HEMK
UTILITY SCALE CENTRAL STRING INVERTER
OUTDOOR DURABILITY
NEMA 3R / IP54
ICOOL 3
ACTIVE HEATING
COMBINING
3 LEVEL TOPOLOGY
THE BENEFITS
OF CENTRAL AND
STRING INVERTERS
ROBUST DESIGN
NEMA 3R / IP54.
POWER ELECTRONICS
By providing full front access the HEMK series simplifies With the HEMK, Power Electronics offers its most compact
the maintenance tasks, reducing the MTTR (and achieving solution, achieving 3.8 MW in just 12ft long, reducing installa-
a lower OPEX). The total access allows a fast swap of the tion costs and labor time, and therefore will minimize the LCOE.
FRUs without the need of qualified technical personnel.
Based on more than 3 years of experience with our MV tion, without having to maintain cumbersome dust filters or
Variable Speed Drive, the iCOOL3 system allows to get IP54 having to use liquid-cooling systems, avoiding the commonly
degree of protection in an outdoor solar inverter. iCOOL3 known inconveniences of it (complex maintenance, risk of
delivers a constant stream of clean air to the FRUs, being the leaks, higher number of components…), therefore resulting in
most effective way of reaching up to IP54 degree of protec- an OPEX cost reduction and a LCOE improvement.
MULTILEVEL TOPOLOGY
VOLTAGE (V)
the 1,500 Vdc design. Power Electronics has many years of
power design in both inverters and MV drives and the HEMK
design is the result of our experience with 3 level topologies.
The 3 level IGBT topology reduces stage losses, increases
inverter efficiency and minimizes total harmonic distortion.
High efciency to deliver the lowest LCOE. TIME (s) TIME (s)
VAR AT NIGHT
At night, in case of solar applications, the HEMK inverter can shift to reactive power compensation mode. The inverter can
respond to an external dynamic signal, a Power Plant Controller command or pre-set reactive power level (kVAr).
ACTIVE HEATING
At night, when the unit is not actively exporting power, the This autonomous heating system is the most efficient and
inverter can import a small amount of power to keep the homogeneous way to prevent condensation, increasing the
inverter internal ambient temperature above -20°C, without inverters availability and reducing maintenance. PATENTED
using external resistors.
EASY TO MONITOR
The Freesun app is the easiest way to monitor the status of and information without the need to open cabinet doors.
our inverters. All our inverters come with built-in wifi, allowing The app user-friendly interface allows quick and easy access
remote connectivity to any smart device for detailed updates to critical information (energy registers, production and events).
HEMK firmware includes the latest utility interactive features (LVRT, OVRT, FRS, FRT, Anti-islanding, active and reactive power
curtailment…), and can be configured to meet specific utility requirements.
1.4
100%
p.u. VOLTAGE
1.2
1.2
1
1
0.8
0.8
0.6 50%
0.6 50%
0.4
0.4
0.2
0.2
0
0 -1 0 1 2 3 4
-1 0 1 2 3 4 SECONDS 0%
50Hz 52Hz
PO12.3 BDEW PREPA SECONDS
CEI-016 HECO 0%
50Hz FREQUENCY (Hz) 52Hz
PO12.3 BDEW PREPA CEI-016 HECO FREQUENCY (Hz)
Low Voltage Ride Through (LVRT or ZVRT). Inverters can withstand any Frequency Regulation System (FRS). Frequency droop algorithm curtails the
voltage dip or profile required by the local utility. In this situation, the inverter active power along a preset characteristic curve supporting grid stabilization.
SLOW
U 0.6 0.6 1.08 1.08
Voltage
Voltage
U
0.5 0.5 1.075 1.075
0.2 0.2
P>0.2Pn P>0.2Pn 1.06 1.06
(lock in) (lock in) TIME (s)
0.1 0.1 1.055 1.055
Qmax(ind) SLOW
Qmax(cap) -Q(max) 0 0 P>0.5Pn 1.05 P>0.5Pn 1.05
-Q(max) (lock out) (lock out)
-0.1 -0.1 1.045 1.045
1 125 250 1 375125 250
500 625375 750500 625
875 750
1000 875 1000
Time (s) Time (s)
Q P QV P V
Q(V) curve. It is a dynamic voltage control function which provides reactive power in order to maintain the voltageFAST
as close as possible to its nominal value.
FAST
ISLANDING CONDITION
FREQUENCY (Hz)
SLOW
Transformer Grid
POI Utility
PV array Freesun breaker
TIME (s) inverter
SLOW
R L C Loads
FAST
Frequency Ride Through (FRT). Freesun solar inverters have flexible frequency Anti-islanding. This protection combines passive and active detection
POI Utility
PV array Freesun breaker
inverter
POWER ELECTRONICS
FRAME 1 FRAME 2
REFERENCE FS2445K FS3670K
OUTPUT AC Output Power(kVA/kW) @50°C [1] 2445 3670
AC Output Power(kVA/kW) @40°C [1] 2530 3800
Max. AC Output Current (A) @40°C 2117 3175
Operating Grid Voltage(VAC) [2] 690V ±10%
Operating Grid Frequency(Hz) 50Hz/60Hz
Current Harmonic Distortion (THDi) < 3% per IEEE519
Power Factor (cosine phi) [3] 0.5 leading … 0.5 lagging adjustable / Reactive Power injection at night
INPUT MPPt @full power (VDC) 976V-1310V
Maximum DC voltage 1500V
Number of PV inputs [2] Up to 36
Number of Freemaq DC/DC inputs [4] Up to 6
Max. DC continuous current (A) [4] 2645 3970
Max. DC short circuit current (A) [4] 4000 6000
EFFICIENCY & AUXILIARY SUPPLY Efficiency (Max) (η) 98.87% 98.93%
Euroeta (η) 98.48% 98.65%
Max. Power Consumption (KVA) 8 10
CABINET Dimensions [WxDxH] (ft) 12 x 7 x 7
Dimensions [WxDxH] (m) 3.7 x 2.2 x 2.2
Weight (lb) 12125 12677
Weight (kg) 5500 5750
Type of ventilation Forced air cooling
ENVIRONMENT Degree of protection NEMA 3R - IP54
Permissible Ambient Temperature -35°C to +60°C / >50°C Active Power derating
Relative Humidity 4% to 100% non condensing
Max. Altitude (above sea level) 2000m; >2000m power derating (Max. 4000m)
Noise level [5] < 79 dBA
CONTROL INTERFACE Communication protocol Modbus TCP
Plant Controller Communication Optional
Keyed ON/OFF switch Standard
PROTECTIONS Ground Fault Protection GFDI and Isolation monitoring device
General AC Protection Circuit Breaker
General DC Protection Fuses
Overvoltage Protection AC, DC Inverter and auxiliary supply type 2
CERTIFICATIONS Safety UL1741, CSA 22.2 No.107.1-16, UL62109-1, IEC62109-1, IEC62109-2
Compliance NEC 2017 / IEC
Utility interconnect EEE 1547.1-2005 / UL1741SA-Feb. 2018 / IEC62116:2014
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
Consult Power Electronics for derating curves. [4] Consult Power Electronics for Freemaq DC/DC connection configurations.
[2] Consult Power Electronics for other configurations. [5] Readings taken 1 meter from the back of the unit.
HEMK 53
FRAME 1 FRAME 2
REFERENCE FS2340K FS3510K
OUTPUT AC Output Power(kVA/kW) @50°C [1] 2340 3510
AC Output Power(kVA/kW) @40°C [1] 2420 3630
Max. AC Output Current (A) @40°C 2117 3175
Operating Grid Voltage(VAC) [2] 660V ±10%
Operating Grid Frequency(Hz) 50Hz/60Hz
Current Harmonic Distortion (THDi) < 3% per IEEE519
Power Factor (cosine phi) [3] 0.5 leading … 0.5 lagging adjustable / Reactive Power injection at night
INPUT MPPt @full power (VDC) 934V-1310V
Maximum DC voltage 1500V
Number of PV inputs [2] Up to 36
Number of Freemaq DC/DC inputs [4] Up to 6
Max. DC continuous current (A) [4] 2645 3970
Max. DC short circuit current (A) [4] 4000 6000
EFFICIENCY & AUXILIARY SUPPLY Efficiency (Max) (η) 98.84% 98.90%
Euroeta (η) 98.48% 98.65%
Max. Power Consumption (KVA) 8 10
CABINET Dimensions [WxDxH] (ft) 12 x 7 x 7
Dimensions [WxDxH] (m) 3.7 x 2.2 x 2.2
Weight (lb) 12125 12677
Weight (kg) 5500 5750
Type of ventilation Forced air cooling
ENVIRONMENT Degree of protection NEMA 3R - IP54
Permissible Ambient Temperature -35°C to +60°C / >50°C Active Power derating
Relative Humidity 4% to 100% non condensing
Max. Altitude (above sea level) 2000m; >2000m power derating (Max. 4000m)
Noise level [5] < 79 dBA
CONTROL INTERFACE Communication protocol Modbus TCP
Plant Controller Communication Optional
Keyed ON/OFF switch Standard
PROTECTIONS Ground Fault Protection GFDI and Isolation monitoring device
General AC Protection Circuit Breaker
General DC Protection Fuses
Overvoltage Protection AC, DC Inverter and auxiliary supply type 2
CERTIFICATIONS Safety UL1741, CSA 22.2 No.107.1-16, UL62109-1, IEC62109-1, IEC62109-2
Compliance NEC 2017 / IEC
Utility interconnect EEE 1547.1-2005 / UL1741SA-Feb. 2018 / IEC62116:2014
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
Consult Power Electronics for derating curves. [4] Consult Power Electronics for Freemaq DC/DC connection configurations.
[2] Consult Power Electronics for other configurations. [5] Readings taken 1 meter from the back of the unit.
POWER ELECTRONICS
FRAME 1 FRAME 2
REFERENCE FS2285K FS3430K
OUTPUT AC Output Power(kVA/kW) @50°C [1] 2285 3430
AC Output Power(kVA/kW) @40°C [1] 2365 3550
Max. AC Output Current (A) @40°C 2117 3175
Operating Grid Voltage(VAC) [2] 645V ±10%
Operating Grid Frequency(Hz) 50Hz/60Hz
Current Harmonic Distortion (THDi) < 3% per IEEE519
Power Factor (cosine phi) [3] 0.5 leading … 0.5 lagging adjustable / Reactive Power injection at night
INPUT MPPt @full power (VDC) 913V-1310V
Maximum DC voltage 1500V
Number of PV inputs [2] Up to 36
Number of Freemaq DC/DC inputs [4] Up to 6
Max. DC continuous current (A) [4] 2645 3970
Max. DC short circuit current (A) [4] 4000 6000
EFFICIENCY & AUXILIARY SUPPLY Efficiency (Max) (η) 98.81% 98.87%
Euroeta (η) 98.43% 98.60%
Max. Power Consumption (KVA) 8 10
CABINET Dimensions [WxDxH] (ft) 12 x 7 x 7
Dimensions [WxDxH] (m) 3.7 x 2.2 x 2.2
Weight (lb) 12125 12677
Weight (kg) 5500 5750
Type of ventilation Forced air cooling
ENVIRONMENT Degree of protection NEMA 3R - IP54
Permissible Ambient Temperature -35°C to +60°C / >50°C Active Power derating
Relative Humidity 4% to 100% non condensing
Max. Altitude (above sea level) 2000m; >2000m power derating (Max. 4000m)
Noise level [5] < 79 dBA
CONTROL INTERFACE Communication protocol Modbus TCP
Plant Controller Communication Optional
Keyed ON/OFF switch Standard
PROTECTIONS Ground Fault Protection GFDI and Isolation monitoring device
General AC Protection Circuit Breaker
General DC Protection Fuses
Overvoltage Protection AC, DC Inverter and auxiliary supply type 2
CERTIFICATIONS Safety UL1741, CSA 22.2 No.107.1-16, UL62109-1, IEC62109-1, IEC62109-2
Compliance NEC 2017 / IEC
Utility interconnect EEE 1547.1-2005 / UL1741SA-Feb. 2018 / IEC62116:2014
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
Consult Power Electronics for derating curves. [4] Consult Power Electronics for Freemaq DC/DC connection configurations.
[2] Consult Power Electronics for other configurations. [5] Readings taken 1 meter from the back of the unit.
HEMK 55
FRAME 1 FRAME 2
REFERENCE FS2235K FS3350K
OUTPUT AC Output Power(kVA/kW) @50°C [1] 2235 3350
AC Output Power(kVA/kW) @40°C [1] 2310 3465
Max. AC Output Current (A) @40°C 2117 3175
Operating Grid Voltage(VAC) [2] 630V ±10%
Operating Grid Frequency(Hz) 50Hz/60Hz
Current Harmonic Distortion (THDi) < 3% per IEEE519
Power Factor (cosine phi) [3] 0.5 leading … 0.5 lagging adjustable / Reactive Power injection at night
INPUT MPPt @full power (VDC) 891V-1310V
Maximum DC voltage 1500V
Number of PV inputs [2] Up to 36
Number of Freemaq DC/DC inputs [4] Up to 6
Max. DC continuous current (A) [4] 2645 3970
Max. DC short circuit current (A) [4] 4000 6000
EFFICIENCY & AUXILIARY SUPPLY Efficiency (Max) (η) 98.79% 98.85%
Euroeta (η) 98.42% 98.59%
Max. Power Consumption (KVA) 8 10
CABINET Dimensions [WxDxH] (ft) 12 x 7 x 7
Dimensions [WxDxH] (m) 3.7 x 2.2 x 2.2
Weight (lb) 12125 12677
Weight (kg) 5500 5750
Type of ventilation Forced air cooling
ENVIRONMENT Degree of protection NEMA 3R - IP54
Permissible Ambient Temperature -35°C to +60°C / >50°C Active Power derating
Relative Humidity 4% to 100% non condensing
Max. Altitude (above sea level) 2000m; >2000m power derating (Max. 4000m)
Noise level [5] < 79 dBA
CONTROL INTERFACE Communication protocol Modbus TCP
Plant Controller Communication Optional
Keyed ON/OFF switch Standard
PROTECTIONS Ground Fault Protection GFDI and Isolation monitoring device
General AC Protection Circuit Breaker
General DC Protection Fuses
Overvoltage Protection AC, DC Inverter and auxiliary supply type 2
CERTIFICATIONS Safety UL1741, CSA 22.2 No.107.1-16, UL62109-1, IEC62109-1, IEC62109-2
Compliance NEC 2017 / IEC
Utility interconnect EEE 1547.1-2005 / UL1741SA-Feb. 2018 / IEC62116:2014
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
Consult Power Electronics for derating curves. [4] Consult Power Electronics for Freemaq DC/DC connection configurations.
[2] Consult Power Electronics for other configurations. [5] Readings taken 1 meter from the back of the unit.
POWER ELECTRONICS
FRAME 1 FRAME 2
REFERENCE FS2180K FS3270K
OUTPUT AC Output Power(kVA/kW) @50°C [1] 2180 3270
AC Output Power(kVA/kW) @40°C [1] 2255 3380
Max. AC Output Current (A) @40°C 2117 3175
Operating Grid Voltage(VAC) [2] 615V ±10%
Operating Grid Frequency(Hz) 50Hz/60Hz
Current Harmonic Distortion (THDi) < 3% per IEEE519
Power Factor (cosine phi) [3] 0.5 leading … 0.5 lagging adjustable / Reactive Power injection at night
INPUT MPPt @full power (VDC) 870V-1310V
Maximum DC voltage 1500V
Number of PV inputs [2] Up to 36
Number of Freemaq DC/DC inputs [4] Up to 6
Max. DC continuous current (A) [4] 2645 3970
Max. DC short circuit current (A) [4] 4000 6000
EFFICIENCY & AUXILIARY SUPPLY Efficiency (Max) (η) 98.79% 98.84
Euroeta (η) 98.41% 98.57%
Max. Power Consumption (KVA) 8 10
CABINET Dimensions [WxDxH] (ft) 12 x 7 x 7
Dimensions [WxDxH] (m) 3.7 x 2.2 x 2.2
Weight (lb) 12125 12677
Weight (kg) 5500 5750
Type of ventilation Forced air cooling
ENVIRONMENT Degree of protection NEMA 3R - IP54
Permissible Ambient Temperature -35°C to +60°C / >50°C Active Power derating
Relative Humidity 4% to 100% non condensing
Max. Altitude (above sea level) 2000m; >2000m power derating (Max. 4000m)
Noise level [5] < 79 dBA
CONTROL INTERFACE Communication protocol Modbus TCP
Plant Controller Communication Optional
Keyed ON/OFF switch Standard
PROTECTIONS Ground Fault Protection GFDI and Isolation monitoring device
General AC Protection Circuit Breaker
General DC Protection Fuses
Overvoltage Protection AC, DC Inverter and auxiliary supply type 2
CERTIFICATIONS Safety UL1741, CSA 22.2 No.107.1-16, UL62109-1, IEC62109-1, IEC62109-2
Compliance NEC 2017 / IEC
Utility interconnect EEE 1547.1-2005 / UL1741SA-Feb. 2018 / IEC62116:2014
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
Consult Power Electronics for derating curves. [4] Consult Power Electronics for Freemaq DC/DC connection configurations.
[2] Consult Power Electronics for other configurations. [5] Readings taken 1 meter from the back of the unit.
HEMK 57
FRAME 1 FRAME 2
REFERENCE FS2125K FS3190K
OUTPUT AC Output Power(kVA/kW) @50°C [1] 2125 3190
AC Output Power(kVA/kW) @40°C [1] 2200 3300
Max. AC Output Current (A) @40°C 2117 3175
Operating Grid Voltage(VAC) [2] 600V ±10%
Operating Grid Frequency(Hz) 50Hz/60Hz
Current Harmonic Distortion (THDi) < 3% per IEEE519
Power Factor (cosine phi) [3] 0.5 leading … 0.5 lagging adjustable / Reactive Power injection at night
INPUT MPPt @full power (VDC) 849V-1310V
Maximum DC voltage 1500V
Number of PV inputs [2] Up to 36
Number of Freemaq DC/DC inputs [4] Up to 6
Max. DC continuous current (A) [4] 2645 3970
Max. DC short circuit current (A) [4] 4000 6000
EFFICIENCY & AUXILIARY SUPPLY Efficiency (Max) (η) 98.78% 98.84%
Euroeta (η) 98.39% 98.56%
Max. Power Consumption (KVA) 8 10
CABINET Dimensions [WxDxH] (ft) 12 x 7 x 7
Dimensions [WxDxH] (m) 3.7 x 2.2 x 2.2
Weight (lb) 12125 12677
Weight (kg) 5500 5750
Type of ventilation Forced air cooling
ENVIRONMENT Degree of protection NEMA 3R - IP54
Permissible Ambient Temperature -35°C to +60°C / >50°C Active Power derating
Relative Humidity 4% to 100% non condensing
Max. Altitude (above sea level) 2000m; >2000m power derating (Max. 4000m)
Noise level [5] < 79 dBA
CONTROL INTERFACE Communication protocol Modbus TCP
Plant Controller Communication Optional
Keyed ON/OFF switch Standard
PROTECTIONS Ground Fault Protection GFDI and Isolation monitoring device
General AC Protection Circuit Breaker
General DC Protection Fuses
Overvoltage Protection AC, DC Inverter and auxiliary supply type 2
CERTIFICATIONS Safety UL1741, CSA 22.2 No.107.1-16, UL62109-1, IEC62109-1, IEC62109-2
Compliance NEC 2017 / IEC
Utility interconnect EEE 1547.1-2005 / UL1741SA-Feb. 2018 / IEC62116:2014
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
Consult Power Electronics for derating curves. [4] Consult Power Electronics for Freemaq DC/DC connection configurations.
[2] Consult Power Electronics for other configurations. [5] Readings taken 1 meter from the back of the unit.