PROJECT DESCRIPTION & SCOPE OF WORK FIRE FIGHTING SYSTEM DESIGN GENERAL NOTES GENERAL DIRECTORATE OF CIVIL DEFENCE
CLEAN AGENT FIRE EXTINGUISHING SYSTEM MINISTRY OF INTERIOR, STATE OF QATAR
GENERAL DESCRIPTIONS: 1. ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS ARE IN METERS UNLESS NOTED OTHERWISE. FF DESIGN CRITERIA FOR CLEAN AGENT FIRE EXTINGUISHING SYSTEMS
>> AUTOMATIC FIRE SUPPRESSION SYSTEM AREA PROTECTED
2. CLEAN AGENT FIRE SUPPRESSION SYSTEM MUST COMPLY WITH NFPA 2001 & 72 AND
THE PROPOSED PROJECT IS A 66/11kV PSS4 SUBSTATION LOCATED IN INDUSTRIAL AREA . KAHRAMAA FIRE SAFETY REQUIREMENT.
REFERENCE:
CRITERIA VALUE UNIT STD. / CODE / CHAPTER
● SPRINKLER SYSTEM PUMP ROOM 3. SYMBOLS USED ARE AS PER NFPA 170 SECTION / TABLE / FIGURE
WITH ANCILLARY BUILDING SUCH AS FIRE PUMP ROOM AND FIRE WATER TANK YARD. 4. THE FINAL LOCATIONS/POSITIONING AND NUMBER OF FIRE ALARM SYSTEM DEVICES ARE SUBJECT TO CHANGE,
● PRE-ACTION SYSTEM _________________ AS PER SITE CONDITIONS. EXTINGUISHING AGENT: HFC-227ea N/A
5. ALL SYSTEM DEVICES AND EQUIPMENT TO BE INSTALLED AS PER NFPA 2001 & 72 AND MANUFACTURER'S REQUIREMENTS
NUMBER OF STOREYS: ● DELUGE WATER SPRAY FIXED SYSTEM POWER TRANSFORMER & AUX. TRANS. & RECOMMENDATIONS. DISCHARGE TIME: 10 Seconds
NFPA-2001,KM SPECIFICATION
● FOAM SYSTEM _________________ 6. ALL CABLING TO COMPLY WITH NFPA 70.
66/11 kV- SUBSTATION BASEMENT, GROUND & ROOF FLOOR STOREY BUILDING 7. THE BACKUP BATTERY SHALL MAINTAIN THE SYSTEM IN NORMAL WORKING CONDITION FOR AT LEAST 24 HOURS. DESIGN CONCENTRATION: 7 %
● CLEAN AGENT SUPPRESSION SYSTEM IT SHALL BE CAPABLE OF SUPPLYING THE FULL EMERGENCY EVACUATION ALARM LOAD FOR AT LEAST 0.5 HOURS.
8. ADDITIONAL DETECTORS SHALL BE PROVIDED IN CASE IF IT IS REQUIRED AS PER SITE CONDITION.
DESIGN TEMPERATURE: 21 °C
9. MANUAL RELEASE STATIONS, ABORT SWITCHES, STATUS INDICATORS TO BE INSTALLED AT SWITCH LEVEL
● FIXED AEROSOL FIRE EXTINGUISHER SYSTEM _________________ NOT LESS THAN 1.07M AND NOT MORE THAN 1.22M ABOVE FFL ACCORDING TO NFPA72.
DESCRIPTION OF EACH LEVELS
10. AUDIBLE & VISUAL ALARMS TO BE INSTALLED 2.25M ABOVE FFL. UNLESS OTHERWISE NOTED.
SUMMARY OF AREAS SERVED BY CLEAN AGENT
● KITCHEN HOOD SUPPRESSION SYSTEM _________________ 11. END OF LINE RESISTORS TO BE INSTALLED ON THE WALL AT 1.4M ABOVE FFL.
1. BASEMENT LEVEL - ELECTRICAL CABLES ON FLOOR & ELECTRICAL CABLE TRAYS. 12. WARNING FLASH LIGHT ARE PROVIDED AT ALL DOORS WHICH ARE PROTECTED BY CLEAN AGENT EXTINGUISHING SYSTEM. ROOM INFORMATION ROOM NAMES
13. MINIMUM DESIGN CONCENTRATION TO BE USED IS 7.0%.
14. WARNING/CAUTION SIGN BOARD SHALL BE PROVIDED OUTSIDE THE PROTECTED AREA. FLOOR LEVEL CONTROL & RELAY PANEL ROOM LV AC/DC PANEL ROOM
2. GROUND LEVEL - 15. FOR EFFECTIVE TOTAL FLOODING OF FM200 CLEAN AGENT EXTINGUISHING SYSTEM,
DESIGN CONCENTRATION IS TO BE ATTAINED AT DISCHARGE & AGENT IS TO BE MAINTAINED FOR 10 MINUTES HOLD TIME. GRID LINE REFERENCE 3 TO 4 / A TO 1 1 TO 3 / F TO I
16. HAZARD VOLUME TO BE AIR TIGHT. SUPPLY & RETURN AIR PATHS IS TO CLOSED AT FIRST STAGE ALARM.
17. ALL MANUAL RELEASE STATIONS SHALL BE HOUSED WITH WEATHER PROOF ENCLOSURE SHEET REFERENCE 11 OF 26 13 OF 26
IF INSTALLED IN AREAS OPEN TO ATMOSPHERE.
3. FIRST LEVEL - ROOM AREA (M²) 244.79 94.55
18. ALL LOW PRESSURE SWITCH SIGNALS SHALL BE CLUBBED TOGETHER AND SEND AS A COMMON SIGNAL
TO THE EXTINGUISHING CONTROL PANEL.
ROOM / FLOOR HEIGHT (M) 4.55 4.55
4. ROOF LEVEL - MEP SERVICE EQUIPMENTS 19. CLEAN AGENT PRESSURE OPERATING SWITCHES SENT THE SIGNALS ACROSS TO FSCP PANEL AND
ALSO TO FIRE ALARM CONTROL PANEL. ROOM / FLOOR VOLUME (M³) 1113.81 430.21
20. THE LOCATION OF EXTINGUISHER SHOWN ON THE DRAWING MAY SLIGHTLY VARY AS PER SITE CONDITION.
MATERIALS ENTRY 21. FIRE EXTINGUISHER IS DESIGNED AS PER THE GUIDE LINES MENTIONED IN NFPA 10,KM SPECIFICATION AND QCDD. ESTIMATED CAPACITY (KG) 705.5 274.5
ANCILLARY BUILDING - FIRE PUMP ROOM & GUARD ROOM SPRINKLER
DIMENSIONS AREA (COMBUSTIBLE OR (ACCESSIBLE OR 22. FIRE EXTINGUISHER SHALL BE MOUNTED ON WALLS AND THE TOP SURFACE NOT MORE THAN 1.5MTS.
(YES / NO)
NON-COMBUSTIBLE) NON-ACCESSIBLE) EACH OF THIS LOCATIONS ON THE WALL SHALL BE MARK "FIRE POINT"IN ENGLISH & ARABIC. NO. OF CYLINDERS &
23. FIRE SHELTER SHALL BE CONNECTED TO THE ROAD/SIDE WALK. CAPACITY PER CYLINDER(KG)
4 / 93.5 & 3 / 110.5 3 / 91.5 APPROVING AUTHORITY
BUILDING CLASSIFICATION : PREVIOUS QCD PLAN APPROVAL REF. NOS.:
<400MM HEIGHT - - - - PS NUMBER : N/2019/0002807 PREVIOUS PS NUMBER :
(HABITABLE HEIGHT)
FF DESIGN CRITERIA FOR WATER SPRAY FIXED SYSTEMS
HIGH-RISE BUILDING (28m) FSD/PS/N/M/R ___________________ >400MM - <800MM - - - - DELUGE WATER SPRAY SYSTEM
HEIGHT
EQUIPMENT PROTECTED: 40MVA POWER TRANSFORMER SHEET REFERENCE / DRAWING NUMBER: SHEET 20 OF 31 / FF-401 CONSULTANT'S ENDORSEMENT
1. ALL DIMENSION ARE IN (MM) MILLIMETER UNLESS OTHERWISE SPECIFIED.
MID-RISE BUILDING (>15m - <28m) N/A FLOOR LEVEL: GROUND FLOOR SPECIFIED AREA OF OPERATION: 40MVA TRANSFORMER -3
- - - - 2. ALL ABOVE GROUND PIPING TO BE SUPPORTED PROPERLY.
LOW-RISE BUILDING (<15m) >800MM HEIGHT I ILAYARAJA NEDUNCHEZIAN NEDUNCHEZIAN AMECHANICAL ENGINEER WITH
3. ALL UNDERGROUND PIPING TO BE PROVIDED IN THE RCC TRENCH (RCC TRENCH BY OTHERS). DELUGE VALVE TAGGING: DV-4 MOST REMOTE
N/A 4. ALL EXTERNAL PIPES WILL BE SEAMLESS SCH.40 ASTM A53, GRADE-B;
UPDA REGISTRATION NO. 14191 AS GRADE "A" BEING THE CONSULTANT HEREBY
REMOTEST NOZZLES ELEVATION DIFFERENCE FROM PUMP SUCTION(M): 4.265 MOST DEMAND
HOT DIPPED GALVANIZE AND RED POWDER COATED. CERTIFY THAT THE FIREFIGHTING SYSTEM SHOWN ON THESE PLANS HAS BEEN
5. ALL INTERNAL PIPES WILL BE SEAMLESS SCH.40 ASTM A53, GRADE-B; TYPE OS SPRINKLER SYSTEM: DESIGNED IN ACCORDANCE WITH THE PROVISIONS OF NFPA
HOT DIPPED GALVANIZE AND RED PAINTED. 10,13,14,15,20,101,170,2001 and 5000 AND LOCAL FIRE SAFETY CODES OR
REFERENCE:
6. PIPES & FITTINGS THREADED UPTO Ø50 mm & GROOVED/WELDED FROM Ø65 mm & ABOVE. CRITERIA VALUE UNIT STD. / CODE / CHAPTER
7. FIRE PROTECTION SYSTEM DESIGN AS PER GUIDE LINES MENTIONED IN SECTION / TABLE / FIGURE
STANDARDS BEING IMPOSED BY QATAR CIVIL DEFENSE.
NFPA.13,14, 15, 20, 22, KM TECHNICAL SPECIFICATION AND QCDD REQUIREMENTS. OCCUPANCY: SPECIAL INDUSTRIAL NA
8. ALL DRAIN VALVES TO BE CONNECTED TO NEAREST DRAIN PIT.
FURTHER, I CERTIFY THAT I AM FULLY AWARE AND COMMIT MYSELF RESPONSIBLE
9. ALL DIMENSION INDICATED IN DRAWING SHALL BE VERIFIED AT SITE BEFORE FABRICATION.
HAZARD CLASSIFICATION: ORDINARY NA TO THIS PROJECT AND ALL THE CONDITIONS PRESCRIBED UNDER THE EXISTING
SYSTEM ACTUATION VALVE: DELUGE VALVE NA LAW NO.19 OF 2005, THE LAW REGULATING THE PRACTICE OF ENGINEERING
PROFESSION IN THE STATE OF QATAR.
EQUIPMENT/HAZARD TO BE NA
POWER TRANSFORMER
PROTECTED:
AFFIXED IS MY SIGNATURE TO ATTEST WITH THE ABOVE UNDERTAKINGS.
DESIGN AREA / NET SURFACE AREA 140 M²
EOL 9. THEN, THE MAIN DRAIN AND ALL SYSTEM DRAINS ARE OPENED TO DRAIN THE SYSTEM. FIRE PUMP & FIRE WATER TANK
RE 10. AFTER WATER CEASES TO DISCHARGE, CLOSE THE AUXILIARY DRAINS. KEEP THE MAIN
DRAIN OPEN. PROJECT TITLE
11. RESET THE WET PILOT ACTUATION SYSTEM, BY REPLACING ANY OPERATED PILOT
SPRINKLERS.
12. OPEN THE DIAPHRAGM CHAMBER SUPPLY VALVE SO THE DIAPHRAGM CHAMBER CAN
BEGIN TO FULL PRESSURE.
13. THE DIAPHRAGM CHAMBER WILL COMPLETELY CLOSE ONCE THE CHAMBER RETURNS TO
FULL PRESSURE.
14. FINALLY, SLOWLY OPEN THE MAIN SUPPLY VALVE AND CLOSE THE MAIN DRAIN ONCE WATER MOTOR
BEGINS TO DISCHARGE FROM THE DRAIN. UNIT CAPACITY TOTAL HEAD DESCRIPTION
EQUIPMENT LOCATION
CLEAN AGENT FIRE SUPPRESSION SYSTEM TAG (GPM) (bars) (TYPE)
HP VOLTS PHASE HZ
I. AUTOMATIC OPERATION
A. ACTUATION OF 1ST DETECTOR WITHIN THE SYSTEM WILL: ELECTRIC GND - FIRE HORIZONTAL
EFP 75 415 3 50 750 8.2
1. ILLUMINATE "ALARM" LAMP ON THE CONTROL PANEL. FIRE PUMP PUMP ROOM SPLIT CASE
AREA OF STATEMENT ABBREVIATION 2. ACTIVATE ALARM BELL INSIDE THE ROOM. (1st STAGE) DIESEL ENGINE GND - FIRE HORIZONTAL
3. SEND PRE-ALARM SIGNAL TO FACP. DFP
FIRE PUMP
115 230 1 50 750 8.2
PUMP ROOM SPLIT CASE
4. SEND SIGNAL TO CLOSE ASSOCIATED FIRE DAMPER OR SHUT DOWN HVAC.
Z ZONE E ENCLOSURE JOCKEY GND - FIRE VERTICAL
B. ACTUATION OF 2ND DETECTOR WITHIN THE SYSTEM WILL: JP 2 415 3 50 15 8.7
PUMP PUMP ROOM MULTISTAGE
D DETECTOR N NOZZLE 1. ILLUMINATE "PRE-DISCHARGE" INDICATOR ON THE FSCP.
2. ACTIVATE HORN STROBES (VISUAL & AUDIO ALARMS) INSIDE & OUTSIDE THE ROOM.
FSCP FIRE SUPPRESSION CONTROL PANEL PS PIPE SUPPORT 3. ENABLE PRE-DISCHARGE TIME DELAY (60 SEC.). LOCATION : INDUSTRIAL AREA PIN : 81050420
4. ENABLED SYSTEM ABORT SEQUENCE.
FACP FIRE ALARM CONTROL PANEL FFL FINISHED FLOOR LEVEL. STREET :
FIRE WATER TANK
AREA : 5500.00 m² PLOT :
IRM IMPULSE RELEASE MODULE EL ELEVATION. C. AFTER PRE-SET TIME DELAY SEQUENCE, THE FOLLOWING SHALL OCCUR:
TYPE OF NO. OF EFFECTIVE
1. ACTUATE CIRCUIT TO RELEASE HFC 227 AGENT TO THE AFFECTED AREA. LOCATION EFFECTIVE DURATION DRAWING TITLE:
CHM CONTROL HEAD MONITOR FWL FINISHED WALKWAY LEVEL. CONSTRUCTION COMPARTMENTS CAPACITY
2. ILLUMINATE "RELEASE" INDICATOR ON THE FSCP.
20 MINUTES.
RP RELAY PANEL FRL FINISHED ROAD LEVEL. 3. SEND RELEASE SIGNAL TO FACP. GROUND FLOOR GALVANIZED STEEL & BOLTED 30.00 CU. M EACH
2 NOS. (AS PER KAHRAMAA
(BESIDE PUMP ROOM) SECTIONAL WITH LINER (60.00 CU. M TOTAL)
REQUIREMENTS)
II. MANUAL OPERATION
POCH PRESSURE OPERATED CONTROL HEAD FGL FINISH GROUND LEVEL.
A. ACTIVATION OF MANUAL RELEASE STATION SHALL:
1. ALL OPERATION OF B & C AS DESCRIBED ABOVE EXCEPT TIME DELAY AND ABORT FUNCTION.
LPS LOW PRESSURE SWITCH RI REMOTE INDICATOR B. ACTIVATION OF MANUAL RELEASE ON THE CYLINDER VALVE SHALL:
BOTTOM OF SLEEVE
1. ALL OPERATION OF B & C AS DESCRIBED ABOVE EXCEPT TIME DELAY AND ABORT FUNCTION. DELUGE WATER SYSTEM GENERAL NOTES & LEGENDS
BOS SLC SIGNALING LINE CERCUIT
III. ABORT OPERATION COVER PAGE
A. IF ABORT SWITCH IS ACTIVATED WITHIN PRE-DISCHARGE PERIOD, THE FOLLOWING SHALL OCCUR;
1. ABORT INDICATION ON THE FSCP.
2. RELEASE OF AGENT IS HELD IF ABORT SWITCH IS PRESSED CONTENTIOUSLY.
3. AGENT WILL RELEASE IF ABORT SWITCH IS DEACTIVATED & COUNT DOWN IS COMPLETED.