NAFFCO was founded in Dubai, UAE to become the worlds leading Our products have been consistently certified by UL, FM, BSI, LPCB
producer and supplier of life safety solutions. By recognizing the and Global Mark according to the latest International Quality
importance and convenience of having easy access to multiple Standard for their strict adherence to ISO 9001 quality management
safety services, we became specialized by offering complete system and certified for ISO 14001 environmental management
solutions under one roof for all types of high quality firefighting systems and BS OHSAS 18001 for occupational safety by UL DQS.
equipment, fire protection systems, fire alarms, addressable
emergency systems, security systems,custom-made vehicles such Our success is driven by our passion to protect; our vision is to
as fire trucks, ambulances, mobile hospitals and airport rescue become the worlds number one provider of innovative solutions in
firefighting vehicles (ARFF). protecting life, environment and property.
With the most talented and dedicated employees from around the
world, NAFFCO has over 450 passionate engineers and over 3 million
square feet of manufacturing facilities. We are currently exporting
to over 100 countries worldwide.
2 www.naffco.com
INERT GAS FIRE SUPPRESSION SYSTEM
NAFFCOInert fire suppression system is an Accessories are used to provide alarms, ventilation
engineered system using with fixed nozzle agent control, door closures or other auxiliary shutdown
and pipe network. NAFFCOInert systems are or functions. Two or more hazard areas can be
designed in accordance with latest edition of protected with a single group of agent cylinders
NFPA 2001,Standard on clean agent systems. by means of directional or selector valve.
This system shall be designed for Class A, Class B NAFFCOInert fire suppression system comes
& Class C application, it extinguish fire by reducing with IG01(100% Argon), IG100(100% Nitrogen),
residual oxygen concentration to a level will no IG55(50%Argon, 50% Nitrogen) and IG541(Argon,
longer support combustion. Nitrogen, CO) gases. It is available as 200 Bar and
The system can actuate by detection and control 300 Bar system which provides optimum design
equipment for automatic operation along with options to the protected hazard.
providing local manual operation when needed.
Telecommunication facilities
Electrical and Electronics hazard areas
Data Centers
Control Rooms
Museums / Archives
Military Installations
Libraries
Medical facilities
PRESSURE REGULATOR
TECHNOLOGY
Pressure Regulators modulate the discharge
pressure to a constant 40-60 Bar which still delivers
the design concentration within 60 seconds, but
with significant performance and cost benefits:
BETTER SAFETY
Prevents discharge freeze-up
Prevents explosive force of discharge
EASY MAINTENANCE
After a system discharge, simply remove
the regulator, recharge, and reconnect. No
reconditioning necessary
Functional tests are possible even while the
system is armed.
www.naffco.com 3
INERT EXTINGUISHANT AGENT
Inert Gas is a colorless, odorless, electrically non- USE AND LIMITATIONS
conductive gas with a density approximately the Inert Gas extinguishes a fire by reducing the
same as air. (See Physical Properties for additional residual oxygen concentration to a level that will
information). no longer support combustion.
Inert Gas is stored as pressurized gas within System shall be used on the following Class of
the cylinder assembly. It is available at storage Hazards:
pressures of 200 Bar and 300 Bar.
When discharged into a protected space, it is clear Class A & C : Electrical and Electronic Hazards,
and does not obscure vision. It leaves no residue Telecommunication Facilities.
and has zero ozone depleting potential and zero High Value assets where the
global warming potential. associated down time be costly
EXPOSURE LIMITATION
Hazard Type Design Concentration/Oxygen Levels Maximum Human Expose time
4 www.naffco.com
PHYSICAL PROPERTIES OF IG-01
Chemical Name Ar (Argon)
Molecular Weight 39.9
Boiling Point at 1.013 Bar -185.9C
Critical Pressure 49 Bar
Critical Temperature -122.3C
Design Concentration for Class A Fire (NFPA) 38.7%
Flooding Factor for Class A Fire (NFPA) 0.481 m/ m
NOAEL 43%
LOAEL 53%
PHYSICAL PROPERTIES OF IG - 55
Chemical Name N/Ar
Molecular Weight 33.95
Boiling Point at 760 mm Hg -190.1C
Critical Pressure 602 psia
Critical Temperature -134.7C
Design Concentration for Class A Fire (NFPA) 37.2%
Flooding Factor for Class A Fire (NFPA) 0.457 m/ m
NOAEL 43%
LOAEL 52%
www.naffco.com 5
CYLINDER /VALVE ASSEMBLY
SPECIFICATION
Working Pressure 200 Bar 300 Bar
Test Pressure 300 Bar 450 Bar
Material 34CrMO4 EN 10 083
CYLINDER DIMENSIONS
67 Litres 67 Litres 80 Litres 80 Litres 140 Litres 140 Litres
Working Pressure 200 Bar 300 Bar 200 Bar 300 Bar 200 Bar 300 Bar
6 www.naffco.com
VALVES FOR INERT GAS CYLINDERS
NAFFCOInert cylinder head valve shall be pressure seat
type valve. The head valve is available in two different
working pressure 200 Bar / 300 Bar to meet the suitable
system requirement.
The head valve can be operated by electric actuator,
pneumatic actuator or pneumatic /manual actuator. The
head valve is equipped with pressure gauge / pressure
switch to monitor the cylinder pressure.
PRESSURE REGULATOR
The pressure regulator modulates the discharge pressure
to a constant pressure, which still delivers the extinguishing
agent within 60 seconds, but with significant performance
and cost benefits. It prevents discharge freeze-up and
explosive force of discharge. Low-pressure manifolds and
pipework can be used - that means lower costs.
After a system discharge, no reconditioning of the pressure
regulator is necessary. Functional tests are possible even
while the system is armed. The pressure regulator is
screwed with a gasket on the discharge port of the valve.
Model No B08400003-NF
Material Brass
Inlet Pressure 200 / 300 Bar
Maximum Inlet Pressure 360 Bar
Orifice diameter 12 mm
Inlet Connection W21.8 x 1/14 DIN 477
Outlet Connection W21.8 x 1/14 DIN 477
Static outlet pressure 60 Bar
www.naffco.com 7
ELECTROMAGNETIC RELEASE DEVICES
Model No B04420065-NF
Material Brass & Stainless Steel
Working Pressure 300 Bar
Valve Connection M 42 x 1.5
Pneumatic Connection G 1/8"
Actuation Force <150N
200 Bar System: P Min = 15
Actuation Force/ Bar; P Max = 240 Bar
Pressure 300 Bar System: P Min = 21
Bar; P Max = 360 Bar
8 www.naffco.com
PNEUMATIC RELEASE DEVICE
Model No B04420066-NF
Material Brass
Working Pressure 300 Bar
Valve Connection M 42 x 1.5
Pneumatic Connection G 1/8"
200 Bar System: P Min = 15
Actuation Force/ Bar; P Max = 240 Bar
Pressure 300 Bar System: P Min = 21
Bar; P Max = 360 Bar
PRESSURE GAUGES
www.naffco.com 9
PILOT HOSE
Bending Radius 75 mm
Nominal Diameter DN 6
Working Pressure 400 Bar
Burst Pressure 1600 Bar
DISCHARGE HOSE
Nominal Diameter DN 12 DN 16
Max. Working Pressure 380 Bar 350 Bar
Burst Pressure 1400 Bar 1520 Bar
10 www.naffco.com
CHECK VALVE
Model No B04600008-NF
Housing - Brass
Material Ball - Stainless Steel
Sealing - Thermoplastic
BLEED VALVE
Model No 029730040-NF
Material Brass
Working Pressure 360 Bar
Connection Thread G1/8" DIN ISO 228-1
Nominal Diameter DN 1.5
Closing Pressure 0.7 - 1.5 Bar
www.naffco.com 11
DISCHARGE NOZZLE
Model No 0282550050-NF
Operating Pressure 2 Bar
Connection G" or G"
Power Source 400 VAC/3A or 24 VAC/10A
IP Rating IP65
12 www.naffco.com
PRESSURE RELIEF DEVICE FOR MANIFOLD
Model No 029730037-NF
66 bar at 20C /
Set pressure
957 psi at 68F
Connection Thread G"
Model No 028200231-NF
Diameter 80 mm
Connection Thread G"
Pressure Gauge Scale 0-400 Bar
Quality Class 1.6
MANIFOLD
Model No B0580001*-NF
Working Pressure 100 Bar
Test Pressure 150 Bar
Inlet Connection Rc1"
Outlet Connection R2"
Material Galvanized Steel
www.naffco.com 13
CYLINDER MOUNTING PARTS
Galvanised steel wall mounting rails and clamps are wooden bracket for double row arrangement. Metal
used to mount the cylinders in a vertical position brackets also available upon request for double row
to the wall for single row arrangement and with arrangement.
14 www.naffco.com
WARNING SIGN
WARNING
The purpose of this sign is to warn the
personal that the room is protected by inert
gas system and to leave the room upon
system activation. Attach warning signs to all
entrance doors of the protected enclosures
www.naffco.com 15
CAT.NO.NF/IGS/08/15