Checklist For Const Building Supervisors PDF
Checklist For Const Building Supervisors PDF
Checklist For Const Building Supervisors PDF
CHECK – LIST
FOREWORD
The Proclamation to define the powers and duties of the Federal and Regional Executive
organs of the Federal Democratic republic of Ethiopia No. 4/1995 empowers the Ministry of
Works & Urban Development to prepare the Country's Building Code, issue Standards and
Guidelines for design and construction works, registration of professionals and consultants and
follow up and supervise the implementation of same.
In exercising these powers and in discharging of its responsibilities, the Ministry is issuing a
series of Building Code Standards, Manuals and Guidelines of general application.
The purpose of these documents is to serve as nationally recognized documents, the application
of which is deemed to ensure compliance of constructions with the minimum requirements for
design, procurement procedures, construction and quality of materials set down by the
Ministry.
The major benefits to be gained in applying these documents are the harmonization of
professional practice and the ensuring of appropriate levels of safety, health and economy with
due consideration of the objective conditions and needs of the country.
As the documents are technical documents which, by their very nature, require periodic
updating, revised editions will be issued by the Ministry from time to time as appropriate.
The Ministry welcomes comments and suggestions on all aspect of the documents. All
feedback received will be carefully reviewed by professional experts in the field with a view to
possible incorporation of amendments in the future editions.
Haile Assegide
Minister
Ministry of Works and
Urban Development
2001
PREFACE
This check-list for site supervisors is issued by the Ministry of Works and Urban Development for
use by Employers, Consultants and Contractors in order to ensure a uniform system of supervision
of building construction projects and as a result ensure a safe and durable construction. It is to be of
use mainly when construction works are carried out by contractors and can in some ways be of use
for construction carried out by direct labour. In this check-list the responsibilities, liabilities and
limitations of the supervisor are briefly mentioned. The steps to be followed in checking building
construction works are expressed in general terms. Details of construction are specified in the
drawings, technical specifications and in the general and special provisions of the contract. The duty
of the site supervisor is to ensure that the construction works are executed in accordance with the
contract requirements. Therefore in the application of this check-list the details specified in the
contract document always precede before the application and use of it. There are also tables and
forms in this check-list that help as records of the incidences affecting the work and as references. In
addition the standard technical specification is used as reference on the preparation of this check-
list.
ACKNOWLEDGEMENT
In July 2000, the Ministry of Works and Urban Development invited National
Consulting firms to compete for the preparation of codes and manuals. One of
these, is the present " ______________________"
TABLE OF CONTENTS
PAGE
FORWARD ……………………………………………………………………… 1
PREFACE .............................................................................................................. 2
ACKNOWLEDGEMENT ...................................................................................... 3
1. INVESTIGATION & PREPARATION OF SITE ...................................................... 6
2. SETTING OUT .......................................................................................................... 6
3. EXCAVATION & EARTHWORK ............................................................................ 6
4. FOUNDATION TRENCH & PIT EXCAVATION .................................................... 7
5. FOUNDATION IN STONE MASONRY .................................................................. 8
6. BACK FILLING .......................................................................................................... 8
7. HARD CORE .............................................................................................................. 9
8. CONCRETE ................................................................................................................ 9
9. PRESTRESSED CONCRETE ................................................................................... 13
10. FORM WORK ............................................................................................................ 14
11. STEEL REINFORCEMENT ..................................................................................... 16
12. MORTAR .................................................................................................................. 17
13. STONE MASONRY .................................................................................................. 17
14. HOLLOW CONCRETE BLOCK WALL ................................................................. 18
15. WALLS WITH BRICKS ............................................................................................ 19
16. WOODEN WALLS .................................................................................................... 20
17. PLASTER AND POINTING ...................................................................................... 20
18. STRUCTURAL STEEL WORK ................................................................................ 20
19. PAVIOR (TILES PAVIOR) ........................................................................................ 22
20. WALL TILES ............................................................................................................. 22
21. P. V. C. TILES ............................................................................................................ 22
22. ROOFING AND CLADDING .................................................................................... 23
23. GUTTERS AND DOWN PIPES ................................................................................ 24
24. CARPENTRY AND JOINERY.................................................................................. 24
25. CEILING ..................................................................................................................... 25
26. PAINTING .................................................................................................................. 25
27. GLAZING ................................................................................................................... 26
28. WATER WELL .......................................................................................................... 26
29. WATER SUPPLY LINES .......................................................................................... 26
30. PLUMBING AND SANITARY INSTALLATIONS ................................................ 26
31 SEWER SYSTEM ..................................................................................................... 27
32. SEPTIC TANK & SOAK AWAY PIT ...................................................................... 28
33. ELECTRICAL INSTALLATIONS ........................................................................... 28
34. RETAINING WALLS ............................................................................................... 29
35. SITE WORK .............................................................................................................. 30
36. ROAD AND FOOTPATHS....................................................................................... 30
37. DRAIN CHANNELS & CULVERTS ....................................................................... 31
38. FENCING AND GATE ............................................................................................. 31
39. PREPARATION OF PAYMENT CERTIFICATES ................................................. 32
TABLE OF CONTENTS
CHECK:
1.2 The site on maps showing the location of underground structures and utilities to avoid
breaking them during construction.
1.3 The site plan and layout of buildings and sewer system specially concerning levels and soil
condition. If changes are necessary submit a written report to the designer.
1.5 The trees and bushes within the foundation to be cut and rooted up as given in the standard
technical specification.
1.6 Permission is obtained from local authorities to cut down trees outside the foundation areas.
1.7 Boarder lines are agreed with local municipality and corner stones placed.
1.8 The connection points for water and electricity are agreed upon with local authorities.
1.9 All necessary temporary drains are constructed to keep the site free of water.
2. SETTING OUT
CHECK:
2.1 The setting out is done correctly with proper measuring tape and accurate levelling
instrument.
2.2 All measurements to confirm the accuracy and correct locations of working areas are
properly stated out.
2.3 The elevation reference point in accordance with the survey map, and confirm.
2.4 All bottom of trenches and floor levels are according to the elevations shown on the
drawings.
3.2 Decide the place to pile up the suitable excavated material and check it is 2 meters outside
the building perimeter.
3.3 Decide the place for the cart away which is not necessary for backfilling or terracing.
CHECK:
3.4 For sites where blasting is proposed, the explosives are used in the quantities and manner
recommended by the manufacturers. Check a written consent is obtained on each occasion
the contractor wished to use explosives.
3.5 All excavations are carried out to the lines, levels, widths and depths shown on the
drawings.
3.6 Any discrepancies in levels, dispositions etc. are reported to the engineer prior to
proceeding with the works.
3.7 All necessary temporary drains and culverts are constructed to keep the site free of water.
3.8 Slopes to embankments, cuttings, shoulders, ditches etc.; are trimmed to the dimensions
and inclinations shown on drawings.
3.9 Cut for roads is carried out until a level of suitable material is allowed.
3.10 Excavations are suitably trimmed and levelled before any concrete or masonry work is
placed.
3.11 In locations where the soil is subject to softening during excavation, a bottom layer of soil
removed immediately before the placing of concrete, in accordance with the standard
technical specification.
CHECK:
4.1 The foundation drawings to correspond with the conditions on the site, if not prepare a
written report and submit to the designer immediately.
4.2 The foundation depth, width, line and levels to correspond the drawings.
4.3 The excavation or foundation is executed 25cm. wider on each side than the thickness of
the foundation wall as given in the standard technical specification.
4.4 The trench and pits to be clean from grass, bushes and pieces of wood.
4.5 The trench and pits to be kept free of water by pumping or other means.
4.6 The foundation engineer has accepted the excavated foundation depths by filling form No.
005.
4.7 The foundation excavation is suitably trimmed and levelled before concrete or masonry
work in placed.
4.8 In the event of over excavation, without approval the area to be filled with selected
excavation or borrowed material or class 5 concrete in accordance with the standard
technical specification.
4.9 The faces of excavation is retained with sheeting, tim-bearing, strutting and shoring to
protect workmen and prevent damage where necessary.
CHECK:
5.1 The trench to be clean from grass, bushes and pieces of wood.
5.3 The stone to be hard, sound, free from cracks and decay and not weathered.
5.6 The stone masonry execution is with specified mortar and with well filled joints.
5.7 The stone masonry during execution is kept free from solid and other kind of dirt.
5.8 The length of stone does not exceed three times its height.
6. BACKFILLING
CHECK:
6.1 All internal back filling is done with approved material, if possible with material excavated
on the site.
6.2 All external backfilling around foundation walls and behind retaining walls shall be done
with approved selected materials, if possible with material excavated on the site which is
capable of being compacted and form a stable filling.
6.3 all organic materials, such as pieces of wood, roots, bushes and black cotton soil are
removed from all backfill material.
6.4 All ground trenches and places where backfilling shall be executed are clean from grass,
bushes and pieces of wood.
6.5 Where pipes and electrical cables are in connection with the backfilling, the work shall be
executed very carefully, so they do not break or get damaged.
6.6 All backfilling to be in layers and compacted to 95% of maximum dry density in
accordance with the standard technical specification.
6.7 Each layer to be well rammed and consolidated with the addition of water as necessary to
achieve the required compaction.
6.8 The maximum layer of fill for one time compaction does not exceed 20cm. thickness in
accordance with the standard technical specification.
6.9 Depressions or voids that are crated during trimming of slopes to embankments, cuttings,
shoulders, ditches etc.; are filled with suitable material and to approved compaction.
6.10 Any material which after repeated compaction does not fulfil the requirements is removed
and replaced.
7. HARD CORE
CHECK:
7.2 All stones in the hardcore are of approximately equal and recommended size.
7.3 All hardcore is well rammed and consolidated with the top surface blinded with crushed
aggregate of 20mm. thickness in accordance with the standard technical specification.
8. CONCRETE
CHECK:
8.1 All ingredients cement, aggregates and water are of the type and quality specified.
8.2 Cement is fresh, not older than six months and is delivered to the site in the manufacturer's
original sealed bags.
8.3 Cement is stored in a dry and well ventilated store, on a wooden floor raised minimum
20cm. above the ground.
8.5 The cement has markings showing the type and date of consignment pinned to it and check
it is used in the order of its arrival.
8.6 Cement more than six months old after production is tested to satisfy the specified
requirements.
8.7 Sand or fine aggregate to be clean river or pits sand of approved quality and consist of
hard, dense, durable uncoated rock fragments.
8.8 Sand to be clear of impurities like dust, mica and organic matter.
8.9 Rejected samples of aggregates are removed from the site within 24 hours.
8.11 Coarse aggregate to be hard, dense, durable non-porous and uncoated rock fragments.
8.12 Coarse aggregate to be free from impurities like clay, soft thin elongated or laminated
pieces and shall be free from alkali and organic matter.
8.13 The gradation of coarse aggregate to comply with the standard technical specification.
8.14 Before any coarse aggregate is delivered to the site, the quality is approved at the quarry by
the designer.
8.15 Aggregates are stored on clear hard surface to prevent contamination by soil.
8.17 Water used for mixing concrete is clean and free from injurious amounts of oil, acids,
alkalies, organic materials.
8.18 Water is not taken from sea or tidal rivers to be used for structural concrete. If possible
water shall be piped or otherwise stored in an enclosed container free from contamination.
8.19 If there are any doubts about the quality of the water a sample shall be sent to the designer
or engineer for testing.
8.20 If the temperature of the water exceeds 60°c it is first mixed with the aggregate before the
cement is added.
8.21 The concrete is mixed to a uniform colour and consistency prior to placing.
8.22 Hand mixing is not allowed but if unavoidable shall be used only for class II concrete and
shall under no circumstance be allowed for concrete of class C-200 and higher.
8.23 Concrete is mixed in an approved mechanical batch mixer machine, the mixer is
thoroughly cleaned from hardened concrete and other kind of dirt before use.
8.24 Mixer which has been out of use for more than 20 minutes is thoroughly washed before any
fresh concrete is mixed as specified in the standard technical specification.
8.25 The mixer drum is tight to avoid loss of mortar. The values must not leak mixing water.
8.26 The specified mixing time is carefully adhere to but in no case shall the mixing discontinue
for less than 2 minutes after adding water as specified in the standard technical
specification.
8.27 The batch capacity. The contractor must not be allowed to exceed the rated capacity of the
mixer.
8.29 The whole of the mixed batch is removed before materials for fresh batch enter the mixer.
8.30 Mixed concrete is not modified by the addition of extra water or cement, in order to
facilitate handling or any other purpose.
8.31 Before any casting starts at the site, test cubes of side dimension 15x15x15 or cylinders of
diameter 15cm and length 30cm of wood or steel are made ready.
8.32 All reinforcement and form work are properly placed prior to any concreting and the mix
approved and also check from No. 004 is filled and approved by the designer.
8.33 For any one structure samples are made at the same time from the same batch and the date
clearly marked on each cube.
8.34 Test cubes are made when directed but not less than one set of nine cubes for each 100m3
of concrete placed, or if the rate of placing is less than 100m3 then each 10 days or every
floor for multi-storey structures in accordance with the standard technical specifications.
8.35 Three cubes of each set are tested at 3 and 7 or 7 and 14 days and the third at 28 days all in
accordance with the code of practice.
8.36 In the absence of approved design mix that the standard mixes in Tables 8.5.3a and table
8.5.3b or the mix design given in the standard technical specification are followed.
8.37 Before any casting starts the consistency of fresh concrete must be measured using the
slump test, from the same batch for test cubes.
8.38 Concrete is son transported as rapidly as practicable and placed such that contamination,
segregation or loss of constituent materials does not occur.
8.39 All placing of concrete starts from one end and continue in the same direction without any
break.
8.40 Concrete is deposited as near as practicable and no concrete is dropped from a height
exceeding 2 meters as specified on the standard technical specification.
8.41 When chutings is used the inclination of the chute shall be such as to allow the concrete to
flow without the use of water in excess of the specified volume for mix and without
segregation or loss of the ingredients. Details of any proposed chuting plant must be
approved before the plant is delivered.
8.42 The vibration is carefully done, and continues until a dense homogeneous mass is produced
and surface is fairly smooth.
8.43 Concrete is not over vibrated so that the consistency of the concrete is maintained and
separation of materials is caused.
8.44 If construction joints are necessary they are approved by the designer.
8.45 When concrete casting continues on a construction joint, the joint is clean from foreign
matter.
8.46 When concrete casting continues on a construction joint, the surface of the joint is
roughened and aggregate is exposed without being damaged.
8.47 The roughened surface of the construction joint is wetted with thin layer of mortar prior to
concreting.
8.48 After casting is completed and for 7 days thereafter, that the concrete is kept damp (cured)
to minimize loss of moisture from the concrete.
8.49 Whenever testing of a material is required fill the requisition from No.005 and for the
evaluation of test result fill form No.006 and get the approval of the engineer or designer
when the result is submitted.
CHECK:
8.51 Pre cast concrete is cast under sheds and remain in the moulds for 3 days and further 7
days after removal from the moulds. Then removed from the sheds and stocked in the
open for at least 7 days to season.
8.52 Random load testing is made on the pre cast units and the damaged ones immediately
replaced.
8.53 Pre cast units and boisted and placed in proper position in such a way as to avoid over
stressing or damaging the units nor causing damage to previously erected structure.
8.54 If any doubt about the quality of, aggregatem dement, reinforcement and water arises
sample are sent for testing.
9. PRESTRESSED CONCRETE
CHECK:
9.1 All pre stressing components are stored in clean dry conditions.
9.2 All pre stressing components are clean and free from loose rust at the time of fixing in
position and subsequent concreting.
9.3 All pre stressing tendons are not welded within the length to be tensioned.
9.4 All pre stressing tendons (cables) are not twisted and individual wires or strands are
identifiable at each member.
9.5 All ducts and tendons are respectively sealed and protected until the tendon is threaded
through and the stressing operations are commenced.
9.6 All anchor cones, blocks and plates are positioned and maintained during concreting such
that the center line of the duct passes axially through the anchorage assembly.
9.7 All bearing surface of the anchorages are clean prior to concreting and tensioning.
9.8 The tendons immediately and during stressing do not exceed the strength specified.
9.9 Stressing is from both ends unless required or agreed by the engineer.
9.10 The tendons are anchored only if the pre stressing is applied to the satisfaction of the
engineer.
9.11 The jack pressure is released in such a way as to avoid shock to the anchorage or
tendons.
9.12 If the pull-in of the tendons at completion of anchoring is greater than that agreed by the
engineer, the load shall be released slowly and tensioning carried out afresh.
9.13 Sufficient test cubes are taken and specified transfer strength is attained.
9.14 The tendons are not cropped or cut prior to 3 days after grouting.
9.15 Full records of all tensioning operations including the measured extensions, pressure
guage or load all readings and the amount of pull-in at each anchorage, are kept.
9.16 All ducts are thoroughly cleaned by compressed air or method specified prior to
grouting.
9.20 Full records of grouting including the date each duct was grouted is kept.
9.21 The grout mixer produces a grout of colloidal and uniform consistency.
9.22 The grout is mixed for a minimum of two minutes unless otherwise specified.
9.23 No admixtures like chloride or nitrates are used. But if other admixtures may be used a
written permission must be submitted from the engineer and check it is applied strictly
with the manufacturer's instructions.
9.24 The gout consists only of ordinary port land cement and water unless otherwise
specified.
9.25 Pre stressed members are lifted or supported only at the points specified and handled
and placed without impact.
9.26 Beams are prevented from moving laterally during the placing of the in situ concrete.
9.27 The engineer informed in advance of the date of commencement of manufacture and the
dates when tensioning of tendons, casting of members and transfer of stress will be
undertaken for the first time for each type of beam.
9.28 All pre stressed concrete construction comply the standard technical specification.
CHECK:
10.1 Form work is so constructed that it can be stripped from the hardened concrete easily
without bammering or without such shock or vibration in order to protect the concrete
or reduce labour cost.
10.2 The bracing of the form work. The form work must be strong enough to carry the load
until the concrete is strong enough to carry itself and hardened sufficiently.
10.3 The inside surface of form works shall, except for permanent form works, or unless
otherwise agreed by the engineer, are coated with a release agent.
10.4 Release agents do not come into contact with the reinforcement and anchorages, and
should not be visible on the finished works.
10.5 Wooden form works for unexposed concrete surface, are executed of sawed boards with
sharp edges and of the same thickness.
10.6 Wooden form works for exposed concrete surface are generally of tongued and grooved
boards of the same thickness and free from knots, holes, cracks and splits.
10.7 Form work lumber shall be kept under shed and in varying thickness and width and
shall be constantly aerated and under weight to prevent it from decay.
10.8 Before any concreting starts, the form work has the right dimensions and is level and
straight.
10.9 Before any concreting starts, all forms are thoroughly cleaned out and free from holes
and dirt.
10.10 The top level of the form work is at the same level as the top of the finished concrete.
10.11 All form work is removed without any damage to the concrete during the striking.
10.12 After removal of the form work remedial treatment to surfaces of the hardened concrete
is carried out immediately without delay and period of removal is as follows:
10.13 Where intended to re-use form work it is thoroughly cleaned and made good to the
satisfaction of the engineer.
10.14 Stripping of form work not to be done until concrete is set i.e. should ring under a
hammer blow. In no circumstances shall form work be struck until the concrete attains a
cube strength of at least twice the stress to which it may be subjected at the time of
striking.
10.15 All form work construction and quality comply the standard technical specification.
CHECK:
11.1 Steel reinforcement is stored in clean condition. It should be free from loose rust.
11.2 All reinforcement bars are of the specified quality and in accordance with the standard
technical specification.
11.3 Given in the design in cases where certificates for ultimate tensile strength, yield stress,
elongation and cold bend tests are not issued by the manufacturers.
11.4 The dimension, length and shape of the reinforcement bars is according to the drawings
and specifications.
11.5 Bending of reinforcement bars is done with adequate bending tools. But heat is strictly
not allowed for bending of reinforcement bars.
11.6 All bars with cracks or splits at the bend are not used for construction.
11.7 All mild steels have their ends booked, and the bending radius meets the specification.
11.8 All reinforcement bars are clean and free from loose rust, grease, oil, or tar and other kind
of dirt.
11.9 The reinforcement bars are placed in position according to the drawings, and firmly
bound together with mild steel wire, diameter 1.6mm in accordance with the standard
technical specification.
11.10 Before any casting of concrete starts, that pre cast concrete blocks or spacers or metal
chairs are prepared and all reinforcement bars are placed on them.
11.11 These blocks or spacers do not turn over when concrete is casted.
11.12 The thickness of concrete cover is according to the requirements of the drawings and
specifications.
11.13 And approve the placing of the reinforcement and form work condition before any
concrete is casted.
11.14 The reinforcement in structures are not welded unless permitted by the designer.
11.15 All reinforcement quality and work comply the standard technical specification.
12. MORTAR
CHECK:
12.1 All mortar is if possible mixed in an approved mechanical batch miser. If not possible it
could be mixed by hand until its color and consistancy are uniform.
12.2 Lime for mortar is freshly burnt limestone. Lime shall be delivered to the site in large
lumps, slaked, run to putty and mature for not less than two weeks before use.
12.3 If hydraulic lime is used, it is stored in the same manner as described for cement.
12.4 Cement used in mortar is port land cement and of quality as described for concrete
works.
12.7 Cement mortar consists of cement and sand as specified. If not given in the
specification, check that cement mortar consists of one part cement to three parts of
sand (1:3) measured by volume.
12.8 Compo mortar consists of cement, lime and sand as specified. If not specified, check
that the compo mortar is composed of one part cement two parts of lime and nine parts
of sand (1:2:9) measured by volume.
CHECK:
13.2 The stone in hard, sound, free from cracks and decay and not weathered.
13.4 The stone masonry execution is with specified mortar and with well finished joints.
13.5 All mortar for stone masonry bedding and jointing is 20mm thick.
13.6 Stone masonry during execution is kept free from solid and other kind of dirt.
13.7 Stone walling is carried up with no portion more than 1000mm above adjacent wall at
any one time.
13.11 All stone masonry walling comply with the standard technical specification.
CHECK:
14.1 The hollow concrete blocks are free from laminations, cracks and other defects that
would impair the proper setting, strength or permanence of the construction.
14.2 The hollow concrete blocks are well compacted, properly cured and uniform colour and
texture.
14.3 The hollow concrete blocks manufactured on the site above the quality of cement and
aggregate as described for concrete works.
14.4 All blocks are manufactured in an approved special hollow block machine and under
shed.
14.5 Before any manufacturing in big scale starts on the site, test samples are made, cured
and sent for testing and test results are approved by the designer.
14.6 For curing of hollow blocks, that they are kept moist, at least for seven days after
casting.
14.7 That the blocks are properly dried under shade for at least 14 days before they are used
for construction.
14.8 Damaged or blocks with defects in the walls are replaced with good ones at the
expenses of the contractor.
14.9 Hollow blocks and the walls are kept free from soil and other kind of dirt during
execution.
14.10 All joints vertical and horizontal are well filled with specified mortar.
14.11 Walling is carried up with no portion more than 1000mm. above adjacent wall at any
one time.
14.13 That the joints and the walls are in plumb within 3m.
14.14 If the wall in designated as load bearing by the designer and special care in taken for the
execution of the work.
14.15 A minimum of 6 blocks per 1000 pcs. for site manufactured blocks are tested.
14.18 The drawings carefully before any wall construction if extra reinforcement or expansion
joints are prescribed.
14.19 The minimum compressive strength class A, class B and class C, hollow concrete
blocks in as follows according to the standard technical specification.
14.20 All hollow concrete block walling comply with the standard technical specification.
CHECK:
15.1 Bricks are not dumped on site but stocked in regular tires as they are unloaded.
15.2 Bricks to be used for different situations are stocked separately on a clean place.
15.3 Bricks are soaked in water for a minimum period of one hour before use.
15.4 Sample panels of not less than 1m2 for each type of brick.
15.5 All brick works are laid in good English bond even and true to line plumb within 3m,
level and all joints accurately kept.
15.6 All joints vertical and horizontal are well filled with specified mortar.
15.8 All bricks of the same dimensions are only used in the same wall.
15.9 Brick samples are taken at random from the load approved also manufacturers test
certificate submitted.
15.10 All brick walling comply with the standard technical specification.
CHECK:
16.1 The quality and dimensions of wood are according to specifications and drawings.
16.2 All wood for wall are well seasoned, fee from major knots, worms, splits and bends.
16.3 All wood for construction are stored free from the ground and well protected against
rain.
16.5 Dimension, placing and number of nails in according to drawings. Unless indicated on
the drawing no wood structure shall be joined.
CHECK:
17.1 The cement plaster and compo plaster quality mixture, thickness and type of surface are
according to the specification and drawing.
17.2 That cement plaster is used where water effect is expected such as in toilets, laundries
and external walls while compomortar is used in all cases unless otherwise specified.
17.3 Before any plaster is applied, the wall is thoroughly cleaned from dirt and dust.
17.5 The wall, depending on the material is kept wet for some time before any plaster
applied. It's not enough to sprinkle water just before plastering.
17.8 All plastering and pointing comply with the standard technical specification.
CHECK:
18.1 The shape and size of structural steel members comply with the requirements of the
specification and the manufacturers standards.
18.5 Production and assembly of steel in carried out in accordance with the detail drawings
and specifications.
18.6 Steel before and after fabrication is straight and free from twist or other damages.
18.9 Sheared or cropped edges are dressed to a neat machine work and are prepared for
welding finish.
18.11 The maximum gap for butt welded section in less that 3mm.
18.12 Each weld in continuous, sound and without interruption and free of creaters.
18.13 Slag in taken away immediately after welding and the weld cleared with metal brush.
18.14 All ends of rectangular, square and circular sections (DHS, CHS) are sealed by welding
to prevent ingress of moisture.
18.15 The steel structure is securely bolted to plates, channels or angle cleates during erection.
18.16 Direct bolting to sides of steel hollow sections in not carried on.
18.17 Holes for fixing electrical fittings, partitions etc. … are correctly positioned.
18.19 All structural steel ready to erect is prevented from water or dirt accumulated against
any of the surfaces.
18.20 All steel which will have concrete cast against them are clean and free from loose rust at
the time of concreting.
18.21 all structural steel work comply with the standard technical specification.
CHECK:
19.1 Before any paving starts, the mass concrete is completely free from standing water.
19.3 In the mass concrete surface immediately before the bedding is laid, a slurry of cement
and water is brushed, unless specified.
19.4 The bedding in of cement mortar, one part cement to four parts sand (1:4), and the slump
in 2-5cm and over.
19.6 The tiles are gently knocked down into the bedding so the mortar will be forced up in the
joints approximately 5mm.
19.7 When the bedding is hard enough usually after one day the joints which shall be 2-4mm
wide are filled with cement mortar.
19.9 The complete floor under construction is protected for the first 14 days and kept wet and
is protected against damage.
CHECK:-
20.1 Wall tiles are soaked in clean water before laying and taken out just before use.
20.2 Tiles are bedded with straight joints in cement and sand (1:3) and grouted in white
cement.
20.4 Only tiles free from defects are used for the construction.
CHECK:
21.1 P.V.C. tiles are laid on floor screeds with approved glue and in accordance with
manufacturer's instruction.
21.2 Only tiles free from defects are used for the construction.
21.3 Damaged tiles are replaced with good ones at the contractor's expense.
CHECK:
22.2 The surface of asbestos cement sheet is of uniform texture and smooth on one side.
22.3 The edges of asbestos cement sheets are square, straight and clean.
22.4 Asbestos cement sheet unless otherwise specified is 6mm thick when used for roofing.
22.6 Galvanized plain and corrugated sheets comply the manufacturer's specifications.
22.7 Steel hock bolts and nuts are zinc coated, the size and use of which shall be as per
manufacturer's instruction.
22.8 Fixing of roofing and flashing is made fully water tight and performed to the standard of
best workmanship.
22.9 Chiseler diamond adges and convex bend nails made of mild steel round wires are used to
fix galvanized steel sheet roofing and flashing to timber members.
22.10 Steel hock bolts and nuts are used to fix galvanized steel sheets and asbestos roofing to
steel and wooden truss members and purlins.
22.14 Sheets are laid with laps not less than 150mm.
22.16 Upper laps of sheets are constructed away from prevailing wind.
22.17 No person other than workmen in roofing have access to roof area.
22.18 All roofing work comply with the standard technical specification.
CHECK:
23.1 Gutters and down pipes are formed with the specified guage galvanized mild steel flat
sheet from suitable lengths and to shapes shown on the drawings.
23.2 Gutter hangers and down pipe supports are 2.25mm anti-rust painted flat sheet spaced at 1
meter center maximum unless otherwise specified.
23.4 Jointer of gutter after welding treated with three coats of zinc paint.
CHECK:
24.1 Timber for carpentry and joinery is as specified and of best quality.
24.2 Timber is reasonably straight grained and obtained from an approved sources.
24.3 And inspect the timber as it arrives, an timber not approved is removed forthwith.
24.5 Timber and assembled wood work are protected from rain and sun.
24.6 Timber and assembled wood work are stored in such away as to prevent attack by
termites, insects or decayed fungi.
24.7 Timber ready for use in free from live borer, beetle or other insect attack.
24.9 Timer in seasoned to moisture content of not more that 20% for Carpentary and 12% for
joinery.
24.10 All timber surface exposed by cutting are treated with three coats of approved
preservations.
24.11 All pressure impregnated timber is treated with preservative chemicals at a pressure of
not less than 10 atmospheres and in accordance with the chemical manufacturers
instruction.
24.12 Fixed joinery is completely protected from damage until the completion of the
construction.
24.13 Profile of sections is not modified from those shown on drawings without approval.
24.14 Right type of door is fixed in the right place and that the doors awing in accordance to the
drawings.
24.15 Door frames and window frames are fixed straight and in plumb.
24.16 Hinges, locks, latches and handles are of approved type and properly fixed.
24.17 Window panels are of the right thickness and properly fixed.
24.18 All carpentry and joinery to comply with the standard technical specification.
25. CEILING
CHECK:
25.1 Material and dimensions are according to the specifications and the drawings.
25.2 Before any mounting, painting of parts in connection with the ceiling such as steel guides
and walls, is completed.
25.3 The ceiling in cleaned and well fixed when the work is completed.
26. PAINTING
CHECK:
26.1 The kind of paints in according to the specifications and designer's instructions.
26.5 All surface to be painted is absolutely dry and free from defects before painting.
26.6 All brushes and tins used for painting are clean and free from old paint.
26.8 All electrical appliances, iron and brass works are removed before painting and properly
refixed after painting.
27. GLAZING
CHECK:
27.2 The type and thickness of glass is according to the specifications and drawings.
CHECK:
28.1 The water well is dug according to the specifications and drawings, if possible dug during
the dry season.
28.2 If septic tanks, soak away pits and dry latrines are situated nearby and inform the designer
to change the position of the wall.
28.3 The water is tested and approved after the digging is completed.
28.4 The masonry work is not started before the test result is known and approved.
CHECK:
29.1 The dimensions and types, tubes valves and water tower is according to the specifications
and drawings.
29.2 All valves, unless otherwise specified is buried in the ground to a minimum depth of
30cm.
29.4 Inspect and approve the supply line before any back filling starts.
CHECK:
30.1 Dimensions and types of pipes, tubes, valves and sanitary ware is according to the
specification and drawings.
30.2 All pipes and tubes to be installed in the floor are placed in position.
30.6 All connection between sanitary ware and sewer system is done with the prescribed
syphon.
30.7 All exposed pipes and tubes are well cleaned and painted as specified.
30.8 All sanitary work comply with the standard technical specification.
CHECK:
31.1 Dimensions and types of pipes and inspection pits is according to the specifications and
the drawings.
31.2 The excavation measurements of the sewer lines is according to the drawings.
31.5 Unless otherwise specified, the pipes are laid on a sand bed with a minimum thickness of
10cm and in an absolutely straight line with an even slope of minimum 1:100 and
covering soil layer is minimum 50cm.
31.6 The joining of concrete to pipes is always done with cement mortar, the joint completely
filled all around.
31.7 Joining of asbestos cement pipes is done according to the manufacturer's instruction.
31.9 All pipes connected to the inspection pit come approximately on the same level and check
channel formed in concrete at the bottom of the pit.
31.10 Back fill soil is of good quality, free from stones and it is not top soil.
31.11 Back filling is in layers of minimum 20cm, if vibrating or roller machine is used the
thickness of the layer can be 40cm unless otherwise specified.
31.12 Each layer of back fill is well rammed and consolidated with the addition of water if
necessary.
31.13 The correct position of the water and sewer systems and prepare a sketch on the site plan
to send to the designer for preparing drawings showing their correct positions as built on
site.
31.14 Measure the correct lengths of all trenches, of all tubes and pipes.
CHECK:
32.1 Dimension and type of septic tank and soak away pit is according to the specifications
and drawings.
32.2 The position of septic tank and soak away pit if situated nearby water wells, and inform
the designer for the change of the positions.
32.3 Level of overflow pipes between different chambers and inlet and outlet pipes are
according to the drawings.
32.4 all plastering in and out, is with cement plaster with thickness and mixture according to
specifications and drawings.
CHECK:
33.2 Materials to be used for the installation strictly follow the specifications and the drawings.
33.3 The electrical subcontractor has a valid certificate issued by EELPA before he starts his
work and his foreman is competent.
33.4 The conduits are free from defects and cover the wires all the way.
33.5 All switches and outlets are properly fixed according to the drawings.
33.7 All external cables are placed with a minimum 10cm depth in concrete or asbestos
cement pipes and 40cm depth in the ground, unless otherwise specified.
33.9 The inspection pits are constructed every 30cm unless otherwise specified.
33.12 The joining of asbestos cement pipes is done with cement mortar, the joint completely
filled around.
33.13 The joining of asbestos cement pipes is done according to the manufacturer's instructions.
33.14 The inspection pits, pipes and joints before back filling.
33.15 The back fill soil is of good quality, free from stones and it is not top soil.
33.16 The back filling is in layers of minimum 20cm if vibrating or rolled machine is used the
thickness of the layer can be 40cm unless otherwise specified.
33.17 Each layer of back fill is well rammed and consolidated with the addition of water if
necessary.
33.18 All underground cable joining are done in special water-tight junction box approved by
EELPA or designated professional.
33.19 All junction boxes used are placed in the inspection pits.
33.21 The correct position of external cables and pits and prepare a sketch on the site plan to
send to the designer for preparing drawings showing their correct positions as built on
site.
33.22 All electrical installation comply with the standard technical specification.
CHECK:
34.1 The trench to be free from loose soil, roots and pieces of wood before construction.
34.2 The depth and width of trench to correspond with the drawing.
34.4 All stones and the wall are kept free from soil and other kind of dirt during execution.
34.8 All retaining wall construction comply with the standard technical specification.
35. SITE WORK
CHECK:
35.1 The clearing of buildings is up to 2 meters from elevation walls on all sides, and check
thin limit is approved by the designer.
35.2 The clearing for roads, footpaths and parking areas is up to 1 meter from their boundaries
and check this limit is approved by the designer.
35.3 All roots are taken out within the building area, under roads footpaths and parking lots
and transported away from the site.
35.4 The place for the down trees and check they are within the building site.
35.6 And decide the place to pile up the excavated to soil and check it is 2 meters outside the
building perimeter.
35.7 And decide the place for the cart away which is not necessary for back filling or terracing.
35.8 All back filling and terracing is done in layers not exceeding 20cm and if vibrating or
roller machine is used the thickness must be 40cm.
35.9 Each layer of back filling and terracing is well rammed and consolidated.
35.11 All site work comply with the standard technical specification.
CHECK:
36.1 Excavation for roads footpaths is executed to bottom of footpaths is executed to bottom
of hard core.
36.2 Back filling for roads and foot paths is done with non expansive selected material.
36.3 All back filling is done in layers not exceeding 20cm and if vibrating or roller machine is
used the thickness must be 40cm.
36.4 Each layer of back filling is well rammed and consolidated with addition of water if
necessary.
36.5 Before back filling starts the ground is free from top soil, grass, bushes, roots and pieces
of wood.
36.7 All stones in the hard core are of approximately equal size.
36.8 The hard core is well rammed, consolidated and the top tightened with crushed stones or
gravel.
36.10 The hard cores as well as the top surface is executed with a minimum slope of 1:100
towards the sides.
36.11 The top surface is executed with material on the specification or drawings.
CHECK:
37.2 Drain channels to have a minimum slope of 1:200, unless otherwise specified.
37.3 Stone channels to be on a bed hard-core or well compacted gravel with joints and
pointing in cement mortar (1:3).
37.4 Channels of half-concrete pipes are on a well compacted layer of fine aggregate with a
thickness not less than 10cm.
37.5 Half-concrete pipes are laid in and joined with cement mortar (1:3).
37.6 Stone channels and culverts are constructed according to the drawings and specifications.
37.7 All pipes are laid so that each one is in contact with the bed throughout the length of its
CHECK:
38.1 The type of fence and gate are according to the specifications and drawings.
38.2 The foundations of fence and gate is according to the specifications and drawings.
40.1 Check a site book is kept for any construction work and the following information is
included:
dates on which excavation, concreting, stripping of form work, back filling, site work
has taken place.
acceptance of materials an components
results of tests and measurements
type of cement and aggregate
inspection and measurement reports of the positioning of reinforcement.
important instruction received.
description of any incidents.
Table 8.5.3a Standard Mixes for Ordinary Structural Concrete per 50kg Bags of Cement
(ESCP 2 : Part 1: 1983)
C30 Total Aggregate (kg) 235 215 210 190 195 170 180 150
Fine Aggregate (%) 30-35 30-40 30-40 35-45 35-45 40-50 40-50 45-55
Vol. of finished concrete (m3) 0.134 0.127 0.124 0.115 0.115 0.106 0.109 0.097
A - 40x50x20
B - 40x50x18
C - 40x50x16
The Contractor, therefore, acknowledges the taking over of the site and immediately the work with
all its explanation clearly defined in the specification and drawings (sketches).
The Contractor, hereinafter, shall be responsible for the damages that occur as a result of his fault,
carelessness or negligence in connection with untimely commencement of the work.
The Contractor, in addition, acknowledges the completion of the said work shall count as from the
date mentioned above and comply with the terms and conditions of the Contract to the Contract to
the satisfaction of the Client.
IN WITNESS HEREOF THIS DOCUMENT HAS BEEN SIGNED BY ALL PRESENCE IN SIX
COPIES OF WHICH THE CLIENT HAS ONE, THE SUPERVISOR ONE, THE
CONTRACTOR ONE, AND THE BUILDING DESIGN ENTERPRISE THREE.
_____________________________ ___________________________
FOR THE CLIENT (EMPLOYER) THE CONTRACTOR
WITNESS
1. _____________________ 1. ___________________
2. _____________________ 2. ___________________
3. _____________________ 3. ___________________
ACQUISITION OF DOCUMENTS
PROJECT : ___________________________________________________
SITE : ___________________________________________________
EMPLOYER : ___________________________________________________
CONTRACTOR : ___________________________________________________
SUPERVISOR : ___________________________________________________
This is to acknowledge that I have received the following set of documents concerning the
project.
______________________________ ___________________________
DATE: ______________________________
PROJECT : ____________________________________________________
SITE : ____________________________________________________
EMPLOYER : ____________________________________________________
CONTRACTOR : ____________________________________________________
SUPERVISOR : ____________________________________________________
REQUIRED TEST
APPROVED BY _____________________________________________________
CONSULTANT OR DESIGNER
DATE _____________________
PROJECT : ___________________________________________________
SITE : ___________________________________________________
EMPLOYER : ___________________________________________________
CONTRACTOR : ___________________________________________________
SUPERVISOR : ___________________________________________________
APPROVED BY : _____________________________________________
CONSULTANT OR DESIGNER
C.C To Site Supervisor
To Contractor
To Employer
PROJECT : _____________________________________________________
SITE : _____________________________________________________
EMPLOYER : _____________________________________________________
CONTRACTOR : _____________________________________________________
SUPERVISOR : _____________________________________________________
RECOMMENDATION OF
FOUNDATION ENGINEER ___________________________________________________
____________________________________________________________________________
INSTRUCTION PASSED TO
THE CONTRACTOR ____________________________________________________
_____________________________________________________________________________
ACKNOWLEDGEMENT OF SUPERVISOR _______________________________________
_____________________________________________________________________________
Project : ____________________________________________________________
Site : ____________________________________________________________
Employer : ____________________________________________________________
Contractor : ____________________________________________________________
Consultant : ____________________________________________________________
Site Supervisor : ____________________________________________________________
1. Weather Conditions : Fine _________ Good ________ Bad _______ Lost Hrs. _______
2. Staff on Site :
Project Eng. ________________ Secretary ______________ Driver ____________
Civ. Eng. _______________ Clerk _________________ Guard ____________
Bld. Eng. _______________ Purchaser ______________ Messenger _________
Technician _______________ Cashier ________________ Cleaner ___________
Eng. Aide _______________ Dresser ________________ Others ____________
3. Labour Force
Gen. Forman _______________ Mason ________________ Plasterer __________
Gen. Operator _______________ Carpenter ______________ Painter __________
Forman ____________________ Barbender ______________ Chiselled __________
Operator ___________________ Plumber ________________ Glazier ___________
Mechanic __________________ Electrician ______________ Labourer _________
Welder ____________________ Helper _________________ Others ____________
9. Remarks: ________________________________________________________________
________________________________________________________________________
________________________________________________________________________
No. Type of Work Value Out Variation Total Value of Work Value of Certificate
of Total Executed Executed
Work Order No. Value of in % This To Date This Month To Date
(Total) Month
1 Excavation & Earth works
2 Stone Masonary Works
3 Concrete in foundation
4 Concrete in superstruc.
No. Type of Work Value Out Variation Total Value of Work Value of Certificate
of Total Executed Executed
Work Order No. Value of in % This To Date This Month To Date
(Total) Month
5 Wall
6 Roofing
7 Metal works
8 Carpentry & Joinery
9 Plastering & Screeding
10 Flooring & Screeding
11 Glazing
12 Painting
13 Sanitary Installation
14 Electrical Installation
15 Site Work
16 Others
REMARK: _________________________________________________________________________________________________________________
If yes, define type of Material, Equipment, also identify source of cash shortage and profession of
manpower.
REMARKS: ___________________________________________________________________
___________________________________________________________________
___________________________________________________________________
___________________________________________________________________
___________________________________________________________________
Current Month
Difference
_____________________________ ___________________________
Supervisor Supervision Office
No. Type of Work Value Out Variation Total Value of Work Executed Value of Certificate
of Total Executed
Work Order No. Value of in % This Month To Date This Month To Date
(Total)
1 Excavation & Earth works
2 Stone Masonary Works
3 Concrete in foundation
4 Concrete in super structure
5 Wall
6 Roofing
No. Type of Work Value Out Variation Total Value of Work Executed Value of Certificate
of Total Executed
Work Order No. Value of in % This Month To Date This Month To Date
(Total)
7 Metal Works
8 Carpentary & Joinery
9 Plastering & Pointing
10 Flooring & Screeding
11 Glazing
12 Painting
13 Sanitary Installation
14 Electrical Installation
15 Site work
16 Others
REMARKS:____________________________________________________________________________________________________________
____________________________________________________________________________________________________________
____________________________________________________________________________________________________________
____________________________________________________________________________________________________________
____________________________________________________________________________________________________________
If yes, define type of Material, Equipment, also identify source of cash shortage and profession
of manpower.
REMARKS: ________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
________________________________________________________________
Current Month
Difference
________________________ _______________________
Supervisor Supervision Office
___________________________ ________________________
Date Date
WORK ORDER
Project ___________________________________________________________
Employer ________________________________________________________
Contractor ________________________________________________________
Date ____________________
I, We ______________________________________________________________
___________________________________________________________________
have recommended and instructed the following.
____________________________________________
_____________________________________________
_____________________________________________
_____________________________________________ SKETCH
_____________________________________________ (Sketched and enclosed
_____________________________________________ drawings should be deta-
_____________________________________________ iled enough to work out
_____________________________________________ quantities.)
_____________________________________________
_____________________________________________
_____________________________________________
_____________________________________________
______________________
Consultant or designer
_______________________ _______________________
Contractor Site Supervisor
C.C:
Employer
Following an inspection of the site as per the above listed items the
contractor is here by advised to take over the site and proceed with the subsequent
Mobilization and site preparation works.
3. Additional Items/Comments :
Following an inspection of the layout and levels of all buildings, site works,
etc. as per the above listed items permission to proceed with the subsequent
Excavation/Earth works is hereby Granted/Refused to the contractor.
Following an inspection of the quality of Masonry Work as per the above listed
items permission to proceed with the subsequent construction /_________/work
is hereby Granted/Refused to the Contractor.
1. Component ________________________
2. Timber Members: – Quality ________________________
– Shape/Size ________________________
– Free from
: Decay ________________________
: Insects attack ________________________
: Other damages ________________________
3. Type Quality of Timber Treatment ________________________
4. Storage protection of Timber ________________________
5. Quality / Size of – Nail ________________________
– Bolts/Nuts ________________________
– Glue ________________________
– Other joinery ________________________
6. Shape/Pattern of Timber work ________________________
7. Quality of Fabrication ________________________
8. Quality/location of Joinery ________________________
9. Quality of Erection ________________________
10. Straightness/Deflection of Timber work ________________________
11. Additional Items/Comments: ________________________
following an inspection of the quality of Timber work as per the above listed
items permission to proceed with the subsequent construction/ ______/ work is
Granted/Refused to the Contractor.
Carpentry & Joinery work Inspection Certificate – For Item Location ___________
1. Ceiling Work
– Quality/Size of ceiling Material ______________________________
– Fixing of ceiling material ______________________________
– Type, colour, quality of ceiling painting ______________________________
– Quality, procedure of ceiling painting ______________________________
– Cleanliness of ceiling ______________________________
2. Doors & Windows
– Location of Door/Windows ______________________________
– Quality of Door/Windows materials ______________________________
– Type of Doors/Windows ______________________________
– Direction of Door/Window swings ______________________________
– Straightness & plumbing of Door/Window
frames ______________________________
– Quality/fixture of Door & Windows
: Hinges ______________________________
: Locks ______________________________
: Latches ______________________________
: Handles ______________________________
– Protection of Fixed Joinery from damage ______________________________
3. Additional Items/Comments
Roofing & Cladding Work Inspection Certificate – For Item Location ________
1. Roofing work
3. Additional Items/Comment :
Following an inspection of the quality of Roofing and cladding work as per the
above listed items permission to proceed with the subsequent construction
/_______________/ work is Granted/Refused to the Contractor.
1. Plastering Work
5. Painting work
– Kind & Quality of paint ________________________
– Cleanliness of wall & brushes prior to
painting ________________________
– Removal of Electrical Appliances prior to
painting ________________________
– Number of coats applied ________________________
– Drying of painted walls & ceilings ________________________
6. Additional Items/Comments:
Following an inspection of the quality of Finishing work as per the above listed items
permission to proceed with the subsequent construction/_____________________/ work
is Grant/ Refused to the Contractor.
5. Additional Items/Comments
Following an inspection of the site works as per the above listed items permission
to proceed with the subsequent work is hereby Granted/Refused to the Contractor.
MINUTES
1. ______________________________ _______________________________
2. ______________________________ _______________________________
3. ______________________________ _______________________________
4. ______________________________ _______________________________
5. ______________________________ _______________________________
6. ______________________________ _______________________________
7. ______________________________ _______________________________
8. ______________________________ _______________________________
I ______________________________________
Outline of remarks and/or changes noticed.
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
C.C.
__________________________
__________________________
__________________________
__________________________
Project : _______________________________________________
Location : _______________________________________________
Employer : _______________________________________________
Contractor : _______________________________________________
Have examined:
a) Contracts, Drawings and Specifications:
b) _________________________________________________________________
c) _________________________________________________________________
and have proceeded with the ascertainment of the completion and Temporary
Acceptance of the above project on the bases of the following information:
A. Date when the contractor took possession of site ___________________________
B. Agreed length of completion time ______________ Calendar days (working days)
ACCOUNT
DEDUCTIONS
REMARKS: _________________________________________________________
_________________________________________________________
_________________________________________________________
_________________________________________________________
Conclusion:
We witness thereof, we have written and signed this temporary acceptance of which one
copy is to be issued to the contractor for all practical purposes after due approval.
__________________________ _____________________
Construction Supervisor Contractor
ATTENDING PARTIES
Date ______________________
Project : _______________________________________________
Location : _______________________________________________
Employer : _______________________________________________
Contractor : _______________________________________________
Have examined:
1. __________________________________________________________________
2. __________________________________________________________________
3. __________________________________________________________________
A. Signes of visible defects: The general examination of the works as well as random
checks and test made of the different parts of the project have shown:
__________________________________________________________________
__________________________________________________________________
B. New facts: Since the provisional Acceptance of the works, the following facts have
occured:
1. ___________________________________________________________________
2. ___________________________________________________________________
3. ___________________________________________________________________
4. ___________________________________________________________________
1. ___________________________________________________________________
2. ___________________________________________________________________
3. ___________________________________________________________________
4. ___________________________________________________________________
ACCOUNT:
B. D E D U C T I O N S
3. Various Deductions:
a.________________________
b. _______________________
CONCLUSION
Therefore, we do hereby declare that the work has been executed in the principle of
good workmanship, and have accepted the project definitely on behalf of
________________________________________________________________
ACT OF RENOUNCMENT
Any action or claim or reservation that we may take in the future shall be deemed as
legally covered by the present Act of Renouncement.
APPENDIX 1
1. Pre-mobilization Stage
1.1 Pursuant to the signing of the Agreement, the Consultant shall ensure
that the Contractor submits the following programs in 3 copies:
1.2 The Employer, consultant and Contractor shall jointly discuss and amend
the programs submitted if necessary. The program as amended by all
three shall be signed by all three.
2.1 The Consultant shall require to submit Quarterly Work Schedules for
following quarters in appreciation of progresses attained during proceeding
quarters. These quarterly Work Programs need to be accompanied by
related delivery schedules for materials and major equipment.
2.2 The Employer, consultant and contractor shall discuss the quarterly
schedules submitted and sign them subsequent to making necessary
adjustments to them.
3. Site Control
3.1 The consultant shall ensure to be present on site to check and approve
that the contractor's performance is generally in accordance to the
conditions of contract and will require to make such visits to site as the
consultant shall consider necessary to satisfy himself that the works are
executed generally according to the contract and otherwise in accordance
with good engineering practice. The consultant's site inspection and
d. Material quality of :
- sand
- aggregates
- water
- concrete block, bricks, stone
- limes
- steel, etc.
e. Concrete works:
- mixes
- form works
- reinforcement bars
- foundation level
- above ground level
- elevation walls
g. Roofing works:
h. Finishing works
a. Employer's representative
b. Consultant's representative
c. Contractor
5. Provisional Acceptance
6. Final Acceptance
APPENDIX 2
3. Reviews the plans and specifications and other pertinent documents that
would be furnished to him for accuracy and completeness.
5. Inspects and approves work methods and quality of all materials used in
the work for conformity with the contract specifications.
8. Arranges periodic and regular site meetings with the designer of the
project, the contractor and the project owner.
11. Advises the project owner on the need for special inspection or testing
other than those referred to in the contract documents.
12. Keeps a site book and records in it, for the duration of the project such as
the following and any other matter relevant to the works:
12.10 The date of receipt on site by the contractor of any part of designs
or modifications and the persons who delivered them;
12.15 And all other matters related to the construction works that have
caused delays and extra expenses or that have helped for the efficient operations;
12.16 The designer also records in the site book any observations be
made and clarifications he gave on the construction works;
15. Rejects any work or materials that fail to conform to the contract
specifications after the same are thoroughly assessed, and informing the designer of
such an action in advance.
16. Suspends that portion of work where in his opinion there is an imminent
danger to the safety of the workers, provided, however, such suspension shall obtain the
approval of the designer or the consultant.
17. Examines any proposal submitted by the contractor and advises the
project owner and the consultant regarding the same.
21. Performs all other duties that may be delegated to him in writing by the
consultant.