Sunny Tripower CORE1 (STP 50-40) : Operating Manual
Sunny Tripower CORE1 (STP 50-40) : Operating Manual
Sunny Tripower CORE1 (STP 50-40) : Operating Manual
ER
IPOW
N Y TR
SUN
Legal Provisions
The information contained in these documents is the property of SMA Solar Technology AG. No
part of this document may be reproduced, stored in a retrieval system, or transmitted, in any form or
by any means, be it electronic, mechanical, photographic, magnetic or otherwise, without the prior
written permission of SMA Solar Technology AG. Internal reproduction used solely for the purpose
of product evaluation or other proper use is allowed and does not require prior approval.
SMA Solar Technology AG makes no representations or warranties, express or implied, with
respect to this documentation or any of the equipment and/or software it may describe, including
(with no limitation) any implied warranties of utility, merchantability, or fitness for any particular
purpose. All such representations or warranties are expressly disclaimed. Neither SMA Solar
Technology AG nor its distributors or dealers shall be liable for any indirect, incidental, or
consequential damages under any circumstances.
The exclusion of implied warranties may not apply in all cases under some statutes, and thus the
above exclusion may not apply.
Specifications are subject to change without notice. Every attempt has been made to make this
document complete, accurate and up-to-date. Readers are cautioned, however, that product
improvements and field usage experience may cause SMA Solar Technology AG to make changes
to these specifications without advance notice, or per contract provisions in those cases where a
supply agreement requires advance notice. SMA Solar Technology AG shall not be responsible for
any damages, including indirect, incidental or consequential damages, caused by reliance on the
material presented, including, but not limited to, omissions, typographical errors, arithmetical errors
or listing errors in the content material.
SMA Warranty
You can download the current warranty conditions from the Internet at www.SMA-Solar.com.
Software Licenses
The licenses for the installed software modules (open source) can be found in the user interface of
the product.
Trademarks
All trademarks are recognized, even if not explicitly identified as such. Missing designations do not
mean that a product or brand is not a registered trademark.
Table of Contents
1 Information on this Document................................................. 6
1.1 Validity ........................................................................................................................ 6
1.2 Target Group.............................................................................................................. 6
1.3 Content and Structure of this Document ................................................................... 6
1.4 Levels of Warning Messages .................................................................................... 6
1.5 Symbols in the Document .......................................................................................... 7
1.6 Typographies in the Document.................................................................................. 7
1.7 Designation in the document ..................................................................................... 7
1.8 Additional Information ............................................................................................... 8
2 Safety ........................................................................................ 9
2.1 Intended Use .............................................................................................................. 9
2.2 IMPORTANT SAFETY INSTRUCTIONS.................................................................... 9
5 Mounting................................................................................... 26
5.1 Requirements for Mounting ....................................................................................... 26
5.2 Mounting the Inverter................................................................................................. 29
7 Commissioning ......................................................................... 51
7.1 Commissioning Procedure ......................................................................................... 51
7.2 Commissioning the Inverter........................................................................................ 52
7.3 Selecting a configuration option ............................................................................... 53
7.4 Starting the Self-Test (for Italy and Dubai)................................................................ 55
8 Operation ................................................................................. 57
8.1 Activating and Operating the Display ...................................................................... 57
8.2 Establishing a connection to the user interface ........................................................ 57
8.2.1 Establishing a Direct Connection via Ethernet ...................................... 57
8.2.2 Establishing a direct connection via WLAN ......................................... 58
8.2.3 Establishing a Connection via Ethernet in the local network ............... 60
8.2.4 Establishing a Connection via WLAN in the Local Network ............... 61
8.3 Logging In and Out of the User Interface................................................................. 61
8.4 Start Page Design of the User Interface.................................................................... 64
8.5 Displaying and Downloading the Stored Data........................................................ 67
8.6 Activating the Smart Inverter Screen......................................................................... 67
8.7 Starting the Installation Assistant ............................................................................... 68
8.8 Activate WPS Function............................................................................................... 69
8.9 Switching WLAN On and Off................................................................................... 69
8.10 Switching the Dynamic Power Display Off............................................................... 70
8.11 Changing the Password............................................................................................. 71
8.12 Changing Operating Parameters.............................................................................. 71
8.13 Configuring the Country Data Set............................................................................. 72
8.14 Configuring the Active Power Mode ........................................................................ 73
8.15 Configuring Q on Demand 24/7 ............................................................................. 73
8.16 Changing the Operating Mode of the Multifunction Relay .................................... 74
8.17 Configuring the Modbus Function............................................................................. 75
8.18 Activating the Receipt of Control Signals (Only for Italy)........................................ 76
8.19 Setting SMA ShadeFix............................................................................................... 77
8.20 Setting the Rated Residual Current of the Residual-Current Device ........................ 77
8.21 Activating String-Failure Detection ............................................................................ 77
8.22 Saving the Configuration in a File............................................................................. 78
8.23 Adopting a Configuration from a File....................................................................... 78
DANGER
Indicates a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE
Indicates a situation which, if not avoided, can result in property damage.
☑ Desired result
Example
2 Safety
2.1 Intended Use
The Sunny Tripower is a transformerless PV inverter, with 6 MPP trackers, that converts the direct
current of the PV array to grid-compliant, three-phase current and feeds it into the utility grid.
The product is suitable for indoor and outdoor use.
The product must only be operated with PV modules of protection class II in accordance with
IEC 61730, application class A. The PV modules must be compatible with this product.
The product is not equipped with an integrated transformer and therefore has no galvanic isolation.
The product must not be operated with PV modules whose outputs are grounded. This can cause
the product to be destroyed. The product may be operated with PV modules whose frame is
grounded.
PV modules with a high capacity to ground must only be used if their coupling capacity does not
exceed 12.6 μF (for information on how to determine the coupling capacity, see the Technical
Information "Leading Leakage Currents" at www.SMA-Solar.com).
All components must remain within their permitted operating ranges and their installation
requirements at all times.
The product must only be used in countries for which it is approved or released by SMA Solar
Technology AG and the grid operator.
Use SMA products only in accordance with the information provided in the enclosed
documentation and with the locally applicable laws, regulations, standards and directives. Any
other application may cause personal injury or property damage.
Alterations to the SMA products, e.g., changes or modifications, are only permitted with the express
written permission of SMA Solar Technology AG. Unauthorized alterations will void guarantee and
warranty claims and in most cases terminate the operating license. SMA Solar Technology AG
shall not be held liable for any damage caused by such changes.
Any use of the product other than that described in the Intended Use section does not qualify as the
intended use.
The enclosed documentation is an integral part of this product. Keep the documentation in a
convenient, dry place for future reference and observe all instructions contained therein.
This document does not replace and is not intended to replace any local, state, provincial, federal
or national laws, regulations or codes applicable to the installation, electrical safety and use of the
product. SMA Solar Technology AG assumes no responsibility for the compliance or non-
compliance with such laws or codes in connection with the installation of the product.
The type label must remain permanently attached to the product.
This section contains safety information that must be observed at all times when working.
The product has been designed and tested in accordance with international safety requirements. As
with all electrical or electronical devices, there are residual risks despite careful construction. To
prevent personal injury and property damage and to ensure long-term operation of the product,
read this section carefully and observe all safety information at all times.
DANGER
Danger to life due to electric shock when live components or DC cables are
touched
When exposed to light, the PV modules generate high DC voltage which is present in the DC
cables. Touching live DC cables results in death or lethal injuries due to electric shock.
• Do not touch non-insulated parts or cables.
• Disconnect the product from voltage sources and make sure it cannot be reconnected
before working on the device.
• Do not disconnect the DC connectors under load.
• Wear suitable personal protective equipment for all work on the product.
DANGER
Danger to life due to electric shock from touching an ungrounded PV module
or array frame
Touching ungrounded PV modules or array frames results in death or lethal injuries due to electric
shock.
• Connect and ground the frame of the PV modules, the array frame and the electrically
conductive surfaces so that there is continuous conduction. Observe the applicable local
regulations.
DANGER
Danger to life due to electric shock when touching live system components in
case of a ground fault
If a ground fault occurs, parts of the system may still be live. Touching live parts and cables
results in death or lethal injuries due to electric shock.
• Disconnect the product from voltage sources and make sure it cannot be reconnected
before working on the device.
• Touch the cables of the PV array on the insulation only.
• Do not touch any parts of the substructure or frame of the PV array.
• Do not connect PV strings with ground faults to the inverter.
DANGER
Danger to life due to electric shock in case of overvoltages and if surge
protection is missing
Overvoltages (e. g. in the event of a flash of lightning) can be further conducted into the building
and to other connected devices in the same network via the network cables or other data cables
if there is no surge protection. Touching live parts and cables results in death or lethal injuries due
to electric shock.
• Ensure that all devices in the same network are integrated in the existing overvoltage
protection.
• When laying the network cable outdoors, ensure that there is suitable surge protection at
the network cable transition from the product outdoors to the network inside the building.
• The Ethernet interface of the inverter is classified as "TNV-1" and offers protection against
overvoltages of up to 1.5 kV.
WARNING
Danger to life due to fire or explosion
In rare cases, an explosive gas mixture can be generated inside the product under fault
conditions. In this state, switching operations can cause a fire inside the product or explosion.
Death or lethal injuries due to hot or flying debris can result.
• In the event of a fault, do not perform any direct actions on the product.
• Ensure that unauthorized persons have no access to the product.
• Do not operate the DC load-break switch on the inverter in the event of ground fault
• Disconnect the PV array from the inverter via an external disconnection device. If there is no
disconnecting device present, wait until no more DC power is applied to the inverter.
• Disconnect the AC circuit breaker, or keep it disconnected in case it has already tripped,
and secure it against reconnection.
• Only perform work on the product (e.g., troubleshooting, repair work) when wearing
personal protective equipment for handling of hazardous substances (e.g., safety gloves,
eye and face protection, respiratory protection).
WARNING
Risk of injury due to toxic substances, gases and dusts.
In rare cases, damages to electronic components can result in the formation of toxic substances,
gases or dusts inside the product. Touching toxic substances and inhaling toxic gases and dusts
can cause skin irritation, burns or poisoning, trouble breathing and nausea.
• Only perform work on the product (e.g., troubleshooting, repair work) when wearing
personal protective equipment for handling of hazardous substances (e.g., safety gloves,
eye and face protection, respiratory protection).
• Ensure that unauthorized persons have no access to the product.
WARNING
Danger to life due to electric shock from destruction of the measuring device
due to overvoltage
Overvoltage can damage a measuring device and result in voltage being present in the
enclosure of the measuring device. Touching the live enclosure of the measuring device results in
death or lethal injuries due to electric shock.
• Only use measuring devices with a DC input voltage range of 1000 V or higher.
CAUTION
Risk of burns due to hot enclosure parts
The enclosure and the enclosure lid may get hot during operation. The DC load-break switch can
not become hot.
• Do not touch hot surfaces.
• Wait until the inverter has cooled down before touching the enclosure or enclosure lid.
CAUTION
Risk of injury due to weight of product
Injuries may result if the product is lifted incorrectly or dropped while being transported or
mounted.
• Carry and lift the product upright with the help of several people. Take the weight and the
center of gravity of the product into account. The center of gravity is on the side of the AC-
Connection Unit.
• Wear suitable personal protective equipment for all work on the product.
• Transport the product using the carrying handles or hoist. Take the weight of the product
into account.
• Use all carrying handles provided during transport with carrying handles.
• Do not use the carrying handles as attachment points for hoist equipment (e.g. straps, ropes,
chains). Insert eye bolts into threads provided on top of the product to attach the hoist
system.
NOTICE
Damage to the enclosure seal in subfreezing conditions
If you open the product when temperatures are below freezing, the enclosure seals can be
damaged. Moisture can penetrate the product and damage it.
• Only open the product if the ambient temperature is not below -5°C.
• If a layer of ice has formed on the enclosure seal when temperatures are below freezing,
remove it prior to opening the product (e.g. by melting the ice with warm air).
NOTICE
Damage to the product due to sand, dust and moisture ingress
Sand, dust and moisture penetration can damage the product and impair its functionality.
• Only open the product if the humidity is within the thresholds and the environment is free of
sand and dust.
• Do not open the product during a dust storm or precipitation.
• Close tightly all enclosure openings.
NOTICE
Damage to the inverter due to electrostatic discharge
Touching electronic components can cause damage to or destroy the inverter through
electrostatic discharge.
• Ground yourself before touching any component.
NOTICE
High costs due to inappropriate Internet tariff
Depending on use, the data volume of the product transferred via the Internet may vary in size.
The data volume depends, for example, on the number of inverters in the system, the frequency
of device updates, the frequency of data transfer to Sunny Portal or the use of FTP push. High
costs for the Internet connection can be the result.
• SMA Solar Technology AG recommends using an Internet flat rate.
NOTICE
Damage to the product due to cleaning agents
The use of cleaning agents may cause damage to the product and its components.
• Clean the product and all its components only with a cloth moistened with clear water.
Change to the names and units of grid parameters to comply with the grid-
connection requirements in accordance with Regulation (EU) 2016/631
(valid from April 27, 2019)
To comply with the EU grid-connection requirements (valid from April 27, 2019) the names
and units of grid parameters were changed. This change is valid from firmware version
≥ 3.00.00.R if a country data set for fulfilling the EU grid-connection requirements (valid from
2019-04-27) is set. Names and units of grid parameters for inverters with firmware version
≤ 2.99.99.R are not affected by this change and remain valid. This also applies from firmware
version ≥ 3.00.00.R if a country data set that is valid for countries outside the EU is set.
3 Scope of Delivery
Check the scope of delivery for completeness and any externally visible damage. Contact your
distributor if the scope of delivery is incomplete or damaged.
A B C D E F G
_
+
H I J K
4 Product Overview
4.1 Product Description
A
C
B
D
E
F
O O
G
N
M
H
L K
J
I
Figure 2: Design of the product
Position Designation
A Cover
B AC Connection Unit
C DC Connection Unit
D LEDs
The LEDs indicate the operating state of the product.
E Display (optional)
The product is equipped with a display upon request. The display shows
the current operating data and events or errors.
F Label with QR Code for scanning via the SMA 360° App and easy con-
nection to the inverter's user interface via WLAN
G Cable glands for data cables
H DC load-break switch
I DC connector
J Fan bracket with three fans
Position Designation
K Type label
The type label clearly identifies the product. The type label must remain
permanently attached to the product. You will find the following informa-
tion on the type label:
• Device type (Model)
• Serial number (Serial No. or S/N)
• Date of manufacture
• Device-specific characteristics
L Additional label with details for registration in Sunny Portal and WLAN
password:
• Identification key (PIC) for registration in Sunny Portal
• Registration ID (RID) for registration in Sunny Portal
• WLAN password (WPA2-PSK) for the direct connection to the user
interface of the inverter via WLAN
M Enclosure opening for AC connection
N Enclosure opening for additional cable
O Enclosure opening for carrying handle
Symbol Explanation
Inverter
Together with the green LED, this symbol indicates the operating state of the in-
verter.
Data transmission
Together with the blue LED, this symbol indicates the status of the network con-
nection.
Grounding conductor
This symbol indicates the position for connecting a grounding conductor.
Grounding
This symbol indicates the position for the connection of an additional ground-
ing conductor.
Three-phase alternating current with neutral conductor
Direct current
WEEE designation
Do not dispose of the product together with the household waste but in accor-
dance with the disposal regulations for electronic waste applicable at the in-
stallation site.
The product is suitable for outdoor installation.
Degree of protection IP65
The product is protected against the penetration of dust and water that is di-
rected as a jet against the enclosure from all directions.
CE marking
The product complies with the requirements of the applicable EU directives.
RoHS labeling
RoHS
The product complies with the requirements of the applicable EU directives.
ICASA
The product complies with the requirements of the South African standards for
telecommunication.
Symbol Explanation
ANATEL
The product complies with the requirements of the Brazilian standards for
08492-17-03337
telecommunication.
Este equipamento opera em caráter secundário, isto é, não tem direito a pro-
teção contra interferência prejudicial, mesmo de estações do mesmo tipo, e
não pode causar interferência a sistemas operando em caráter primário.
The product complies with the Moroccan safety and EMC requirements for
electronic products.
SMA Webconnect
The inverter is equipped with a Webconnect function as standard. The Webconnect function
enables direct data transmission between the inverter and Sunny Portal without any additional
communication device and for a maximum of 4 inverters per visualized system. In PV systems with
more than 4 inverters, there is the option of establishing data transmission between the inverters
and Sunny Portal via the data logger (e.g., SMA Data Manager) or distributing the inverters over
several systems. You can directly access your visualized system via the web browser on your end
device.
WLAN connection to SMA 360° app
The product has a QR code. By scanning the QR Code attached to the product via the SMA 360°
app, access to the product is established via WLAN and the connection to the user interface is
made automatically.
WLAN
The product is equipped with a WLAN interface as standard. The inverter is delivered with the
WLAN interface activated as standard. If you do not want to use WLAN, you can deactivate the
WLAN interface.
In addition, the product has a WPS function. The WPS function is for automatically connecting the
product to a network (e.g. via router) and establish a direct connection between the product and
an end device.
Expanding the radio range in the WLAN network
In order to expand the radio range of the inverter in the WLAN network, you can install the
Antenna Extension Kit accessory set in the inverter.
Modbus
The product is equipped with a Modbus interface. The Modbus interface is deactivated by default
and must be configured as needed.
The Modbus interface of the supported SMA products is designed for industrial use – via SCADA
systems, for example – and has the following tasks:
• Remote query of measured values
• Remote setting of operating parameters
• Setpoint specifications for system control
Module slots
The inverter is standard-equipped with two module slots. The module slots are located on the
communication assembly and allow additional modules to be connected (e.g. SMA Sensor
Module). The modules are available as accessories. The installation of two identical modules is not
permissible.
SMA RS485 Module
With the assembly of the RS485 Module, the inverter can communicate with special
SMA communication products (Information on assembly and connection see manual of the SMA
RS485 Module). The SMA RS485 Module can be retrofitted.
String-Failure Detection
The string-failure detection measures the total current of every input and continuously calculates the
mean values for the inputs in question. The total currents are compared with the mean values. If a
total current exceeds or falls short of the mean value by the set tolerance value, an event is
reported. Marginally increased total currents are reliably detected over several query intervals and
distinguished from typical current fluctuations of the PV array. String-failure detection is deactivated
by default and must be activated. In addition, the tolerance value can be set via the user interface
and the mean values read off.
Surge arrester type 1 and 2
On the AC and DC side, the inverter is equipped with slots for type 1 and 2 surge protection
devices. The surge protection devices limit dangerous overvoltages. The surge protection devices
can be retrofitted.
SMA Smart Connected
SMA Smart Connected is the free monitoring of the product via the SMA Sunny Portal. Thanks to
SMA Smart Connected, the operator and qualified person will be informed automatically and
proactively about product events that occur.
SMA Smart Connected is activated during registration in Sunny Portal. In order to use SMA Smart
Connected, it is necessary that the product is permanently connected to Sunny Portal and the data
of the operator and qualified person is stored in Sunny Portal and up-to-date.
Universal mounting system (UMS_Kit-10)
The universal mounting system enables wall mounting of the inverter or serves as platform for higher
mounting on the ground. The universal mounting system is available as an accessory.
CUSTOMER SYSTEM
LOAD
SMA PV SYSTEM
MEDIUM VOLTAGE
DISTRIBUTION BOARD TRANSFORMER
POWER SUPPLY UNIT SMA DATA SMA
CLCON-PWRSUPPLY MANAGER M ENERGY METER
max. max.
100 A 100 A
3 3 3
SUNNY
TRIPOWER CORE1 LOAD
Cable DC+ 24 V
Cable DC– 24 V
Cable DC+ 1000 V
PV MODULES Cable DC– 1000 V
Line conductor
Neutral conductor
Neutral conductor (optional)
Grounding conductor
INTERNET
SUNNY SMA
TRIPOWER CORE1 SWITCH ENERGY METER
2 ... 1
5 Mounting
5.1 Requirements for Mounting
Requirements for the Mounting Location:
WARNING
Danger to life due to fire or explosion
Despite careful construction, electrical devices can cause fires. This can result in death or serious
injury.
• Do not mount the product in areas containing highly flammable materials or gases.
• Do not mount the product in potentially explosive atmospheres.
☐ The mounting location must be inaccessible to children.
☐ The mounting location must be suitable for the weight and dimensions of the product (see
Section 13 "Technical Data", page 108).
☐ The installation site can be exposed to direct solar irradiation. There is, however, the possibility
that the product reduces its power output to avoid overheating due to high temperatures.
☐ The mounting location should be freely and safely accessible at all times without the need for
any auxiliary equipment (such as scaffolding or lifting platforms). Non-fulfillment of these
criteria may restrict servicing.
☐ The DC load-break switch of the product must always be freely accessible.
☐ All ambient conditions must be met (see Section 13, page 108).
112.85
119.17
M8x14/17+1
395
M8x14/17+1
112.85
119.17
46.2 46.2
155 155
205 205
Structural Stability:
☐ When mounting with feet or profile rails, the width of one foot or the profile rail must be at
least 175 mm to ensure structural stability.
☐ The inverter must be attached under the following conditions:
– Inclination of the support surface: > 3°
– Wind speed (without wind gusts): > 25 m/s
– Height of the feet or the profile rail: > 100 mm
☐ When mounting with profile rails, an attachment or fixation by loading is required. When
mounting with profile rails, SMA Solar Technology AG recommends to bolt the profile rails
e.g. to the profile of the module frame or to attach a sheet metal (which can be weighted with
stones or with sandbags) at the profile rails. This will ensure that the inverter is fixed.
_ _
+ _ + _
+ +
Recommended clearances:
If you maintain the recommended clearances, adequate heat dissipation will be ensured. Thus, you
will prevent power reduction due to excessive temperature.
☐ Maintain the recommended clearances to roof edges, skylights, walls as well as to other
inverters or objects. This ensures that the DC load-break switch on the inverter can be operated
easily and the LED signals can be read without difficulty.
☐ For possible service deployments, SMA Solar Technology AG recommends ensuring sufficient
clearance from walls, other inverters or objects on all four sides of the inverter enclosure. Non-
fulfillment of these criteria may restrict servicing.
☐ If multiple inverters are mounted in areas with high ambient temperatures, increase the
clearances between the inverters and ensure sufficient fresh-air supply.
(11.81)
300
1000
(39.3 7)
7) (39.3
1000
3) 1000
(35.4 (39.3
900 7)
_
+ _
+
CAUTION
Risk of injury due to the weight of the inverter
Injuries may result if the inverter is lifted incorrectly or dropped while being transported or when
mounting it to the wall mounting bracket.
• Carry and lift the inverter upright with the help of several people. In doing so, keep in mind
the weight of the inverter and take hold of the carrying handles on the inverter. Always take
hold of the two carrying handles mounted both on each side.
• Transport the product using the carrying handles or hoist. Take the weight of the product
into account.
• Do not use the carrying handles as attachment points for hoist equipment (e.g. straps, ropes,
chains). Insert eye bolts into threads provided on top of the product to attach the hoist
system.
• Use all carrying handles provided during transport with carrying handles.
• Take into account the center of gravity of the inverter. The center of gravity is on the side of
the AC-Connection Unit.
Procedure:
1. Attach each foot with two M8x40 hexagon head
screws and two washers on the two external taps
(M8x14) on the underside of the inverter (torque:
16 Nm). Press the packaging on the bottom side
down or cut it open. The screw holes on the bottom
of the inverter must be exposed. 4x
5. If the inverter is positioned by means of a hoist at the mounting location, screw the eye bolts
into the threads on the top of the inverter and attach the hoist to them. The hoist must be
suitable to take the weight of the inverter.
6. Make sure that the inverter is stable.
6 Electrical Connection
6.1 Overview of the Connection Area
J
G
D
_+
_ +
I
A E
F _
+ _
+
B
F
H
E
C D
Figure 9: Connection areas of the inverters' AC Connection Unit and DC Connection Unit
Position Designation
A Slots for AC surge protection devices
B Terminal blocks for AC connection
C Bridge between N and enclosure
D Grounding terminal for grounding conductor connection
E Enclosure opening for cable gland M63
F Enclosure opening for additional cable
G Cable glands for network cables and, if needed, for the connection cables of
the Antenna Extension Kit or other data cables
H Positive and negative connectors for DC connection
I Slots for DC surge protection devices
J Communication assembly
6.2 AC Connection
6.2.1 Requirements for the AC Connection
AC cable requirements as follows:
☐ Conductor type: aluminum and copper wire
☐ External diameter: 35 mm to 48 mm
☐ Conductor cross-section of grounding conductor: 25 mm² to 120 mm²
☐ Conductor cross-section of line conductor and neutral conductor: 35 mm² to 120 mm²
☐ Insulation stripping length: 30 mm
☐ Sheath stripping length: 290 mm
☐ The cable must be dimensioned in accordance with the local and national directives for the
dimensioning of cables. The requirements for the minimum wire size derive from these
directives. Examples of factors influencing cable dimensioning are: nominal AC current, type of
cable, routing method, cable bundling, ambient temperature and maximum desired line losses
(for calculation of line losses, see the design software "Sunny Design" from software
version 2.0 at www.SMA-Solar.com).
Overview of the required length of the conductor inside the AC connection unit
181
193
300
Figure 10: Interior view of the AC connection unit with dimensions for the conductors (Dimensions in mm)
Overvoltage category:
The inverter can be used in grids of overvoltage category III or lower in accordance with
IEC 60664-1. That means that the inverter can be permanently connected to the grid-connection
point of a building. In case of installations with long outdoor cabling routes, additional measures to
reduce overvoltage category IV to overvoltage category III are required (see the Technical
Information "Overvoltage Protection" at www.SMA-Solar.com).
Requirements:
☐ The connection requirements of the grid operator must be met.
☐ The grid voltage must be within the permissible range. The exact operating range of the
inverter is specified in the operating parameters.
Procedure:
1. Disconnect the circuit breaker from all three line conductors and secure against reconnection.
2. Ensure that the DC load-break switch is in the O position and is secured against reconnection.
3. If the enclosure lid of the AC Connection Unit is
mounted, remove all ten screws of the enclosure lid 10x
using a Torx screwdriver (TX25) and remove the
enclosure lid towards the front.
4. Remove the adhesive tape from the enclosure opening for the AC connection.
6. Thread the AC cable through the cable gland into the AC Connection Unit. If necessary,
slightly loosen the swivel nut of the cable gland.
7. Dismantle the AC cable.
8. Strip off the insulation of L1, L2, L3, N and PE by 30 mm.
9. Connect the grounding conductor to the ground
terminal. Use a Torx screwdriver (TX 25) to slightly
loosen one of the screws with which the clip and
connection plate are connected to the ground
connection and to completely remove the other
screw. Then place the grounding conductor onto the
connection plate, route the clip via the grounding
conductor and tighten both screws with a Torx
screwdriver (TX 25) (torque: 6 Nm).
10. Ensure that the conductor is on the connection plate.
11. Connect L1, L2, L3 and, if necessary, N to the
terminals according to the label. To do so, position 2 L1
each conductor as far as they will go into the L2 1
corresponding terminal and tighten the screw of the L3
terminal using an Allen key (AF 8, length: 50 mm) N
(20 Nm torque for a conductor cross-section of
35 mm² to 95 mm²; 30 Nm torque for a cable
cross-section of 120 mm²).
12. WARNING
Danger to life due to electric shock
The inverter is delivered with a bridge between N and the enclosure as standard. The
bridge is absolutely essential if the connection to a utility grid is established without a neutral
conductor.
• If the connection to a utility grid is established with a neutral conductor, the bridge must
always be removed as described in the next step.
14. Ensure that the correct conductors are assigned to all the terminals.
15. Make sure that all conductors are securely in place.
DANGER
Danger to life due to electric shock in case of overvoltages and if surge
protection is missing
Overvoltages (e. g. in the event of a flash of lightning) can be further conducted into the building
and to other connected devices in the same network via the network cables or other data cables
if there is no surge protection. Touching live parts and cables results in death or lethal injuries due
to electric shock.
• Ensure that all devices in the same network are integrated in the existing overvoltage
protection.
• When laying the network cable outdoors, ensure that there is suitable surge protection at
the network cable transition from the product outdoors to the network inside the building.
• The Ethernet interface of the inverter is classified as "TNV-1" and offers protection against
overvoltages of up to 1.5 kV.
Procedure:
1. DANGER
Danger to life due to electric shock
• Disconnect the inverter from all voltage sources (see Section 9, page 81).
2. If the enclosure lid of the DC-Connection Unit is
closed, remove it as follows: Unscrew all ten screws 10x
with a Torx screwdriver (TX25) and remove the
enclosure lid carefully forward.
3. Set the screws and the enclosure lid aside and store safely.
4. Remove the swivel nut from the cable gland for the communication cable.
5. Thread the swivel nut over the network cable.
6. Remove the two-hole cable support sleeve from the cable gland.
7. Remove the sealing plug from one of the enclosure openings of the two-hole cable support
sleeve and insert the network cable into the enclosure opening.
8. Press the two-hole cable support sleeve with the cable into the cable gland and guide the
network cable to the communication assembly in the DC Connection Unit. Ensure that any
unused enclosure openings of the two-hole cable support sleeve are sealed with sealing plugs.
9. When using a self-assembly network cable, assemble the RJ45 connectors and connect them
to the network cable (see connector documentation).
Max. 30V DC
10. Put the RJ45 plug of the cable into one of the
USB
X2
network sockets of the communication assembly.
M2
B
ANT.
SPS
11. Ensure that the RJ45 plug is securely in place by pulling slightly on the cable.
12. Tighten the swivel nut on the cable gland hand-tight. This will secure the network cable in
place.
13. If the inverter is installed outdoors, install overvoltage protection for all components in the
network.
14. If you would like to integrate the inverter into a local network, connect the other end of the
network cable to the local network (e.g. via a router).
Procedure See
1. Select for which operating mode you would like to use the Section 6.4.2, page 38
multifunction relay.
2. Connect to the multifunction relay according to the operat- Section 6.4.3, page 39
ing mode and the associated connection variant. and Section 6.4.4,
page 42
3. After commissioning the inverter, change the operating Section 8.16, page 74
mode of the multifunction relay, if necessary.
= max. 30 VDC
=
Fuse Fuse
Error in the
B F B F inverter
1 2 3 1 2 3
Inverter
B F B F in operation
1 2 3 1 2 3
Inverter
B F B F in operation
1 2 3 1 2 3
Grounding,
Light on if applicable Light on
Figure 11: Circuit diagram with multiple inverters for connection to an operation indicator and circuit diagram
for connection to a fault indicator (example)
=
max. 30 VDC Fuse
B F
1 3
K1
=
Figure 12: Wiring diagram for connection for controlling a load or for the power-dependent charging of the
batteries
Inverter 1:
Grid relay closed max. 30 VDC
B F
1 2 3
Inverter 2:
Grid relay open
B F
1 2 3
Inverter n:
Grid relay open
B F
1 2 3 1 kΩ Signal to
grid operator
Figure 13: Wiring diagram for signaling the switching status of the grid relay (example)
Requirement:
☐ The technical requirements of the multifunction relay must be met (see Section 13 "Technical
Data", page 108).
Cable requirements:
☐ Conductor cross-section: 0.2 mm² to 1.5 mm²
☐ The cable type and cable-laying method must be appropriate for the application and location.
Procedure:
1. DANGER
Danger to life due to high voltages
• Disconnect the inverter from all voltage sources (see Section 9, page 81).
2. If the enclosure lid of the DC-Connection Unit is
closed, remove it as follows: Unscrew all ten screws 10x
with a Torx screwdriver (TX25) and remove the
enclosure lid carefully forward.
3. Set the screws and the enclosure lid aside and store safely.
4. Remove the swivel nut from the cable gland for the communication cable.
5. Remove the two-hole cable support sleeve from the cable gland and insert the cable into the
enclosure opening of the two-hole cable support sleeve.
6. Press the two-hole cable support sleeve with the cable into the cable gland and guide the
cable to the communication assembly in the DC Connection Unit. Ensure that any unused
enclosure openings of the two-hole cable support sleeve are sealed with sealing plugs.
7. Strip 9 mm of the cable insulation at maximum.
8. Connect the cable to the 3-pole terminal block
according to the circuit diagram, depending on the
3
2
1
BAT
Max. 30V DC
MFR
M1
X2
FCC ID: SVF-KP20
IC: 9440A-KP20
A
M2
Max. 30V DC
B
ANT.
MFR
SPS
USB
6.5 DC Connection
6.5.1 Requirements for the DC Connection
Requirements for the PV modules per input:
☐ All PV modules should be of the same type.
☐ All PV modules should be aligned and tilted identically.
☐ On the coldest day based on statistical records, the open-circuit voltage of the PV array must
never exceed the maximum input voltage of the inverter.
☐ The same number of series-connected PV modules must be connected to each string.
☐ The maximum input current per string must be maintained and must not exceed the through-
fault current of the DC connectors (see Section 13 "Technical Data", page 108).
☐ The thresholds for the input voltage and the input current of the inverter must be adhered to
(see Section 13 "Technical Data", page 108).
☐ The positive connection cables of the PV modules must be equipped with positive DC
connectors (see Section 6.5.2, page 44).
☐ The negative connection cables of the PV modules must be equipped with the negative DC
connectors (see Section 6.5.2, page 44).
Use of Y adapters for parallel connection of strings
The Y adapters must not be used to interrupt the DC circuit.
• Do not use the Y adapters in the immediate vicinity of the inverter. The adapters must not
be visible or freely accessible.
• In order to interrupt the DC circuit, always disconnect the inverter as described in this
document (see Section 9, page 81).
DANGER
Danger to life due to electric shock when live components or DC cables are
touched
When exposed to light, the PV modules generate high DC voltage which is present in the DC
cables. Touching live DC cables results in death or lethal injuries due to electric shock.
• Do not touch non-insulated parts or cables.
• Disconnect the product from voltage sources and make sure it cannot be reconnected
before working on the device.
• Do not disconnect the DC connectors under load.
• Wear suitable personal protective equipment for all work on the product.
NOTICE
Destruction of the inverter due to overvoltage
If the open-circuit voltage of the PV modules exceeds the maximum input voltage of the inverter,
the inverter can be destroyed due to overvoltage.
• If the open-circuit voltage of the PV modules exceeds the maximum input voltage of the
inverter, do not connect any strings to the inverter and check the design of the PV system.
For connection to the inverter, all PV module connection cables must be fitted with the DC
connectors provided. Assemble the DC connectors as described in the following. The procedure is
identical for both connectors (+ and -). The graphics for the procedure are shown for only the
positive connector as an example. Pay attention to the correct polarity when assembling the DC
connectors. The DC connectors are marked with the symbols "+" and "-".
Cable requirements:
☐ Cable type: PV1-F, UL-ZKLA, USE2
☐ External diameter: 5 mm to 8 mm
☐ Conductor cross-section: 2.5 mm² to 6 mm²
☐ Qty single wires: minimum 7
☐ Nominal voltage: minimum 1000 V
☐ Using bootlace ferrules is not allowed.
Procedure:
1. Strip 12 mm of the cable insulation.
2. Insert the stripped cable into the DC connector up to
the stop. When doing so, ensure that the stripped
cable and the DC connector are of the same
polarity.
+
4. If the stranded wire is not visible in the chamber, the cable is not correctly inserted and the
connector must be reassembled. To do this, the cable must be removed from the connector.
• Release the clamping bracket. To do so, insert
a screwdriver (blade width: 3.5 mm) into the 2
clamping bracket and pry the clamping bracket
open.
1
2
+
5. Push the swivel nut up to the thread and tighten (torque: 2 Nm).
WARNING
Danger to life due to electric shock from destruction of the measuring device
due to overvoltage
Overvoltage can damage a measuring device and result in voltage being present in the
enclosure of the measuring device. Touching the live enclosure of the measuring device results in
death or lethal injuries due to electric shock.
• Only use measuring devices with a DC input voltage range of 1000 V or higher.
NOTICE
Damage to the inverter due to ground fault on DC side during operation
Due to the transformerless topology of the product, the occurance of ground faults on DC side
during operation can lead to irreparable damage. Damages to the product due to a faulty or
damaged DC installation are not covered by warranty. The product is equipped with a protective
device that checks whether a ground fault is present during the starting sequence. The product is
not protected during operation.
• Ensure that the DC installation is carried out correctly and no ground fault occurs during
operation.
NOTICE
Damage to the DC connectors due to the use of contact cleaner of other
cleaning agents
Some contact cleaners or other cleaning agents may contain substances that decompose the
plastic of the DC connectors.
• Do not use contact cleaners or other cleaning agents for cleaning the DC connectors.
NOTICE
Destruction of the inverter due to overvoltage
If the open-circuit voltage of the PV modules exceeds the maximum input voltage of the inverter,
the inverter can be destroyed due to overvoltage.
• If the open-circuit voltage of the PV modules exceeds the maximum input voltage of the
inverter, do not connect any strings to the inverter and check the design of the PV system.
Procedure:
1. Ensure that the circuit breaker is switched off and that it cannot be reconnected.
2. Set the DC load-break switch of the inverter to
position O.
4. Measure the PV array voltage. Ensure that the maximum input voltage of the inverter is
adhered to and that there is no ground fault in the PV array.
5. Check whether the DC connectors have the correct polarity.
If the DC connector is equipped with a DC cable of the wrong polarity, the DC connector must
be reassembled. The DC cable must always have the same polarity as the DC connector.
6. Ensure that the open-circuit voltage of the PV array does not exceed the maximum input
voltage.
7. Connect the assembled DC connectors to the
inverter.
A
C
☑ The DC connectors snap into place.
8. Ensure that all DC connectors are securely in place.
9. NOTICE
Damage to the product due to sand, dust and moisture ingress if the DC
inputs are not closed
The product is only properly sealed when all unused DC inputs are closed with DC
connectors and sealing plugs. Sand, dust and moisture penetration can damage the product
and impair its functionality.
• Seal all unused DC inputs using the DC connectors and sealing plugs as described in
the following. When doing so, do not plug the sealing plugs directly into the DC inputs
on the inverter.
10. For unused DC connectors, push down the clamping bracket and push the swivel nut up to the
thread.
11. Insert the sealing plug into the DC connector.
C
_ +
_+
☑ The DC connectors snap into place.
13. Ensure that the DC connectors with sealing plugs are securely in place.
DANGER
Danger to life due to electric shock when touching exposed DC conductors or
DC plug contacts if the DC connectors are damaged or loose
The DC connectors can break or become damaged, become free of the DC cables, or no longer
be connected correctly if the DC connectors are released and disconnected incorrectly. This can
result in the DC conductors or DC plug contacts being exposed. Touching live DC conductors or
DC plug connectors will result in death or serious injury due to electric shock.
• Wear insulated gloves and use insulated tools when working on the DC connectors.
• Ensure that the DC connectors are in perfect condition and that none of the DC conductors
or DC plug contacts are exposed.
• Carefully release and remove the DC connectors as described in the following.
Procedure:
1. Release and remove the DC connectors. To do so,
insert a flat-blade screwdriver or an angled
screwdriver (blade width: 3.5 mm) into one of the 1
side slots and pull the DC connectors out. When 2
doing so, do not lever the DC connectors out, but
insert the tool into one of the side slots only to
release the locking mechanism, and do not pull on
the cable.
2. Remove the DC connector swivel nut.
7 Commissioning
7.1 Commissioning Procedure
Procedure See
6. For PV systems in Italy or Dubai: Start the self-test. Section 7.4, page 55
7. Make further inverter settings as needed. Section 8, page 57
Requirements:
☐ The AC circuit breaker must be correctly rated and mounted.
☐ The inverter must be correctly mounted.
☐ All cables must be correctly connected.
☐ Unused enclosure openings must be sealed tightly with sealing plugs.
Procedure:
1. Position the enclosure lid of the AC-Connection Unit
on the AC-Connection Unit and first tighten the 10x
upper-left and lower-right screws, and then the
remaining screws crosswise (TX 25, torque: 6 Nm). 1 10x
2
2. Position the enclosure lid of the DC-Connection Unit on the DC-Connection Unit and first
tighten the upper-left and lower-right screws, and then the remaining screws crosswise (TX 25,
torque: 6 Nm).
3. Connect the DC connector to the inverter in its original position.
☑ The DC connectors snap into place.
4. Ensure that all DC connectors are securely in place.
5. Turn the DC load-break switch of the inverter to
position I. To do so, first remove the padlock.
7. If the green LED is still flashing, the conditions for activating feed-in operation are not yet met.
As soon as the conditions for feed-in operation are met, the inverter starts with feed-in
operation and, depending on the available power, the green LED will light up continuously or
it will pulse.
8. If the red LED lights up, an event has occurred. Find out which event has occurred and, if
necessary, initiate countermeasures.
After having assigned the password to the Installer or User, the Configuring the Inverter page
opens.
D C
Figure 15: Layout of the Configuring the Inverter page
Configuration options:
On the Configuring the Inverter page, different configuration options are available to choose
from. Select one of the options and proceed for the selected option as described below. SMA
Solar Technology AG recommends carrying out the configuration with the installation assistant. This
way, you ensure that all relevant parameters are set for optimal inverter operation.
• Adoption of configuration from a file
• Configuration with the installation assistant (recommended)
• Manual configuration
Accepting the settings
Saving the made settings is indicated by an hourglass symbol on the user interface. If the DC
voltage is sufficient, the data is transferred directly to the inverter and accepted. If the DC
voltage is too low (e. g. in the evening), the settings are saved, but they cannot be directly
transferred to or accepted by the inverter. As long as the inverter has not yet received and
accepted the settings, the hourglass symbol will continue to be displayed on the user interface.
The settings will be accepted when there is sufficient DC voltage applied and the inverter
restarts. As soon as the hourglass symbol appears on the user interface, the settings have been
saved. The settings will not be lost. You can log off of the user interface and leave the system.
Adopting the Configuration from a File
You can adopt the inverter configuration from a file. To do this, there must be an inverter
configuration saved to a file.
Procedure:
1. Select the configuration option Adopting configuration from a file.
2. Select [Browse...] and select the desired file.
3. Select [Import file].
Configuring the Installation Assistant (Recommended)
Procedure:
1. Select the configuration option Configuration with Installation Assistant.
☑ The installation assistant will open.
2. Follow the installation assistant steps and make the settings appropriate for your system.
3. For every setting made in a step, select [Save and next].
☑ In the last step, all made settings are listed in a summary.
4. To correct settings you made, select [Back], navigate to the desired step, correct settings and
select [Save and continue].
5. Once all settings are correct, select [Next] in the summary.
6. To save the settings to a file, select [Export a summary] and save the file on your end
device.
7. To export all parameters and their settings, select [Export all parameters]. This exports all
parameters and their settings into an HTML file.
☑ The start page of the user interface opens.
Manual configuration
You can configure the inverter manually by setting the desired parameters.
Procedure:
1. Select the configuration option Manual Configuration.
☑ The Device Parameters menu on the user interface will open and all available
parameter groups of the inverter will be displayed.
2. Select [Edit parameters].
3. Select the desired parameter group.
☑ All available parameters of the parameter group will be displayed.
4. Set the desired parameters.
5. Select [Save all].
☑ The inverter parameters are set.
The self-test is only required for inverters that are to be commissioned in Italy or Dubai. The Italian
standard CEI 0-21 and the DEWA (Dubai Electricity and Water Authority) stipulate that all inverters
that feed into the utility grid are equipped with a self-test function. During the self-test, the inverter
will consecutively check the reaction times for overvoltage, undervoltage, maximum frequency and
minimum frequency.
The self-test changes the upper and lower disconnection values for each protective function on a
linear basis for frequency monitoring and voltage monitoring. As soon as the measured value
exceeds the permitted disconnection threshold, the inverter disconnects from the utility grid. In this
way, the inverter determines the reaction time and checks itself.
After the self-test has been completed, the inverter automatically switches back to feed-in operation,
resets the original disconnection conditions and connects to the utility grid. The test takes
approximately three minutes.
Requirements:
☐ The country data set of the inverter must be set to CEI 0-21 internal or DEWA 2016
internal.
Procedure:
1. Select the menu Device Configuration.
2. Select [Settings].
3. Select [Starting the Self-Test] in the subsequent context menu.
4. Follow the instructions appearing in the dialog and save the report of the self-test where
necessary.
8 Operation
8.1 Activating and Operating the Display
You can activate and operate the display by tapping on the enclosure lid of the DC-
Connection Unit.
Procedure:
1. Activate the display. Tap on the enclosure lid of the DC-Connection Unit once.
☑ The backlight is switched on.
2. To move to the next message, tap on the enclosure lid of the DC-Connection Unit once.
Procedure:
1. Open the web browser of your end device, enter the IP address 169.254.12.3 in the address
bar and press the enter key.
2. Web browser signals a security vulnerability
After the IP address has been entered, a message might appear indicating that the
connection to the user interface of the product is not secure. SMA Solar Technology AG
guarantees the security of the user interface.
• Continue loading the user interface.
☑ The login page of the user interface opens.
Importing and exporting files with end devices having an iOS operating
system is not possible.
For technical reasons, importing and exporting files (e.g., importing an inverter configuration,
saving the current inverter configuration or exporting events and parameters) is not possible
with mobile end devices having an iOS operating system.
• Use an end device that does not have an iOS operating system for importing and
exporting files.
You have several options to connect the product to an end device. The procedure can be different
depending on the end devices. If the procedures described do not apply to your end device,
establish the direct connection via WLAN as described in the manual of your end device.
The following connection options ar available:
• Connection to SMA 360° App
• Connection with WPS
• Connection with WLAN network search
Connection to SMA 360° App
Requirements:
☐ An end device with camera must be available.
☐ The SMA 360° App must be installed on the end device.
☐ An user account for Sunny Portal must already exist.
Procedure:
1. Open the SMA 360° App and login with dem Sunny Portal account details.
Procedure:
1. Enable the WPS function on the inverter. To do this, tap twice in succession on the enclosure
lid of the DC-Connection Unit next to the LEDs.
☑ The blue LED flashes quickly for approx. two minutes. The WPS function is active during
this time.
2. Enable the WPS function on your end device.
☑ The end device automatically connects to the inverter. The web browser of your end
device opens and the login page of the user interface is displayed.
3. If the web browser of your end device does not open automatically and the login page of the
user interface is not displayed, open the web browser and enter https://smalogin.net in the
address bar.
Connection with WLAN network search
1. Search for WLAN networks with your end device.
2. Select the SSID of the inverter SMA[serial number] in the list with the found WLAN
networks.
3. Enter the device-specific WLAN password (see WPA2-PSK on the type label of the product or
the rear side of the manual included in delivery).
4. Open the web browser of your end device and enter https://smalogin.net in the address
bar.
☑ The login page of the user interface is displayed.
5. If the login page of the user interface does not open, enter the IP address 192.168.12.3 or, if
your end device supports mDNS services, SMA[serial number].local or https://
SMA[serial number] in the address bar of the web browser.
Requirements:
☐ The product must be connected to the local network via a network cable (e.g. via a router).
☐ The product must be integrated into the local network. Tip: There are various methods of
integrating the product into the local network with the aid of the installation assistant.
☐ An end device (e.g. computer, tablet PC or smartphone) must be available.
☐ The end device must be in the same local network as the product.
☐ The respective latest version of one of the following web browsers must be installed: Chrome,
Edge, Firefox, Internet Explorer or Safari.
☐ The SMA Grid Guard code of the Installer must be available for the changing of grid-relevant
settings after completion of the first ten feed-in hours or installation assistant (see "Application
for SMA Grid Guard Code" at www.SMA-Solar.com).
Procedure:
1. Open the web browser of your end device, enter the IP address of the inverter in the address
bar of the web browser and press the enter key.
2. Web browser signals a security vulnerability
After the IP address has been entered, a message might appear indicating that the
connection to the user interface of the product is not secure. SMA Solar Technology AG
guarantees the security of the user interface.
• Continue loading the user interface.
☑ The login page of the user interface opens.
Requirements:
☐ The product must be commissioned.
☐ The product must be integrated into the local network. Tip: There are various methods of
integrating the product into the local network with the aid of the installation assistant.
☐ An end device (e.g. computer, tablet PC or smartphone) must be available.
☐ The end device must be in the same local network as the product.
☐ The respective latest version of one of the following web browsers must be installed: Chrome,
Edge, Firefox, Internet Explorer or Safari.
☐ The SMA Grid Guard code of the Installer must be available for the changing of grid-relevant
settings after completion of the first ten feed-in hours or installation assistant (see "Application
for SMA Grid Guard Code" at www.SMA-Solar.com).
Importing and exporting files with end devices having an iOS operating
system is not possible.
For technical reasons, importing and exporting files (e.g., importing an inverter configuration,
saving the current inverter configuration or exporting events and parameters) is not possible
with mobile end devices having an iOS operating system.
• Use an end device that does not have an iOS operating system for importing and
exporting files.
Procedure:
• Enter the IP address of the inverter in the address bar of the web browser.
☑ The login page of the user interface opens.
Usage of cookies
For the correct display of the user interface, cookies are required. The cookies are used for
convenience only. By using this user interface you agree to the placement of cookies.
Log in as Installer or User for the First Time
Password assignment for user and installer
The passwords for the user groups Installer and User must be assigned when accessing the
user interface for the first time. If the inverter was registered in a communication device (e.g.,
SMA Data Manager) and the system password was assigned, the system password is also the
installer password. In this case, only the user password must be assigned.
• If you as a specialist assign the user password, only pass the password on to persons to
access the inverter data via the user interface.
• If you as a user assign the installer password, only pass the password on to persons to
receive access to the system.
Procedure:
1. In the drop-down list Language, select the desired language.
2. In the Password field, enter a password for the User user group.
3. In the Repeat password field, enter the password again.
4. Click on Save.
5. In the New password field, enter a password for the Installer user group. Assign a uniform
password to all SMA devices to be registered in a system. The installer password is also the
system password.
6. In the Repeat password field, enter the password again.
7. Click on Save and log in.
☑ The Configuring the Inverter page opens.
Log in as the User or Installer
1. In the drop-down list Language, select the desired language.
2. In the User group drop-down list, select the entry Installer or User.
3. Enter the password in the field Password.
4. Select Login.
☑ The start page of the user interface opens.
Procedure:
1. Activate the user interface (see Section 8.2, page 57).
2. Log into the user interface (see Section 8.3, page 61).
3. Select the menu Data.
4. Select the folder Data.
5. To call up the data, select the respective folder and click on the required file.
6. To download the data, select the data type to be exported in the drop-down list. Then apply
the time filter and select Data export.
Procedure:
1. Activate the user interface (see Section 8.2, page 57).
2. Log in as Installer or User.
3. Select the menu User Settings (see Section 8.4, page 64) on the start page of the user
interface.
4. Select [Smart Inverter Screen].
☑ The Smart Inverter Screen has been activated.
The installation assistant leads you step-by-step through the steps necessary for the initial
configuration of the inverter.
C B
Requirement:
☐ When configuring after completion of the first ten feed-in hours or after exiting the installation
assistant, the SMA Grid Guard code must be available in order to change the grid-relevant
parameters (see "Application for SMA Grid Guard Code" at www.SMA-Solar.com).
Procedure:
1. Open the user interface (see Section 8.2, page 57).
2. Log in as Installer.
3. Select the menu User Settings (see Section 8.4, page 64) on the start page of the user
interface.
4. In the context menu, select [Starting the installation assistant].
☑ The installation assistant will open.
Procedure:
1. Activate the user interface (see Section 8.2, page 57).
2. Log in as Installer.
3. Start the installation assistant (see Section 8.7, page 68).
4. Select Network configuration.
5. Select WPS for WLAN network button in the WLAN tab.
6. Select Activate WPS.
7. Select Save and next and exit the installation assistant.
☑ The WPS function is activated and the automatic connection to the network can be
established.
Activating the WPS function for direct connection to the end device.
• Activate the WPS function on the inverter. To do this, tap twice in succession on the enclosure
lid of the DC-Connection Unit next to the LEDs.
☑ The blue LED flashes quickly for approx. two minutes. The WPS function is active during
this time.
Procedure:
• To switch off the direct connection in the parameter group PV system communication >
WLAN, select the parameter Soft-access-point is turned on and set this to No.
• To switch off the connection in the local network in the parameter group PV system
communication > WLAN, select the parameter WLAN is turned on and set this to No.
Switching WLAN On
If you have switched the WLAN function for direct connection or for connection in the local network
off, you can switch the WLAN function back on in accordance with the following procedure.
Requirement:
☐ If the WLAN function was previously switched off completely, the inverter must be connected
to a computer or router via Ethernet.
Procedure:
• To switch on the WLAN direct connection, in the parameter group PV system
communication > WLAN, select the parameter Soft-access-point is turned on and set this
to Yes.
• To switch on the WLAN connection in the local network, in the parameter group System
communication > WLAN, select the parameter WLAN is turned on and set this to Yes.
Procedure:
• In the parameter group Device > Operation, select the parameter Dynamic power
display via green LED and set this to Off.
Procedure:
1. Activate the user interface (see Section 8.2, page 57).
2. Log into the user interface (see Section 8.3, page 61).
3. Call up the menu Device Parameters.
4. Select [Edit parameters].
5. In the parameter group User Rights > Access Control change the password of the desired
user group.
6. Select [Save all] to save the changes.
Requirements:
☐ Changes to grid-relevant parameters must be approved by the responsible grid operator.
Procedure:
1. Open the user interface (see Section 8.2, page 57).
2. Log into the user interface (see Section 8.3, page 61).
3. Call up the menu Device Parameters.
4. Click on [Edit parameters].
5. Log in using the SMA Grid Guard code to change those parameters designated by a lock
(only for installers):
• Select the menu User Settings (see Section 8.4, page 64).
• In the subsequent context menu, select [SMA Grid Guard login].
By default, the inverter is set to a universally valid country data set. You must adjust the country
data set for the installation site.
The country data set must be set correctly.
If you select a country data set which is not valid for your country and purpose, it can cause a
disturbance in the PV system and lead to problems with the grid operator. When selecting the
country data set, you must always observe the locally applicable standards and directives as
well as the properties of the PV system (e.g. PV system size, grid-connection point).
• If you are not sure which standards and directives are valid for your country or purpose,
contact the grid operator.
Change to the names and units of grid parameters to comply with the grid-
connection requirements in accordance with Regulation (EU) 2016/631
(valid from April 27, 2019)
To comply with the EU grid-connection requirements (valid from April 27, 2019) the names
and units of grid parameters were changed. This change is valid from firmware version
≥ 3.00.00.R if a country data set for fulfilling the EU grid-connection requirements (valid from
2019-04-27) is set. Names and units of grid parameters for inverters with firmware version
≤ 2.99.99.R are not affected by this change and remain valid. This also applies from firmware
version ≥ 3.00.00.R if a country data set that is valid for countries outside the EU is set.
The basic procedure for changing operating parameters is explained in another section (see
Section 8.12 "Changing Operating Parameters", page 71).
Procedure:
• In the parameter group Grid monitoring > Grid monitoring select the parameter Set
country standard and set the required country data set.
This means that if the "Q on Demand 24/7" function" is active, no other grid-supporting functions
(e.g., cos phi) are possible between day and night operation of the inverter. Should an
independent reactive power provision be desired between day- and night operation, the reactive
power provision must be communicated to the inverter via a superordinate control unit.
Currently, the provision of reactive power can only be read off via the phase currents and phase
voltages in the instantaneous values (Instantaneous values > AC Side > Phase currents /
Phase voltage) or requested via Modbus.
The basic procedure for changing operating parameters is explained in another section (see
Section 8.12 "Changing Operating Parameters", page 71).
Procedure:
1. Select the parameter Reactive power mode in case of active power output and set the
desired procedure. When doing so, note that for "Q on Demand 24/7", the modes Cos
Phi(P) characteristic curve or Cos Phi(U) characteristic curve may not be selected.
2. Select the parameter Reactive power mode in case of zero active power and set the
desired procedure.
3. Set the parameters associated with the reactive power mode.
The default operating mode of the multifunction relay is Fault indication (FltInd) . If you decide to
use another operating mode and have established the correct electrical connection for this
operating mode and the associated connection variant, you will have to change the operating
mode of the multifunction relay and make other settings, if necessary.
The basic procedure for changing operating parameters is explained in another section (see
Section 8.12 "Changing Operating Parameters", page 71).
Procedure:
1. Call up the menu Device Parameters.
2. Select [Edit parameters].
3. In the parameter group Device > Multifunction relay > Operating mode select the
parameter Operating mode of multifunction relay or Mlt.OpMode and set the desired
operating mode.
4. Once you have set the operating mode Self-consumption or SelfCsmp, you can configure
other settings:
• In the parameter group Device > Multifunction relay > Self-consumption >
Minimum On power select the parameter Minimum On power for MFR self-
consumption or Mlt.MinOnPwr and set the desired value. This will configure the
power threshold from which a load is to be activated.
• In the parameter group Device > Multifunction relay > Self-consumption >
Minimum power On time select the parameter Minimum power On time, MFR self-
consumption or Mlt.MinOnPwrTmm and set the desired value. This will configure the
minimum time for which the power must have exceeded the minimum switch-on power
threshold in order to trip activation of the load.
• In the parameter group Device > Multifunction relay > Self-consumption >
Minimum On power select the parameter Minimum On time for MFR self-
consumption or Mlt.MinOnTmm and set the desired value. This will configure the
minimum time for which the load remains activated.
5. If you have set the operating mode Control via communication or ComCtl, in the
parameter group Device > Multifunction relay > Control via communication > Status
select the parameter Status of MFR with control via communication or Mlt.ComCtl.Sw
and set the desired value. This determines whether the multifunction relay can be controlled via
a communication product.
6. If you have set the operating mode Battery bank or BatCha, make further settings:
• In the parameter group Device > Multifunction relay > Battery bank > Minimum On
power select the parameter Minimum On power for MFR battery bank or
Mlt.BatCha.Pwr and set the desired value. This will configure the power threshold from
which the battery is to be charged.
• In the parameter group Device > Multifunction relay > Battery bank > Minimum
time before reconnection select the parameter Minimum time before reconnection
of MFR battery bank or Mlt.BatCha.Tmm and set the desired value. This will
configure the minimum time which must elapse after charging the battery before the
battery can be charged again.
7. Select [Save all] to save the changes.
The Modbus interface is deactivated by default and the communication ports 502 set.
In order to access SMA invertes with SMA Modbus® or SunSpec® Modbus®, the Modbus interface
must be activated. After activating the interface, the communication ports of both IP protocols can
be changed. For information on commissioning and configuration of the Modbus interface, see the
technical information "SMA and SunSpec Modbus® Interface" at www.SMA-Solar.com.
For information on which Modbus registers are supported, see the technical information "Modbus®
parameters and measured values" at www.SMA-Solar.com.
Procedure:
• Activate the Modbus interface and adjust the communication ports if necessary (see the
technical information "SMA and SunSpec Modbus® Interface" at www.SMA-Solar.com).
In order for PV systems in Italy to receive control commands from the grid operator, set the
following parameters.
The basic procedure for changing operating parameters is explained in another section (see
Section 8.12 "Changing Operating Parameters", page 71).
Parameter Value/range Resolution Default
Application ID 0 to 16384 1 16384
GOOSE-Mac address 01:0C:CD:01:00:00 to 1 01:0C:CD:01:00:00
01:0C:CD:01:02:00
Procedure:
1. Select the parameter group External communication > IEC 61850 configuration.
2. In the field Application ID, enter the application ID of the grid operator gateway. You will
receive this value from your grid operator. You can enter a value between 0 and 16384. The
value 16384 indicates "deactivated".
3. In the field GOOSE-Mac address, enter the MAC address of the grid operator gateway
from which the inverter is to receive the control commands. You will receive this value from
your grid operator.
☑ The receipt of control signals from the grid operator is activated.
You can set the time interval in which the inverter has to determine the optimum operating point. If
you do not want to use SMA ShadeFix, you can disable the feature.
The basic procedure for changing operating parameters is explained in another section (see
Section 8.12 "Changing Operating Parameters", page 71).
Procedure:
• In the parameter group DC-side > DC settings > SMA ShadeFix, set the parameter Time
interval of SMA ShadeFix and set the required time interval. The ideal time interval is
usually six minutes. This value should only be increased if the shading situation changes
extremely slowly.
☑ The inverter optimizes the MPP of the PV system at the predetermined time interval.
• In order to disable the SMA ShadeFix feature, in the parameter group DC-side > DC settings
> SMA ShadeFix, set the parameter SMA ShadeFix switched on to Off.
When using residual-current devices with a rated residual current of < 500 mA, set the rated
residual current to the respective value in the inverter. In this way the inverter reduces the
operational leakage currents and prevents a false triggering of the residual-current device (further
information see technical information "Leading Leakage Currents" at www.SMA-Solar.com).
The basic procedure for changing operating parameters is explained in another section (see
Section 8.12 "Changing Operating Parameters", page 71).
Procedure:
• In the parameter group Device > Inverter, select the parameter RCD adjustment and set it
to the rated residual current of the residual-current device that is used.
Procedure:
1. Activate the user interface (see Section 8.2, page 57).
2. Log into the user interface (see Section 8.3, page 61).
3. Select the menu Device Configuration.
4. Select [Settings].
5. In the context menu, select [Saving the configuration in a file].
6. Follow the instructions in the dialog.
To configure the inverter, you can adopt the configuration from a file. To be able to do this, you
must first save the configuration of another inverter from the same type or device family in a file (see
Section 8.22 "Saving the Configuration in a File", page 78). When saving, only the device
parameters will be adopted, not any passwords.
Requirements:
☐ Changes to grid-relevant parameters must be approved by the responsible grid operator.
☐ The SMA Grid Guard code must be available (see "Application for SMA Grid Guard Code"
at www.SMA-Solar.com).
Procedure:
1. Open the user interface (see Section 8.2, page 57).
2. Log into the user interface as an Installer (see Section 8.3, page 61).
3. Select the menu Device Configuration.
4. Select [Settings].
5. In the context menu, select [Adopting the configuration from a file].
6. Follow the instructions in the dialog.
If no automatic update is set for the inverter in the communication product (e.g.
SMA Data Manager, Cluster Controller, Sunny Portal) or via the user interface of the inverter, you
have the option of carrying out a manual firmware update.
You have the following options to update the firmware:
• Update the firmware with the existing update file via the user interface of the inverter.
• Update the firmware with the existing update file via USB flash drive.
• Search and install the firmware via the user interface of the inverter.
Update the firmware with the existing update file via the user interface of the
inverter.
Requirements:
☐ An update file with the desired inverter firmware must be available. The update file is, for
example, available for download on the product page of the inverter at www.SMA-Solar.com.
Procedure:
1. Open the user interface (see Section 8.2, page 57).
2. Log into the user interface as an Installer (see Section 8.3, page 61).
3. Select the menu Device Configuration.
4. In the inverter row, click on the gear icon and select Update firmware.
5. Select [Browse] and select the update file for the inverter.
6. Select Update firmware.
7. Follow the instructions in the dialog.
Update the firmware with the existing update file via USB flash drive.
Requirements:
☐ A USB flash drive with maximum 32 GB and file system FAT32 must be available.
Procedure:
1. Create an "UPDATE" folder on the USB stick.
2. Save the update file with the required firmware in the "UPDATE" folder on the USB flash drive.
The update file is, for example, available for download on the product page of the inverter at
www.SMA-Solar.com. Ensure that only the update file to which the inverter is to be updated
must be stored on the USB flash drive.
3. DANGER
Danger to life due to high voltages
• Disconnect the inverter from all voltage sources and open the enclosure lid of the DC
connection unit (see Section 9, page 81).
4. Insert the USB flash drive in the USB port on the communication assembly.
5. Commission the inverter (see Section 7.2, page 52).
☑ During start-up phase of the inverter, the desired firmware is being installed.
6. DANGER
Danger to life due to high voltages
• Disconnect the inverter from all voltage sources and open the enclosure lid of the DC
connection unit (see Section 9, page 81).
Procedure:
1. Open the user interface (see Section 8.2, page 57).
2. Log into the user interface as an Installer (see Section 8.3, page 61).
3. Click on [Edit parameters].
4. Go to Device > Update.
5. Select the parameter Check for update and install it and set it to Execute.
6. Click on [Save all].
☑ The firmware is updated in the background.
Prior to performing any work on the inverter, always disconnect it from all voltage sources as
described in this section. Always adhere to the prescribed sequence.
WARNING
Danger to life due to electric shock from destruction of the measuring device
due to overvoltage
Overvoltage can damage a measuring device and result in voltage being present in the
enclosure of the measuring device. Touching the live enclosure of the measuring device results in
death or lethal injuries due to electric shock.
• Only use measuring devices with a DC input voltage range of 1000 V or higher.
Procedure:
1. Disconnect the AC circuit breaker and secure it against reconnection.
2. Set the DC load-break switch of the inverter to position O.
3. Secure the DC load-break switch against reconnection using a suitable padlock.
4. If the multifunction relay is used, switch off any supply voltage to the load.
5. Wait until the LEDs have gone out.
6. Use a current clamp to ensure that no current is
present in the DC cables.
A
B
<0.5A
7. DANGER
Danger to life due to electric shock when touching exposed DC
conductors or DC plug contacts if the DC connectors are damaged or
loose
The DC connectors can break or become damaged, become free of the DC cables, or no
longer be connected correctly if the DC connectors are released and disconnected
incorrectly. This can result in the DC conductors or DC plug contacts being exposed.
Touching live DC conductors or DC plug connectors will result in death or serious injury due
to electric shock.
• Wear insulated gloves and use insulated tools when working on the DC connectors.
• Ensure that the DC connectors are in perfect condition and that none of the DC
conductors or DC plug contacts are exposed.
• Carefully release and remove the DC connectors as described in the following.
B
<30V
C
11. Unscrew (TX25) all ten screws of the enclosure lid of
the AC-Connection Unit and remove the enclosure 10x
lid carefully towards the front.
12. Set the screws and the enclosure lid aside and store safely.
13. Ensure there is no voltage on the AC terminal block
between L1 and N, L2 and N, and L3 and N using L1
a suitable measuring device. To do so, insert the test L2
probe (maximum diameter: 2.5 mm) into the L3
measuring points of the respective terminal blocks. N
0.00
11 Troubleshooting
11.1 Forgotten Password
If you have forgotten the password for the inverter, you can unlock the inverter with a Personal
Unlocking Key (PUK). For each inverter, there is one PUK for each user group (User and Installer).
Tipp: With PV systems that are registered in a communication product, you can also assign a new
password for the user group Installer via the communication product. The password for the user
group Installer is the same as the system password in the communication product.
Procedure:
1. Request PUK (application form available at www.SMA-Solar.com).
2. Open the user interface (see Section 8.2, page 57).
3. Enter the PUK instead of the password into the field Password.
4. Select Login.
5. Call up the menu Device Parameters.
6. Click on [Edit parameters].
7. In the parameter group User Rights > Access Control change the password of the desired
user group.
8. Select [Save all] to save the changes.
Password assignment for inverters that are registered in a communication
product
The password for the user group Installer is also the system password for the system in the
communication product. Changing the password of the user group Installer can lead to the
inverter no longer being able to be reached by the communication product.
• In the communication product, assign the changed password of the user group Installer
as the new system password (see the manual of the communication product).
Grid fault
The grid voltage or grid impedance at the connection point of the inverter is
too high. The inverter has disconnected from the utility grid.
Corrective measures:
• Check whether the grid voltage at the connection point of the inverter is
permanently in the permissible range.
If the grid voltage is outside the permissible range due to local grid
conditions, contact the grid operator. The grid operator must agree with
an adjustment of the voltage at the feed-in point or with a change of the
monitored operating limits.
If the grid voltage is permanently within the permissible range and this
message is still displayed, contact Service.
301
Grid fault
The ten-minute average value of the grid voltage is no longer within the per-
missible range. The grid voltage or grid impedance at the connection point is
too high. The inverter disconnects from the utility grid to maintain power qual-
ity.
Corrective measures:
• During the feed-in operation, check whether the grid voltage at the
connection point of the inverter is permanently in the permissible range.
If the grid voltage is outside the permissible range due to local grid
conditions, contact the grid operator. The grid operator must agree with
an adjustment of the voltage at the feed-in point or with a change of the
monitored operating limits.
If the grid voltage is permanently within the permissible range and this
message is still displayed, contact Service.
401
Grid fault
The inverter has disconnected from the utility grid. A stand-alone grid or a very
large change in the power frequency was detected.
Corrective measures:
• Check the grid connection for significant short-term frequency fluctuations.
Grid fault
The power frequency is not within the permissible range. The inverter has dis-
connected from the utility grid.
Corrective measures:
• If possible, check the power frequency and observe how often
fluctuations occur.
If fluctuations occur frequently and this message is displayed often,
contact the grid operator and request approval to change the operating
parameters of the inverter.
If the grid operator gives his approval, discuss any changes to the
operating parameters with the Service.
601
Grid fault
The inverter has detected an excessively high proportion of direct current in
the grid current.
Corrective measures:
• Check the grid connection for direct current.
• If this message is displayed frequently, contact the grid operator and
check whether the monitoring threshold on the inverter can be raised.
801
Waiting for grid voltage > Grid failure > Check AC circuit breaker
The AC cable is not correctly connected or the country data set is not correctly
configured.
Corrective measures:
• Ensure that the circuit breaker is switched on.
• Ensure that the AC cable is not damaged and that it is connected
correctly.
• Ensure that the country data set has been configured correctly.
• Check whether the grid voltage at the connection point of the inverter is
permanently in the permissible range.
If the grid voltage is outside the permissible range due to local grid
conditions, contact the grid operator. The grid operator must agree with
an adjustment of the voltage at the feed-in point or with a change of the
monitored operating limits.
If the grid voltage is permanently within the permissible range and this
message is still displayed, contact Service.
Incompatible file
The configuration file is not suitable for this inverter.
Corrective measures:
• Ensure that the selected configuration file is suitable for this inverter.
• Retry import.
7348
Interference device
The cause must be determined by the Service.
Corrective measures:
• Contact Service.
7801
Abort self-test
The self-test (Italy only) was terminated.
Corrective measures:
• Ensure that the AC connection is correct.
• Restart the self-test.
9033 Rapid Shutdown was triggered
The inverter detected the triggering of a Rapid Shutdown. The AC side of the
inverter was disconnected.
If the red LED is glowing and the event number 3501, 3601 or 3701 is being displayed in the
Results menu on the inverter user interface, there may be a ground fault present. The electrical
insulation from the PV system to ground is defective or insufficient.
DANGER
Danger to life due to electric shock when touching live system components in
case of a ground fault
If a ground fault occurs, parts of the system may still be live. Touching live parts and cables
results in death or lethal injuries due to electric shock.
• Disconnect the product from voltage sources and make sure it cannot be reconnected
before working on the device.
• Touch the cables of the PV array on the insulation only.
• Do not touch any parts of the substructure or frame of the PV array.
• Do not connect PV strings with ground faults to the inverter.
WARNING
Danger to life due to electric shock from destruction of the measuring device
due to overvoltage
Overvoltage can damage a measuring device and result in voltage being present in the
enclosure of the measuring device. Touching the live enclosure of the measuring device results in
death or lethal injuries due to electric shock.
• Only use measuring devices with a DC input voltage range of 1000 V or higher.
Procedure:
In order to check the PV system for ground faults, perform the following actions in the prescribed
order. The exact procedure is described in the following sections.
• Check the PV system for ground faults by measuring the voltage.
• If the voltage measurement was not successful, check the PV system via insulation resistance
measurement for ground faults.
Test by Measuring the Voltage
Proceed as follows to check each string in the PV system for ground faults.
Procedure:
1. DANGER
Danger to life due to high voltages
• Disconnect the inverter from all voltage sources (see Section 9, page 81).
2. Measure the voltages:
• Measure the voltage between the positive terminal and the ground potential (PE).
• Measure the voltage between the negative terminal and the ground potential (PE).
• Measure the voltage between the positive and negative terminals.
If the following results are present at the same time, there is a ground fault in the PV
system:
☑ All measured voltages are stable.
☑ The sum of the two voltages to ground potential is approximately equal to the
voltage between the positive and negative terminals.
3. If a ground fault is present, determine the location of the ground fault via the ratio of the two
measured voltages and eliminate the ground fault.
4. If a definite ground fault cannot be measured and the message is still displayed, measure the
insulation resistance.
5. Reconnect the strings without ground faults to the inverter and recommission the inverter (see
inverter installation inverter).
The example shows a ground fault between the second and third PV module.
V1 = 200 V V2 = 300 V
total
The exact insulation resistance of a PV module can be obtained from the module manufacturer
or the datasheet.
For the resistance of a PV module an average value can be assumed: for thin-film PV modules
approximately 40 MOhm and for polycrystalline and monocrystalline PV modules
approximately 50 MOhm per PV module (for further information on calculating the insulation
resistance see the Technical Information "Insulation Resistance (Riso) of Non-Galvanically
Isolated PV Systems" at www.SMA-Solar.com).
Required devices:
☐ Suitable device for safe disconnection and short-circuiting
☐ Measuring device for insulation resistance
Device required for safe disconnection and short-circuiting of the PV array
The insulation resistance can only be measured with a suitable device for safe disconnection
and short-circuiting of the PV array. If no suitable device is available, the insulation
measurement must not be carried out.
Procedure:
1. Calculate the expected insulation resistance per string.
2. DANGER
Danger to life due to high voltages
• Disconnect the inverter from all voltage sources (see Section 9, page 81).
3. Install the short circuit device.
4. Connect the measuring device for insulation resistance.
5. Short-circuit the first string.
6. Set the test voltage. The test voltage should be as close as possible to the maximum system
voltage of the PV modules but must not exceed it (see datasheet of the PV modules).
7. Measure the insulation resistance.
8. Eliminate the short circuit.
9. Measure the remaining strings in the same manner.
☑ If the insulation resistance of a string deviates considerably from the theoretically
calculated value, there is a ground fault present in that string.
10. Reconnect to the inverter only those strings from which the ground fault has been eliminated.
11. Reconnect all other strings to the inverter.
To decommission the inverter completely upon completion of its service life, proceed as described
in this Section.
CAUTION
Risk of injury when lifting the inverter, or if it is dropped
The inverter weighs 84 kg. You risk injury if you lift the inverter incorrectly or if it is dropped while
being transported or mounted.
• Carry and lift the inverter in an upright position with several people without tilting it.
Requirements:
☐ A pallet must be available.
☐ Original packaging with paddings must be available.
☐ All transport handles must be in place.
Procedure:
1. DANGER
Danger to life due to high voltages
• Disconnect the inverter from all voltage sources (see Section 9, page 81).
2. CAUTION
Risk of burns due to hot enclosure parts
• Wait 30 minutes for the enclosure to cool down.
3. Remove the AC cable from the inverter. To do so,
loosen the screws (AF8) and pull the cables out of
the terminal.
1 L1
L2
L3 2
N
2 1
Max. 30V DC
10. Set the screws and the enclosure lid aside and store safely.
11. Remove all connection cables from the
USB
X2
communication assembly and pull out the
connection cables out of the DC-Connection Unit.
FCC ID: SVF-KP20
IC: 9440A-KP20
A
M2
B
ANT.
SPS
12. Remove all cable glands from the inverter. To do so, unscrew the counter nut from inside and
remove the cable glad from the enclosure opening.
surge arrester.
1 2
17. To remove the feet or profile rails, lay the inverter carefully on the AC-Connection Unit side.
18. If the inverter is to be stored or shipped, pack the inverter in its original packaging.
• Place the lower part of the original packaging with padding on the pallet
• Place the inverter with padding on the pallet. For this purpose, put the AC-Connection
Unit side of the inverter on top of the padding.
• Pull the upper part of the original packaging over the inverter.
• Insert the upper padding.
• Close the packaging.
• Secure the packaging and pallet with strapping or with fastening belts.
19. Dispose of the inverter in accordance with the locally applicable disposal regulations for
electronic waste.
13 Technical Data
DC Input
Maximum PV array power 75000 Wp STC
Maximum input voltage 1000 V
MPP voltage range 500 V to 800 V
Rated input voltage 670 V
Minimum input voltage 150 V
Initial input voltage 188 V
Maximum input current per DC connector 20 A
Maximum input current per input 20 A
Maximum short-circuit current per input* 30 A
Maximum reverse current into the PV array 0 A
Number of independent MPP inputs 6
Strings per MPP input 2
Surge category in accordance with II
IEC 62109-1
* In accordance with IEC 62109-2: ISC PV
AC Output
Rated power at 230 V, 50 Hz 50000 W
Maximum apparent AC power 50000 VA
Rated grid voltage 230 V
Nominal AC voltage 400 V / 230 V
AC voltage range* 202 V to 264 V
Nominal AC current at 230 V 72.5 A
Maximum output current 72.5 A
Maximum output current under fault conditions 86 A
Total harmonic distortion of the output current < 2 %
with total harmonic distortion of the AC voltage
<2%, and AC power >50% of the rated power
Inrush current < 10% of the nominal AC current for a
maximum of 10 ms
Rated power frequency 50 Hz
AC power frequency* 50 Hz / 60 Hz
Multifunction relay
Maximum DC switching voltage 30 V
Maximum AC switching current 1.0 A
Maximum DC switching current 1.0 A
Minimum load 0.1 W
Minimum electrical endurance when the maxi- 100000 switching cycles
mum switching voltage and maximum switching
current are complied with*
* Corresponds to 20 years at 12 switching operations per day
Efficiency
Maximum efficiency, ηmax > 98.1 %
European weighted efficiency, ηEU > 97.8 %
Protective Devices
DC reverse polarity protection Short-circuit diode
Input-side disconnection point DC Load-Break Switch
DC surge protection Surge arrester type 1 and 2 (optional)
AC short-circuit current capability Current control
Grid monitoring SMA Grid Guard 10.0
Maximum overcurrent protection 100 A
Ground fault monitoring Insulation monitoring: Riso > 34 kΩ
All-pole sensitive residual-current monitoring unit Available
General Data
Width x height x depth, without feet or DC load- 592 mm x 733 mm x 679 mm
break switch
Weight 84 kg
Length x width x height of the packaging 800 mm x 600 mm x 886 mm
Transport weight 100 kg
Climatic category in accordance with IEC 4K4H
60721-3-4
Environmental category Outdoors
Pollution degree of all enclosure parts 2
Operating temperature range -25°C to +60°C
Maximum permissible value for relative humidity 100 %
(condensing)
Maximum operating altitude above mean sea 3000 m
level (MSL)
Typical noise emission 64 dB(A)
Power loss in night mode 5 W
Topology Transformerless
Cooling method SMA OptiCool
Number of fans 3
Degree of protection for electronics in accor- IP65
dance with IEC 60529
Protection class in accordance with I
IEC 62109-1
Radio technology WLAN 802.11 b/g/n
Radio spectrum 2.4 GHz
Maximum transmission power 100 mW
Grid configurations TN-C, TN-S, TN-C-S, TT (when VN_PE < 20 V)
Climatic Conditions
Installation in accordance with IEC 60721-3-4, Class 4K4H
Extended temperature range -25°C to +60°C
Extended humidity range 0% to 100%
Equipment
DC connection SUNCLIX DC connector
AC terminal Screw terminals
Multifunction relay As standard
Surge protection devices Type II for AC and/or Optional
DC
Torques
Screws for the DC-Connection Unit and AC-Con- 6 Nm
nection Unit enclosure lids
Screws for AC terminals with conductor cross- 20 Nm
section of 35 mm² to 95 mm²
Screws for AC terminals with conductor cross- 30 Nm
section of 120 mm²
Screws for attaching the feet or profile rails 16 Nm
Screws for the cover on the top of the inverter 6 Nm
Counter nut of M63 cable gland 14 Nm
Swivel nut for M63 cable gland 33 Nm
Swivel nut for M32 cable gland 5 Nm
SUNCLIX swivel nut 2 Nm
14 Accessories
You will find the accessories for your product in the following overview. If required, these can be
ordered from SMA Solar Technology AG or your distributor.
Designation Short designation SMA order number
SMA Antenna Exten- Accessory set for one SMA inverter for the EXTANT-40
sion Kit optimization of the SMA inverter’s WLAN
radio range.
SMA Sensor Module Interface for one SMA inverter as retrofit kit MD.SEN-40
for capturing environmental data (e.g. solar
irradiation, ambient temperature, cell tem-
perature, wind speed or S0 meters).
Universal mounting sys- For wall mounting or as a platform for UMS_KIT-10
tem higher mounting of the inverter on the
ground
SMA 485 Module Interface for establishing cable-bound com- MD.485-40
munication via RS485
SMA I/O modules Interface to implement grid management MD.IO-40
services and/or grid and PV system protec-
tion
AC overvoltage protec- Surge protection devices Type II for AC AC_SPD_Kit1-10
tion elements side
DC overvoltage protec- Surge protection devices Type II for DC DC_SPD_Kit4-10
tion elements side
15 Contact
If you have technical problems with our products, please contact the SMA Service Line. The
following data is required in order to provide you with the necessary assistance:
• Device type
• Serial number
• Firmware version
• Event message
• Mounting location and mounting height
• Type and number of PV modules
• Optional equipment, e.g. communication products
• Use the name of the system in Sunny Portal (if available)
• Access data for Sunny Portal (if available)
• Special country-specific settings (if available)
• Operating mode of the multifunction relay
Deutschland SMA Solar Technology AG Belgien SMA Benelux BVBA/SPRL
Österreich Niestetal Belgique Mechelen
Schweiz Sunny Boy, Sunny Mini Central, België +32 15 286 730
Sunny Tripower, Sunny High- Luxemburg for Netherlands: +31 30 2492
power: +49 561 9522‑1499 Luxembourg 000
Monitoring Systems Nederland SMA Online Service Center:
(Kommunikationsprodukte): www.SMA-Service.com
+49 561 9522‑2499
Česko SMA Service Partner TERMS
Hybrid Controller:
+49 561 9522-3199 Magyarország a.s.
Slovensko +420 387 6 85 111
Sunny Island, Sunny Boy Stor-
age, Sunny Backup: SMA Online Service Center:
+49 561 9522-399 www.SMA-Service.com
Sunny Central, Sunny Central Türkiye SMA Service Partner DEKOM
Storage: Telekomünikasyon A. Ş.
+49 561 9522-299 +90 24 22430605
SMA Online Service Center: SMA Online Service Center:
www.SMA-Service.com www.SMA-Service.com
France SMA France S.A.S. Ελλάδα SMA Service Partner AKTOR
Lyon Κύπρος FM.
+33 472 22 97 00 Αθήνα
SMA Online Service Center : +30 210 8184550
www.SMA-Service.com SMA Online Service Center:
www.SMA-Service.com
España SMA Ibérica Tecnología Solar, United King- SMA Solar UK Ltd.
Portugal S.L.U. dom Milton Keynes
Barcelona +44 1908 304899
+34 935 63 50 99 SMA Online Service Center:
SMA Online Service Center: www.SMA-Service.com
www.SMA-Service.com
Italia SMA Italia S.r.l. Australia SMA Australia Pty Ltd.
Milano Sydney
+39 02 8934-7299 Toll free for Australia:
SMA Online Service Center: 1800 SMA AUS
www.SMA-Service.com (1800 762 287)
International:
+61 2 9491 4200
United Arab SMA Middle East LLC India SMA Solar India Pvt. Ltd.
Emirates Abu Dhabi Mumbai
+971 2234 6177 +91 22 61713888
SMA Online Service Center:
www.SMA-Service.com
ไทย Service Partner for String inverter: 대한민국 Enerone Technology Co., Ltd
Solar Power Engineering Co., Ltd. 4th Fl, Jungbu Bldg, 329,
333/7,8,9 United Tower Build- Yeongdong-daero, Gangnam-
ing 4th floor. gu,
Soi Sukhumvit 55 (Thonglor 17), Seoul, 06188, Korea
Klongton Nua, Wattana, +82-2-520-2666
10110 Bangkok, Thailand
Argentina SMA South America SPA
+66 20598220
Brasil Santiago de Chile
smaservice@spe.co.th
Chile +562 2820 2101
Service Partner for Utility:
Perú
Tirathai E & S Co., Ltd
South Africa SMA Solar Technology South
516/1 Moo 4, Bangpoo Indus-
Africa Pty Ltd.
trial Estate
Cape Town
Sukhumvit Road, T. Praksa, A.
Muang 08600SUNNY (08600
78669)
10280 Samutprakarn, Thailand
International: +27 (0)21 826
+63 1799866
0699
servicepartner.sma@tirathai.co.th
SMA Online Service Center:
www.SMA-Service.com
Other coun- International SMA Service Line
tries Niestetal
00800 SMA SERVICE
(+800 762 7378423)
SMA Online Service Center:
www.SMA-Service.com
16 EU Declaration of Conformity
within the scope of the EU directives
• Electromagnetic compatibility 2014/30/EU (29.3.2014 L 96/79-106)
(EMC)
• Low Voltage Directive 2014/35/EU (29.3.2014 L 96/357-374) (LVD)
• Radio Equipment Directive 2014/53/EU (22.5.2014 L 153/62) (RED)
• Restriction of the use of certain hazardous substances 2011/65/EU
(L 174/88, June 8, 2011) and 2015/863/EU (L 137/10, March 31,
2015) (RoHS)
SMA Solar Technology AG confirms herewith that the products described in this document are in
compliance with the fundamental requirements and other relevant provisions of the above-
mentioned directives. The entire EU Declaration of Conformity can be found at www.SMA-
Solar.com.