The rectifier provides 1350 W down to 21 VDC and 230 VAC nominal
input voltage.
FLATPACK 1500 24 V OTHER SPECIFICATIONS
Efficiency > 88%
Isolation 3.0 KVAC – input and output
SPECIFICATIONS 1.5 KVAC – input earth
1.0 KVDC – input earth
INPUT Rectifier Alarm Mains failure
Module failure
Input voltage 85-310 VAC*
Overvoltage shutdown
Frequency 45 to 66Hz Fan Failure
Maximum Current 8.5 Arms maximum at 185 Visual Green LED: ON, no faults
VAC and 1350 W output indications Red LED: Rectifier failure
Power factor > 0.99 at 50% load or more Yellow LED bargraph: 10 LEDs
Input protection Soft start showing load current (0-100%)
Surge protection (varistors) Operating temp -40 to +70°C (-40 to +158°F)
Internal fuses (L & N) Storage temp -40 to +85°C (-40 to +185°F)
Automatic disconnect at 310 Cooling 2 fans (front to back airflow)
VAC Brushless w/ magnetic bearing
OUTPUT MTBF > 213,600 hours Telcordia Issue I,
Voltage 24 VDC (range: 20-29,5 VDC) method III (a)
Output power 1350 W at 185-275 VAC Acoustic Noise < 55dBA
derate at lower input Humidity Operating:
voltages. 5% to 95% RH non-condensing
Maximum current 64 Amps at 21 VDC Storage:
(230 VAC nom.) 0% to 99% RH non-condensing
Current share ± 2 Amps from true average Dimensions 214 x 41.5 x 243mm (wxhxd)
current between modules (8.43 x 1.64 x 9.57”)
(4 Amps overall) Weight 2.8kg (6,17lbs)
Static voltage ±0.5% from 0 to full load APPLICABLE STANDARDS
regulation Electrical safety EN 60950
Dynamic voltage ±1.0% for 10-90% or 90- UL 60950
regulation 10% load variation < 10ms EMC ETSI EN 300 386 V.1.3.1
Hold up time > 20ms (telecommunication network)
Ripple and Noise < 100 mV peak to peak, EN 61000-6-3
30 MHz bandwith (emission, light industry)
< 0.96mV rms psophometric EN 61000-6-2
Output Protection Overvoltage shutdown (immunity, industry)
Blocking diode Telcordia GR1089 CORE
Short circuit proof Harmonics EN 61000-3-2
High temperature protection Environment ETSI EN 300 019-2
ETSI EN 300 132-2
Telcordia GR63 CORE Zone 4
*Above 275 VAC some parameters may vary outside given values. Specifications are subject to change without notice.
ORDERING INFORMATION
Part no. Description
241114.300 Flatpack 1500 24V rectifier module
241114.300.DS3 v.01