suite Attachment Kit
FC: EC05 Rear Door Heat eXchanger Indicator
FC: EC06 Rack Front Door (Blue)
1164-95X IBM Rear Door Heat eXchanger
Reference Material
IBM ToR Switches & IBM Storwize V7000 Power Numbers
Device Max # of PSUs Max Current Max Wattage Max BTU
G8264R Ethernet Switch 2* 1.74A 348W 1189 BTU/Hr
G8052R Ethernet Switch 2* 0.9A 180W 615 BTU/Hr
SAN24B-4 SAN Switch 1 0.41A 82W 280 BTU/Hr
Storwize V7000 Controller (2076-124) 2** 2.79A 558W 1906 BTU/Hr
Storwize V7000 Expansion (2076-224) 2** 1.08A 216W 738 BTU/Hr
* – Comes with 2x PSUs by default ** – Storwize FC: 9801 includes 2x PSUs
N+1 PSU redundancy is where N is the minimum number of PSUs need to keep the system operational, plus one
PSU for redundancy. N+1 is used when a system needs only to tolerate a single PSU failure and stay operational
(See example “N+N and N+1 Examples” diagram below). Think of N+1 as having one PSU as a hot spare.
PSU
P
Device – 4x PSU
PSU PSU
P
Device – 4x PSU
PSU
P P
PSU PSU PSU PSU
P
PSU PSU PSU PSU
P
Device – 2x PSU
PSU PSU
PDU PDU
Power Source A Power Source B
Pin Configuration Amperage Device Type Polarization Environmental Rating Yellow 100V - 130V
Orange 125V/250V
3 - 2 Pole + G 20 30 32 P - Plug Clock W-WATERTIGHT
Blue 200V - 250V
4 - 3 Pole + G 60 63 100 C - Connector Position (SCREW CAP &
5 – 3 Pole + N + G R - Receptacle Of Female LOCKING RING) Gray 277V
B - Inlet Sleeve
Red 380V - 480V
IP 0 – No Protection 0 – No Protection
1 ≥ 50mm Diameter 1 – Vertically Dripping
2 ≥ 12.5mm Diameter 2 – Dripping At 15° Of Tilt
First Number: degree of protection 3 ≥ 2.5mm Diameter 3 – Spraying Up To 60° Of Tilt
for persons against access of
hazardous parts inside the enclosure 4 ≥ 1.0mm Diameter 4 – Splashing
and/or against foreign objects. 5 – Jetting
5 – Dust-Protected
Second Number: degree of 6 – Dust-Tight 6 – Power Jetting
protection of equipment inside
enclosures against damage from
7 – Temporary Immersion
ingress of water. 8 – Continuous Immersion
Ingress Protection (IP ) is defined in IEC 60529 Standard.
P =E Y xI Y x pf (W) A
E 220V
PTOTAL = 3 x P
EL 380V I
= 3 x EL/√3 x I x pf
= √3 x EL x IL x pf N
EL 380V
= √3 x 380V x 32A x 1
= 21061W B IB
P =E Y xI Y x pf (W) A
E 220V
PTOTAL = 3 x P
EL 380V I
= 3 x EL/√3 x I x pf
= √3 x EL x IL x pf N
EL 380V
= √3 x 380V x 16A x 1
= 10530W B IB
Helpful Links
The latest copy of this document
http://www.ibm.com/support/techdocs/atsmastr.nsf/WebIndex/WP102111
IBM, the IBM Logo, IBM Flex System, BladeCenter, DPI, IntelliStation, iDataPlex, and System x are registered trademarks or
trademarks of International Business Machines Corporation in the United States, other countries or both. For a list of
additional IBM trademarks, please see http://ibm.com/legal/copytrade.shtml.
Other company, product or service names may be trademarks or service marks of others.