The HEMK is the second 1500V inverter generation, based on the more than proven HEC
V1500. This modular solar inverter offers the advantages of both central and string inverters.
Reaching a very high power density, and an output power of 3.8MW, it is available in 6
different AC voltages, providing the flexibility to choose the best solution for each PV plant.
The power stage architecture, composed of six field replaceable units (FRU), is designed to
provide the highest availability and optimize yield production.
The innovative iCOOL3 cooling system allows the HEMK to be installed in the harshest
environments, thanks to a degree of protection of up to IP65. This advanced air-cooling
system, reduces the OPEX cost compared to other cooling solutions, that need the use of
complex liquid-cooling systems.
28-29
COMPACT DESIGN
THE MOST COMPACT SOLAR INVERTER
With the HEMK, Power Electronics offers its most compact solution, achieving 3.8MW in just 12ft long,
reducing installation costs and labor time.
HEMK is also available with a single MPPt, where all the power
stages are physically joined in the DC side and therefore, in the
event of a fault, the faulty module is taken off-line and its output
power is distributed evenly among the remaining functioning
FRUs.
iCOOL3 delivers a constant stream of clean air to the FRUs and the MV transformer, being the most
HEMK
effective way of reaching up to IP65 degree of protection, without having to maintain cumbersome
dust filters or having to use liquid-cooling systems, avoiding the commonly known inconveniences
of it (complex maintenance, risk of leaks, higher number of components…), therefore resulting in an
OPEX cost reduction.
AIR OUTLETS
AIR OUTLETS
AIR INLET
DUST
PARTICLES
ROBUST DESIGN
HEMK inverter modules have a design life of greater than 30 years of operation in harsh environments
and extreme weather conditions. HEMK units are tested and ready to withstand conditions from the
frozen Siberian tundra to the Californian Death Valley, featuring:
• Totally sealed electronics cabinet protects electronics against dust and moisture.
• Temperature and humidity controlled active heating prevents internal water condensation.
• 50mm mineral panel isolates the cabinet from solar heat gains.
• Roof cover designed to dissipate solar radiation, reduce heat build-up and avoid water leakages.
The solid HEMK structure avoids the need of additional external structures.
• Random units selected to pass a Factory Water Tightness Test ensuring product quality.
• IP65 available.
30-31
MULTILEVEL TOPOLOGY
The multilevel IGBT topology is the most efficient approach to manage high DC link voltages
and makes the difference in the 1,500 Vdc design. Power Electronics has many years of power
design in both inverters and MV drives and the HEMK design is the result of our experience with 3
level topologies. The 3 level IGBT topology reduces stage losses, increases inverter efficiency and
minimizes total harmonic distortion.
THREE-LEVEL INVERTER
VOLTAGE (V)
TWO-LEVEL INVERTER
TIME (s)
*Power Electronics solution VOLTAGE (V)
TIME (s)
*Other inverter
EASY TO SERVICE
By providing full front access the HEMK series simplifies the maintenance tasks, reducing the MTTR
(and achieving a lower OPEX). The total access allows a fast swap of the FRUs without the need of
qualified technical personnel.
HEMK
ACTIVE HEATING
At night, when the unit is not actively exporting power, the inverter can import a small amount
of power to keep the inverter internal ambient temperature above -20°C, without using external
resistors. This autonomous heating system is the most efficient and homogeneous way to prevent
condensation, increasing the inverters availability and reducing the maintenance. (patented)
VAR AT NIGHT
At night, the HEMK inverter can shift to reactive power compensation mode. The inverter can
respond to an external dynamic signal, a Power Plant Controller command or pre-set reactive power
level (kVAr).
32-33
DYNAMIC GRID SUPPORT
HEMK firmware includes the latest utility interactive features (LVRT, OVRT, FRS, FRT, Anti-islanding,
active and reactive power curtailment…), and can be configured to meet specific utility requirements.
100%
1.2
0.8
0.6 50%
0.4
0.2 Pmin
0
-1 0 1 2 3 4
SECONDS 0%
50Hz 52Hz
PO12.3 BDEW PREPA CEI-016 HECO FREQUENCY (Hz)
LVRT or ZVRT (Low Voltage Ride Through). FRS (Frequency Regulation System).
Inverters can withstand any voltage dip or Frequency droop algorithm curtails the active
profile required by the local utility. The inverter power along a preset characteristic curve
can immediately feed the fault with full reactive supporting grid stabilization.
power, as long as the protection limits are not
exceeded.
EXAMPLE: Q(U)
Q(U) 1.2 1.11
VOLTAGE
Qmax(ind) 1.1 STEP 2 1.105
Q(max)
1 1.1
VOLTAGE
Active and Reactive Power
0.9 1.095
STEP 1
0.8 1.09
0.7 1.085
Voltage
0.6 1.08
U
0.5 1.075
0.4 1.07
0.3 1.065
Q(V) curve: It is a dynamic voltage control function which provides reactive power in order to
maintain the voltage as close as possible to its nominal value.
SLOW
Transformer Grid
POI Utility
PV array HEC breaker
inverter
TIME (s)
SLOW
R L C Loads
FAST
690V
FRAME 1 FRAME 2
NOTES [1] Values at 1.00•Vac nom and cos Ɏ= 1. Consult Power Electronics for derating curves.
[2] Depending on the project configuration.
[3] Consult P-Q charts available: Q(kVAr)=(S(kVA)2-P(kW)2).
[4] Heating resistors kit option below -20°C.
[5] Readings taken 1 meter from the back of the unit.
34-35
HEMK
TECHNICAL CHARACTERISTICS
660VAC
660V
FRAME 1 FRAME 2
NOTES [1] Values at 1.00•Vac nom and cos Ɏ= 1. Consult Power Electronics for derating curves.
[2] Depending on the project configuration.
[3] Consult P-Q charts available: Q(kVAr)=(S(kVA)2-P(kW)2).
[4] Heating resistors kit option below -20°C.
[5] Readings taken 1 meter from the back of the unit.
645V
FRAME 1 FRAME 2
NOTES [1] Values at 1.00•Vac nom and cos Ɏ= 1. Consult Power Electronics for derating curves.
[2] Depending on the project configuration.
[3] Consult P-Q charts available: Q(kVAr)=(S(kVA)2-P(kW)2).
[4] Heating resistors kit option below -20°C.
[5] Readings taken 1 meter from the back of the unit.
36-37