This manual is intended for use with the ANSUL® FM-200* Clean
Agent Total Flood Fire Suppression System. These systems are
specifically engineered for total flooding application in either
unoccupied or occupied areas. Planning, installation, recharge,
and maintenance of the system must conform to the limitations
detailed in this manual. Installation and maintenance shall be
performed by an individual holding current ANSUL Certification
from an ANSUL FM-200 System Training Program with train-
ing to plan, install, recharge, and maintain the FM-200 Agent
System(s).
Those who plan, install, operate, reset, program, inspect, or
maintain these systems should read this entire manual. Specific
sections will be of particular interest depending upon one’s
responsibilities.
As with all electrical, mechanical, pneumatic equipment, the
system needs periodic care to provide maximum assurance
that it will operate effectively and safely. Inspection frequency
shall be performed consistently, depending on operating and/
or environmental conditions. Maintenance shall be performed
semi-annually, or more frequently, depending on operating and/
or environmental conditions.
The application and use of the FM-200 System is limited to
the applications and uses described in this manual. For other
applications, contact your Authorized ANSUL Distributor,
Territory Manager, or Tyco Fire Protection Products – Technical
Services Department, Marinette, Wisconsin 54143-2542, USA.
Note: Metric and English conversions are rounded as appropriate to stay within
maximum and minimum approved values.
ANSUL, AUTOPULSE, and the product names listed in this material are marks
and/or registered marks. Unauthorized use is strictly prohibited.
! DANGER
Indicates a hazardous situation in which a person will experi-
ence serious personal injury or death if the situation is not
avoided.
! WARNING
Indicates a hazardous situation in which a person could expe-
rience serious personal injury or death if the situation is not
avoided.
! CAUTION
Indicates a hazardous situation in which a person could experi-
ence minor or moderate personal injury if the situation is not
avoided.
CAUTION
Addresses practices not related to personal injury, such as a
system part malfunctioning, property damage, or system failure.
NOTICE
Addresses general practices or observations
related to system function that are not related
to personal injury.
FM-200 Total Flood Fire TABLE OF CONTENTS
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE TOC-1
SECTION PAGE
FM-200 FIRE EXTINGUISHANT CLEAN AGENT The noise created by the FM-200 fire extinguishant discharging
Approvals include, but are not limited to: can be loud enough to startle people in the vicinity, but is
unlikely to cause any permanent injury. Turbulence caused by
ppro ed the high velocity discharge can dislodge substantial objects
nderwriters aboratories nc ecogni ed directly in its path, and cause enough general turbulence within
Component the protected area to move paper and light objects.
eport nrestricted isted lternati e Direct contact with the vaporizing liquid discharged from
an FM-200 fire extinguishant nozzle has a chilling effect
MANUFACTURED SYSTEMS on objects and in extreme cases can cause frostbite to the
skin. The liquid phase vaporizes rapidly when mixed with air
Approvals include, but are not limited to:
and therefore limits the risk in the immediate vicinity of the
nderwriters aboratories nc isted nozzle. Minor reduction in visibility may occur for a brief period
actory utual because of the condensation of water vapor.
FM-200 fire extinguishant is manufactured in strict accordance HMIS: 0-0-3/heptafloropropane/contents under pressure.
with the internationally recognized Quality assurance Standard, 0-0-0/nitrogen expellant gas/very cold, contents under
BS EN IS0 9000 and approved to ISO 9001. pressure.
FM-200 systems must be designed, installed, inspected, Consult: The Chemours Company, 1007 Market Street, PO
maintained, tested and recharged by qualified, trained Box 2047, Wilmington, DE 19899;
personnel in accordance with NFPA 2001, “Clean Agent Fire
Product Information: 1-844-773-CHEM (outside the U.S.
Extinguishing Systems,” and to be used in accordance with
1-302-773-1000)
Environmental Protection Agency (EPA) Significant New
Alternatives Program (SNAP). Where determined to be appro- Medical Emergency: 1-866-595-1473 (outside the U.S.
priate by the Authority Having Jurisdiction, other applicable 1-302-773-2000)
standards may additionally be utilized to specific system Transport Emergency: CHEMTREC: 1-800-424-9300 (outside
requirements for these purposes. the U.S. 1-703-527-3887)
AGENT CONTAINER AND VALVE ASSEMBLY Container and Valve Assembly Technical Information
(Part No. See Table, page 2-3) Nominal working pressure: 25.0 bar at 21 °C (360 psi 70 °F)
The container assembly consists of a container fitted with a Max. system pressure: 34.0 bar (482.6 psi)
valve and internal siphon tube, factory filled with FM-200 fire
extinguishant agent, and super-pressurized with dry nitrogen Max. fill density 1 kg/L (62.4 lb/ft3)
to 25 bar at 21 °C (360 psi at 70 °F). Containers sharing Min. fill density 0.5 kg/L (31.2 lb/ft3)
the same manifold shall be equal in size and fill density.
Temperature rating 0 °C to 54 °C (32 °F to 130 °F)
Containers are finished in red and are available in various
sizes. A nameplate is mounted to the container displaying the DOT Technical Information
agent weight, tare weight, gross weight, fill density, charge
date and fill location. A low discharge pressure switch and The containers are manufactured in accordance with DOT
liquid level indicator are options that may be specified when 4BW500 or 4BW450. (343 L container in accordance with DOT
ordering. 4BW450 only).
DOT 4BW500 DOT 4BW450
Hydraulic test 69.0 bar 62.1 bar
pressure: (1000 psi) (900 psi)
Maximum service 34.5 bar at 21 °C 31.0 bar at 21 °C
pressure: (500 psi at 70 °F) (450 psi at 70 °F)
Material: Carbon Steel Carbon Steel
FIGURE 2-1
AGENT CONTAINER AND VALVE ASSEMBLY
009668
FM-200 Total Flood Fire SECTION 2 – SYSTEM COMPONENTS
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 2-3
FIGURE 2-2
CONTAINER LABEL (Part No. 442881)
009669
FIGURE 2-3
8 L CONTAINER LABEL (Part No. 442880)
009670
FM-200 Total Flood Fire SECTION 2 – SYSTEM COMPONENTS
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 2-5
VALVE ASSEMBLY
(Part No. See Table)
The valve assembly is factory-fitted to the container and is
supplied pre-assembled with a low pressure switch (to be
ordered separately), pressure gauge and burst disc.
The replacement valve assembly is available for field
replacement. The 25 mm (1 in.) and 50 mm (2 in.) valve
assemblies are supplied with a plug in the pressure gauge
port. (Pressure gauge (Part No. 570055) must be ordered
separately.) The 80 mm (3 in.) valve is supplied with the gauge
factory installed. The replacement valve is 100% leak tested
before it leaves the factory.
Part No. Description
570535 25 mm (1 in.) Valve assembly
570536 50 mm (2 in.) Valve assembly
FIGURE 2-4
570302 80 mm (3 in.) Valve assembly VALVE ASSEMBLY
009671
Technical Information
Valve Size: 25 mm (1 in.) Valve 50 mm (2 in.) Valve 80 mm (3 in.) Valve
Part No.: 570535 570536 570302
Body material: Brass Brass Brass
Outlet safety cap material: Brass Brass Brass
Max. system pressure: 34 bar (493 psi) 34 bar (493 psi) 34 bar (493 psi)
Outlet: 25 mm (1 in. BSPP) 50 mm (2 in. BSPP) 80 mm (3 in. Flared*)
Low pressure switch port: 1/8 in. NPT 1/8 in. NPT 1/8 in. NPT
Gauge port: 1/8 in. NPT 1/8 in. NPT 1/8 in. NPT
Actuation pressure port: 1/4 in. BSPP 1/4 in. BSPP 1/4 in. NPT
Overall size: 130 mm (L) x 62 mm (Dia) 173 mm (L) x 100 mm (Dia) 241 mm (L) x 129 mm (Dia)
(5.12 in. (L) x 2.44 in. (Dia)) (6.12 in. (L) x 3.94 in. (Dia)) (9.50 in. (L) x 5.06 in. (Dia))
Weight: 2.96 kg (6.526 lb) 9.18 kg (20.238 lb) 18.82 kg (41.49 lb)
Equivalent length: 6.096 m (20 ft) 10.668 m (35 ft) 25.91 m (85 ft)
*3 in. NPT and Grooved Outlet adaptors are available.
SECTION 2 – SYSTEM COMPONENTS FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 2-6 REV. 0 2015-OCT-09 (Part No. 442940)
BURST DISC
(Part No. See Table)
A burst disc is factory fitted to every valve assembly. It
is designed to rupture when the container becomes over
pressurized when subjected to temperatures above the
designed storage temperature of the container.
PRESSURE GAUGE
(Part No. 570055)
A Pressure Gauge is factory fitted to the valve, and is field
replaceable.
Technical Information
Type: Bourdon Tube Pressure Gauge
Entry: Back Axial
Nominal size: Dia 40 mm (1.6 in.)
Pressure range: 0 bar to 48 bar (0 psi to 700 psi) FIGURE 2-6
Connection: 1/8 in. NPT PRESSURE GAUGE
009702
FIGURE 2-7
LOW PRESSURE SWITCH
009673
MOUNTING BRACKETS
(Part No. See Table)
The bracket assembly consists of a nut and bolt with two
bracket half straps, (back channel must be supplied by others); BACK CHANNEL
approved type of Unistrut channel is series P1000T 41 mm (SUPPLIED BY OTHERS)
Technical Information
Material: Mild Steel
Finish: Red polyester powder or
black plastic powder
Mounting: Unirax/Unistrut ch10 channel (Back channel)
(Supplied by others)
Recommended
Length of
Container Container Back Channel Weight of
Size Diameter per Container Strap
Part No. L mm (in.) mm (in.) kg (lb)
570085 8 to 32 254 (10) 500 (19.69) 0.30 (0.66)
570092 52 to 180 406 (16) 600 (23.60) 0.46 (1.01)
570336 343 610 (24) 900 (35.40) 0.71 (1.56)
SECTION 2 – SYSTEM COMPONENTS FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 2-10 REV. 0 2015-OCT-09 (Part No. 442940)
Manual actuation force: 50 N (11.00 Ibf) Overall size: 89 mm (L) x 45 mm (W) x 19 mm (D)
(3.5 in. (L) x 1.75 in. (W) x 3/4 in. (D))
Nominal pin travel: 4.4 mm (0.17 in.)
Weight: 0.11 kg (0.25 lb)
Electrical connection: 3-Pin plug connector
Certification: UL / ULC / FM Approved
Overall size: 104 mm (L) x 44 mm (Dia)
x 89 mm (W)
(4.09 in. (L) x 1.73 in. (Dia)
x 3.5 in. (W))
Weight: 0.95 kg (2.09 lb)
SECTION 2 – SYSTEM COMPONENTS FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 2-12 REV. 0 2015-OCT-09 (Part No. 442940)
FIGURE 2-13
AUTOPULSE EQUIPMENT
009679
FM-200 Total Flood Fire SECTION 2 – SYSTEM COMPONENTS
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 2-13
Dimension A Dimension B
Part No. Description mm (in.) mm (in.)
570539 25 mm (1 in.) Hose 405.0 (15.9) 81.5 (3.2)
570538 50 mm (2 in.) Hose 520.0 (20.5) 126.0 (5.0)
Hose construction: Twin steel wire braided oil resistant Twin steel wire braided oil resistant
seamless synthetic rubber core seamless synthetic rubber core
Connection material: Zinc Passivated Mild Steel Zinc Passivated Mild Steel
Connections: 25 mm (1 in. NPT) straight fixed male 50 mm (2 in. NPT) straight fixed male
25 mm (1 in. BSPP) 90° female swivel union 50 mm (2 in. BSPP) 90° female swivel union
Max. bend angle: 15° at 0 °C (32 °F) 15° at 0 °C (32 °F)
Max. system pressure: 34 bar (493 psi) 34 bar (493 psi)
Test Pressure 132 bar (1915 psi) 120 bar (1740 psi)
Weight: 1.25 kg (2.76 lb) 3.90 kg (8.60 lb)
Equivalent length: 3.14 m (10.3 ft) 5.36 m (17.6 ft)
FM-200 Total Flood Fire SECTION 2 – SYSTEM COMPONENTS
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 2-15
FIGURE 2-16
80 mm (3 IN.) DISCHARGE HOSE/ FIGURE 2-17
CHECK VALVE ASSEMBLY 80 mm (3 IN.) DISCHARGE HOSE
009682 009683
FIGURE 2-18
25 mm (1 IN.) AND 50 mm (2 IN.) UNION ADAPTOR
009684
FIGURE 2-19
80 mm (3 IN.) VALVE SINGLE CONTAINER ADAPTOR
Technical Information 009685
Material: Steel
Technical Information
Plating: Zinc plated and passivated
Body: Cadmium-plated mild steel
25 mm (1 in.) Union Adaptor
3 in. Flared to 3 in. NPT
Joint type: 1 in. BSPP swivel cone (hydraulic) x
1 in. NPT fixed female Overall size: 115 mm (L) x 102 mm (W)
(4.51 in. (L) x 4.00 in. (W))
Overall size: 63.5 mm (L) x 44 mm (W)
(2.5 in. (L) x 1.73 in. (W)) Weight: 2.84 kg (6.27 lb)
Technical Information
Check valve: 25 mm (1 in.) 50 mm (2 in.)
Part No.: 570566 570568
Body material: Brass Brass
Stem material: Stainless Steel Stainless Steel
Spring material: Stainless Steel Stainless Steel
Bottom plate material: Brass Brass
Top plate material: Stainless Steel Stainless Steel
Seal material: Nitrile Nitrile
Inlet connection thread: 25 mm (1 in. NPT) Female 50 mm (2 in. NPT) Female
Outlet connection thread: 40 mm (1 1/2 in. NPT) Male 65 mm (2 1/2 in. NPT) Male
Overall size: 54 mm (L) x 52.4 mm (W) 73 mm (L) x 83 mm (W)
(2.13 in. (L) x 2.06 in. (W)) (2.87 in. (L) x 3.25 in.(W))
Equivalent length: 0.40 m (1.3 ft) 6.66 m (21.8 ft)
Max system pressure: 34 bar (493 psi) 34 bar (493 psi)
Test pressure: 79 bar (1145 psi) 79 bar (1145 psi)
Weight: 0.63 kg (1.39 lb) 1.60 kg (3.53 lb)
SECTION 2 – SYSTEM COMPONENTS FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 2-18 REV. 0 2015-OCT-09 (Part No. 442940)
ACTUATION ISOLATOR
(Part No. 56803)
The actuation isolator is only required for use with 343 L
containers installed in a main and reserve fire suppression
system.
FIGURE 2-23
FEMALE ACTUATION HOSE
009701
Technical Information
Outer sheath: Stainless Steel braided
Inner sheath: PTFE
Max. working pressure: 68.9 bar (1000 psi)
Min. bend radius: 60 mm at 0 °C (2.4 in. at 32 °F)
FIGURE 2-22
1/4 IN. ACTUATION HOSE Connections: Zinc Passivated Mild Steel
009700 2 x 7/16 - 20 female swivel
Technical Information
Outer sheath: Stainless Steel braided
Inner sheath: PTFE
Max. working pressure: 68.9 bar (1000 psi)
Min. bend radius: 60 mm at 0 °C (2.4 in. at 32 °F)
Connections: Zinc Passivated Mild Steel
2 x 1/4 in. NPT male swivel
x 7/16 - 20 female swivel
SECTION 2 – SYSTEM COMPONENTS FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 2-20 REV. 0 2015-OCT-09 (Part No. 442940)
FIGURE 2-25
MALE ADAPTOR
Technical Information
Housing: C.R. Steel (Painted red)
Body: Forged Brass
Switch point: 2.8 bar rising (40 psi)
Tolerance: ± 0.7 bar (± 10 psi)
IP rating: IP65
FIGURE 2-28
Electrical connection: 1/2 in. and 3/4 in. conduit knockouts DISCHARGE PRESSURE SWITCH
with #6-32 UNC terminal screws 009693
FIGURE 2-29
7 AND 8 PORT NOZZLES BRASS CONFIGURATION
009694/006139(180) / 009695/006139(360)
FM-200 Total Flood Fire SECTION 2 – SYSTEM COMPONENTS
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 2-23
BRASS
STAINLESS
ROSETTE
(Part No. See Table)
A rosette is a plastic trim ring used to reinforce the penetration
of a nozzle into the hazard area. It is drilled for the system
piping through ceilings or walls, and attaches directly to the
discharge nozzle. A rosette is used to enhance the look of a
discharge nozzle installation and is available in 7 sizes, one for
each nozzle size.
PRESSURE TRIP
(Part No. 5156)
The pressure trip is connected to the 1/4 in. actuation piping
from the AUTOMAN II-C release. By either pneumatic or
manual actuation, the pressure trip can release spring or
weight powered devices to close doors and windows, open
fuel dump valves, close fire dampers or close fuel line valves.
The pressure trip is constructed of brass with two 1/4 in. NPT
fittings for connection to actuation piping. The link on the
pressure switch is released either pneumatically, by nitrogen
pressure from the cartridge in the AUTOMAN II-C release, or
manually, by use of the pull ring. The link then releases the
device which performs the auxiliary functions.
Operating pressure must be a minimum of 5.2 bar (75 psi) with
a maximum load of 31.7 kg (70 lb).
NOTICE
The pressure trip must not be installed in the FIGURE 2-31
agent discharge piping. PRESSURE TRIP
009696
Technical Information
Body: Brass
Spring: Stainless Steel
Pull ring: Stainless Steel
Pressure ports: 1/4 in. NPT
Mounting holes: 7.1 mm (0.281 in.) Dia.
Min. operating pressure: 5.2 bar (75 psi)
Max. load at 31.7 kg (70 lb)
5.2 bar (75 psi):
Overall size: 95 mm (L) x 76 mm (W)
(3.75 in. (L) x 3 in. (W))
SECTION 2 – SYSTEM COMPONENTS FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 2-26 REV. 0 2015-OCT-09 (Part No. 442940)
Technical Information
Body: Brass
Spring: Stainless Steel
Pull ring: Stainless Steel
Inlet: 1/4 in. Male
Set point: 18.3 bar (265 psi)
a nstallation tor ue ft-lb
Overall size: 50.8 mm (L) x 17.5 mm (W)
(2 in. (L) x 0.69 in. (W))
FIGURE 2-32
SAFETY VENT VALVE
009697
FM-200 Total Flood Fire SECTION 2 – SYSTEM COMPONENTS
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 2-27
FIGURE 2-35
MANUAL RELEASE SIGN
009705
FIGURE 2-34
DOOR NOTICE (LESS THAN NOAEL)
009704
Technical Information
Material: 2 mm (0.08 in.) Craylon
Finish: Gloss, scratch resistant
Overall Size: 210 mm (L) x 210 mm (W)
(8.25 in. (L) x 8.25 in. (W))
SECTION 2 – SYSTEM COMPONENTS FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 2-28 REV. 0 2015-OCT-09 (Part No. 442940)
Technical Information
Mounting thread: 1.3125-12UN-2A
Stem material: Brass
Mounting material: Brass
Float material: ECCO
FM-200 Total Flood Fire SECTION 2 – SYSTEM COMPONENTS
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 2-29
18
19
16
12
15
11
7
13
6
8 2, 3
4
9
14
10
17
20
FIGURE 2-37
TYPICAL MANIFOLD SYSTEM
009699
NOTES:
FM-200 Total Flood Fire SECTION 3 – GENERAL INFORMATION
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 3-1
INTRODUCTION
The FM-200 fire extinguishant agent is a clean, safe, and The agent has an acceptable toxicity level for use in
effective fire fighting agent for use in total flooding automatic occupied spaces when used as specified in the United States
suppression systems. Environmental Protection Agency (EPA) proposed Significant
Design concentration for Class A UL hazards is 6.7%. New Alternative Policy (SNAP) program rules, as well as NFPA
2001.
Design Concentration for FM is 7.17%.
FM-200 fire extinguishant agent suppresses fires through its
FM-200 systems utilize one or more storage containers cooling effect, not by displacement of oxygen as is the extin-
arranged to provide the protected area with a pre-determined guishment mechanism of CO2. The agent therefore provides
quantity of agent. the ability to utilize an FM-200 system in occupied areas.
The agent storage containers are designed to hold the agent in Exposure to the agent at the design concentration of up to
liquid form. Nitrogen is used to super-pressurize the container 9.0% is not a health hazard. Exposure to higher concentra-
to 25 bar (360 psi) at 21 °C (70 °F). tions is permissible for limited periods. Refer to NFPA 2001
Handling and installation of FM-200 equipment should only or exposure limits. As with halons, the EPA and the National
be conducted by persons trained in dealing with this type of Fire Protection Association (NFPA) recommend avoiding any
equipment. unnecessary exposure to an extinguishing agent. Personnel
must evacuate protected areas as quickly as possible to avoid
FM-200 fire extinguishant agent contains no particulates or oily
the decomposition products of a fire.
residues and is produced under ISO 9001 guidelines to strict
manufacturing specifications ensuring product purity. The noise created by the discharging agent can be loud
enough to startle people in the vicinity, but it is unlikely to
The agent suppresses fires quickly through a combination of
cause any permanent injury. Turbulence caused by the high
chemical interaction and physical heat removal. The agent
velocity discharge can dislodge substantial objects directly in its
removes heat energy from fire and absorbs heat from the
path, and cause general turbulence within the protected area
flame zone and interrupts the chemical chain reaction of the
and may move paper and light objects.
combustion process.
Direct contact with the vaporizing liquid discharged from a
The agent decomposes at approximately 482 °C (900 °F) and
nozzle has a chilling effect on objects and in extreme cases
it is therefore important to avoid applications involving hazards
can cause frostbite to the skin. The liquid phase vaporizes
where continuously hot surfaces are involved. Upon exposure
rapidly when mixed with air and therefore limits the risk to the
to the flame, the agent will decompose to form halogen acids.
immediate vicinity of the nozzle. Reduction in visibility will occur
Their presence will be readily detected by a sharp, acrid odor
due to the condensation of water vapor.
which is easily detected and acts as a warning and safeguard
to personnel. In most discharge situations, the positive pressure is greater
than the initial decrease. Thus, care must be taken not to
The primary objective of an FM-200 system is to detect and
over-pressurize the room. The nominal leakage of most
suppress a fire in its incipient stage long before smoke gener-
existing rooms generally ensures against over-pressurization.
ation causes damage. Fire often begins before smoke or fire
In fact, many areas need additional sealing to assure a satis-
is visible, or before intense heat is present. When fires are
factory holding time for the fire suppressing agent.
stopped at the incipient stage, the risk of explosion, production
of toxic combustion byproducts, or extensive damage are
eliminated. ! CAUTION
Once a system has discharged, remove the agent and any
The discharge of clean agent systems to suppress a fire can
harmful combustion by-products from the space by simple
result in a potential hazard to personnel from the natural form
ventilation.
of the clean agent or from the products of combustion that
result from exposure of the agent to the fire or hot surfaces.
HEALTH AND SAFETY
Unnecessary exposure of personnel to either of these potential
A properly designed and installed suppression system should hazards must be avoided.
not present any significant health or safety problems. However,
there are basic precautions to take to avoid accidents,
and aspects of the system operation that should be fully
understood.
Reference should be made to NFPA 2001 – “Clean Agent
Fire Extinguishing Systems” – for the toxic and asphyxiating
hazards of clean agent replacement.
SECTION 3 – GENERAL INFORMATION FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 3-2 REV. 0 2015-OCT-09 (Part No. 442940)
Electrical
! CAUTION Automatic electric actuation of the cylinder valve, through
FM-200 agent is not effective on the following: an approved control panel, can be accomplished by using
an electric actuator. The actuator is energized by an electric
lass Deep seated fires signal from the detection/control panel. When using the electric
lass D o bustible etals actuator, a mechanical actuating device can be attached as a
he icals capable of auto-ther al reco position secondary means of actuation. When using electric actuation,
a means of manual release must also be provided.
he icals capable of rapid o idation
nclosures with hot surfaces Mechanical
Mechanical actuation is accomplished by means of a local
FM-200 fire extinguishant agent suppresses fires by a combi- manual actuator mounted on top of the container valve or
nation of physical and chemical means. It does not significantly on top of the electric actuator. The container is actuated by
deplete the oxygen content in the room. removing the safety pin on the actuator and depressing the
A system consists of one or more containers connected strike knob. The pin in the actuator opens the container valve,
to a system of piping and nozzles. The agent is liquefied allowing the container to discharge the agent.
compressed gas, super-pressurized with nitrogen pressure and
stored in steel containers, each of which is fitted with a valve Pneumatic
specially designed to allow the contents of the container to Pneumatic actuation is accomplished with the AUTOMAN II-C
discharge within 10 seconds. When the valve opens, the agent Release and pneumatic actuators on the container(s).
flows into the distribution piping and then to the discharge
nozzles where it is rapidly dispersed as a vapor. TYPES OF DETECTION
Discharged FM-200 fire extinguishant gives the appearance of The approved type of detection available for the ANSUL
a fog which may reduce visibility. This normally clears rapidly FM-200 system is by use of an electronic control panel.
and should not obstruct the ability of personnel to safely exit
the protected area. Electronic Control Panel
ANSUL FM-200 engineered fire suppression systems are Electric actuation of the ANSUL FM-200 system is obtained
particularly valuable in suppressing fires in enclosures through the use of electronic control systems that monitor and
containing hazards, where a clean, electrically non-conductive control various system functions. All detection equipment must
agent is essential; or where the cleaning up of foam, water, or be installed according to NFPA 70 and NFPA 72. Available
dry chemical would be difficult. detection devices include: ionization smoke detectors, photo-
electric smoke detectors, flame detectors, and rate compen-
APPROVALS sated heat detectors.
The ANSUL FM-200 Fire Suppression System has been Note: When designing the system, make certain the type of
tested and is UL and ULC Listed (EX4510) as well as FM detector used is appropriate for the type of hazard so proper
Approvals as an engineered system for Class A, B, and C fire response is attained in a fire situation.
suppression, at temperatures between 0 °C to 54 °C (32 °F to
For FM-200 fire suppression systems, the typical area
130 °F).
coverage for a single smoke detector is 23.2 m2 (250 ft2)
and 20.9 m2 (225 ft2) for a heat detector. When a detector
TYPE OF SYSTEM
senses a fire, a signal is sent to the control panel. The panel
Total flooding is the approved type of system available. A total in turn sends an electrical signal to the actuator located on the
flooding system normally consists of a fixed supply of agent master container valve. The actuator opens the master valve,
connected to piping with nozzles which will direct the agent actuating that container and causing pneumatic actuation
into an enclosed hazard space. In a total flooding system, the of the remaining containers from the pressure of the master
enclosure around the hazard must be tight enough to hold the container.
required percentage of agent concentration for a period of time
to suppress the fire.
FM-200 Total Flood Fire SECTION 4 – PLANNING
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 4-1
INTRODUCTION 11. Identify all potential fire hazards and determine the corre-
Planning for the design and installation of an FM-200 system sponding agent concentration requirements. Select the
should start when the customer is first contacted in regards to highest design concentration determined for protection of
protecting his/her hazard with the FM-200 fire extinguishant the hazard area.
agent. Most of the information needed for the design of a
Agent Supply Requirements and Considerations:
system is collected during the first meeting with the customer.
The information gathered at this point will determine the ease 1. Will the containers be located in a dedicated space? If so,
or difficulty of the rest of the project. One of the key elements record the dimensions of the space.
for fire protection is to correctly define the hazard and conduct 2. Is the operating temperature range within 0 °C to 54 °C
a complete survey to determine if the system will properly (32 °F to 130 °F)?
protect the hazard. Coordination with all parties involved in the
project will further improve the flow of the overall project. 3. Determine if the floor will support the containers and
bracketing
A thorough hazard analysis is required to determine the
amount of protection required. It is important to cover each 4. Will the container bracketing be secured to a wall? If so, is
element and accurately record the information. This information the wall strong enough to support the bracketing and the
will be used to determine the size and location of the FM-200 containers?
system and can be used to determine if any changes were 5. Will a reserve supply of agent be required? If so, will it
made to the hazard after the system was installed. Information need to be connected to the manifold?
necessary for the design of a system is listed in the following 6. Will a discharge test be required?
paragraphs.
Actuation and Alarm Requirements and Considerations:
Initial General Information:
1. Will the system be actuated automatically as well as
1. Are Specifications available? If so, obtain a copy. manually?
2. Who is the “Authority Having Jurisdiction”? Is it the owner? 2. What type of manual actuation is required?
3. Will the system need to be approved by any other 3. Will multiple areas be protected by a single system? If so,
regulatory or insurance agencies? will the areas be protected separately or simultaneously?
4. Will any special requirements apply to the system design or 4. Identify locations of all manual release and abort stations
installation?
5. If automatic detection is a part of the system, provide
Hazard Information: ceiling details
1. Secure the general arrangement drawings of the areas to 6. What types of alarm devices are required: audible and/or
be protected. visible?
2. If the general arrangement drawings do not include all of 7. Where will the system actuation be annunciated?
the necessary information, then you must obtain it. 8. Does the hazard area require explosion-proof or weather-
3. Record all dimensions of the hazard areas such as length, proof wiring and devices?
width, ceiling height, angles of corners if not 90°,etc. 9. What devices need to be shut down or started up? Identify
4. Draw a sketch including plan and elevation views of the the number of contacts required
hazard area if drawings are not available.
Piping and Wiring Information:
5. Indicate the quantity and location of all exits from the
hazard area on the sketches. 1. Determine the container location
6. Record all dimensions for any structural objects such as 2. Identify preferred supply piping routes
beams or columns, built-in cabinets, ducts, etc. which may 3. Indicate any obstructions to the piping or wiring runs
allow a reduction of the hazard volume.
4. Distribution piping will be installed only with approved
7. Identify anything unique about the hazard area that would piping
affect system design or installation.
5. Pipe size reductions may be made by using reducing tees,
8. Identify the normal, maximum, and minimum ambient bushings or couplings
temperatures of the hazard area.
9. Will the hazard area normally be occupied?
10. Identify any openings or potential openings in the hazard
enclosure that may cause loss of agent during or after
discharge.
SECTION 4 – PLANNING FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 4-2 REV. 0 2015-OCT-09 (Part No. 442940)
SYSTEM LIMITATIONS
The calculation method is designed for specific types of fittings,
8.7 m
pipe, and pipe inside diameter. When these limitations are (28.6 FT)
not maintained, there is a risk the system will not supply the
required quantity of agent.
NOTICE
If a system design violates these limits,
contact Technical Services.
FIGURE 5-3
MAXIMUM ELEVATION BETWEEN NOZZLES
009745
SECTION 5 – SYSTEM DESIGN FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 5-4 REV. 0 2015-OCT-09 (Part No. 442940)
OW
FL MINIMUM
LENGTH OF 10
OW X NOMINAL PIPE
FL
DIAMETER
MINIMUM LENGTH
OF 10 X NOMINAL
PIPE DIAMETER 10-30%
70-30%
OW
FL
OW
FL
a i u agent in pipe STEP NO. 12 Determine the nozzle locations and lay out the
etween - 1 seconds discharge ti e interconnecting piping
g 1 lb ft3) - 1.0 kg/L (62.4 lb/ft3) fill density STEP NO. 13 Complete an isometric sketch of the
a i u agent arri al ti e i balance of 1 seconds piping layout
a i u agent run out ti e of seconds STEP NO. 14 Estimate pipe size for all areas (optional)
ini u of 1 agent in pipe before first tee
STEP NO. 15 Perform flow calculations
a i u of 1 enclosures per syste
he ratio between the no le area and the pipe cross STEP NO. 16 Verify system performance
sectional area immediately preceding the nozzle is limited to
a minimum of 20% and a maximum of 80% STEP NO. 17 Complete layout of the system
3.66 m 3.66 m
Fire
(12 FT) (12 FT) Classification UL FM
SWITCH Class A 6.70% 7.17%
ROOM
3.05 m Class B Refer to Refer to
10.06 m
(10 FT) Technical Services Technical Services
(33 FT)
Class C 7.20% 8.10%
Note 1: For design concentrations for Class B flammable
liquids, consult Technical Services. However, the minimum
3.05 m
(10 FT) design concentration for flammable liquids is 9.0% based on
COMPUTER ROOM commercial grade heptane.
Class A, B (contact Technical Services for types), and C
4.57 m
hazards are UL listed and FM Approved for FM-200 systems.
0.3 m
(15 FT) (1 FT)
Complete this step for each area protected by the system.
Design Concentrations are determined by NFPA 2001 (Design
Concentration Requirements) and UL-2166 (Class A and B
Fire Clean Agent Extinguishment Agents).
SUBFLOOR
(COMPUTER ROOM)
Manually actuated systems require a safety factor determined
by the AHJ.
FIGURE 5-8 For this example a design concentration of 7.2% was selected.
007400
SECTION 5 – SYSTEM DESIGN FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 5-8 REV. 0 2015-OCT-09 (Part No. 442940)
SYSTEM DESIGN PROCEDURE (Continued) Metric example using NFPA 2001 formula
S = 0.1269 + (0.0005 x 21 °C) = 0.1374 m3/kg
STEP NO. 4 Determine minimum quantity of FM-200 fire
extinguishant agent required o puter oo
(7.2% required design concentration example only)
This step is used to determine the minimum amount of FM-200
140.22 m3
agent required to protect each hazard area. The amount of
agent in the system must always be at least this much and
W =
0.1374 m /kg 3
x
( 7.2%
100 - 7.2% ) = 79.18 kg
may be exceeded.
CAUTION ubfloor
(7.2% required design concentration example only)
Failure to supply the minimum amount of agent calculated may 13.79 m3
inhibit the system from suppressing a fire. W =
0.1374 m3/kg
x
( 7.2%
100 - 7.2% ) = 7.79 kg
W =
V
S
x
( C
100 - C )
ubfloor
Where: (7.2% required design concentration example only)
W = Weight of agent required in kg (lb) 495 ft3
V = Hazard volume in m (ft ) 3 3 W =
3
2.207 ft /lb
x
( 7.2%
100 - 7.2% ) = 17.40 lbs
at design temperature (T) The second option for calculating the required quantity of agent
Note: This formula includes an allowance for the normal is to refer to the Flooding Factors Table on pages 5-15 and
leakage (efflux) from a tight enclosure due to agent expansion. 5-16 to determine the correct flooding factor to use. To do this,
start by locating the Minimum Ambient Temperature in the left
NOTICE column, follow this line across until you reach the column for
the Minimum Design Concentration needed for the design.
The actual design concentration of agent The number listed where the temperature line and the concen-
cannot be less than the concentration selected tration column meet is the Flooding Factor to be used.
in Step No. 3 Note: If the minimum temperature or the minimum design
concentration, or both are not listed, interpolation will be
required.
Next, to determine the quantity of agent, multiply the Reduced
Hazard Volume by the Flooding Factor determined from the
table.
Complete this step for each area protected by the system.
FM-200 Total Flood Fire SECTION 5 – SYSTEM DESIGN
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 5-9
SYSTEM DESIGN PROCEDURE (Continued) STEP NO. 6 Determine the total system agent quantity
STEP NO. 4 (Continued) required
Example using flooding factors Add quantities from all areas to determine the minimum total
agent quantity required for the entire system.
Minimum Ambient Temperature = 21 °C (70 °F)
Minimum Design Concentration =7.2% Example:
Flooding Factor = 0.5647 kg/m3 (0.0352 lb/ft3) Minimum Quantity Required:
o puter oo 79.18 kg + 7.79 kg + 23.07 kg = 110.04 kg
3 3 rounded up to 111 kg of agent
140.22 m x 0.5647 kg/m = 79.18 kg of agent
(4950 ft3 x 0.0352 lb/ft3 = 174.24 lb of agent) (174.02 lb + 17.40 lb + 50.62 lb = 242.04 lb
rounded up to 243 lb of agent)
ubfloor
13.79 m3 x 0.5647 kg/m3 = 7.79 kg of agent STEP NO. 7 Determine estimated number of containers
(495 ft3 x 0.0352 lb/ft3 = 17.42 lb of agent) required
witch oo When the minimum quantity of agent has been calculated the
3 3
40.86 m x 0.5647 kg/m = 23.07 kg of agent weight is compared to the available agent container size.
(1440 ft3 x 0.0352 lb/ft3 = 50.69 lb of agent) The container size must be equal to or greater than the weight
of agent (see Table 2-1a and 2-1b, page 2-3).
STEP NO. 5 Adjust quantity of agent with altitude
Note: When manifolding tanks, all tanks on the manifold must
correction factor
be the same size and fill weight.
It may be necessary at this point to adjust the required initial
With the appropriate container selected, the previous equation
FM-200 agent quantity for altitude effects. An increase in
can be rearranged to determine the concentration based on the
altitude causes the agent to expand and occupy more space,
actual weight as containers are filled to the nearest kg.
which will lead to a higher concentration if the agent quantity is
not reduced accordingly. A decrease in altitude will cause the 100 WS
opposite effect, increasing the quantity of agent required. This C =
(WS + V)
same effect will apply to increases or decreases in the ambient
pressure which could be caused by ventilation systems To calculate the required agent for each hazard volume as a
designed to maintain a positive or negative pressure within the percentage of the total agent required;
enclosure. To apply the proper adjustment, first look up the
Individual hazard volume
altitude or pressure of the hazard on the Altitude Correction % Hazard Agent =
Factors Chart on Page 5-14 in this section. Sum of hazard volumes
Determine the total agent required by multiplying the quantity of Calculate required agent for each hazard volume:
agent required (see Step 5) by the Altitude Correction Factor. Example:
If the altitude is between 914 m (3000 ft) below sea level and
914 m (3000 ft) above sea level, use of the altitude correction 140.22 m3
Computer Room = = 71.96%
factor is optional. Interpolation of the table may be necessary if 194.87 m3
the actual altitude or pressure is not listed.
(4950 ft3)
= (71.90%)
Example: (6885 ft3)
The hazard altitude is at sea level. Referring to the chart on
Page 5-9, the altitude correction factor of sea level is 1.00, 13.79 m3
Subfloor = = 7.08%
therefore, there is no change in FM-200 agent quantities. 194.87 m3
Example – Continue using NFPA 2001 formula values (495 ft3)
= (7.19%)
o puter oo (6885 ft3)
79.18 kg of agent x 1.00 = 79.18 kg of agent
(174.02 lb of agent x 1.00 = 174.02 lb of agent) 40.86 m3
Switch Room = = 20.97%
194.87 m3
ubfloor
7.79 kg of agent x 1.00 = 7.79 kg of agent (1440 ft3)
(17.40 lb of agent x 1.00 = 17.40 lb of agent) = (20.92%)
(6885 ft3)
witch oo
23.07 kg of agent x 1.00 = 23.07 kg of agent
(50.62 lb of agent x 1.00 = 50.62 lb of agent)
SECTION 5 – SYSTEM DESIGN FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 5-10 REV. 0 2015-OCT-09 (Part No. 442940)
SYSTEM DESIGN PROCEDURE (CONTINUED) STEP NO. 8 Determine the design concentration at the
maximum ambient temperature for each area
STEP NO. 7 (Continued)
This step determines the Design Concentration of FM-200
Note: The subfloor is less than 10% of the total volume; a agent in each protected area using the Reduced Volume (see
separate container may be required because of hydraulic Step No. 3) and the supplied quantity of agent for the area at
limitations. the Maximum Ambient Temperature. It is necessary to avoid
Therefore: over-concentrating the area due to the additional agent actually
supplied to the area and the increased volume of agent caused
140.22 m3
Computer Room = = 77.44% by increased temperature.
181.08 m3
Example:
(4950 ft3)
= (77.46%) Maximum Ambient Temperature = 26.7 °C (80 °F)
(6390 ft3)
The following calculation is used:
40.86 m3
Switch Room = = 22.56% 100W
181.08 m3
C = V
(1440 ft3) + W
= (22.54%) S
(6390 ft3)
Where:
3
13.79 m W = Weight of agent used - kg (lb)
Subfloor = = 100%
13.79 m3 V = Volume of hazard - m3 (ft3)
(495 ft3) S = Specific vapor volume in m3/kg (ft3/lb)
= (100%)
(495 ft3) where S = 0.1269 + 0.0005T m3/kg
To determine the size and quantity of containers required, add (where S = 1.885 + 0.0046T ft3/lb)
the hazard agent quantities together:
T = Maximum ambient temperature - °C (°F)
Computer Room + Switch Room
C = Design agent concentration at maximum ambient
79.18 kg + 23.07 kg = 102.25 kg rounded up to 103 kg temperature (T)
(174.02 lb + 50.62 lb = 224.64 lb rounded up to 225 lb)
Then, C ÷ altitude correction factor
Subfloor = design concentration at maximum temperature
7.79 kg rounded up to 8 kg (17.40 lb rounded up to 18 lb)
Example:
Final Quantity required after rounding up:
o puter oo
o puter oo 1 g 79.76 kg
(225 lb x 0.7746 = 174.28 lb) 100 (79.76 kg)
( )
It is estimated that a 106 L container may be used for the 100 (174.28 lb)
Computer Room and Switch Room and a 16 L container may C = 4950 ft3
be used for the Subfloor. + 174.28 Ib
2.253 ft3/lb
Note: Actual container size(s) and fill weight(s) may change
based upon the FM-200 System Flow Calculation Program.
C = 7.39% (7.35%)
Design concentration at maximum temperature
= 7.39% (7.35%) ÷ 1.00 (altitude correction factor)
= 7.39% (7.35%)
FM-200 Total Flood Fire SECTION 5 – SYSTEM DESIGN
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 5-11
SYSTEM DESIGN PROCEDURE (Continued) STEP NO. 9 Determine the nozzle quantity
STEP NO. 8 (Continued) Nozzle quantity will be determined by many factors, such as
witch oo size and shape of the hazard area, height of the ceiling, flow
rates through the nozzles, available orifice sizes, etc.
100 (23.24 kg)
The number of nozzles required is based on the hazard size
C = 40.86 m3 and configuration, as well as the coverage provided by the
+ 23.24 kg
0.14025 m3/kg nozzle. To determine the quantity of nozzles required, divide
the area by 95.3 m2 (1026 ft2) and round up to the next whole
number. This whole number is the minimum number of nozzles
( )
100 (50.72 lb) required.
C = 1440 ft3 Refer to Page 5-3 for nozzle placement specifications.
+ 50.72 Ib
2.253 ft3/lb
Complete this step for each area protected by the system.
Design concentration at maximum temperature The maximum coverage area per nozzle is 95.3 m2 (1026 ft2).
= 7.39% (7.35%) ÷ 1.00 (altitude correction factor) o puter oo
= 7.39% (7.35%) 10.06 m x 4.57 m = 45.97 m2
45.97 m2 ÷ 95.3 m2 = 1 nozzle
ubfloor (33 ft x 15 ft = 495 ft2)
(495 ft2 ÷ 1026 ft2 = 1 nozzle)
100 (8 kg)
witch oo
C = 13.79 m3 3.66 m x 3.66 m = 13.40 m2
+ 8 kg
0.14025 m3/kg 13.40 m2 ÷ 95.3 m2 = 1 nozzle
(12 ft x 12 ft = 144 ft2)
( )
100 (18 lb) (144 ft2 ÷ 1026 ft2 = 1 nozzle)
C = 495 ft3 ubfloor
+ 18 Ib 10.06 m x 4.97 m = 45.97 m2
2.253 ft3/lb
45.97 m2 ÷ 95.3 m2 = 1 nozzle
(33 ft x 15 ft = 495 ft2)
C = 7.52% (7.57%) (495 ft2 ÷ 1026 ft2 = 1 nozzle)
Design concentration at maximum temperature One nozzle required for each hazard area (Computer room,
= 7.52% (7.57%) ÷ 1.00 (altitude correction factor) Switch room and Subfloor).
= 7.52% (7.57%)
STEP NO. 10 Estimate agent flow rate for each area
Verify the actual agent concentration is within the design This step estimates the total flow rate into each protected
concentration range of 7.2% to 9.0%. It is important to verify space, allowing the designer to estimate nozzle sizes for
that the worst case design concentration will not exceed limits quotation purposes. Note: This is an estimate only. It is
for fire suppression on the low end and life safety on the high the designer’s responsibility to assess the correctness of
end. this estimate. If the flow rate approaches the top end of the
allowable flow rate for a given size pipe, it may be in the
Note: Normally occupied space is defined as one that is
designer’s best interest to increase the pipe si e
intended for occupancy by NFPA 2001. The appendix of NFPA
2001 states spaces occasionally visited by personnel, such as Complete this step for each area protected by the system.
transformer bays, switch-houses, pump rooms, vaults, engine
test stands, cable trays, tunnels, microwave relay stations, Example:
flammable liquid storage areas, enclosed energy systems, etc., o puter oo
are examples of areas considered not normally occupied.
79.76 kg ÷ 10 seconds = 7.98 kg/sec.
Refer to NFPA 2001 for detailed exposure conditions. (174.28 lb ÷ 10 seconds = 17.43 lb/sec.)
Complete this step for each area protected by the system. witch oo
23.24 kg ÷ 10 seconds = 2.32 kg/sec.
Example:
(50.72 lb ÷ 10 seconds = 5.07 lb sec.)
6.53% and 6.79% are between 7.2% and 9.0%, therefore the
ubfloor
system design is acceptable.
8.0 kg ÷ 10 seconds = 0.8 kg/sec.
(18 lb ÷ 10 seconds = 1.8 lb/sec.)
SECTION 5 – SYSTEM DESIGN FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 5-12 REV. 0 2015-OCT-09 (Part No. 442940)
SYSTEM DESIGN PROCEDURE (Continued) STEP NO. 13 Complete an isometric sketch of the piping
STEP NO. 11 Estimate the nozzle flow rates layout
If all of the nozzles within the hazard area have the same flow Create an isometric sketch of the piping for use when inputting
rate, divide the Estimated Flow Rate for the Area (Step No. 11) the information in the ANSUL FM-200 System Flow Calculation
by the nozzle quantity (Step No. 9). Program. After the sketch is complete, identify all of the pipe
lengths.
If all of the nozzles within the hazard area will not have the
same flow rate, perform a percentage calculation using the Piping Node Points
volume protected by each nozzle divided by the total volume
A node point defines the start or end of a branch (segment)
for the area and then multiply the flow rate for the area
in the piping. A branch can consist of a run of pipe or another
(Step No. 12) by the volume percent calculated previously
object such as a flex hose or check valve. Each node point is
to determine the flow rate for that nozzle. Complete this
indicated on the isometric screen of the software by a circle.
procedure for each nozzle in the system.
Segment 1 (Node 0 to 1) always represents the cylinder. This
If the design includes multiple levels of nozzles, remember to
segment can never be changed. The pipe length is the siphon
include all nozzles on all levels in this step.
tube/valve length (which is also the elevation change for the
Complete this step for each area protected by the system. vertical cylinder); the total equivalent length is the calculated
Example: equivalent length of the siphon tube/valve assembly. The
designer program will number the rest of the pipe segments as
o puter oo
they are entered.
7.98 kg/sec ÷ 1 nozzle = 7.98 kg/sec per nozzle
(17.43 lb/sec ÷ 1 nozzle = 17.43 lb/sec per nozzle) Nozzles
witch oo Nozzles are indicated with the number of the enclosure
2.32 kg/sec ÷ 1 nozzle = 2.32 kg/sec per nozzle and the number of the nozzle in the enclosure (i.e., E1N1 –
(5.07 lb/sec ÷ 1 nozzle = 5.07 lb sec per nozzle) E1N2). The designer program assigns the nozzle indicators.
Sequential placement is not required, however, it is recom-
ubfloor mended that the designer use some sort of numbering system
0.8 kg/sec ÷ 1 nozzle = 0.8 kg/sec per nozzle to prevent confusion.
(1.8 lb/sec ÷ 1 nozzle = 1.8 lb/sec per nozzle)
100 31.4 49.08 At this point, all final details of the system can be finalized.
(4) (69.25) (108.2)
STEP NO. 18 Create estimated bill of materials
150 49.08 110.4
Create a list of all materials necessary to install the system.
(6) (108.2) (243.49)
Note: Actual container size(s) and fill weights may change
Note: This information is for Schedule 40 pipe and is for
based upon the Flow Calculation Program system calculations.
estimating only. Pipe and nozzle sizes need to be confirmed
by the calculation program. When estimating, use a larger pipe STEP NO. 19 Create installation drawings
size.
The final step in the design of a FM-200 system is completion
of installation drawings for submittal to the appropriate
authority and the customer. These drawings should include all
details necessary for installation of this system.
SAMPLE APPLICATIONS
Refer to the ANSUL flow calculation printout example in
Appendix A. By reviewing this example, it may help answer
some questions concerning the total design process.
SECTION 5 – SYSTEM DESIGN FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 5-14 REV. 0 2015-OCT-09 (Part No. 442940)
1 W/V [Agent Weight Requirements (kg/m3)] = kilograms of agent required per cubic meter of protected volume
to produce indicated concentration at temperature specified.
W =
V
S
x
( C
100 – C )
2 T [Temperature (°C)] – The design temperature in the hazard area.
3 S [specific volume (m3/kg)] of superheated FM-200 (HFC 227ea) vapor can be approximated by the formula:
S = 0.1269 + 0.0005T where T is the temperature in °C
4 C [Concentration (%)] – Volumetric concentration of FM-200 (HFC 227ea) in air at the design temperature indicated.
SECTION 5 – SYSTEM DESIGN FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 5-16 REV. 0 2015-OCT-09 (Part No. 442940)
1 W/V [Agent Weight Requirements (lb/ft3)] = pounds of agent required per cubic feet of protected volume
to produce indicated concentration at temperature specified.
W =
V
S
x
( C
100 – C )
2 T [Temperature (°F)] – The design temperature in the hazard area.
3 S [specific volume (ft3/lb)] of superheated FM-200 (HFC 227ea) vapor can be approximated by the formula:
S = 1.8850 + 0.0046T where T is the temperature in °F
4 C [Concentration (%)] – Volumetric concentration of FM-200 (HFC 227ea) in air at the design temperature indicated.
FM-200 Total Flood Fire SECTION 5 – SYSTEM DESIGN
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 5-17
Nominal
Pipe Size 90° Elbow 45° Elbow Thru Tee Side Tee Union
mm (in.) m (ft) m (ft) m (ft) m (ft) m (ft)
10 (3/8) 0.4 (1.2) 0.18 (0.5) 0.24 (0.7) 0.82 (2.5) 0.09 (0.3)
15 (1/2) 0.52 (1.6) 0.24 (0.7) 0.3 (0.9) 1.04 (3.2) 0.12 (0.4)
20 (3/4) 0.67 (2.0) 0.3 (0.9) 0.42 (1.3) 1.37 (4.2) 0.15 (0.5)
25 (1) 0.85 (2.6) 0.4 (1.2) 0.55 (1.7) 1.74 (5.3) 0.18 (0.6)
32 (1 1/4) 1.13 (3.4) 0.52 (1.6) 0.7 (2.1) 2.29 (7.0) 0.24 (0.7)
40 (1 1/2) 1.31 (4.0) 0.61 (1.7) 0.82 (2.5) 2.65 (8.0) 0.27 (0.8)
50 (2) 1.68 (5.1) 0.79 (2.4) 1.06 (3.2) 3.41 (10.4) 0.37 (1.1)
65 (2 1/2) 2.01 (6.1) 0.94 (1.5) 1.25 (3.8) 4.08 (12.4) 0.43 (1.3)
80 (3) 2.5 (7.6) 1.16 (3.5) 1.55 (4.7) 5.06 (15.4) 0.55 (1.7)
100 (4) 3.26 (10.0) 1.52 (4.6) 2.01 (6.1) 6.64 (20.2) 0.73 (2.2)
125 (5) 4.08 (12.4) 1.92 (5.9) 2.56 (7.8) 8.35 (25.5) 0.91 (2.8)
150 (6) 4.94 (15.0) 2.32 (7.1) 3.08 (9.4) 10.00 (30.5) 1.07 (3.3)
Equivalent Length Table for Pipe Fittings. Figures based upon schedule 40 ASTM A 106-77 pipe (nominal pipe size given in table)
Figures based upon schedule 40 ASTM A 106-77 pipe (nominal pipe size given in table).
DATE: ______________________________________________________________________________ FM-200 SYSTEM DESIGN CALCULATION WORKSHEET
QUOTE/JOB NUMBER: ________________________________________________________________
Page 1 of 2
CUSTOMER: _________________________________________________________________________
UL EX4510
PAGE 5-18
Width (ft):
Height (ft):
SECTION 5 – SYSTEM DESIGN
Volume Reductions:
Structural Reductions (cu ft):
Net Volume:
(Volume – Structural Reductions)
ALTITUDE CORRECTION:
Height Above or Below Sea Level:
Factor:
(From Design Manual Table)
(From Page 1)
AREA 1 AREA 2 AREA 3 AREA 4 AREA 5
Suppression System Manual
Area Name:
DISCHARGE TIME:
Normal Ambient Temperature:
Design Concentration at Ambient Temp.:
(Locate Actual Agent Conc. at Ambient Temp. on Table, or Use Calc. in Design Manual)
Nozzle Quantity:
[area ÷ 1026 (rounded to next highest wole number) then verify maximum radial distance]
NOTES:
FM-200 Total Flood Fire SECTION 6 – INSTALLATION
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 6-1
GENERAL INFORMATION The FM-200 system components are designed and tested to
All installations are to be performed by an Authorized ANSUL operate in the temperature range of 0 °C to 54 °C (32 °F to
Distributor in accordance with the parameters of this manual 130 °F) or as stated in separate component approvals.
and all appropriate codes and standards from Authorities Installation drawings shall be submitted for approval to the
Having Jurisdiction (AHJ). appropriate authority prior to system installation.
Specific installation drawings must be prepared for the hazard On receipt, unpack the supplied items and ensure the
area in accordance with system design as calculated by the components comply with the packing list and installation
ANSUL FM-200 System Flow Calculation Program. These drawings.
drawings should be followed closely in order to ensure the The container weight is checked at the factory prior to
system meets its design criteria. The pipe network is sized in shipment, and recorded on the label attached to the container.
order to obtain correct discharge time, nozzle pressures, agent If there is any doubt regarding the weight, or leakage is
quantity and various other design considerations. If for any suspected, the container should be weighed to confirm no
reason, the pipe network requires modifications the system weight loss. To check agent weight in 106 L, 147 L, 180 L,
must be recalculated before proceeding with installation. and 343 L containers with an installed liquid level measuring
Installation drawings contain the following information: device, see Section 8 – Maintenance. Determine the container
nclosure olu es storage temperature and refer to the Temperature Correction
gent uantities Table in Section 9 – Recharging Procedure, page 9-5, to check
the pressure within the container.
caled pipe networ plan
ipe networ iso etric
ipe dia eters pipe length drops and rises
o le data
ontainer data
lectrical actuator technical data
ow pressure switch wiring chart
ittings data
SECTION 6 – INSTALLATION FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 6-2 REV. 0 2015-OCT-09 (Part No. 442940)
6. Install the initial pipe run and then disconnect the container
OUTLET
SAFETY CAP
and refit the outlet safety cap to the valve outlet. See pipe
installation, page 6-8.
7. Re-connect the pipe to the container after the pipework
system is complete and the discharge nozzles have been
installed.
FIGURE 6-1
OUTLET SAFETY AND SAFETY CAPS
009671
DISCHARGE
HOSE OR PIPE
SINGLE CONTAINER
DISCHARGE ADAPTOR
PIPE
UNION
COUPLING
ELBOW ELBOW
FIGURE 6-2
DISCHARGE OUTLET CONNECTIONS
009709 / 009710
FM-200 Total Flood Fire SECTION 6 – INSTALLATION
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 6-3
TABLE 6-1: BRACKET MOUNTING HEIGHTS General Piping Requirements (Including manifolds)
se chedule blac iron gal ani ed chro e-plated or
stainless steel pipe conforming to ASTM A53 or A106. All
No. of Height From Floor to Bracket fittings must be a minimum Class 300, malleable or ductile
Container
Back iron.
Size
Channels mm (in.) ipe unions are acceptable
L A B A B educing bushings and reducing fittings are allowed when
reducing pipe size.
8 1 130 -- (5.0) --
ast iron pipe and fittings are not acceptable
16 2 60 330 (2.5) (13.0) eflon tape is the only acceptable pipe sealant and
must be applied to male threads only.
32 2 160 595 (6.25) (23.5)
NOTICE
52 2 110 343 (4.25) (13.5)
Do not allow tape to overlap the pipe opening,
106 2 300 750 (11.75) (29.5) as this could cause possible blockage of the
agent. Thread sealant or compound must
147 2 300 1000 (11.75) (39.25) not be used.
FIGURE 6-3
CONTAINER STRAP LOCATION (106 L EXAMPLE)
009711
SECTION 6 – INSTALLATION FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 6-4 REV. 0 2015-OCT-09 (Part No. 442940)
MANIFOLDS
NOTICE
Manifolds are supplied by others. The infor-
mation supplied here is to assist design and
installation.
CAUTION
Do not allow tape to o erlap the pipe opening as this could
cause possible blockage of the agent.
hread sealant or co pound ust not be used
efore asse bling the pipe and fittings a e certain all ends
are carefully reamed and blown clear of chips, debris and
scale. The inside of pipe and fittings must be free of oil and
dirt.
B C
FIGURE 6-4
TYPICAL MANIFOLD ASSEMBLY
(DIMENSIONS IN TABLE 6-2, NEXT PAGE)
009712
FM-200 Total Flood Fire SECTION 6 – INSTALLATION
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 6-5
MANIFOLDS (Continued)
Inlet Inlet
Nominal to End Cap to Inlet Container
No. of Manifold End Overall Length
Distance Distance Size
Inlets Pipe Connection (A)
(B) (C)
Diameter
mm (in.) mm (in.) mm (in.) L
2 650 (25.6)
3 2 1/2 in. NPT 1000 (39.4) 150 (6) 350 (14) 8 to 32
4 1350 (53.1)
2 808 (31.8)
3 1316 (51.80
4 3 in. NPT 1824 (71.80 150 (6) 508 (20) 52 to 180
5 2332 (91.8)
6 2840 (111.8)
2 808 (31.8)
3 1316 (51.80
4 4 in. NPT 1824 (71.8) 150 (6) 508 (20) 52 to 180
5 2332 (91.8)
6 2840 (111.8)
3 1366 (53.8)
4 1874 (73.8)
5 2382 (93.8)
6 2890 (113.8)
6 in. Flange 150 (6) 508 (20) 52 to 180
7 3398 (133.8)
8 3906 (153.8)
9 4414 (173.8)
10 4922 (193.8)
2 1011 (40.0)
3 4 in. NPT 1722 (68.0) 150 (6) 711 (28) 343
4 2433 (96.0)
2 1061 (42.0)
3 1772 (70.0)
4 2483 (98.0)
5 3192 (126.0)
6 6 in. Flange 3905 (154.0) 150 (6) 711 (28) 343
7 4616 (182.0)
8 5327 (210.0)
9 6038 (238.0)
10 6749 (266.0)
SECTION 6 – INSTALLATION FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 6-6 REV. 0 2015-OCT-09 (Part No. 442940)
Nominal
Height from
Floor to
Container Valve Manifold Underside of
Size Size Size Manifold Pipe
(A)
80 (3)
106 50 (2) 1601 (63.0)
100 (4)
L
VE
LE
80 (3) OO
R
FL
ED
147 50 (2) 100 (4) 1931 (76.0) SH
FINI
100 (4)
343 80 (3) 2274 (89.5)
150 (6)
CAUTION
NOTICE
Do not allow tape to o erlap the pipe opening as this could
cause possible blockage of the agent. Cautionary information indicating the calcula-
tion method has been investigated for specific
efore asse bling the pipe and fittings a e certain all ends
types of fittings, type of pipe and pipe inside
are carefully reamed and blown clear of chips, debris and
diameter. Also, when the specified limita-
scale. The inside of pipe and fittings must be free of oil and dirt
tions are not maintained, there is the risk the
hread sealant or co pound ust not be used system will not supply the required quantity
of suppression agent. The flow calculation
program contains pipe and fitting options
TABLE 6-4: US STEEL PIPE REQUIREMENTS together with Equivalent Length information
for pipe and fittings.
Pipe Nominal
Pipe Reference Connection
Type Pipe Size
ASTM A -106 Pipe Hangers
Threaded Sch. 40 3/8 in. - 6 in.
Seamless Grade C
Pipe hangers must be approved by the Authority Having
ASTM A -106/A-53 Jurisdiction (AHJ).
Threaded Sch. 40 3/8 in. - 6 in.
Seamless Grade B
Pipe hangers must be spaced according to the size of pipe
ASTM A -106/A-53 (see Table 6-6).
Threaded Sch. 40 3/8 in. - 6 in.
Seamless Grade A
Hangers must be placed within 300 mm (12 in.) of the
ASTM A -53 ERW discharge nozzle (see Figure 6-7, next page).
Threaded Sch. 40 3/8 in. - 6 in.
Grade B
Hangers must be placed between elbows that are more than
ASTM A -53 ERW 600 mm (24 in.) apart (see Figure 6-8, next page).
Threaded Sch. 40 3/8 in. - 6 in.
Grade A
Hangers must be mounted to a structure capable of supporting
ASTM A -53 Furnace the pipework.
Threaded Sch. 40 3/8 in. - 6 in.
Weld Class F
ASTM A -106 TABLE 6-6: HANGER SPACING
Welded Sch. 40 3/8 in. - 6 in.
Seamless Grade C
Maximum
ASTM A -106/A-53 Pipe Size
Welded Sch. 40 3/8 in. - 6 in. Spacing
Seamless Grade B
mm (in.) m (ft)
ASTM A -106/A-53 15 (1/2) 1.5 (5.0)
Welded Sch. 40 3/8 in. - 6 in.
Seamless Grade A
20 (3/4) 1.8 (6.0)
ASTM A -53 ERW 25 (1) 2.1 (7.0)
Welded Sch. 40 3/8 in. - 6 in.
Grade B
32 (1 1/4) 2.4 (8.0)
ASTM A -53 ERW 40 (1 1/2) 2.7 (9.0)
Welded Sch. 40 3/8 in. - 6 in.
Grade A 50 (2) 3.4 (11.0)
ASTM A -53 Furnace 65 (2 1/2) 3.5 (11.5)
Welded Sch. 40 3/8 in. - 6 in.
Weld Class F 80 (3) 3.7 (12.0)
100 (4) 4.3 (14.0)
150 (6) 5.2 (17.0)
FM-200 Total Flood Fire SECTION 6 – INSTALLATION
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 6-9
PIPE INSTALLATION (Continued) Where the design basic insulation level (BIL) is not available,
and where nominal voltage is used for the design criteria, the
Pipe Hangers (Continued) highest minimum clearance listed for this group shall be used.
Reference NFPA 2001 and Table 6-7.
NOZZLES
A false ceiling with loose tiles must have the tiles retained
within a 1.22 m (4 ft) radius of the nozzle including all perimeter
tiles to help prevent movement during system discharge.
Nozzles should be installed a maximum of 305 mm (12 in.)
below the ceiling.
FIGURE 6-8
ELBOW SUPPORT
009716
1 1 ubpart
SECTION 6 – INSTALLATION FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 6-10 REV. 0 2015-OCT-09 (Part No. 442940)
ACTUATION INSTALLATION
The method of actuation depends on the system configuration
which can be broken down as follows:
ingle ontainer ctuation
ultiple ontainer ctuation
ELECTRICAL ACTUATOR
The electrical actuator is installed to the top of the valve
assembly as follows:
1. Check the actuator pin to ensure it is in the non-fired posi-
tion by fully screwing in the reset tool, i.e. pin retracted
(see Figure 6-9).
4.8 mm - 5.2 mm
2. Remove the shipping cap from the top of the valve (0.189 IN. - 0.205 IN.)
assembly.
3. Carefully screw the actuator to the valve assembly (see
Figure 6-10). FIGURE 6-9
ACTUATOR PIN NON-FIRED POSITION
If no other actuators are to be installed to the top of the 009718
! CAUTION
The actuator must be hand-tight only. Over-tightening may
damage the valve and cause actuation of the container.
FIGURE 6-10
INSTALLED ELECTRICAL ACTUATOR
009719
FM-200 Total Flood Fire SECTION 6 – INSTALLATION
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 6-11
TERMINAL 2 GROUND
FIGURE 6-11
ELECTRICAL ACTUATOR CONNECTION BOARD
- BRIDGE RECTIFIER FIGURE 6-12
009738
PLACEMENT INDICATOR SWITCH
Before this system is put into operation, the removable 009678
! CAUTION
Failure to reset the actuator will result in a potentially hazardous
discharge of the container(s).
FIGURE 6-13
INDICATOR SWITCH INSTALLED
009739
SECTION 6 – INSTALLATION FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 6-12 REV. 0 2015-OCT-09 (Part No. 442940)
FIGURE 6-14
PNEUMATIC ACTUATOR NON-FIRED POSITION
FIGURE 6-12 009723
FIGURE 6-15
PNEUMATIC ACTUATOR INSTALLED
FIGURE 6-13 009724
FIGURE 6-16
MULTIPLE CONTAINER ACTUATION
009725
SECTION 6 – INSTALLATION FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 6-14 REV. 0 2015-OCT-09 (Part No. 442940)
RELEASE OPTIONS
AUTOPULSE Control Panel
The master container is actuated electrically using an electrical
actuator connected to an AUTOPULSE control panel.
Additional slave containers are pneumatically actuated from
the master container valve actuation port. See Figure 6-17.
FIGURE 6-17
ELECTRICAL ACTUATION WITH AUTOPULSE PANEL
009726
FIGURE 6-18
MASTER AND SLAVE ACTUATION WITH AUTOMAN II-C RELEASE
009727
FM-200 Total Flood Fire SECTION 6 – INSTALLATION
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 6-15
ACTUATION ISOLATOR
The actuation isolator is only required for use with 343 L
containers installed in a main and reserve fire suppression
PIPE PLUG
system. (REMOVED
FROM VALVE
ACTUATION
Application and Description PORT)
Because of the many variables associated with the application MALE CONNECTOR
(PART NO. 32338)
and installation of check valves in manifolded, multi-container
systems, it is not always possible to ensure the check valves ACTUATION
HOSE
are pressure tight when flow is reversed. This can cause a VALVE
ASSEMBLY
problem on main/reserve systems because the main discharge
pressure can escape through the common manifold to the
discharge port of the reserve master container valve. The
slave actuation port of the master container receives the same MALE ELBOW ACTUATION
pressure as the discharge port; therefore, it is possible for (PART NO. 31810) ISOLATOR
the reserve slave containers to be accidentally actuated. Two (PART NO. 56803)
MASTER MASTER
CONTAINER CONTAINER
SLAVE SLAVE
CONTAINER CONTAINER
ACTUATION ISOLATOR
(PART NO. 56803)
DETAIL OF TYPICAL
INSTALLATION FOR ACTUATION
ISOLATOR TO MASTER
CONTAINER VALVE.
! WARNING
Failure to tighten the actuation isolator, as stated, would
allow back pressure Into the slave actuation line. This back
pressure may cause the reserve slave containers to be
accidentally actuated upon discharge of the main system.
Do NOT over-tighten the Isolator.
FIGURE 6-23
DISCHARGE PRESSURE SWITCH INSTALLATION
(MULTIPLE CONTAINER SYSTEM)
009730
FIGURE 6-22
DISCHARGE PRESSURE SWITCH INSTALLATION
(SINGLE CONTAINER SYSTEM)
009729
SECTION 6 – INSTALLATION FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 6-18 REV. 0 2015-OCT-09 (Part No. 442940)
FIGURE 6-24
PRESSURE SWITCH CONTACTS
008922
! WARNING
To ensure the discharge pressure switch maintains its listed
IP rating, proper conduit seals must be used when connecting
the conduit system to the discharge pressure switch enclosure.
Failure to do so may result in premature discharge pressure
switch failure, resulting in a potentially hazardous condition that
could cause serious injury or death.
FM-200 Total Flood Fire SECTION 6 – INSTALLATION
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 6-19
anual syste s depend on hu an detection of a fire in the UL Listed Detection and Control Equipment
hazard area and prompt action to actuate the manual actuator
for the - fire e tinguishant agent syste to discharge Detectors shall be UL Listed for the intended application.
and flood the protected area and suppress the fire. Control Panels shall be UL Listed for releasing device service
and co patible with detection and - gent ngineered
All other instructions associated with manual operation form otal looding ire uppression yste
part of the user’s procedures on safety precautions and fire
drill. If required, assistance can be provided to help the user
prepare procedures for safety and fire precautions.
Once a system has discharged, remove the agent and any
harmful combustion by-products from the space by simple
ventilation.
SECTION 7 – SYSTEM OPERATION FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 7-2 REV. 0 2015-OCT-09 (Part No. 442940)
NOTES:
FM-200 Total Flood Fire SECTION 8 – MAINTENANCE
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 8-1
INSPECTION SERVICE AND MAINTENANCE arry out a full isual chec of the enclosure for integrity
Systems shall be thoroughly inspected and tested for proper and confirm the dimensions and the configuration of the
operation by qualified distributor in accordance with NFPA as ha ard atch the latest appro ed drawings f drawings
well as any other standard accepted to the Authority Having are not available, dimensions and calculations should be
Jurisdiction. Before any checks are carried out, ensure the made, per Section 5 – System Design, to validate system
Suppression system is isolated electrically and mechanically design.
and remove all electrical and pneumatic actuators. No mainte- hec all warning signs throughout the area a e
nance work should be carried out without obtaining approval certain they are in place, mounted securely, are readable,
from the Responsible Person and advising any personnel and are not damaged.
within the hazard area. The following Program should be hec the condition of the control panel for ta pering
carried out in addition to the ser’s rogra of nspection he corrosion, or damage. Test the panel by referring to the
user shall be provided with a signed and dated report of the appropriate AUTOPULSE Control System manual.
inspection advising any rectification carried out or needed.
hec all detectors in accordance with a e
SIX MONTH INSPECTION certain they are in place, clean, and not damaged.
f re uired chec the sensiti ity of each per the
Check the condition of all actuators by completing the instruction of the detector manufacturer. See appro-
following: priate AUTOPULSE Control System manual for detailed
1. Remove all actuators from the container valves (electric, instructions.
manual, and pneumatic). hile chec ing the detectors and electric pull station
2. For pneumatic actuator, check the condition of each inspect each alarm device. Check the condition of the
actuator to make certain they operate freely. Reset the alarm and verify correct operation when energized.
actuator ensuring the pin is in the non-fired position, see Reset the alarm circuit after each test.
Figure 6-14, page 6-12. hec all anual release stations a e certain stations
3. For electric actuators, make certain all wires are properly are in place, and are not blocked or damaged. Operate
connected. Test-fire the actuator and ensure the pin each manual release station to confirm the control panel
operates freely. Reset the actuator ensuring the pin is in operation. Reset each manual release station.
the non-fired position, see Figure 6-9, page 6-10. ll syste hoses should be e a ined for da age f
est and ser ice all electrical detection and alar isual e a ination shows any deficiency the hose shall
systems as recommended in NFPA as well as any other be replaced.
standard accepted by the Authority Having Jurisdiction.
ternally inspect containers for signs of da age or
unauthorized modifications. Check container labels are
securely mounted and legible. Check container brackets
and fittings.
a ine the container pressure gauge reading and
refer to the te perature correction table f the container
pressure corrected to temperature is below 10% of the
stated pressure, it must be replaced or recharged.
erification of - fire e tinguishant agent fill weight
in the containers may be achieved through either liquid
le el detection or container weighing f containers
e ceed an agent loss of ore than or a pressure
loss (adjusted for temperature) of more than 10%, the
container should be refilled/recharged or replaced.
hec the condition of the piping to a e certain it
is properly secured in the hangers and all fittings are
connected tightly. Look for signs of damage or corrosion.
Repair pipework as necessary.
nspect no les for dust and debris clean out where
necessary, and ensure correct distribution pattern, nozzle
orifice code, and orientation.
SECTION 8 – MAINTENANCE FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 8-2 REV. 0 2015-OCT-09 (Part No. 442940)
NOTICE
The internal container temperature can
be determined by measuring the ambient
temperature at the container location. The
container must be stored at this temperature
for at least 24 hours to obtain an accurate
liquid level reading.
FM-200 Total Flood Fire SECTION 8 – MAINTENANCE
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 8-3
USING THE LIQUID LEVEL MEASURING DEVICE Example: Using The Container Weight Conversion Table
(Continued) si - onth weight chec is being perfor ed on a 1
container filled with 1 g 1 lb of - fire e tin-
Operation (Continued)
guishant agent. The temperature of the container is 15 °C
(60 °F). The liquid level measuring device reading is 36 cm
(14 1/4 in.).
Find the 36 cm (14 1/4 in.) line on the left side of the 180 L
container table and read horizontally across the table to the
15 °C (60 °F) column. Then, by reading the weight of the agent
at the level/temperature column intersection, it is determined
that the weight of the agent is 135.8 kg (299.2 lb).
To determine if this is within the 5% weight loss tolerance,
READ LEVEL multiply the weight of charge (taken from the container
HERE
nameplate) by 0.95 to determine the minimum weight of agent
required in this container:
1 g 1 g 1 lb lb
Because the 135.8 kg (299.2 lb) measured weight of the agent
is more than the minimum required agent weight of 130 kg
(286 lb), the weight of the agent is within the 5% weight loss
tolerance.
f the easured weight had been less than the weight loss
tolerance, the container should be weighed to verify the liquid
le el easure ent f the weight loss still e ceeds of the
FIGURE 8-2 weight of charge, the container must be refilled or replaced.
READING LIQUID LEVEL
12 MONTH INTEGRITY TEST
4. To reinstall tape, quickly pull on the tape to disengage the ntegrity test the enclosure to deter ine if the lea age area has
magnetic interlock. Then slide the tape into the housing changed significantly from that measured during installation.
and replace the protective cap.
sing the i uid e el ndicator eight on ersion able 5 YEAR INSPECTION
located in ppendi deter ine the agent weight of
Hoses need to be tested every 5 years. Refer to NFPA 2001
charge as follows:
for detailed testing requirements.
a. Find the liquid level reading along the left hand vertical
line of the table. 10 YEAR ELECTRICAL ACTUATOR LIFESPAN
b. From that point, follow the horizontal line to the point The removable electrical actuator has a life span of 10 years
where it intersects with the temperature column (using from manufacture, which is indicated on the label, and should
the agent container temperature noted in Step 3). be replaced before this date is reached.
c. Read the weight of the agent at the level/temperature
column intersection. CONTAINER TEST
6. Compare the weight from the table to the weight of charge Refer to NFPA 2001 or Authority Having Jurisdiction.
sta ped on the container na eplate f the easure ent
shows a net weight loss of more than 5%, the container PERSONNEL TRAINING
ust be weighed to erify the li uid le el easure ent f ll persons who ay be e pected to inspect test aintain or
the weight loss still e ceeds of the weight of charge operate the fire suppression system shall be kept adequately
the container requires refilled or replaced. trained in the functions they are e pected to perfor
Personnel working in an enclosure protected by a gaseous
suppressant shall receive training in the operation and use of
the system and safety issues.
SECTION 8 – MAINTENANCE FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 8-4 REV. 0 2015-OCT-09 (Part No. 442940)
FINAL INSPECTION
Carry out a final visual inspection of the system and the
protected area to ensure that all equipment has been
reinstalled and reconnected properly. Ensure any associated
control panel is displaying normal operation. Complete the site
log boo recording wor carried out and parts used nfor
the responsible person the work is complete and the system is
back on-line.
FM-200 Total Flood Fire SECTION 9 – RECHARGING PROCEDURE
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 9-1
442781 442781
6 Pressure gauge 570055 570055
5 – BURST DISC
a. Remove the valve and siphon tube assembly from the
container. 4 – OUTLET
SAFETY CAP
b. Remove the siphon tube locking screw to allow removal
of the siphon tube from the valve.
c. Remove the socket head cap screw that holds the recoil 6 – PRESSURE SIPHON
TUBE
cap chain to the valve body. GAUGE
O-RING*
d. Remove bonnet locking screw from the same port as COLLAR
O-RING*
socket head cap screw removed in Step c. Unscrew
the bonnet assembly, using spanner wrench (Part * INCLUDED WITH
No. 570574). Remove and discard o-ring from bonnet O-RING KIT (3)
i. Install top cap on valve body. Hand tighten. 50 mm (2 in.) 570276 570579 570592
j. Valve assembly is now ready to be function and leak 80 mm (3 in.) 570374 570579 69891
tested. See Testing Section. The valve assembly is assembled to the test bottom cap. The
outlet filling adaptor assembly is assembled to the valve outlet.
Attach the nitrogen line and ensure the vent valve on the outlet
filling adaptor assembly is closed.
FM-200 Total Flood Fire SECTION 9 – RECHARGING PROCEDURE
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 9-3
Metric
Developed Developed
Temperature Pressure Temperature Pressure
°C bar °C bar
0 20.2 28 26.9
1 20.4 29 27.2
2 20.7 30 27.4
3 20.9 31 27.6
4 21.2 32 27.9
5 21.4 33 28.1
6 21.6 34 28.4
7 21.9 35 28.6
8 22.1 36 28.8
9 22.4 37 29.1
10 22.6 38 29.3
11 22.8 39 29.8
12 23.1 40 30.2
13 23.3 41 30.5
14 23.6 42 30.8
15 23.8 43 31.2
16 24.0 44 31.5
17 24.3 45 31.8
18 24.5 46 32.2
19 24.8 47 32.5
20 25.0 48 32.8
21 25.2 49 33.1
22 25.5 50 33.5
23 25.7 51 33.8
24 26.0 52 34.1
25 26.2 53 34.5
26 26.4 54 34.8
27 26.7 55 35.1
SECTION 9 – RECHARGING PROCEDURE FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 9-6 REV. 0 2015-OCT-09 (Part No. 442940)
English
NOTES:
FM-200 Total Flood Fire APPENDIX A – FM-200 SYSTEM PROGRAM PRINTOUT
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 10-1
FM-200 SYSTEM
CALCULATION PROGRAM
CONSOLIDATED REPORT
APPENDIX A – FM-200 SYSTEM PROGRAM PRINTOUT FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 10-2 REV. 0 2015-OCT-09 (Part No. 442940)
FM-200 Total Flood Fire APPENDIX A – FM-200 SYSTEM PROGRAM PRINTOUT
Suppression System Manual UL EX4510
(Part No. 442940) 2015-MAR-16 REV. 0 PAGE 10-3
APPENDIX A – FM-200 SYSTEM PROGRAM PRINTOUT FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 10-4 REV. 0 2015-OCT-09 (Part No. 442940)
FM-200 Total Flood Fire APPENDIX A – FM-200 SYSTEM PROGRAM PRINTOUT
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 10-5
APPENDIX A – FM-200 SYSTEM PROGRAM PRINTOUT FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 10-6 REV. 0 2015-OCT-09 (Part No. 442940)
FM-200 Total Flood Fire APPENDIX A – FM-200 SYSTEM PROGRAM PRINTOUT
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 10-7
APPENDIX A – FM-200 SYSTEM PROGRAM PRINTOUT FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 10-8 REV. 0 2015-OCT-09 (Part No. 442940)
FM-200 Total Flood Fire APPENDIX A – FM-200 SYSTEM PROGRAM PRINTOUT
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 10-9
APPENDIX A – FM-200 SYSTEM PROGRAM PRINTOUT FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 10-10 REV. 0 2015-OCT-09 (Part No. 442940)
FM-200 Total Flood Fire APPENDIX A – FM-200 SYSTEM PROGRAM PRINTOUT
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 10-11
APPENDIX A – FM-200 SYSTEM PROGRAM PRINTOUT FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 10-12 REV. 0 2015-OCT-09 (Part No. 442940)
FM-200 Total Flood Fire APPENDIX A – FM-200 SYSTEM PROGRAM PRINTOUT
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 10-13
APPENDIX A – FM-200 SYSTEM PROGRAM PRINTOUT FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 10-14 REV. 0 2015-OCT-09 (Part No. 442940)
FM-200 Total Flood Fire APPENDIX A – FM-200 SYSTEM PROGRAM PRINTOUT
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 10-15
APPENDIX A – FM-200 SYSTEM PROGRAM PRINTOUT FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 10-16 REV. 0 2015-OCT-09 (Part No. 442940)
FM-200 Total Flood Fire APPENDIX A – FM-200 SYSTEM PROGRAM PRINTOUT
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 10-17
APPENDIX A – FM-200 SYSTEM PROGRAM PRINTOUT FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 10-18 REV. 0 2015-OCT-09 (Part No. 442940)
FM-200 Total Flood Fire APPENDIX A – FM-200 SYSTEM PROGRAM PRINTOUT
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 10-19
APPENDIX A – FM-200 SYSTEM PROGRAM PRINTOUT FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 10-20 REV. 0 2015-OCT-09 (Part No. 442940)
FM-200 Total Flood Fire APPENDIX A – FM-200 SYSTEM PROGRAM PRINTOUT
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 10-21
APPENDIX A – FM-200 SYSTEM PROGRAM PRINTOUT FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 10-22 REV. 0 2015-OCT-09 (Part No. 442940)
FM-200 Total Flood Fire APPENDIX A – FM-200 SYSTEM PROGRAM PRINTOUT
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 10-23
APPENDIX A – FM-200 SYSTEM PROGRAM PRINTOUT FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 10-24 REV. 0 2015-OCT-09 (Part No. 442940)
FM-200 Total Flood Fire APPENDIX A – FM-200 SYSTEM PROGRAM PRINTOUT
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 10-25
APPENDIX A – FM-200 SYSTEM PROGRAM PRINTOUT FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 10-26 REV. 0 2015-OCT-09 (Part No. 442940)
FM-200 Total Flood Fire APPENDIX A – FM-200 SYSTEM PROGRAM PRINTOUT
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 10-27
APPENDIX A – FM-200 SYSTEM PROGRAM PRINTOUT FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 10-28 REV. 0 2015-OCT-09 (Part No. 442940)
FM-200 Total Flood Fire APPENDIX A – FM-200 SYSTEM PROGRAM PRINTOUT
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 10-29
APPENDIX A – FM-200 SYSTEM PROGRAM PRINTOUT FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 10-30 REV. 0 2015-OCT-09 (Part No. 442940)
FM-200 Total Flood Fire APPENDIX A – FM-200 SYSTEM PROGRAM PRINTOUT
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 10-31
APPENDIX A – FM-200 SYSTEM PROGRAM PRINTOUT FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 10-32 REV. 0 2015-OCT-09 (Part No. 442940)
FM-200 Total Flood Fire APPENDIX A – FM-200 SYSTEM PROGRAM PRINTOUT
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 10-33
APPENDIX A – FM-200 SYSTEM PROGRAM PRINTOUT FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 10-34 REV. 0 2015-OCT-09 (Part No. 442940)
FM-200 Total Flood Fire APPENDIX A – FM-200 SYSTEM PROGRAM PRINTOUT
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 10-35
APPENDIX A – FM-200 SYSTEM PROGRAM PRINTOUT FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 10-36 REV. 0 2015-OCT-09 (Part No. 442940)
FM-200 Total Flood Fire APPENDIX A – FM-200 SYSTEM PROGRAM PRINTOUT
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 10-37
APPENDIX A – FM-200 SYSTEM PROGRAM PRINTOUT FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 10-38 REV. 0 2015-OCT-09 (Part No. 442940)
NOTES:
FM-200 Total Flood Fire APPENDIX B – SAFETY DATA SHEET
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 10-39
FM-200 FIRE
EXTINGUISHANT AGENT
SAFETY DATA SHEET
(SDS)
http://tycosds.thewercs.com/external/private/search.aspx?language=EN
Note: To find the SDS, enter the part number of a product containing agent.
APPENDIX B – SAFETY DATA SHEET FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 10-40 REV. 0 2015-OCT-09 (Part No. 442940)
1. Identification
2. Hazards Identification
Classification
OSHA Regulatory Status
This chemical is considered hazardous by the 2012 OSHA Hazard Communication Standard (29 CFR 1910.1200)
hazard statements
_____________________________________________________________________________________________
FM-200 Total Flood Fire APPENDIX B – SAFETY DATA SHEET
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 10-41
Precautionary Statements
Storage
Protect from sunlight. Store in a well-ventilated place.
3. Composition/information on Ingredients
3.1. Mixture
The following component(s) in this product are considered hazardous under applicable OSHA(USA).
Skin contact In case of contact with liquefied gas, thaw frosted parts with lukewarm water. (Get medical
attention immediately if symptoms occur.).
Inhalation Immediate medical attention is required. IF INHALED: Remove victim to fresh air and keep
at rest in a position comfortable for breathing. Administer oxygen if breathing is difficult. If
breathing is irregular or stopped, administer artificial respiration.
Ingestion None under normal use conditions. (Get medical attention immediately if symptoms occur.).
4.2. Most Important Symptoms and Effects, Both Acute and Delayed
Symptoms Unconsciousness.
4.3. Indication of Any Immediate Medical Attention and Special Treatment Needed
Note to physicians Treat symptomatically.
5. Fire-fighting measures
Advice on safe handling Ensure adequate ventilation, especially in confined areas. Use personal protective
equipment as required. Use with local exhaust ventilation. Do not breathe
dust/fume/gas/mist/vapors/spray.
Storage Conditions Keep containers tightly closed in a dry, cool and well-ventilated place.
_____________________________________________________________________________________________
Eye/Face Protection Avoid contact with eyes. Tight sealing safety goggles.
Skin and Body Protection Wear protective gloves and protective clothing.
Respiratory Protection Use positive pressure airline respirator with escape cylinder or self-contained breathing
apparatus for oxygen-deficient atmospheres (<19.5%).
Ventilation Use local exhaust ventilation to prevent accumulation of high concentrations and maintain
air-oxygen levels at or above 19.5%.
_____________________________________________________________________________________________
10.2. Reactivity
No data available
None known.
None known.
None known.
INHALATION In high concentration the gas may cause a suffocation. Victim may not be aware of
asphyxiation. In confined or poorly ventilated areas, vapors can readily accumulate and can
cause unconsciousness and death.
Acute Toxicity
11.3. Delayed and immediate effects as well as chronic effects from short and long-term exposure
sensitization No information available.
Germ Cell Mutagenicity No information available
carcinogenicity This product does not contain any carcinogens or potential carcinogens as listed by OSHA,
IARC or NTP.
Reproductive Toxicity Lack of oxygen during pregnancy has produced developmental abnormalities in humans
and experimental animals.
STOT - Single Exposure No information available.
STOT - Repeated Exposure No information available.
Target organ effects Respiratory System.
Aspiration Hazard No information available.
_____________________________________________________________________________________________
12.1. ecotoxicity
Not classified
12.3. Bioaccumulation
No information available.
DOT
UN/ID no UN3296
Description UN3296, Heptafluoropropane, 2.2
Proper Shipping Name Heptafluoropropane
Hazard class 2.2
Special Provisions T50
Emergency Response Guide 126
Number
TDG
UN/ID no UN3296
Description UN3296, Heptafluoropropane, 2.2
Proper Shipping Name Heptafluoropropane
Hazard class 2.2
MEX
_____________________________________________________________________________________________
UN/ID no UN3296
Description UN3296, Heptafluoropropane, 2.2
Proper Shipping Name Heptafluoropropane
Hazard class 2.2
ICAO (air)
UN/ID no UN3296
Description UN3296, Heptafluoropropane, 2.2
Proper Shipping Name Heptafluoropropane
Hazard class 2.2
IATA
UN/ID no UN3296
Description UN3296, Heptafluoropropane, 2.2
Proper Shipping Name Heptafluoropropane
Hazard class 2.2
ERG Code 2L
IMDG
UN/ID no UN3296
Description UN3296, Heptafluoropropane, 2.2
Proper Shipping Name Heptafluoropropane
Hazard class 2.2
EmS-No F-C, S-V
Legend:
TSCA - United States Toxic Substances Control Act Section 8(b) Inventory
DSL/NDSL - Canadian Domestic Substances List/Non-Domestic Substances List
ENCS - Japan Existing and New Chemical Substances
IECSC - China Inventory of Existing Chemical Substances
KECL - Korean Existing and Evaluated Chemical Substances
PICCS - Philippines Inventory of Chemicals and Chemical Substances
AICS - Australian Inventory of Chemical Substances
Reactive Hazard No
CERCLA
This material, as supplied, does not contain any substances regulated as hazardous substances under the Comprehensive
Environmental Response Compensation and Liability Act (CERCLA) (40 CFR 302) or the Superfund Amendments and
Reauthorization Act (SARA) (40 CFR 355). There may be specific reporting requirements at the local, regional, or state level
pertaining to releases of this material
This product does not contain any substances regulated by state right-to-know regulations
_____________________________________________________________________________________________
NOTES:
FM-200 Total Flood Fire APPENDIX C – LIQUID LEVEL INDICATOR (LLI) TABLES
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 10-49
19.5
20 50.8 50.6 50.3
20.5 51.6 51.4 51.1 50.6 50.1
21 52.5 52.2 52.0 51.5 50.9 50.6 50.3
21.5 53.3 53.1 52.8 52.3 51.7 51.4 51.0 50.7 50.3
22 54.2 53.9 53.6 53.1 52.6 52.2 51.8 51.4 51.0 50.3
22.5 55.1 54.8 54.5 53.9 53.4 53.0 52.6 52.2 51.8 51.0
23 55.9 55.6 55.3 54.7 54.2 53.8 53.4 53.0 52.5 51.8
23.5 56.8 56.4 56.1 55.5 55.0 54.5 54.2 53.7 53.2 52.5
24 57.6 57.3 56.9 56.4 55.8 55.3 54.9 54.5 54.0 53.2 50.8
24.5 58.5 58.1 57.8 57.2 56.6 56.1 55.7 55.2 54.7 53.9 51.5
25 59.3 59.0 58.6 58.0 57.4 56.9 56.5 56.0 55.5 54.6 52.2
25.5 60.2 59.8 59.4 58.8 58.2 57.7 57.3 56.8 56.2 55.4 52.9
26 61.0 60.6 60.3 59.6 59.0 58.5 58.1 57.5 56.9 56.1 53.7
26.5 61.9 61.5 61.1 60.5 59.8 59.3 58.8 58.3 57.7 56.8 54.4
27 62.7 62.3 61.9 61.3 60.6 60.1 59.6 59.0 58.4 57.5 55.1
27.5 63.6 63.2 62.7 62.1 61.5 60.9 60.4 59.8 59.1 58.3 55.8
28 64.4 64.0 63.6 62.9 62.3 61.7 61.2 60.6 59.9 59.0 56.5
28.5 65.3 64.8 64.4 63.7 63.1 62.5 62.0 61.3 60.6 59.7 57.2
29 66.1 65.7 65.2 64.6 63.9 63.3 62.7 62.1 61.4 60.4 57.9
29.5 67.0 66.5 66.1 65.4 64.7 64.1 63.5 62.9 62.1 61.2 58.6
30 67.8 67.4 66.9 66.2 65.5 64.9 64.3 63.6 62.8 61.9 59.3
30.5 68.7 68.2 67.7 67.0 66.3 65.7 65.1 64.4 63.6 62.6 60.0
31 69.5 69.0 68.5 67.8 67.1 66.5 65.9 65.1 64.3 63.3 60.7
31.5 70.4 69.9 69.4 68.6 67.9 67.3 66.6 65.9 65.1 64.1 61.4
32 71.2 70.7 70.2 69.5 68.7 68.1 67.4 66.7 65.8 64.8 62.1
32.5 72.1 71.6 71.0 70.3 69.5 68.9 68.2 67.4 66.5 65.5 62.8
33 73.0 72.4 71.9 71.1 70.4 69.7 69.0 68.2 67.3 66.2 63.5
33.5 73.8 73.2 72.7 71.9 71.2 70.5 69.8 68.9 68.0 67.0 64.2
34 74.7 74.1 73.5 72.7 72.0 71.3 70.5 69.7 68.7 67.7 65.0
34.5 75.5 74.9 74.3 73.6 72.8 72.0 71.3 70.5 69.5 68.4 65.7
35 76.4 75.8 75.2 74.4 73.6 72.8 72.1 71.2 70.2 69.1 66.4
35.5 77.2 76.6 76.0 75.2 74.4 73.6 72.9 72.0 71.0 69.8 67.1
36 78.1 77.4 76.8 76.0 75.2 74.4 73.7 72.8 71.7 70.6 67.8
36.5 78.9 78.3 77.6 76.8 76.0 75.2 74.5 73.5 72.4 71.3 68.5
37 79.8 79.1 78.5 77.6 76.8 76.0 75.2 74.3 73.2 72.0 69.2
37.5 80.6 80.0 79.3 78.5 77.6 76.8 76.0 75.0 73.9 72.7 69.9
38 81.5 80.8 80.1 79.3 78.4 77.6 76.8 75.8 74.7 73.5 70.6
38.5 82.3 81.6 80.9 80.1 79.2 78.4 77.6 76.6 75.4 74.2 71.3
39 83.1 82.4 81.7 80.9 80.1 79.2 78.4 77.3 76.1 74.9 72.0
39.5 84.0 83.2 82.5 81.7 80.8 80.0 79.1 78.1 76.9 75.6 72.7
40 84.8 84.1 83.3 82.5 81.6 80.8 79.9 78.8 77.6 76.4 73.4
40.5 85.6 84.9 84.1 83.3 82.4 81.6 80.7 79.6 78.4 77.1 74.1
41 86.5 85.7 84.9 84.1 83.2 82.3 81.5 80.4 79.1 77.8 74.8
41.5 87.3 86.5 85.7 84.9 84.0 83.1 82.2 81.1 79.8 78.5 75.5
42 88.1 87.3 86.5 85.6 84.8 83.9 83.0 81.9 80.6 79.3 76.3
FM-200 Total Flood Fire APPENDIX C – LIQUID LEVEL INDICATOR (LLI) TABLES
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 10-51
42.5 89.0 88.1 87.3 86.4 85.6 84.7 83.8 82.6 81.3 80.0 77.0
43 89.8 89.0 88.1 87.2 86.4 85.5 84.5 83.4 82.0 80.7 77.7
43.5 90.6 89.8 88.9 88.0 87.1 86.2 85.3 84.1 82.8 81.4 78.4
44 91.5 90.6 89.7 88.8 87.9 87.0 86.1 84.9 83.5 82.1 79.1
44.5 92.3 91.4 90.5 89.6 88.7 87.8 86.9 85.6 84.2 82.9 79.9
45 93.2 92.2 91.3 90.4 89.5 88.6 87.6 86.4 85.0 83.6 80.6
45.5 94.0 93.0 92.1 91.2 90.3 89.4 88.4 87.2 85.7 84.3 81.3
46 94.8 93.9 92.9 92.0 91.1 90.1 89.2 87.9 86.4 85.0 82.0
46.5 95.7 94.7 93.7 92.8 91.9 90.9 89.9 88.7 87.1 85.7 82.8
47 96.5 95.5 94.5 93.6 92.7 91.7 90.7 89.4 87.9 86.5 83.5
47.5 97.3 96.3 95.3 94.4 93.4 92.5 91.5 90.2 88.6 87.2 84.2
48 98.2 97.1 96.1 95.1 94.2 93.3 92.3 90.9 89.3 87.9 84.9
48.5 99.0 97.9 96.9 95.9 95.0 94.0 93.0 91.7 90.1 88.6 85.7
49 99.8 98.8 97.7 96.7 95.8 94.8 93.8 92.4 90.8 89.4 86.4
49.5 100.7 99.6 98.5 97.5 96.6 95.6 94.6 93.2 91.5 90.1 87.1
50 101.5 100.4 99.3 98.3 97.4 96.4 95.3 93.9 92.3 90.8 87.9
50.5 102.4 101.2 100.1 99.1 98.2 97.1 96.1 94.7 93.0 91.5 88.6
51 103.2 102.0 100.8 99.9 99.0 97.9 96.9 95.5 93.7 92.2 89.3
51.5 104.0 102.8 101.6 100.7 99.7 98.7 97.7 96.2 94.5 93.0 90.0
52 104.9 103.7 102.4 101.5 100.5 99.5 98.4 97.0 95.2 93.7 90.8
52.5 105.7 104.5 103.2 102.3 101.3 100.3 99.2 97.7 95.9 94.4 91.5
53 106.5 105.3 104.0 103.1 102.1 101.0 100.0 98.5 96.6 95.1 92.2
53.5 107.4 106.1 104.8 103.9 102.9 101.8 100.7 99.2 97.4 95.8 93.0
54 108.2 106.9 105.6 104.7 103.7 102.6 101.5 100.0 98.1 96.6 93.7
54.5 109.0 107.7 106.4 105.4 104.5 103.4 102.3 100.7 98.8 97.3 94.4
55 109.9 108.5 107.2 106.2 105.2 104.2 103.1 101.5 99.6 98.0 95.1
55.5 110.7 109.4 108.0 107.0 106.0 104.9 103.8 102.2 100.3 98.7 95.9
56 111.5 110.2 108.8 107.8 106.8 105.7 104.6 103.0 101.0 99.5 96.6
56.5 106.5 105.4 103.8 101.8 100.2 97.3
57 107.3 106.1 104.5 102.5 100.9 98.1
57.5 106.9 105.3 103.2 101.6 98.8
58 106.0 104.0 102.3 99.5
58.5 106.8 104.7 103.1 100.2
59 105.4 103.8 101.0
59.5 106.2 104.5 101.7
60 106.9 105.2 102.4
60.5 106.0 103.1
61 106.7 103.9
61.5 107.4 104.6
62 105.3
62.5 106.1
63 106.8
APPENDIX C – LIQUID LEVEL INDICATOR (LLI) TABLES FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 10-52 REV. 0 2015-OCT-09 (Part No. 442940)
26
26.5 70.8 70.6 70.4 69.8
27 71.7 71.5 71.3 70.7 70.1 69.6
27.5 72.6 72.4 72.1 71.5 70.9 70.5 70.0
28 73.5 73.3 73.0 72.4 71.8 71.3 70.8 70.1
28.5 74.4 74.1 73.9 73.2 72.6 72.1 71.6 70.9 69.9
29 75.3 75.0 74.7 74.1 73.5 72.9 72.4 71.6 70.7
29.5 76.2 75.9 75.6 74.9 74.3 73.7 73.2 72.4 71.5 69.8
30 77.1 76.8 76.5 75.8 75.1 74.6 74.0 73.2 72.2 70.6
30.5 78.0 77.7 77.3 76.6 76.0 75.4 74.8 74.0 73.0 71.4
31 78.9 78.6 78.2 77.5 76.8 76.2 75.6 74.8 73.8 72.1
31.5 79.8 79.4 79.1 78.4 77.6 77.0 76.4 75.6 74.6 72.9
32 80.7 80.3 79.9 79.2 78.5 77.8 77.2 76.3 75.3 73.7
32.5 81.6 81.2 80.8 80.1 79.3 78.6 78.0 77.1 76.1 74.4
33 82.5 82.1 81.7 80.9 80.2 79.5 78.8 77.9 76.9 75.2 70.0
33.5 83.4 83.0 82.5 81.8 81.0 80.3 79.6 78.7 77.6 76.0 70.8
34 84.3 83.8 83.4 82.6 81.8 81.1 80.4 79.5 78.4 76.7 71.6
34.5 85.2 84.7 84.3 83.5 82.7 81.9 81.2 80.3 79.2 77.5 72.4
35 86.1 85.6 85.1 84.3 83.5 82.7 82.0 81.0 80.0 78.3 73.1
35.5 87.0 86.5 86.0 85.2 84.3 83.6 82.8 81.8 80.7 79.0 73.9
36 87.9 87.4 86.9 86.0 85.2 84.4 83.6 82.6 81.5 79.8 74.7
36.5 88.8 88.3 87.7 86.9 86.0 85.2 84.4 83.4 82.3 80.6 75.5
37 89.7 89.1 88.6 87.7 86.9 86.0 85.2 84.2 83.0 81.3 76.2
37.5 90.6 90.0 89.5 88.6 87.7 86.8 86.0 85.0 83.8 82.1 77.0
38 91.5 90.9 90.3 89.4 88.5 87.6 86.8 85.7 84.6 82.9 77.8
38.5 92.4 91.8 91.2 90.3 89.4 88.5 87.6 86.5 85.3 83.6 78.6
39 93.3 92.7 92.1 91.1 90.2 89.3 88.4 87.3 86.1 84.4 79.3
39.5 94.2 93.6 92.9 92.0 91.0 90.1 89.2 88.1 86.9 85.2 80.1
40 95.1 94.4 93.8 92.8 91.9 90.9 90.0 88.9 87.7 85.9 80.9
40.5 96.0 95.3 94.7 93.7 92.7 91.7 90.8 89.7 88.4 86.7 81.7
41 96.9 96.2 95.5 94.5 93.5 92.6 91.6 90.4 89.2 87.5 82.4
41.5 97.8 97.1 96.4 95.4 94.4 93.4 92.4 91.2 90.0 88.2 83.2
42 98.7 98.0 97.3 96.3 95.2 94.2 93.2 92.0 90.7 89.0 84.0
42.5 99.6 98.9 98.1 97.1 96.1 95.0 94.0 92.8 91.5 89.8 84.8
43 100.4 99.7 99.0 98.0 96.9 95.8 94.8 93.6 92.3 90.5 85.5
43.5 101.3 100.6 99.9 98.8 97.7 96.6 95.6 94.4 93.1 91.3 86.3
44 102.2 101.5 100.8 99.7 98.6 97.5 96.4 95.1 93.8 92.1 87.1
44.5 103.1 102.4 101.6 100.5 99.4 98.3 97.2 95.9 94.6 92.8 87.9
45 104.0 103.3 102.5 101.4 100.2 99.1 98.0 96.7 95.4 93.6 88.6
45.5 104.9 104.1 103.4 102.2 101.1 99.9 98.8 97.5 96.1 94.4 89.4
46 105.8 105.0 104.2 103.1 101.9 100.7 99.5 98.3 96.9 95.1 90.2
46.5 106.7 105.9 105.1 103.9 102.8 101.6 100.3 99.0 97.7 95.9 91.0
47 107.6 106.8 106.0 104.8 103.6 102.4 101.1 99.8 98.4 96.7 91.7
47.5 108.5 107.7 106.8 105.6 104.4 103.2 101.9 100.6 99.2 97.4 92.5
48 109.4 108.6 107.7 106.5 105.3 104.0 102.7 101.4 100.0 98.2 93.3
48.5 110.3 109.4 108.6 107.3 106.1 104.8 103.5 102.2 100.8 99.0 94.1
FM-200 Total Flood Fire APPENDIX C – LIQUID LEVEL INDICATOR (LLI) TABLES
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 10-53
49 111.2 110.3 109.4 108.2 106.9 105.6 104.3 103.0 101.5 99.7 94.8
49.5 112.1 111.2 110.3 109.0 107.8 106.5 105.1 103.7 102.3 100.5 95.6
50 112.9 112.0 111.1 109.9 108.6 107.3 105.9 104.5 103.1 101.3 96.4
50.5 113.7 112.8 111.9 110.7 109.4 108.1 106.7 105.3 103.8 102.0 97.2
51 114.6 113.7 112.8 111.5 110.3 108.9 107.5 106.1 104.6 102.8 97.9
51.5 115.4 114.5 113.6 112.3 111.1 109.7 108.3 106.9 105.4 103.6 98.7
52 116.3 115.3 114.4 113.1 111.9 110.5 109.1 107.7 106.2 104.3 99.5
52.5 117.1 116.1 115.2 113.9 112.7 111.3 109.9 108.4 106.9 105.1 100.3
53 118.0 117.0 116.0 114.7 113.5 112.1 110.7 109.2 107.7 105.9 101.0
53.5 118.8 117.8 116.8 115.5 114.3 112.9 111.5 110.0 108.5 106.6 101.8
54 119.7 118.6 117.6 116.3 115.1 113.7 112.3 110.8 109.2 107.4 102.6
54.5 120.5 119.5 118.4 117.1 115.8 114.4 113.0 111.5 110.0 108.2 103.3
55 121.4 120.3 119.2 117.9 116.6 115.2 113.8 112.3 110.8 108.9 104.1
55.5 122.2 121.1 120.0 118.7 117.4 116.0 114.5 113.1 111.5 109.7 104.9
56 123.1 121.9 120.8 119.5 118.2 116.8 115.3 113.8 112.3 110.4 105.7
56.5 123.9 122.8 121.6 120.3 119.0 117.6 116.1 114.6 113.0 111.2 106.5
57 124.7 123.6 122.4 121.1 119.8 118.3 116.8 115.3 113.7 111.9 107.3
57.5 125.6 124.4 123.2 121.9 120.6 119.1 117.6 116.1 114.5 112.7 108.1
58 126.4 125.2 124.0 122.7 121.4 119.9 118.4 116.8 115.2 113.4 108.9
58.5 127.3 126.1 124.8 123.5 122.1 120.7 119.1 117.6 115.9 114.1 109.6
59 128.1 126.9 125.6 124.3 122.9 121.4 119.9 118.3 116.7 114.9 110.4
59.5 129.0 127.7 126.4 125.1 123.7 122.2 120.7 119.1 117.4 115.6 111.1
60 129.8 128.5 127.2 125.9 124.5 123.0 121.4 119.8 118.1 116.3 111.9
60.5 130.7 129.4 128.0 126.7 125.3 123.8 122.2 120.6 118.9 117.1 112.6
61 131.5 130.2 128.8 127.5 126.1 124.5 122.9 121.3 119.6 117.8 113.4
61.5 132.4 131.0 129.7 128.3 126.9 125.3 123.7 122.1 120.3 118.5 114.2
62 133.2 131.8 130.5 129.1 127.7 126.1 124.5 122.8 121.1 119.3 114.9
62.5 134.1 132.7 131.3 129.9 128.5 126.9 125.2 123.6 121.8 120.0 115.7
63 134.9 133.5 132.1 130.7 129.2 127.7 126.0 124.3 122.6 120.7 116.4
63.5 135.7 134.3 132.9 131.5 130.0 128.4 126.8 125.1 123.3 121.5 117.2
64 136.6 135.1 133.7 132.2 130.8 129.2 127.5 125.8 124.0 122.2 117.9
64.5 137.4 136.0 134.5 133.0 131.6 130.0 128.3 126.6 124.8 122.9 118.7
65 138.3 136.8 135.3 133.8 132.4 130.8 129.1 127.3 125.5 123.7 119.4
65.5 139.1 137.6 136.1 134.6 133.2 131.5 129.8 128.1 126.2 124.4 120.2
66 140.0 138.4 136.9 135.4 134.0 132.3 130.6 128.8 127.0 125.1 120.9
66.5 140.8 139.3 137.7 136.2 134.8 133.1 131.4 129.6 127.7 125.9 121.7
67 141.7 140.1 138.5 137.0 135.6 133.9 132.1 130.3 128.4 126.6 122.4
67.5 142.5 140.9 139.3 137.8 136.3 134.6 132.9 131.1 129.2 127.3 123.2
68 143.4 141.7 140.1 138.6 137.1 135.4 133.6 131.8 129.9 128.1 123.9
68.5 144.2 142.6 140.9 139.4 137.9 136.2 134.4 132.6 130.6 128.8 124.7
69 145.1 143.4 141.7 140.2 138.7 137.0 135.2 133.3 131.4 129.5 125.4
69.5 145.9 144.2 142.5 141.0 139.5 137.7 135.9 134.1 132.1 130.3 126.2
70 146.8 145.0 143.3 141.8 140.3 138.5 136.7 134.8 132.8 131.0 126.9
70.5 147.6 145.9 144.1 142.6 141.1 139.3 137.5 135.6 133.6 131.7 127.7
71 148.4 146.7 144.9 143.4 141.9 140.1 138.2 136.3 134.3 132.5 128.4
71.5 149.3 147.5 145.8 144.2 142.6 140.9 139.0 137.1 135.1 133.2 129.2
APPENDIX C – LIQUID LEVEL INDICATOR (LLI) TABLES FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 10-54 REV. 0 2015-OCT-09 (Part No. 442940)
72 150.1 148.3 146.6 145.0 143.4 141.6 139.8 137.8 135.8 133.9 129.9
72.5 151.0 149.2 147.4 145.8 144.2 142.4 140.5 138.6 136.5 134.7 130.7
73 151.8 150.0 148.2 146.6 145.0 143.2 141.3 139.3 137.3 135.4 131.4
73.5 152.7 150.8 149.0 147.4 145.8 144.0 142.0 140.1 138.0 136.1 132.2
74 153.5 151.6 149.8 148.2 146.6 144.7 142.8 140.8 138.7 136.9 132.9
74.5 154.4 152.5 150.6 149.0 147.4 145.5 143.6 141.6 139.5 137.6 133.7
75 146.3 144.3 142.3 140.2 138.3 134.4
75.5 147.1 145.1 143.1 140.9 139.1 135.2
76 147.8 145.9 143.8 141.7 139.8 135.9
76.5 146.6 144.6 142.4 140.5 136.7
77 147.4 145.3 143.1 141.3 137.4
77.5 146.1 143.9 142.0 138.2
78 146.8 144.6 142.7 138.9
78.5 147.6 145.3 143.5 139.7
79 146.1 144.2 140.4
79.5 146.8 144.9 141.2
80 147.6 145.7 141.9
80.5 146.4 142.7
81 147.1 143.5
81.5 147.8 144.2
82 145.0
82.5 145.7
83 146.5
83.5 147.2
FM-200 Total Flood Fire APPENDIX C – LIQUID LEVEL INDICATOR (LLI) TABLES
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 10-55
6
6.5 86.5
7 87.4 86.9 86.3
7.5 88.3 87.8 87.2 86.6
8 89.2 88.6 88.0 87.5 86.9 86.6 86.4
8.5 90.1 89.5 88.9 88.4 87.8 87.5 87.2 86.2
9 91.0 90.4 89.8 89.2 88.6 88.3 88.0 87.0
9.5 91.9 91.3 90.7 90.1 89.5 89.1 88.8 87.8
10 92.9 92.2 91.5 90.9 90.3 90.0 89.6 88.6 86.9
10.5 93.8 93.1 92.4 91.8 91.2 90.8 90.4 89.4 87.7
11 94.7 94.0 93.3 92.7 92.0 91.6 91.3 90.2 88.5 86.5
11.5 95.6 94.9 94.2 93.5 92.9 92.5 92.1 90.9 89.2 87.3
12 96.5 95.7 95.0 94.4 93.7 93.3 92.9 91.7 90.0 88.1
12.5 97.4 96.6 95.9 95.3 94.6 94.1 93.7 92.5 90.8 88.8
13 98.3 97.5 96.8 96.1 95.5 94.9 94.5 93.3 91.6 89.6
13.5 99.2 98.4 97.7 97.0 96.3 95.8 95.3 94.1 92.4 90.4
14 100.1 99.3 98.5 97.8 97.2 96.6 96.1 94.9 93.1 91.1
14.5 101.0 100.2 99.4 98.7 98.0 97.4 96.9 95.7 93.9 91.9 86.8
15 101.9 101.1 100.3 99.6 98.9 98.3 97.7 96.5 94.7 92.7 87.5
15.5 102.8 102.0 101.2 100.4 99.7 99.1 98.5 97.3 95.5 93.4 88.2
16 103.7 102.9 102.0 101.3 100.6 99.9 99.4 98.1 96.3 94.2 89.0
16.5 104.6 103.7 102.9 102.2 101.4 100.8 100.2 98.9 97.0 95.0 89.7
17 105.5 104.6 103.8 103.0 102.3 101.6 101.0 99.7 97.8 95.7 90.5
17.5 106.4 105.5 104.7 103.9 103.1 102.4 101.8 100.5 98.6 96.5 91.2
18 107.3 106.4 105.5 104.7 104.0 103.3 102.6 101.3 99.4 97.3 91.9
18.5 108.2 107.3 106.4 105.6 104.8 104.1 103.4 102.1 100.2 98.0 92.7
19 109.1 108.2 107.3 106.5 105.7 104.9 104.2 102.8 100.9 98.8 93.4
19.5 110.0 109.1 108.2 107.3 106.5 105.8 105.0 103.6 101.7 99.6 94.2
20 110.9 110.0 109.0 108.2 107.4 106.6 105.8 104.4 102.5 100.4 94.9
20.5 111.8 110.8 109.9 109.1 108.2 107.4 106.6 105.2 103.3 101.1 95.6
21 112.7 111.7 110.8 109.9 109.1 108.3 107.5 106.0 104.1 101.9 96.4
21.5 113.6 112.6 111.6 110.8 109.9 109.1 108.3 106.8 104.9 102.7 97.1
22 114.5 113.5 112.5 111.6 110.8 109.9 109.1 107.6 105.6 103.4 97.8
22.5 115.4 114.4 113.4 112.5 111.6 110.7 109.9 108.4 106.4 104.2 98.6
23 116.3 115.3 114.3 113.4 112.5 111.6 110.7 109.2 107.2 105.0 99.3
23.5 117.2 116.2 115.1 114.2 113.3 112.4 111.5 110.0 108.0 105.7 100.1
24 118.1 117.1 116.0 115.1 114.2 113.2 112.3 110.8 108.8 106.5 100.8
24.5 119.0 117.9 116.9 116.0 115.0 114.1 113.1 111.6 109.5 107.3 101.5
25 119.9 118.8 117.8 116.8 115.9 114.9 113.9 112.4 110.3 108.0 102.3
25.5 120.8 119.7 118.6 117.7 116.7 115.7 114.7 113.2 111.1 108.8 103.0
26 121.7 120.6 119.5 118.5 117.6 116.6 115.6 114.0 111.9 109.6 103.8
26.5 122.6 121.5 120.4 119.4 118.4 117.4 116.4 114.7 112.7 110.3 104.5
27 123.5 122.4 121.3 120.3 119.3 118.2 117.2 115.5 113.4 111.1 105.2
27.5 124.4 123.3 122.1 121.1 120.1 119.1 118.0 116.3 114.2 111.9 106.0
28 125.3 124.2 123.0 122.0 121.0 119.9 118.8 117.1 115.0 112.6 106.7
28.5 126.2 125.0 123.9 122.8 121.8 120.7 119.6 117.9 115.8 113.4 107.4
APPENDIX C – LIQUID LEVEL INDICATOR (LLI) TABLES FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 10-56 REV. 0 2015-OCT-09 (Part No. 442940)
29 127.1 125.9 124.8 123.7 122.7 121.6 120.4 118.7 116.6 114.2 108.2
29.5 128.0 126.8 125.6 124.6 123.5 122.4 121.2 119.5 117.3 114.9 108.9
30 128.9 127.7 126.5 125.4 124.4 123.2 122.0 120.3 118.1 115.7 109.7
30.5 129.8 128.6 127.4 126.3 125.2 124.0 122.8 121.1 118.9 116.5 110.4
31 130.7 129.5 128.3 127.2 126.1 124.9 123.7 121.9 119.7 117.2 111.1
31.5 131.6 130.4 129.1 128.0 126.9 125.7 124.5 122.7 120.5 118.0 111.9
32 132.5 131.3 130.0 128.9 127.8 126.5 125.3 123.5 121.2 118.8 112.6
32.5 133.4 132.2 130.9 129.7 128.6 127.4 126.1 124.3 122.0 119.5 113.4
33 134.3 133.0 131.7 130.6 129.5 128.2 126.9 125.1 122.8 120.3 114.1
33.5 135.2 133.9 132.6 131.5 130.3 129.0 127.7 125.9 123.6 121.1 114.8
34 136.1 134.8 133.5 132.3 131.2 129.9 128.5 126.6 124.4 121.8 115.6
34.5 137.0 135.7 134.4 133.2 132.0 130.7 129.3 127.4 125.1 122.6 116.3
35 137.9 136.5 135.2 134.1 132.9 131.5 130.1 128.2 125.9 123.4 117.0
35.5 138.7 137.4 136.1 134.9 133.7 132.4 130.9 129.0 126.7 124.1 117.8
36 139.5 138.3 137.0 135.8 134.6 133.2 131.8 129.8 127.5 124.9 118.5
36.5 140.4 139.1 137.8 136.6 135.4 134.0 132.6 130.6 128.3 125.7 119.3
37 141.2 139.9 138.6 137.4 136.3 134.9 133.4 131.4 129.0 126.5 120.0
37.5 142.0 140.7 139.4 138.3 137.1 135.7 134.2 132.2 129.8 127.2 120.7
38 142.9 141.6 140.3 139.1 137.9 136.5 135.0 133.0 130.6 128.0 121.5
38.5 143.7 142.4 141.1 139.9 138.7 137.3 135.8 133.8 131.4 128.8 122.2
39 144.5 143.2 141.9 140.7 139.5 138.0 136.6 134.6 132.2 129.5 123.0
39.5 145.4 144.1 142.7 141.5 140.2 138.8 137.4 135.4 132.9 130.3 123.7
40 146.2 144.9 143.6 142.3 141.0 139.6 138.1 136.1 133.7 131.1 124.4
40.5 147.1 145.7 144.4 143.1 141.8 140.4 138.9 136.9 134.5 131.8 125.2
41 147.9 146.5 145.2 143.9 142.6 141.1 139.6 137.6 135.2 132.6 125.9
41.5 148.7 147.4 146.0 144.7 143.4 141.9 140.4 138.4 136.0 133.4 126.6
42 149.6 148.2 146.8 145.5 144.2 142.7 141.1 139.1 136.8 134.1 127.4
42.5 150.4 149.0 147.7 146.3 144.9 143.4 141.9 139.9 137.6 134.9 128.1
43 151.2 149.9 148.5 147.1 145.7 144.2 142.6 140.6 138.3 135.6 128.9
43.5 152.1 150.7 149.3 147.9 146.5 145.0 143.4 141.4 139.0 136.4 129.7
44 152.9 151.5 150.1 148.7 147.3 145.7 144.1 142.1 139.8 137.1 130.5
44.5 153.7 152.3 151.0 149.5 148.1 146.5 144.9 142.9 140.5 137.9 131.3
45 154.6 153.2 151.8 150.3 148.9 147.3 145.6 143.6 141.2 138.6 132.1
45.5 155.4 154.0 152.6 151.1 149.6 148.0 146.4 144.3 141.9 139.3 132.9
46 156.2 154.8 153.4 151.9 150.4 148.8 147.1 145.1 142.7 140.0 133.6
46.5 157.1 155.7 154.2 152.7 151.2 149.6 147.9 145.8 143.4 140.8 134.3
47 157.9 156.5 155.1 153.5 152.0 150.3 148.6 146.5 144.1 141.5 135.1
47.5 158.8 157.3 155.9 154.3 152.8 151.1 149.4 147.3 144.8 142.2 135.8
48 159.6 158.2 156.7 155.1 153.6 151.9 150.1 148.0 145.6 142.9 136.5
48.5 160.4 159.0 157.5 155.9 154.3 152.6 150.9 148.8 146.3 143.7 137.3
49 161.3 159.8 158.4 156.7 155.1 153.4 151.7 149.5 147.0 144.4 138.0
49.5 162.1 160.6 159.2 157.5 155.9 154.2 152.4 150.2 147.8 145.1 138.7
50 162.9 161.5 160.0 158.3 156.7 154.9 153.2 151.0 148.5 145.8 139.5
50.5 163.8 162.3 160.8 159.1 157.5 155.7 153.9 151.7 149.2 146.6 140.2
51 164.6 163.1 161.6 159.9 158.2 156.5 154.7 152.5 149.9 147.3 140.9
51.5 165.4 164.0 162.5 160.8 159.0 157.2 155.4 153.2 150.7 148.0 141.7
FM-200 Total Flood Fire APPENDIX C – LIQUID LEVEL INDICATOR (LLI) TABLES
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 10-57
52 166.3 164.8 163.3 161.6 159.8 158.0 156.2 153.9 151.4 148.7 142.4
52.5 167.1 165.6 164.1 162.4 160.6 158.8 156.9 154.7 152.1 149.5 143.1
53 168.0 166.4 164.9 163.2 161.4 159.5 157.7 155.4 152.8 150.2 143.9
53.5 168.8 167.3 165.8 164.0 162.2 160.3 158.4 156.1 153.6 150.9 144.6
54 169.6 168.1 166.6 164.8 162.9 161.1 159.2 156.9 154.3 151.6 145.3
54.5 170.5 168.9 167.4 165.6 163.7 161.8 159.9 157.6 155.0 152.4 146.1
55 171.3 169.8 168.2 166.4 164.5 162.6 160.7 158.4 155.8 153.1 146.8
55.5 172.1 170.6 169.0 167.2 165.3 163.4 161.4 159.1 156.5 153.8 147.5
56 173.0 171.4 169.9 168.0 166.1 164.1 162.2 159.8 157.2 154.5 148.3
56.5 173.8 172.2 170.7 168.8 166.9 164.9 162.9 160.6 157.9 155.3 149.0
57 174.6 173.1 171.5 169.6 167.6 165.7 163.7 161.3 158.7 156.0 149.7
57.5 175.5 173.9 172.3 170.4 168.4 166.4 164.4 162.1 159.4 156.7 150.5
58 176.3 174.7 173.2 171.2 169.2 167.2 165.2 162.8 160.1 157.4 151.2
58.5 177.1 175.6 174.0 172.0 170.0 168.0 165.9 163.5 160.9 158.2 151.9
59 178.0 176.4 174.8 172.8 170.8 168.7 166.7 164.3 161.6 158.9 152.7
59.5 178.8 177.2 175.6 173.6 171.6 169.5 167.4 165.0 162.3 159.6 153.4
60 179.7 178.1 176.4 174.4 172.3 170.3 168.2 165.8 163.0 160.3 154.1
60.5 180.5 178.9 177.3 175.2 173.1 171.0 168.9 166.5 163.8 161.1 154.9
61 181.3 179.7 178.1 176.0 173.9 171.8 169.7 167.2 164.5 161.8 155.6
61.5 182.2 180.5 178.9 176.8 174.7 172.6 170.4 168.0 165.2 162.5 156.4
62 183.0 181.4 179.7 177.6 175.5 173.3 171.2 168.7 165.9 163.2 157.1
62.5 183.8 182.2 180.6 178.4 176.3 174.1 171.9 169.4 166.7 164.0 157.8
63 184.7 183.0 181.4 179.2 177.0 174.9 172.7 170.2 167.4 164.7 158.6
63.5 185.5 183.9 182.2 180.0 177.8 175.6 173.4 170.9 168.1 165.4 159.3
64 186.3 184.7 183.0 180.8 178.6 176.4 174.2 171.7 168.9 166.1 160.0
64.5 187.2 185.5 183.8 181.6 179.4 177.2 174.9 172.4 169.6 166.9 160.8
65 188.0 186.3 184.7 182.4 180.2 177.9 175.7 173.1 170.3 167.6 161.5
65.5 188.9 187.2 185.5 183.2 181.0 178.7 176.5 173.9 171.0 168.3 162.2
66 189.7 188.0 186.3 184.0 181.7 179.5 177.2 174.6 171.8 169.0 163.0
66.5 190.5 188.8 187.1 184.8 182.5 180.2 178.0 175.4 172.5 169.8 163.7
67 181.0 178.7 176.1 173.2 170.5 164.4
67.5 181.8 179.5 176.8 173.9 171.2 165.2
68 182.5 180.2 177.6 174.7 171.9 165.9
68.5 181.0 178.3 175.4 172.7 166.6
69 181.7 179.0 176.1 173.4 167.4
69.5 182.5 179.8 176.9 174.1 168.1
70 180.5 177.6 174.8 168.8
70.5 181.3 178.3 175.6 169.6
71 182.0 179.0 176.3 170.3
71.5 182.7 179.8 177.0 171.0
72 180.5 177.7 171.8
72.5 181.2 178.5 172.5
73 182.0 179.2 173.2
73.5 182.7 179.9 174.0
74 180.6 174.7
74.5 181.4 175.4
APPENDIX C – LIQUID LEVEL INDICATOR (LLI) TABLES FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 10-58 REV. 0 2015-OCT-09 (Part No. 442940)
75 182.1 176.2
75.5 182.8 176.9
76 177.6
76.5 178.4
77 179.1
77.5 179.8
78 180.6
78.5 181.3
79 182.0
79.5 182.8
FM-200 Total Flood Fire APPENDIX C – LIQUID LEVEL INDICATOR (LLI) TABLES
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 10-59
15
15.5
16
16.5
17
17.5
18
18.5
19
19.5
20
20.5 165.2 164.2 163.3 162.3
21 167.2 166.2 165.2 164.2 163.2
21.5 169.3 168.2 167.1 166.1 165.0 162.5
22 171.3 170.2 169.1 168.0 166.9 164.3
22.5 173.3 172.2 171.0 169.9 168.7 166.2 163.2
23 175.3 174.1 173.0 171.8 170.6 168.0 165.0 162.0
23.5 177.3 176.1 174.9 173.7 172.5 169.9 166.8 163.8
24 179.3 178.1 176.8 175.6 174.3 171.7 168.7 165.6 162.6
24.5 181.4 180.1 178.8 177.5 176.2 173.5 170.5 167.4 164.4
25 183.4 182.1 180.7 179.4 178.1 175.4 172.3 169.3 166.2 163.1
25.5 185.4 184.0 182.7 181.3 179.9 177.2 174.1 171.1 168.0 164.9
26 187.4 186.0 184.6 183.2 181.8 179.1 176.0 172.9 169.8 166.7 163.6
26.5 189.4 188.0 186.5 185.1 183.6 180.9 177.8 174.7 171.6 168.4 165.3
27 191.5 190.0 188.5 187.0 185.5 182.7 179.6 176.5 173.3 170.2 167.1
27.5 193.5 192.0 190.4 188.9 187.4 184.6 181.4 178.3 175.1 172.0 168.8
28 195.5 193.9 192.4 190.8 189.2 186.4 183.3 180.1 176.9 173.8 170.6
28.5 197.5 195.9 194.3 192.7 191.1 188.3 185.1 181.9 178.7 175.5 172.3
29 199.5 197.9 196.2 194.6 193.0 190.1 186.9 183.7 180.5 177.3 174.1
29.5 201.6 199.9 198.2 196.5 194.8 191.9 188.7 185.5 182.3 179.1 175.8
30 203.6 201.9 200.1 198.4 196.7 193.8 190.5 187.3 184.1 180.8 177.6
30.5 205.6 203.8 202.1 200.3 198.5 195.6 192.4 189.1 185.9 182.6 179.3
31 207.6 205.8 204.0 202.2 200.4 197.5 194.2 190.9 187.6 184.4 181.1
31.5 209.6 207.8 206.0 204.1 202.3 199.3 196.0 192.7 189.4 186.1 182.9
32 211.7 209.8 207.9 206.0 204.1 201.1 197.8 194.5 191.2 187.9 184.6
32.5 213.7 211.8 209.8 207.9 206.0 203.0 199.7 196.3 193.0 189.7 186.4
33 215.7 213.7 211.8 209.8 207.9 204.8 201.5 198.1 194.8 191.5 188.1
33.5 217.7 215.7 213.7 211.7 209.7 206.7 203.3 199.9 196.6 193.2 189.9
34 219.7 217.7 215.7 213.6 211.6 208.5 205.1 201.7 198.4 195.0 191.6
34.5 221.8 219.7 217.6 215.5 213.4 210.3 206.9 203.6 200.2 196.8 193.4
35 223.8 221.7 219.5 217.4 215.3 212.2 208.8 205.4 201.9 198.5 195.1
35.5 225.8 223.6 221.5 219.3 217.2 214.0 210.6 207.2 203.7 200.3 196.9
36 227.8 225.6 223.4 221.2 219.0 215.9 212.4 209.0 205.5 202.1 198.6
36.5 229.8 227.6 225.4 223.1 220.9 217.7 214.2 210.8 207.3 203.8 200.4
37 231.8 229.6 227.3 225.0 222.8 219.5 216.1 212.6 209.1 205.6 202.1
37.5 233.9 231.6 229.2 226.9 224.6 221.4 217.9 214.4 210.9 207.4 203.9
APPENDIX C – LIQUID LEVEL INDICATOR (LLI) TABLES FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 10-60 REV. 0 2015-OCT-09 (Part No. 442940)
38 235.9 233.5 231.2 228.8 226.5 223.2 219.7 216.2 212.7 209.2 205.6
38.5 237.9 235.5 233.1 230.7 228.3 225.1 221.5 218.0 214.5 210.9 207.4
39 239.9 237.5 235.1 232.6 230.2 226.9 223.3 219.8 216.2 212.7 209.1
39.5 241.9 239.5 237.0 234.5 232.1 228.7 225.2 221.6 218.0 214.5 210.9
40 244.0 241.5 238.9 236.4 233.9 230.6 227.0 223.4 219.8 216.2 212.6
40.5 246.0 243.4 240.9 238.3 235.8 232.4 228.8 225.2 221.6 218.0 214.4
41 248.0 245.4 242.8 240.2 237.7 234.3 230.6 227.0 223.4 219.8 216.2
41.5 250.0 247.4 244.8 242.1 239.5 236.1 232.5 228.8 225.2 221.5 217.9
42 252.0 249.4 246.7 244.0 241.4 237.9 234.3 230.6 227.0 223.3 219.7
42.5 254.1 251.4 248.7 245.9 243.2 239.8 236.1 232.4 228.8 225.1 221.4
43 256.1 253.3 250.6 247.8 245.1 241.6 237.9 234.2 230.5 226.9 223.2
43.5 258.1 255.3 252.5 249.7 247.0 243.5 239.8 236.0 232.3 228.6 224.9
44 260.0 257.2 254.4 251.6 248.8 245.3 241.6 237.9 234.1 230.4 226.7
44.5 262.0 259.1 256.3 253.5 250.7 247.1 243.4 239.7 235.9 232.2 228.4
45 263.9 261.1 258.2 255.4 252.5 249.0 245.2 241.5 237.7 233.9 230.2
45.5 265.8 263.0 260.1 257.3 254.4 250.8 247.0 243.3 239.5 235.7 231.9
46 267.8 264.9 262.0 259.1 256.3 252.7 248.9 245.1 241.3 237.5 233.7
46.5 269.7 266.8 263.9 261.0 258.1 254.5 250.7 246.9 243.1 239.2 235.4
47 271.6 268.7 265.8 262.9 259.9 256.3 252.5 248.7 244.8 241.0 237.2
47.5 273.6 270.6 267.7 264.7 261.7 258.1 254.3 250.4 246.6 242.8 238.9
48 275.5 272.5 269.5 266.5 263.6 259.9 256.1 252.2 248.4 244.5 240.7
48.5 277.4 274.4 271.4 268.4 265.4 261.7 257.9 254.0 250.2 246.3 242.5
49 279.4 276.3 273.3 270.2 267.2 263.5 259.6 255.8 251.9 248.1 244.2
49.5 281.3 278.2 275.1 272.1 269.0 265.3 261.4 257.6 253.7 249.8 246.0
50 283.2 280.1 277.0 273.9 270.8 267.1 263.2 259.3 255.5 251.6 247.7
50.5 285.2 282.0 278.9 275.7 272.6 268.9 265.0 261.1 257.2 253.4 249.5
51 287.1 283.9 280.8 277.6 274.4 270.7 266.8 262.9 259.0 255.1 251.2
51.5 289.0 285.8 282.6 279.4 276.2 272.5 268.6 264.7 260.8 256.9 253.0
52 291.0 287.7 284.5 281.3 278.0 274.3 270.4 266.5 262.6 258.6 254.7
52.5 292.9 289.6 286.4 283.1 279.8 276.1 272.2 268.2 264.3 260.4 256.5
53 294.8 291.5 288.2 285.0 281.7 277.9 273.9 270.0 266.0 262.1 258.1
53.5 296.8 293.4 290.1 286.8 283.5 279.6 275.6 271.6 267.6 263.6 259.6
54 298.7 295.3 292.0 288.6 285.3 281.4 277.3 273.3 269.2 265.2 261.1
54.5 300.6 297.2 293.9 290.5 287.1 283.1 279.0 274.9 270.8 266.7 262.6
55 302.6 299.1 295.7 292.3 288.9 284.9 280.8 276.6 272.4 268.3 264.1
55.5 304.5 301.0 297.6 294.2 290.7 286.7 282.5 278.3 274.1 269.9 265.7
56 306.4 302.9 299.5 296.0 292.5 288.4 284.2 279.9 275.7 271.4 267.2
56.5 308.4 304.8 301.3 297.8 294.3 290.2 285.9 281.6 277.3 273.0 268.7
57 310.3 306.8 303.2 299.7 296.1 292.0 287.6 283.2 278.9 274.5 270.2
57.5 312.2 308.7 305.1 301.5 297.9 293.7 289.3 284.9 280.5 276.1 271.7
58 314.2 310.6 307.0 303.4 299.8 295.5 291.0 286.6 282.1 277.7 273.2
58.5 316.1 312.5 308.8 305.2 301.6 297.3 292.7 288.2 283.7 279.2 274.7
59 318.0 314.4 310.7 307.0 303.4 299.0 294.5 289.9 285.3 280.8 276.2
59.5 320.0 316.3 312.6 308.9 305.2 300.8 296.2 291.6 286.9 282.3 277.7
60 321.9 318.2 314.4 310.7 307.0 302.5 297.9 293.2 288.6 283.9 279.2
60.5 323.8 320.1 316.3 312.6 308.8 304.3 299.6 294.9 290.2 285.5 280.7
FM-200 Total Flood Fire APPENDIX C – LIQUID LEVEL INDICATOR (LLI) TABLES
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 10-61
61 325.8 322.0 318.2 314.4 310.6 306.1 301.3 296.5 291.8 287.0 282.2
61.5 327.7 323.9 320.1 316.2 312.4 307.8 303.0 298.2 293.4 288.6 283.8
62 329.6 325.8 321.9 318.1 314.2 309.6 304.7 299.9 295.0 290.1 285.3
62.5 331.6 327.7 323.8 319.9 316.0 311.4 306.4 301.5 296.6 291.7 286.8
63 333.5 329.6 325.7 321.8 317.9 313.1 308.2 303.2 298.2 293.3 288.3
63.5 335.4 331.5 327.5 323.6 319.7 314.9 309.9 304.9 299.8 294.8 289.8
64 337.4 333.4 329.4 325.4 321.5 316.7 311.6 306.5 301.4 296.4 291.3
64.5 339.3 335.3 331.3 327.3 323.3 318.4 313.3 308.2 303.1 297.9 292.8
65 341.2 337.2 333.2 329.1 325.1 320.2 315.0 309.8 304.7 299.5 294.3
65.5 343.1 339.1 335.0 331.0 326.9 321.9 316.7 311.5 306.3 301.1 295.8
66 345.1 341.0 336.9 332.8 328.7 323.7 318.4 313.2 307.9 302.6 297.3
66.5 347.0 342.9 338.8 334.6 330.5 325.5 320.1 314.8 309.5 304.2 298.8
67 348.9 344.8 340.6 336.5 332.3 327.2 321.9 316.5 311.1 305.7 300.4
67.5 350.9 346.7 342.5 338.3 334.1 329.0 323.6 318.1 312.7 307.3 301.9
68 352.8 348.6 344.4 340.2 336.0 330.8 325.3 319.8 314.3 308.9 303.4
68.5 354.7 350.5 346.3 342.0 337.8 332.5 327.0 321.5 315.9 310.4 304.9
69 356.7 352.4 348.1 343.9 339.6 334.3 328.7 323.1 317.6 312.0 306.4
69.5 358.6 354.3 350.0 345.7 341.4 336.1 330.4 324.8 319.2 313.5 307.9
70 360.5 356.2 351.9 347.5 343.2 337.8 332.1 326.5 320.8 315.1 309.4
70.5 339.6 333.8 328.1 322.4 316.7 310.9
71 341.3 335.6 329.8 324.0 318.2 312.4
71.5 343.1 337.3 331.4 325.6 319.8 313.9
72 344.9 339.0 333.1 327.2 321.3 315.4
72.5 340.7 334.8 328.8 322.9 317.0
73 342.4 336.4 330.4 324.5 318.5
73.5 344.1 338.1 332.0 326.0 320.0
74 339.7 333.7 327.6 321.5
74.5 341.4 335.3 329.1 323.0
75 343.1 336.9 330.7 324.5
75.5 344.7 338.5 332.3 326.0
76 340.1 333.8 327.5
76.5 341.7 335.4 329.0
77 343.3 336.9 330.5
77.5 344.9 338.5 332.0
78 340.1 333.6
78.5 341.6 335.1
79 343.2 336.6
79.5 344.7 338.1
80 339.6
80.5 341.1
81 342.6
81.5 344.1
APPENDIX C – LIQUID LEVEL INDICATOR (LLI) TABLES FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 10-62 REV. 0 2015-OCT-09 (Part No. 442940)
7.5
7.75 110.9 110.4 109.8
8 113.2 112.8 112.2 110.9 109.7
8.25 115.6 115.1 114.5 113.2 112.0 111.2 110.4
8.5 118.0 117.5 116.8 115.5 114.2 113.4 112.5 111.7 110.8
8.75 120.4 119.8 119.1 117.8 116.5 115.6 114.7 113.8 112.9
9 122.8 122.2 121.4 120.1 118.7 117.8 116.9 115.9 114.9 112.0
9.25 125.1 124.5 123.7 122.4 121.0 120.0 119.0 118.0 116.9 114.0
9.5 127.5 126.9 126.1 124.6 123.2 122.2 121.2 120.1 119.0 116.0
9.75 129.9 129.2 128.4 126.9 125.5 124.4 123.4 122.2 121.0 118.0
10 132.3 131.6 130.7 129.2 127.7 126.6 125.5 124.3 123.0 120.0
10.25 134.7 133.9 133.0 131.5 130.0 128.9 127.7 126.4 125.1 122.0
10.5 137.1 136.3 135.3 133.8 132.3 131.1 129.9 128.5 127.1 124.0
10.75 139.4 138.6 137.6 136.1 134.5 133.3 132.0 130.6 129.1 126.0
11 141.8 141.0 140.0 138.4 136.8 135.5 134.2 132.7 131.2 128.0
11.25 144.2 143.3 142.3 140.6 139.0 137.7 136.4 134.8 133.2 130.0
11.5 146.6 145.7 144.6 142.9 141.3 139.9 138.5 136.9 135.3 132.0
11.75 149.0 148.1 146.9 145.2 143.5 142.1 140.7 139.0 137.3 134.1
12 151.4 150.4 149.2 147.5 145.8 144.3 142.9 141.1 139.3 136.1
12.25 153.7 152.8 151.5 149.8 148.0 146.5 145.0 143.2 141.4 138.1
12.5 156.1 155.1 153.8 152.1 150.3 148.7 147.2 145.3 143.4 140.1
12.75 158.5 157.5 156.2 154.4 152.6 151.0 149.4 147.4 145.4 142.1
13 160.9 159.8 158.5 156.6 154.8 153.2 151.5 149.5 147.5 144.1
13.25 163.3 162.2 160.8 158.9 157.1 155.4 153.7 151.6 149.5 146.1
13.5 165.7 164.5 163.1 161.2 159.3 157.6 155.9 153.7 151.5 148.1
13.75 168.0 166.9 165.4 163.5 161.6 159.8 158.0 155.8 153.6 150.1
14 170.4 169.2 167.7 165.8 163.8 162.0 160.2 157.9 155.6 152.1
14.25 172.8 171.6 170.1 168.1 166.1 164.2 162.4 160.0 157.6 154.1
14.5 175.2 173.9 172.4 170.4 168.3 166.4 164.5 162.1 159.7 156.1
14.75 177.6 176.3 174.7 172.6 170.6 168.6 166.7 164.2 161.7 158.1
15 179.9 178.6 177.0 174.9 172.9 170.9 168.9 166.3 163.7 160.1
15.25 182.2 180.9 179.2 177.2 175.1 173.1 171.0 168.4 165.8 162.1
15.5 184.6 183.2 181.5 179.4 177.4 175.3 173.2 170.5 167.8 164.2
15.75 186.9 185.5 183.7 181.6 179.6 177.5 175.4 172.6 169.8 166.2
16 189.3 187.8 185.9 183.8 181.8 179.6 177.5 174.7 171.9 168.2
16.25 191.6 190.1 188.2 186.1 184.0 181.8 179.7 176.8 173.9 170.2
16.5 194.0 192.4 190.4 188.3 186.2 184.0 181.8 178.9 175.9 172.2
16.75 196.3 194.7 192.6 190.5 188.4 186.2 184.0 181.0 178.0 174.2
17 198.6 197.0 194.8 192.7 190.6 188.3 186.1 183.0 180.0 176.2
17.25 201.0 199.2 197.1 194.9 192.8 190.5 188.3 185.1 182.0 178.2
17.5 203.3 201.5 199.3 197.1 195.0 192.7 190.4 187.2 184.0 180.2
17.75 205.7 203.8 201.5 199.3 197.2 194.9 192.6 189.3 186.0 182.3
18 208.0 206.1 203.8 201.6 199.4 197.0 194.7 191.4 188.1 184.3
18.25 210.4 208.4 206.0 203.8 201.6 199.2 196.8 193.5 190.1 186.3
18.5 212.7 210.7 208.2 206.0 203.8 201.4 199.0 195.5 192.1 188.4
18.75 215.0 213.0 210.5 208.2 206.0 203.6 201.1 197.6 194.1 190.4
FM-200 Total Flood Fire APPENDIX C – LIQUID LEVEL INDICATOR (LLI) TABLES
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 10-63
19 217.4 215.3 212.7 210.4 208.2 205.7 203.3 199.7 196.1 192.4
19.25 219.7 217.6 214.9 212.6 210.4 207.9 205.4 201.8 198.1 194.4
19.5 222.1 219.9 217.2 214.9 212.6 210.1 207.6 203.9 200.2 196.5
19.75 224.4 222.2 219.4 217.1 214.8 212.2 209.7 206.0 202.2 198.5
20 226.8 224.5 221.6 219.3 217.0 214.4 211.9 208.0 204.2 200.5
20.25 229.1 226.8 223.8 221.5 219.2 216.6 214.0 210.1 206.2 202.6
20.5 231.4 229.1 226.1 223.7 221.4 218.8 216.2 212.2 208.2 204.6
20.75 233.8 231.3 228.3 225.9 223.6 220.9 218.3 214.3 210.2 206.6
21 236.1 233.6 230.5 228.1 225.8 223.1 220.5 216.4 212.3 208.6
21.25 238.5 235.9 232.8 230.4 228.0 225.3 222.6 218.4 214.3 210.7
21.5 240.8 238.2 235.0 232.6 230.2 227.5 224.8 220.5 216.3 212.7
21.75 237.2 234.8 232.4 229.6 226.9 222.6 218.3 214.7
22 239.5 237.0 234.6 231.8 229.1 224.7 220.3 216.7
22.25 236.8 234.0 231.2 226.8 222.3 218.8
22.5 239.0 236.2 233.4 228.9 224.4 220.8
22.75 235.5 230.9 226.4 222.8
23 237.7 233.0 228.4 224.9
23.25 239.8 235.1 230.4 226.9
23.5 242.0 237.2 232.4 228.9
23.75 234.4 230.9
24 236.5 233.0
24.25 235.0
24.5 237.0
APPENDIX C – LIQUID LEVEL INDICATOR (LLI) TABLES FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 10-64 REV. 0 2015-OCT-09 (Part No. 442940)
10
10.25 154.2 153.8 153.3
10.5 156.7 156.3 155.8 154.4 153.0
10.75 159.2 158.7 158.2 156.7 155.3 154.2 153.0
11 161.7 161.2 160.6 159.1 157.6 156.4 155.2 153.2 151.2
11.25 164.2 163.7 163.0 161.5 159.9 158.7 157.4 155.4 153.4
11.5 166.7 166.1 165.4 163.8 162.3 161.0 159.7 157.6 155.5
11.75 169.2 168.6 167.8 166.2 164.6 163.2 161.9 159.7 157.6
12 171.7 171.1 170.2 168.6 166.9 165.5 164.1 161.9 159.8 153.3
12.25 174.2 173.5 172.7 170.9 169.2 167.7 166.3 164.1 161.9 155.4
12.5 176.7 176.0 175.1 173.3 171.6 170.0 168.5 166.2 164.0 157.6
12.75 179.2 178.5 177.5 175.7 173.9 172.3 170.7 168.4 166.2 159.7
13 181.7 180.9 179.9 178.1 176.2 174.5 172.9 170.6 168.3 161.9
13.25 184.2 183.4 182.3 180.4 178.5 176.8 175.1 172.7 170.4 164.0
13.5 186.7 185.8 184.7 182.8 180.9 179.1 177.3 174.9 172.5 166.2
13.75 189.2 188.3 187.2 185.2 183.2 181.3 179.5 177.1 174.7 168.3
14 191.7 190.8 189.6 187.5 185.5 183.6 181.7 179.2 176.8 170.5
14.25 194.2 193.2 192.0 189.9 187.8 185.9 183.9 181.4 178.9 172.6
14.5 196.7 195.7 194.4 192.3 190.2 188.1 186.1 183.6 181.1 174.8
14.75 199.2 198.2 196.8 194.7 192.5 190.4 188.3 185.8 183.2 176.9
15 201.7 200.6 199.2 197.0 194.8 192.7 190.5 187.9 185.3 179.0
15.25 204.3 203.1 201.7 199.4 197.1 194.9 192.7 190.1 187.5 181.2
15.5 206.8 205.6 204.1 201.8 199.5 197.2 194.9 192.3 189.6 183.3
15.75 209.3 208.0 206.5 204.1 201.8 199.4 197.1 194.4 191.7 185.5
16 211.8 210.5 208.9 206.5 204.1 201.7 199.3 196.6 193.9 187.6
16.25 214.3 213.0 211.3 208.9 206.4 204.0 201.5 198.8 196.0 189.8
16.5 216.8 215.4 213.7 211.3 208.8 206.2 203.7 200.9 198.1 191.9
16.75 219.3 217.9 216.2 213.6 211.1 208.5 205.9 203.1 200.3 194.1
17 221.8 220.4 218.6 216.0 213.4 210.8 208.1 205.3 202.4 196.2
17.25 224.3 222.8 221.0 218.4 215.7 213.0 210.3 207.4 204.5 198.4
17.5 226.8 225.3 223.4 220.7 218.1 215.3 212.5 209.6 206.7 200.5
17.75 229.3 227.7 225.8 223.1 220.4 217.6 214.7 211.8 208.8 202.6
18 231.8 230.2 228.2 225.5 222.7 219.8 216.9 213.9 210.9 204.8
18.25 234.3 232.7 230.7 227.8 225.0 222.1 219.1 216.1 213.0 206.9
18.5 236.8 235.1 233.1 230.2 227.4 224.4 221.3 218.3 215.2 209.1
18.75 239.3 237.6 235.5 232.6 229.7 226.6 223.6 220.4 217.3 211.2
19 241.8 240.1 237.9 235.0 232.0 228.9 225.8 222.6 219.4 213.4
19.25 244.3 242.5 240.3 237.3 234.3 231.1 228.0 224.8 221.6 215.5
19.5 246.6 244.9 242.7 239.7 236.7 233.4 230.2 226.9 223.7 217.7
19.75 249.0 247.3 245.1 242.0 239.0 235.7 232.4 229.1 225.8 219.8
20 251.4 249.6 247.3 244.3 241.3 237.9 234.6 231.3 228.0 221.9
20.25 253.7 251.9 249.6 246.6 243.6 240.2 236.8 233.4 230.1 224.1
20.5 256.1 254.2 251.8 248.8 245.8 242.4 239.0 235.6 232.2 226.2
20.75 258.5 256.5 254.1 251.1 248.0 244.6 241.2 237.8 234.4 228.4
21 260.8 258.8 256.3 253.3 250.2 246.8 243.4 239.9 236.5 230.5
21.25 263.2 261.2 258.6 255.5 252.4 249.0 245.5 242.1 238.6 232.7
FM-200 Total Flood Fire APPENDIX C – LIQUID LEVEL INDICATOR (LLI) TABLES
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 10-65
21.5 265.6 263.5 260.8 257.7 254.6 251.1 247.6 244.2 240.8 234.8
21.75 267.9 265.8 263.1 260.0 256.8 253.3 249.8 246.3 242.9 237.0
22 270.3 268.1 265.3 262.2 259.0 255.5 251.9 248.4 245.0 239.1
22.25 272.7 270.4 267.6 264.4 261.2 257.6 254.0 250.5 247.0 241.3
22.5 275.0 272.7 269.8 266.6 263.4 259.8 256.1 252.6 249.1 243.4
22.75 277.4 275.0 272.1 268.9 265.6 261.9 258.2 254.7 251.1 245.5
23 279.8 277.4 274.3 271.1 267.8 264.1 260.4 256.7 253.1 247.6
23.25 282.1 279.7 276.6 273.3 270.0 266.3 262.5 258.8 255.2 249.6
23.5 284.5 282.0 278.8 275.5 272.2 268.4 264.6 260.9 257.2 251.7
23.75 286.9 284.3 281.1 277.8 274.4 270.6 266.7 263.0 259.2 253.7
24 289.2 286.6 283.3 280.0 276.6 272.7 268.8 265.1 261.3 255.8
24.25 291.6 288.9 285.6 282.2 278.8 274.9 270.9 267.1 263.3 257.9
24.5 294.0 291.2 287.8 284.4 281.0 277.0 273.1 269.2 265.4 259.9
24.75 296.3 293.6 290.1 286.7 283.2 279.2 275.2 271.3 267.4 262.0
25 298.7 295.9 292.3 288.9 285.4 281.4 277.3 273.4 269.4 264.1
25.25 301.1 298.2 294.6 291.1 287.6 283.5 279.4 275.4 271.5 266.1
25.5 303.4 300.5 296.8 293.3 289.8 285.7 281.5 277.5 273.5 268.2
25.75 305.8 302.8 299.1 295.5 292.0 287.8 283.7 279.6 275.5 270.3
26 308.2 305.1 301.3 297.8 294.2 290.0 285.8 281.7 277.6 272.3
26.25 310.5 307.4 303.6 300.0 296.4 292.2 287.9 283.7 279.6 274.4
26.5 312.9 309.8 305.8 302.2 298.6 294.3 290.0 285.8 281.6 276.4
26.75 315.3 312.1 308.1 304.4 300.8 296.5 292.1 287.9 283.7 278.5
27 317.6 314.4 310.3 306.7 303.0 298.6 294.2 290.0 285.7 280.6
27.25 320.0 316.7 312.6 308.9 305.2 300.8 296.4 292.1 287.8 282.6
27.5 322.4 319.0 314.8 311.1 307.4 302.9 298.5 294.1 289.8 284.7
27.75 324.7 321.3 317.1 313.3 309.6 305.1 300.6 296.2 291.8 286.8
28 327.1 323.6 319.3 315.6 311.8 307.3 302.7 298.3 293.9 288.8
28.25 329.4 326.0 321.6 317.8 314.0 309.4 304.8 300.4 295.9 290.9
28.5 323.8 320.0 316.2 311.6 307.0 302.4 297.9 293.0
28.75 326.1 322.2 318.4 313.7 309.1 304.5 300.0 295.0
29 328.3 324.5 320.6 315.9 311.2 306.6 302.0 297.1
29.25 330.6 326.7 322.8 318.1 313.3 308.7 304.1 299.2
29.5 325.0 320.2 315.4 310.8 306.1 301.2
29.75 327.2 322.4 317.5 312.8 308.1 303.3
30 329.4 324.5 319.7 314.9 310.2 305.3
30.25 331.6 326.7 321.8 317.0 312.2 307.4
30.5 323.9 319.1 314.2 309.5
30.75 326.0 321.1 316.3 311.5
31 328.1 323.2 318.3 313.6
31.25 330.3 325.3 320.4 315.7
31.5 322.4 317.7
31.75 324.4 319.8
32 326.5 321.9
32.25 323.9
32.5 326.0
APPENDIX C – LIQUID LEVEL INDICATOR (LLI) TABLES FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 10-66 REV. 0 2015-OCT-09 (Part No. 442940)
14 305.4 302.9 299.7 296.8 293.9 290.4 287.0 281.8 276.6 268.7
14.25 307.7 305.2 302.1 299.2 296.3 292.7 289.2 284.0 278.8 270.8
14.5 310.1 307.6 304.4 301.5 298.6 295.0 291.4 286.2 280.9 272.9
14.75 312.4 309.9 306.7 303.9 301 297.3 293.7 288.4 283.1 275.0
15 314.8 312.2 309.0 306.1 303.2 299.5 295.9 290.6 285.3 277.1
15.25 317.1 314.5 311.3 308.3 305.4 301.7 298.1 292.8 287.4 279.3
15.5 319.4 316.8 313.6 310.6 307.5 304.0 300.4 295.0 289.6 281.4
15.75 321.8 319.2 315.9 312.8 309.7 306.1 302.5 297.1 291.8 283.5
16 324.1 321.5 318.2 315.0 311.9 308.2 304.6 299.2 293.9 285.6
16.25 326.4 323.8 320.5 317.3 314.1 310.4 306.7 301.4 296.1 287.7
16.5 328.8 326.1 322.8 319.5 316.2 312.5 308.8 303.5 298.2 289.8
16.75 331.1 328.4 325.1 321.8 318.4 314.6 310.8 305.6 300.4 291.9
17 333.5 330.8 327.4 324.0 320.6 316.8 312.9 307.7 302.5 294.1
17.25 335.8 333.1 329.7 326.2 322.8 318.9 315.0 309.7 304.5 296.2
17.5 338.1 335.4 332.0 328.5 325.0 321.0 317.1 311.8 306.5 298.3
17.75 340.5 337.7 334.3 330.7 327.1 323.1 319.2 313.8 308.5 300.4
18 342.8 340.1 336.6 333.0 329.3 325.3 321.3 315.9 310.5 302.5
18.25 345.2 342.4 338.9 335.2 331.5 327.4 323.3 317.9 312.6 304.5
18.5 347.5 344.7 341.2 337.4 333.7 329.5 325.4 320.0 314.6 306.5
18.75 349.8 347.0 343.5 339.7 335.8 331.7 327.5 322.1 316.6 308.6
19 352.2 349.3 345.8 341.9 338.0 333.8 329.6 324.1 318.6 310.6
19.25 354.5 351.7 348.1 344.2 340.2 335.9 331.7 326.2 320.6 312.6
19.5 356.8 354.0 350.4 346.4 342.4 338.1 333.8 328.2 322.7 314.7
19.75 359.2 356.3 352.7 348.6 344.6 340.2 335.8 330.3 324.7 316.7
20 361.5 358.6 355.0 350.9 346.7 342.3 337.9 332.3 326.7 318.8
20.25 363.9 360.9 357.3 353.1 348.9 344.5 340.0 334.4 328.7 320.8
20.5 366.2 363.3 359.6 355.3 351.1 346.6 342.1 336.4 330.7 322.8
20.75 368.5 365.6 361.9 357.6 353.3 348.7 344.2 338.5 332.8 324.9
21 370.9 367.9 364.2 359.8 355.4 350.8 346.3 340.5 334.8 326.9
21.25 373.2 370.2 366.5 362.1 357.6 353.0 348.3 342.6 336.8 328.9
21.5 375.6 372.6 368.8 364.3 359.8 355.1 350.4 344.6 338.8 331.0
21.75 377.9 374.9 371.1 366.5 362.0 357.2 352.5 346.7 340.9 333.0
22 380.2 377.2 373.4 368.8 364.2 359.4 354.6 348.7 342.9 335.0
22.25 382.6 379.5 375.7 371.0 366.3 361.5 356.7 350.8 344.9 337.1
22.5 384.9 381.8 378.0 373.3 368.5 363.6 358.8 352.8 346.9 339.1
22.75 387.2 384.2 380.3 375.5 370.7 365.8 360.8 354.9 348.9 341.1
23 389.6 386.5 382.6 377.7 372.9 367.9 362.9 356.9 351.0 343.2
23.25 391.9 388.8 384.9 380.0 375.0 370.0 365.0 359.0 353.0 345.2
23.5 394.3 391.1 387.2 382.2 377.2 372.2 367.1 361.0 355.0 347.3
23.75 396.6 393.4 389.5 384.4 379.4 374.3 369.2 363.1 357.0 349.3
24 398.9 395.8 391.8 386.7 381.6 376.4 371.3 365.1 359.0 351.3
24.25 401.3 398.1 394.1 388.9 383.8 378.5 373.3 367.2 361.1 353.4
24.5 403.6 400.4 396.4 391.2 385.9 380.7 375.4 369.3 363.1 355.4
24.75 406.0 402.7 398.7 393.4 388.1 382.8 377.5 371.3 365.1 357.4
25 408.3 405.1 401.0 395.6 390.3 384.9 379.6 373.4 367.1 359.5
25.25 403.3 397.9 392.5 387.1 381.7 375.4 369.1 361.5
APPENDIX C – LIQUID LEVEL INDICATOR (LLI) TABLES FM-200 Total Flood Fire
UL EX4510 Suppression System Manual
PAGE 10-68 REV. 0 2015-OCT-09 (Part No. 442940)
19.25 613.8 607.8 600.4 593.0 585.5 576.1 566.7 557.3 547.9 538.5
19.50 619.2 613.2 605.6 598.1 590.6 581.2 571.7 562.3 552.9 543.4
19.75 624.6 618.5 610.9 603.3 595.6 586.2 576.7 567.3 557.8 548.4
20.00 630.0 623.8 616.1 608.4 600.7 591.2 581.7 572.2 562.7 553.3
20.25 635.4 629.1 621.3 613.5 605.7 596.2 586.7 577.2 567.7 558.2
20.50 640.8 634.5 626.6 618.7 610.8 601.2 591.7 582.2 572.6 563.1
20.75 646.2 639.8 631.8 623.8 615.8 606.2 596.7 587.1 577.6 568.0
21.00 651.6 645.1 637.0 628.9 620.8 611.1 601.4 591.7 582.0 572.2
21.25 657.0 650.4 642.3 634.1 625.9 616.0 606.1 596.3 586.4 576.5
21.50 662.4 655.8 647.5 639.2 630.9 620.9 610.9 600.8 590.8 580.7
21.75 667.8 661.1 652.7 644.3 636.0 625.8 615.6 605.4 595.2 585.0
22.00 673.2 666.4 658.0 649.5 641.0 630.7 620.3 609.9 599.6 589.2
22.25 678.6 671.7 663.2 654.6 646.1 635.5 625.0 614.5 604.0 593.5
22.50 684.0 677.1 668.4 659.8 651.1 640.4 629.7 619.1 608.4 597.7
22.75 689.4 682.4 673.6 664.9 656.1 645.3 634.5 623.6 612.8 602.0
23.00 694.8 687.7 678.9 670.0 661.2 650.2 639.2 628.2 617.2 606.2
23.25 700.2 693.0 684.1 675.2 666.2 655.1 643.9 632.8 621.6 610.5
23.50 705.6 698.4 689.3 680.3 671.3 660.0 648.6 637.3 626.0 614.7
23.75 711.0 703.7 694.6 685.4 676.3 664.8 653.4 641.9 630.4 618.9
24.00 716.4 709.0 699.8 690.6 681.4 669.7 658.1 646.5 634.8 623.2
24.25 721.8 714.3 705.0 695.7 686.4 674.6 662.8 651.0 639.2 627.4
24.50 727.2 719.7 710.3 700.9 691.4 679.5 667.5 655.6 643.6 631.7
24.75 732.6 725.0 715.5 706.0 696.5 684.4 672.3 660.1 648.0 635.9
25.00 738.0 730.3 720.7 711.1 701.5 689.3 677.0 664.7 652.4 640.2
25.25 743.4 735.6 726.0 716.3 706.6 694.1 681.7 669.3 656.8 644.4
25.50 748.8 741.0 731.2 721.4 711.6 699.0 686.4 673.8 661.3 648.7
25.75 754.2 746.3 736.4 726.5 716.7 703.9 691.2 678.4 665.7 652.9
26.00 759.6 751.6 741.6 731.7 721.7 708.8 695.9 683.0 670.1 657.2
26.25 765.0 756.9 746.9 736.8 726.7 713.7 700.6 687.5 674.5 661.4
26.50 770.4 762.3 752.1 741.9 731.8 718.6 705.3 692.1 678.9 665.6
26.75 775.8 767.6 757.3 747.1 736.8 723.4 710.1 696.7 683.3 669.9
27.00 781.2 772.9 762.6 752.2 741.9 728.3 714.8 701.2 687.7 674.1
27.25 786.6 778.2 767.8 757.4 746.9 733.2 719.5 705.8 692.1 678.4
27.50 752.0 738.1 724.2 710.4 696.5 682.6
27.75 757 743.0 728.9 714.9 700.9 686.9
28.00 762.0 747.9 733.7 719.5 705.3 691.1
28.25 767.1 752.7 738.4 724.0 709.7 695.4
28.50 772.1 757.6 743.1 728.6 714.1 699.6
28.75 777.2 762.5 747.8 733.2 718.5 703.8
29.00 782.2 767.4 752.6 737.7 722.9 708.1
29.25 787.3 772.3 757.3 742.3 727.3 712.3
29.50 792.3 777.2 762.0 746.9 731.7 716.6
29.75 797.3 782.0 766.7 751.4 736.1 720.8
30.00 802.4 786.9 771.5 756.0 740.5 725.1
30.25 807.4 791.8 776.2 760.6 744.9 729.3
30.50 812.5 796.7 780.9 765.1 749.3 733.6
FM-200 Total Flood Fire APPENDIX C – LIQUID LEVEL INDICATOR (LLI) TABLES
Suppression System Manual UL EX4510
(Part No. 442940) 2015-OCT-09 REV. 0 PAGE 10-71
NOTES: