NAFFCOInert®

Fire
Suppression
System
(IG01, IG100,
IG55, IG541)
AN INTRODUCTION TO NAFFCO
NAFFCO was founded in Dubai, UAE to become the world’s leading producer and supplier of life safety solutions. By recognizing
the importance and convenience of having easy access to multiple safety services, we became specialized by offering
complete solutions under one roof for all types of high quality firefighting equipment, fire protection systems, fire alarms,
addressable emergency systems, security systems, custom-made vehicles such as fire trucks, ambulances, mobile hospitals
and airport rescue firefighting vehicles (ARFF).
With the most talented and dedicated employees from around the world, NAFFCO has over 2,000 passionate engineers and
over 6.5 million square feet of manufacturing facilities. We are currently exporting to over 100 countries worldwide.
NAFFCO manufactures UL, FM, BSI & Global Mark approved products in our facility in consistent with International Standards
UL-DQS, BSI certifies for the Quality Management System against ISO 9001. Our Environmental (ISO 14001) & Occupational
Health & Safety (ISO 45001) Management Systems have been certified by UL-DQS. Our Trucks & Vehicles division has been
assessed & certified for Quality Management System requirement for Aviation, Space & Defense organization (AS 9100) by
UL-DQS.
Our success is driven by our passion to protect; our vision is to become the world’s number one provider of innovative solutions
in protecting life, environment and property.

2 www.naffco.com
INERT GAS FIRE SUPPRESSION SYSTEM
NAFFCOInert® fire suppression system is an engineered system using with fixed nozzle agent and pipe network. NAFFCOInert®
systems are designed in accordance with latest edition of NFPA 2001,Standard on "clean agent systems”. This system shall be
designed for Class A, Class B & Class C application, it extinguish fire by reducing residual oxygen concentration to a level will
no longer support combustion.
The system can actuate by detection and control equipment for automatic operation along with providing local manual operation
when needed. Accessories are used to provide alarms, ventilation control, door closures or other auxiliary shutdown or functions.
Two or more hazard areas can be protected with a single group of agent cylinders by means of directional or selector valve.
NAFFCOInert® fire suppression system offers IG01, IG100, IG55 and IG541 gases. It is available as 200 Bar and 300 Bar system
which provides optimum design options to the protected hazard.

BASIC USES:
NAFFCOInert® fire suppression system is particularly useful for suppressing fires in hazard areas where an electrically non-
conductive medium is essential or desirable. Where the clean environment and the hazard obstructions require the use of a
gaseous agent. It is an ideal replacement agent for Halon 1301 alternative.
• Telecommunication facilities
• Electrical and Electronics hazard areas
• Data Centers
• Control Rooms
• Museums / Archives
• Military Installations
• Libraries
• Medical facilities

PRESSURE REGULATOR TECHNOLOGY


Pressure Regulators modulate the discharge pressure to a constant
40-60 Bar which still delivers the design concentration up to 120
seconds, but with significant performance and cost benefits:

BETTER SAFETY
• Prevents discharge freeze-up
• Prevents explosive force of discharge

EASY MAINTENANCE
• After a system discharge, simply remove
the regulator, recharge, and reconnect.
No reconditioning necessary
• Functional tests are possible even
while the system is armed

SAVES TIME AND MONEY


• Enables low pressure manifolds & pipework to be
used that are of lower cost and easy to install
• Reduces the difficulty and cost of locating/
fitting pressure vents in the protected space.

www.naffco.com 3
INERT EXTINGUISHANT AGENT
Inert Gas is a colorless, odorless, electrically non-conductive gas with a density approximately the same as air.
(See Physical Properties for additional information).
Inert Gas is stored as pressurized gas within the cylinder assembly. It is available at storage pressures of 200 Bar and 300 Bar.
When discharged into a protected space, it is clear and does not obscure vision. It leaves no residue and has zero ozone
depleting potential and zero global warming potential.

FEATURES & BENEFITS


• Natural gas present in the atmosphere
• Suitable for occupied areas
• Non Toxic and Non Corrosive
• Colorless, odourless and compressed gas
• Stored and discharge as gas
• Fogging does not occur when agent is discharged
• Electrically non – conductive
• Leaves no residue
• Zero Ozone Depletion
• Zero Global warming
• Zero Atmospheric Life Time

USE AND LIMITATIONS


Inert Gas extinguishes a fire by reducing the residual oxygen concentration to a level that will no longer support combustion.
System shall be used on the following Class of Hazards:
• Class A & C :Electrical and Electronic Hazards, Telecommunication Facilities.
High Value assets where the associated down time be costly
• Class B : Flammable liquid and Gases
System shall “NOT” be used on fires involving the following materials:
• Chemical or mixtures of chemical that are capable of rapid oxidation in the absence of air.
(Example include: Cellulose Nitrate and Gunpowder)
• Reactive metal such as lithium, sodium, potassium, magnesium, Titanium, Zirconium, Uranium and plutonium.
• Metal Hydrides such as sodium hydride and lithium aluminum hydride.
• Chemical capable of undergoing auto-thermal decomposition
(Example: Organic Peroxide and Hydrazine).

EXPOSURE LIMITATION
Hazard Type Design Concentration/Oxygen Levels Maximum Human Expose time

Normally Occupied Up to 43% / 12% minimum 5 Min


Space 43% to 52% / 12% to 10% 3 Min

Normally 52% to 62% / Minimum 8% 30 Sec


Un-Occupied Space Above 62% / 8% or lower 0 Sec (Personal CANNOT be exposed)
*NOTES: EN 15005, ISO 14520 & NFPA 2001 does not allow Clean Agent Systems to be used in any occupiable spaces where the design concentration
required is above 52% unless provided with supervised system lockout valve, pneumatic pre-discharge alarm, pneumatic time delay and warning signs.
NAFFCO does not recommend NAFFCOInert® systems to be used in normally occupied spaces where the design concentration required is above 52%.

4 www.naffco.com
PHYSICAL PROPERTIES OF IG-01
Chemical Name Ar (Argon)
Molecular Weight 39.90 g/mole
Boiling Point at 1.013 Bar -185.9°C
Critical Pressure 4903 Kpa
Critical Temperature -122.3°C
NOAEL 43%
LOAEL 52%

PHYSICAL PROPERTIES OF IG - 100


Chemical Name N² (Nitrogen)
Molecular Weight 28.02 g/mole
Boiling Point at 1.013 Bar -196°C
Critical Pressure 3399 Kpa
Critical Temperature -146.95°C
NOAEL 43%
LOAEL 52%

PHYSICAL PROPERTIES OF IG - 55
Chemical Name N²/Ar
Molecular Weight 33.95 g/mole
Boiling Point at 1.013 bar -196.00ºC
Critical Pressure 4150 Kpa
Critical Temperature -134.7ºC
NOAEL 43%
LOAEL 52%

PHYSICAL PROPERTIES OF IG - 541


Chemical Name N²/Ar/CO²
Molecular Weight 34.00 g/mole
Boiling Point at 1.013 Bar -196ºC
Critical Pressure N/A
Critical Temperature N/A
NOAEL 43%
LOAEL 52%

www.naffco.com 5
CYLINDER /VALVE ASSEMBLY
NAFFCOInert® cylinders shall be High Pressure Seamless Cylinder available in different capacities (i.e. 67, 80 & 140 Ltrs).
The Cylinder filling pressure shall be either 200 Bar or 300 Bar to meet suitable system requirement. Cylinders arrives with valves
pre-assembled.

SPECIFICATION
Working Pressure 200 Bar 300 Bar
Test Pressure 300 Bar 450 Bar
Material 34CrMO4 EN10 083
Color RAL 3000
Thread Connection W28.8 x 1/14" - BS EN ISO 11363-1
Conformity ISO 9809 Part 1&2/TUV+UN
Mounting Vertical

Electric/Pneumatic -
Input from Control Panel
Cylinder Actuation
Manual/ Pneumatic -
Input from Push Knob
Cylinder Storage
-20ºC to +65ºC
Temperature

CYLINDER DIMENSIONS
67 Litres 67 Litres 80 Litres 80 Litres 140 Litres 140 Litres
Working Pressure 200 Bar 300 Bar 200 Bar 300 Bar 200 Bar 300 Bar

Diameter 267/360 mm 267/360 mm 267/360 mm 267/360 mm 360 mm 360 mm

Height 1470/900 mm 1526/900 mm 1710/1025 mm 1780/1090 mm 1690 mm 1760 mm


Model Number NFIG01-200- NFIG01-300- NFIG01-200- NFIG01-300- NFIG01- NFIG01-
(IG01) 067A/B 067A/B 080A/B 080A/B 200-140 300-140
Model Number NFIG100-200- NFIG100-300- NFIG100-200- NFIG100-300- NFIG100- NFIG100-
(IG100) 067A/B 067A/B 080A/B 080A/B 200-140 300-140
Model Nutmber NFIG55-200- NFIG55-300- NFIG55-200- NFIG55-300- NFIG55- NFIG55-
(IG55) 067A/B 067A/B 080A/B 080A/B 200-140 300-140
Model Number NFIG541-200- NF IG541-300- NFIG541-200- NFIG541-300- NFIG541- NFIG541-
(IG541) 067A/B 067A/B 080A/B 080A/B 200-140 300-140
Approval: TPED (π Mark)

6 www.naffco.com
DISCHARGE VALVES FOR INERT GAS CYLINDERS
NAFFCOInert® cylinder head valve shall be pressure seat type valve. The head valve is available in two different working
pressure 200 Bar/300 Bar to meet the suitable system requirement.
The head valve can be operated by electric actuator, pneumatic actuator or pneumatic /manual actuator. The head valve is
equipped with pressure gauge/pressure switch to monitor the cylinder pressure.

SPECIFICATION
Model No. B04801218-NF B04802020-NF
Operating
200 Bar 300 Bar
Pressure @ 15°
Test Pressure 300 Bar 450 Bar
Material Brass
Discharge Port W21.8 x 1/14”
Inlet Connection W28.8 x 14TPI (25E ENISO 113631 - 1)
Connection for
M42 x 1.5
Release Device
Port for Pilot
G ⅛"
Hose
Monitoring Port M10 x 1
Orifice Size Ø12mm
Flow Rate Kv= 2.66; Cv= 3.09

CONSTANT FLOW & PRESSURE DISCHARGE REGULATOR


The pressure regulator modulates the discharge pressure to a constant pressure, which still delivers the extinguishing agent
up to 120 seconds, but with significant performance and cost benefits. It prevents discharge freeze-up and explosive force of
discharge. Low-pressure manifolds and pipework can be used - that means lower costs.
After a system discharge, no reconditioning of the pressure regulator is necessary. Functional tests are possible even while the
system is armed. The pressure regulator is screwed with a gasket on the discharge port of the valve.

SPECIFICATION
B08400003-NF
Model No B08401000-NF
Material Brass
Inlet Pressure 200 / 300 Bar
Maximum Inlet Pressure 360 Bar
Orifice diameter 12 mm
Inlet Connection W21.8 x 1/14” DIN 477
Outlet Connection W21.8 x 1/14” DIN 477
Static outlet pressure 60 Bar

www.naffco.com 7
ELECTROMAGNETIC RELEASE DEVICES
The electromagnetic release device is used to actuate the system electrically. It is mounted on top of the master valve and
is operated by an electrical signal from a fire detection system. In order to actuate the electromagnetic release device a
constant DC voltage of 24V is required.
The electromagnetic release device can be combined with the manual/pneumatic release device.

SPECIFICATION
Model No B04425146-NF B04425147-NF
with Diode without Diode
Nominal Voltage 24 VDC
Brass and stainless steel
Material
Plastic protection cap
Nominal Current 0.5A
Protection class IP 65
Valve Connection M42 x 1.5

MONITORING SWITCH FOR ELECTROMAGNETIC


RELEASE DEVICES
The Monitoring switch for electromagnetic release device
monitors that the electromagnetic actuator is properly in
place to actuate the system. It is connected to the alarm box.

It is a compact design remains in the cylinder and simply


clamps around the valve base. Also it is easy to retrofit with
the existing installation set up.

APPLICATION
• Specifying a physical switch to disconnect the release
circuit in place of a software controlled disconnect
• Creating a supervisory condition on
the associated release panel
*Note: Pin from switch needs to be pushed in at least 3mm after installation.

SPECIFICATION
Part Number 02990520 0 - NF
Artical Code B0480
Dimensions W x H x D: 11,8 cm x 9,1 cm x 6,6 cm
Contact NO or NF (Cables Included)
Temperature
-30° C to 60°C (-22° F to 140° F)
Range
* Only UL Listed

8 www.naffco.com
MANUAL/PNEUMATIC RELEASE DEVICE
The manual/pneumatic release device allows manual or pneumatic actuation of several system components. This release device
is used for pneumatic actuation of multiple cylinders in series, which are connected to the master cylinder by a pilot hose.
Manual actuation is accomplished by pulling the hand lever on the manual/pneumatic release device. In the closed position
the manual/pneumatic release device is secured with a safety pin. By removing the safety pin, the hand lever can be
manually pressed down to activate the valve so that inert gas is released

SPECIFICATION
Model No B04420065-NF
Material Brass & Stainless Steel
Working Pressure 300 Bar
Valve Connection M 42 x 1.5
Pneumatic
G ⅛"
Connection
Actuation Force <150N

200 Bar System:


Actuation Force/ P Min = 15 Bar; P Maxt = 240 Bar
Pressure 300 Bar System:
P Min = 21 Bar; P Max = 360 Bar

PNEUMATIC RELEASE DEVICE


This release device is used for pneumatic actuation of multiple cylinders in series, which are connected to the master cylinder
by a pilot hose. Cylinders equipped with the pneumatic release device serve as slave cylinders.

APPLICATION
Model No B04420066-NF
Material Brass
Working Pressure 300 Bar
Valve Connection M 42 x 1.5
Pneumatic Connection G ⅛"

200 Bar System:


Actuation Force/ P Min = 15 Bar; P Max = 240 Bar
Pressure 300 Bar System:
P Min = 21 Bar; P Max = 360 Bar

www.naffco.com 9
PRESSURE GAUGES
The pressure gauge measures the pressure in the cylinder. It is equipped with an integrated pressure switch to supervise the
loss of pressure in the cylinder. A separate 200 Bar or 300 Bar pressure gauge is used for each inert gas.

Each valve must be equipped with a pressure gauge. The pressure gauge is connected to the monitoring port of the valve.

SPECIFICATION
Working Pressure 200 Bar 300 Bar
Connection M10 x 1 M10 x 1
Model Number(IG01) 029720221-NF 029720217-NF
Model Number(IG100) 029720219-NF 029720215-NF
Model Number(IG55) 029720220-NF 029720216-NF
Model Number(IG541) 029720222-NF 029720218-NF

PILOT HOSE
The pilot hose is used to build up the pilot line, e.g. for the connection of several release devices and/or for the connection
of the valve to the release device.

The pilot hose may only be used in accordance with component approval in stationary inert gases fire
extinguishing systems. Several cylinders, equipped with valves,
can be connected with pilot hoses.

SPECIFICATION
Model No. B06920211-NF B06920212-NF B06920213-NF
Length 400 mm 700 mm 500 mm
Connection 2 x M12 x 1.5
Bending Radius 75 mm
Nominal Diameter DN 6
Working Pressure 400 Bar
Burst Pressure 1600 Bar

• Connection - Galvanised steel


• Hose inner layer - Oil resistant synthetic rubber
Material
• Hose insert - Two high tensile steel wire braided inserts
• Hose outer layer - Oil resistant and weatherproof synthetic rubber

10 www.naffco.com
DISCHARGE HOSE
The discharge hose is used for the connection of the pressure regulator to the check valve.
The W21.8 x 1/14“ nut with the inserted gasket is installed on the pressure regulator.
The G¾“ nut with the inserted gasket is connected to a check valve.

SPECIFICATION
Model No. B06920224-NF B06920225-NF
Length 400 mm 400 mm
Connection W21.8 x 1/14” • G¾” W21.8 x 1/14” • G¾”
Bending Radius 130 mm 180 mm
Nominal Diameter DN 12 DN 16
Max. Working Pressure 380 Bar 350 Bar
Burst Pressure 1520 Bar 1400 Bar
• Connection - Galvanised steel
• Hose inner layer - Oil resistant synthetic rubber
Material
• Hose insert - Two high tensile steel wire braided inserts
• Hose outer layer - Oil resistant and weatherproof synthetic rubber

MANIFOLD CHECK VALVE


The check valve prevents a back-flow of the extinguishing agent into the cylinder. The check valve is provided with a connection
thread R1“ DIN EN 10226-1 for the connection to the manifold and a connection thread G¾“ DIN ISO 228-1 for the connection
to the discharge hose.

SPECIFICATION
Model No B04600008-NF
• Housing - Brass
Material • Ball - Stainless Steel
• Sealing - Thermoplastic
Connection Thread Inlet G¾" DIN ISO 228-1

Connection Thread Outlet R1” DIN EN 10226-1

Nominal Diameter DN 12
Working Pressure 300 Bar
Pressure to Open <0.1 Bar

www.naffco.com 11
BLEED VALVE
The bleed valve is a part of the pilot line. The device must be mounted at the end of each pilot line at the last pneumatic
release device. This device is a security part, which protects the system from unwanted tripping when a cylinder has a leak
and the pressure would increase in the pilot line. It allows a bleeding till the pressure in the pilot line is under 0.7 Bar. The
bleed valve prevents an accidental system release.

SPECIFICATION
Model No 029730040-NF
Material Brass
Working Pressure 300 Bar
Connection Thread G⅛" ISO 228-1
Closing Pressure 0.7 - 1.5 Bar

DISCHARGE NOZZLE
Discharge nozzles are made of brass in four different sizes, for
different application. Nozzles are available with a connection
thread R1½“, R1“, R½“ and R¾“ and can be screwed into every
fitting corresponding to the pressure stage and the thread. Orifice
design to particular requirement with computer aided calculation
to assure the effectiveness of extinguishing agent and reliable
system design.

The nozzle is used to discharge the agent from the cylinder through
piping network to the enclosed hazard volume. The nozzle selection
depends on the hazard and location to be protected. The nozzle
has to be mounted at the ceiling level with the orifice tip pointed
vertically down. The nozzle outlet must point downwards to distribute
the extinguishing agent effectively and to prevent pollution. The
discharge pattern of the nozzle shall be 360°.

The nozzle distributes the extinguishing agent evenly in the


extinguishing zone in the calculated flooding time. Nozzles are
designed to direct the discharge of inert gas using the stored
pressure from the cylinders.

SPECIFICATION
Model No. N 360***15 N 360***20 N 360***25 N 360***40
Size R½" R¾" R1" R1½"
Thread EN 10226-1
Orifice Diameter Ø3-Ø9.5 mm Ø7-Ø13.5 mm Ø10-Ø17.5 mm Ø15-Ø25.5 mm
Material Brass
Working Pressure 60 Bar
The orifice diameter is defined with flow calculation software

12 www.naffco.com
PRESSURE & FLOW DETECTOR SWITCH
Used to send a signal that the system is discharging. Sends a signal to a control panel or alarm box at the earliest phase
of discharge.

The pressure and flow detector switch is connected to the manifold and to a power supply. It reacts in the earliest stage of
extinguishing agent discharge at 2 Bar pressure and energises or de-energises electrically operated equipment.

Model No 028250050-NF
Operating Pressure 2 Bar
Connection G½" or G¾"
Power Source 400 VAC/3A or 24 VAC/10A
IP Rating IP65

SELECTOR VALVE
(MULTI-ZONE DISTRIBUTION)
Selector Valve allow a single agent supply to be utilized for protection of multiple zones by using the same number of cylinders.
It is necessary to use the selector valve to utilize the multiple cylinders to protect the multiple zones. Selector Valves direct
the extinguishing agent to the appropriate flooding zone and reduces the total amount of agent and number of cylinders required.

The Selector Valve body is available in carbon steel. Selector valve is a ball valve that control the flow of Inert gas through the
piping network until the valve is activated either by manually or electrically. The actuation pressure for the selector valve is
8-10 bar pressure. Each Selector Valve is equipped with the monitoring device which shows the valve Position (Open or
Closed) that provides a visual indication of the valve status.

SPECIFICATION
Part B05511 B05511 B05511 B05511 B05511
Number 050-NF 150-NF 250-NF 350-NF 450-NF
G1" G1½" G2" G2½" G3"
Diamater
(DN25) (DN40) (DN50) (DN65) (DN80)
Working
140 Bar
Pressure
Actuation
8 - 10 Bar
Pressure

Material Carbon Steel

www.naffco.com 13
PNEUMATIC CONTROL PANEL
(MULTI-ZONE DISTRIBUTION)
The pneumatic control panel is made of several individual components, which are fixed on a support of control panel arrangement.

S. No. Description S. No. Description


3/2Way Valve / Electro Pneumatic / 24 DC / UL-Coil / G1/8 /
1 13 Reducing, Brass, G 1/4"I, 1/4" NPT 0, WP 16 Bar, WS17
Bistable / 1-10bar / DN5 / Temp. -10 to +60°C
2 Mounting plate for 3/2-way Valve Connection G 1/8 14 Fixation "Normafix" K, Size 1, Clamp Size 63-80mm
L-fitting (Blue Series), Rotatable, R1/4a., for tube outside-Ø8 mm, Connector Type B / IP 65 / Contacts 2 + Grounding /
3 15 Cable Inlet PG / Ø6-8mm1
WP max. 15bar, Plastic/MS vern.
Fitting Straight, R 1/8 a, tube outside -Ø8 mm,
4 16 Screw in Fitting AGN 1/4" CEL06
WP max. 315 bar, WS117, WS214, Steel Zinc Coated
Plug, Hex 6mm, G1/4, O-Ring, WP Max. 60 Bar,
5 17 HP Tube 2SC DN 6 / B06920212
WT max. 80°C, Brass Nickel Coated
6 Silencer Sintered, Flat, G1/4a., WP Max. 10 Bar, WT-10°C bis 250°C 18 Bleed Valve 029730040
Plug with Hex / 1/4"NPT / Type Straight /
7 Hose Clamp, Steel Coated (W1), Clamp Size 60,0 - 80,0mm, B 20,0 mm 19 Steel Calv. Coated / Thread Sealed
8 Manometer Typ 111.11, Ø2.5", G 1/4" Bottom Radial, 0-16 Bat, UL252 20 Distance Sheet, Aluminium, 56 x 15 x 7 mm

9 Cover Sheet for Mounting Plate G1/4 for Connection G1/8 21 Distance Sheet, Aluminium, 45 x 45 x 8 mm

10 HP Regulator / 1/4' / NPT / 5-125 psig (0,3 to 3,5 Bar) / without Manometer 22 Screw Hex M8 x 20

11 Mounting Plate Aluminium / 450(H) x 1000(L) x 6(D) mm 23 Electrical Interface Box Rittal PK9521.050
Reducing Nipple, G 1/4a., G 1/8i., WS 17, WP Max. 60 Bar,
12 24 Connector
WT Max. 150°C, Brass Zinc Coated
25 Cable Trunking

PNEUMATIC CONTROL PANEL SIZE


PART NO. NAME ZONES LENGTH (mm) HEIGHT (mm) DEPTH (mm)
NF-SVCB02 2 Zones 470 450 6
NF-SVCB03 3 Zones 470 450 6
NF-SVCB04 4 Zones 470 450 6
NF-SVCB05 5 Zones 470 450 6
NF-SVCB06 6 Zones 700 450 6
NF-SVCB07 7 Zones 700 450 6
NF-SVCB08 Control panel with different 8 Zones 700 450 6
NF-SVCB09 configurations (zones) 9 Zones 700 450 6
NF-SVCB10 10 Zones 700 450 6
NF-SVCB11 11 Zones 1000 450 6
NF-SVCB12 12 Zones 1000 450 6
NF-SVCB13 13 Zones 1000 450 6
NF-SVCB14 14 Zones 1000 450 6
NF-SVCB15 15 Zones 1000 450 6

14 www.naffco.com
SELECTOR VALVE WITH PILOT - CYLINDER ASSEMBLY
(MULTI-ZONE DISTRIBUTION)

Pilot cylinder assembly for selector valve actuation consists of Manual / Pneumatic release device which allows manual or
pneumatic actuation of the selector valve for the individual zones for system operation. Manual actuation is accomplished by
pulling the hand lever on the manual/pneumatic release device is secured with a safety pin. By removing the safety pin, the
hand lever can be manually pressed down to actuate the valve so that the nitrogen is released from the cartridge. Electric
magnetic device is used to actuate the system electrically. It is mounted top of the pilot cylinder valve and is operated by
an electrical signal of constant DC voltage of 24V electric solenoid from the fire detection system. Both of these actuation
methods result in the opening of a nitrogen pilot cylinder that pneumatically opens the Selector Valve. Each Selector Valve
is equipped with the monitoring device which shows the valve Position (Open or Closed) that provides a visual indication of
the valve status. Pop Off Valve is used to reset the Selector Valve after the system discharge.

NAFFCOinert & CO2 SYSTEM B04390031 (24V) / B04390051 (12V)


1. Selector Valve 1. Selector Valve
2. High Pressure Primary Regulator 2. High Pressure Primary Regulator
(Set Pressure 6 to 10 Bar) UL Listed (Set Pressure - 6 to 10 Bar) UL Listed
3. ¼" High Pressure Pilot Hose 3. ¼" High Pressure Pilot Hose
(Max. Length 1.5Mtr)
4. Discharge Valve,
4. Constant Flow & Pressure Discharge Regulator, Part Number: B04390031 (24V)/B04390051 (12V)
Part number: B8400003-NF
5. Pilot Cylinder, W28.8 x 14TPI Threaded to
5. Discharge Valve, 25E EN ISO 113631-1
Part number: B04801218-NF
6. Pop Off Valve, Set Pressure 175Psi
6. Electromagnetic Release Device
Part number: B04425146-NF
7. Manual/Pneumatic Release Device
Part number: B04420065-NF
8. Pressure Gauge,
Part number: 029720221-NF
9. Pilot Cylinder, W28.8x14TPI Threaded to
25E EN ISO 113631-1
10. Pop off Valve, Set Pressure 175 Psi

www.naffco.com 15
PRESSURE RELIEF DEVICE FOR MANIFOLD
The pressure relief device for manifold is a safety device to prevent overpressure during discharge.

SPECIFICATION
Model No 029730037-NF
66 bar at 20°C /
Set Pressure
957 psi at 68°F
Connection Thread G½"

MANIFOLD
Manifolds are used to connect several cylinders at 100 bar pressure. They can only be used with valves with pressure regulators
it available in 1 row and 2 row arrangement to connect 2 to 20 cylinders.

SPECIFICATION
Manifold 267 Dia. 360 Dia.
Description Cylinder Cylinder
2 Cylinder Manifold NFIG-267-SRM2 NFIG-360-SRM2
3 Cylinder Manifold NFIG-267-SRM3 NFIG-360-SRM3
4 Cylinder Manifold NFIG-267-SRM4 NFIG-360-SRM4
5 Cylinder Manifold NFIG-267-SRM5 NFIG-360-SRM5

CYLINDER MOUNTING PARTS


Galvanised steel wall mounting rails and clamps are used to mount the cylinders in a vertical position to the wall for single
& double row arrangement with metal bracket. For floor mounting, channels are used to mount the cylinders.

CYLINDER MOUNTING PARTS SINGLE & DOUBLE ROW ARRANGEMENT

NOTE: Steel Brackets Available Upon Request

16 www.naffco.com
WARNING SIGN

Model No.: 02800318-NF

GAS STORAGE AREA


The purpose of this sign is to warn the personal that
the room is stored inert gas cylinders. Attach warning
signs to all entrance doors of the gas storage room.

Model No.: 02800319-NF

WARNING
The purpose of this sign is to warn the personal
that the room is protected by inert gas system and
to leave the room upon system activation. Attach
warning signs to all entrance doors of the
protected enclosures

Model No.: 02800320-NF

UPON SYSTEM ACTIVATION


The purpose of this sign is to warn the personal
that to leave the room upon system activation is
stored inert gas cylinders. Attach warning signs to
all exit doors of the protected enclosures

www.naffco.com 17