Six-channel digital

controller TR604 OUT

1 ALR
SP
OUT

“RING Engineering” 2

3
ALR
SP
OUT
ALR

4000 Plovdiv, tel. (+359 32) 622146 SP


OUT

4 ALR

e-mail: office@ring-bg.com SP
OUT

5 ALR

www:ring-bg.com SP
OUT

6 ALR
SP

TR604 is a 6-channel microprocessor based Each channel on TR604 may work with PID
controller dedicated to monitor and control or ON/OFF algorithm with separate
temperatures, pressures or levels. configuration for setpoint, input type and
Main features alarms.
 6 channels control  Alarm output
TR604 allow control of 6 fully independent The build-in alarm output (one for all
channels. channels) is turned on when an alarm
 Separate display and push-buttons on situation occurs in some channel. This
each channel allows TR604 to work as part of
This allows simultaneous monitoring of sophisticated systems.
input value on all 6 channels of TR604.  Communication
 Easy to set-up and configure An optional RS232 or RS485
The set-up of parameters is made by a communications interface with RI485
hierarchical system of menus. All protocol is available. It provides a link
parameters are stored in non-volatile between TR604 and PLCs or PC for
EEPROM memory. monitoring or configurations.
 Universal power supply These features made TR604 sum up six
The switch-mode power supply works over a single-channel controllers in one enclosure,
wide range of input voltage and is protected but in lower cost.
from short-duration input peaks. The TR604 is suitable for applications
 Universal analog inputs requiring control from 3 to 6 zones such as
TR604 maintain 6 types of TC, one type of the plastics and food industries, furnaces and
RTD and voltage input. The type of input is others.
set from the front panel and may be different
for each channel. Models with opto-isolated Dimensions.
analog inputs are offered.
 PID or ON/OFF algorithm
96
90

154 96
8 169 110
91

91
TECHNICAL SPECIFICATIONS
Main characteristics:
Power supply 100 – 250 VAC / 5 VA
Dimensions (ш, в, д) 96х96х177 мм
Mounting hole 91х91 мм ±1мм
Protections:
- Front panel IP54
- Other parts IP40
Operating conditions 0 – 60 °С / 0 – 70 % RH no humidity
Storage conditions -20 – 80 °С / 0 – 95 % RH
Inputs:
Thermocouple type “E” 0 –800 °С
Thermocouple type “J” 0 – 1000 °С
Thermocouple type “K” 0 – 1000 °С
Thermocouple type “R” 0 – 1000 °С
Thermocouple type “S” 0 – 1000 °С
Thermocouple type “T” 0 – 400 °С
RTD Pt100 -100 – 650 °С
Linear voltage -50 +50 mV
Linear voltage or current 0 +50 mV or 0 – 20 mA
Linear current (with external resistor 2,5 Ω) 0(4) – 20 mA
Outputs:
NPN open collector 40mA / 30VDC
Electromechanical relay NO 5А / 220VAC / 30VDC
Triac with zero-crossing 0,5A / 220VAC
Alarm output Relay NO
Control:
Algorithm PID or ON/OFF
Communications:
Interface RS232 or RS485
Protocol RI485
Speed 9600 or 38400 B/s

Ordering info:
TR604-
1 2 3 4

1. Output . 3. Communication.
 D – NPN ;  K – RS232;
 R – relay ;  M – RS485;
 А – triac.  N – none.
2. Opto-isolation on analog inputs. 4. Controller type.
 I – yes;  R – ON/OFF;
 N – none.  P - PID;
 T – ON/OFF + timer.