WIRING DIAGRAM ELEVATOR

HOTEL SANTIKA – TMII


JAKARTA

LINE ®

ELEVATOR

PT.INDUSTRI LIFT INDO NUSANTARA


FACTORY :
JL. RAYA MANUKAN KULON NO. 60 BLOK E3-4
Telp : 031-7411392 . Fax : 031-7458035
SURABAYA
PANEL LISTRIK
MDP
3P & 1P
R/S/T/L0/N
GROUND

R S T Lo N PE

U
V
W MOTOR
PE

BK+
BK-
Coil Brake MACHINE
101 TRACTION
CONTROL 102 Safety Gear
PANEL PA
PB PG
VCC
GND
SHIELD

100
Governoor
101

2
1
0 -------- AJI DJH BI
DRAWING CHECKED APPROVED
REV. DATE
BY BY BY
PROJECT :
HOTEL SANTIKA 4/4
PREPARED BY :
LINE ®
ELEVATOR

DRAWING TITLE :
BLOK DIAGRAM 1

DRAWING NO. : REV.


I/008/NL-S/V-11
0

UNIT : SCALE : A4 (210 x 297)


CONTROL PANEL

FLU TRAVELLING
24 CORE

UPL

SLU 1

SLU 2
#
nDLS
HOP
LT.n
COP

MAINTENANCE BOX

HOP
LT.2 LEVEL OVER LOAD
2DLS

DOOR SWITCH SAFETY EDGE

HOP LAMP &FAN


LT.1
DOOR MOTOR

PARKING
CAR
1DLS

FIRE # : Untuk speed diatas 60 mpm

SLD 2
#
2
1
SLD 1 0 -------- AJI DJH BI

HOIST REV. DATE


DRAWING
BY
CHECKED
BY
APPROVED
BY
DNL WAY PROJECT :
HOTEL SANTIKA 4/4
FLD PREPARED BY :
LINE ®
ELEVATOR

E.S PIT DRAWING TITLE :


BLOCK DIAGRAM 2
POWER PIT DRAWING NO. : REV.
I/008/NL-S/V-11
0

UNIT : SCALE : A4 (210 x 297)


MC1 : MAIN CONTACTOR
R S T MC2 : UPS CONTACTOR
KC : RUNNING CONTACTOR
PG : PULSA GENERATOR
F1 : MCB 3P
F1 BRAKING
RESISTOR
INV. : INVERTER YASKAWA L1000

B1 B2
A A1
L1 A3 U
L1 T1 U
B B1
L2 B3 V MOTOR
L2 T2 V 3 PHASA
C C1
L3 C3 W
L3 T3 W
PE
MC PE

INV.
CM
FWD S1 PG-B3
REV MC2
S2
SC S3 A+
SPD.3 S4 A-
SPD.2 S5 B+
SPD.1 S6 B-
RST S7 Z+
Z-
PG
BTRY S8
SD
COM3 SN
IP
SC IG
SP FE

M1 MB A0
MC IG
M2 M5 B0 To Mico
M6 IG Control
M3 M1 Z0
IG
N24 M2

M3P M3 M3J
INV.
M1 X20 X4 X1 ERROR
INV.
M2 X50 X2 X5 RUNNING
2
ZERO
M3 - X3 X6 SPEED
1
0 -------- AJI DJH BI
DRAWING CHECKED APPROVED
REV. DATE
BY BY BY
M3P M3 M3J PROJECT :
FWD Y11 Y16 Y4 1 1 1 1 HOTEL SANTIKA 4/4
REV Y12 Y15 Y5 1 1 1 1 PREPARED BY :
SPD.3 Y14 Y22 Y7 1 0 0 1 LINE ®
ELEVATOR

SPD.2 Y15 Y23 Y10 0 0 1 0 DRAWING TITLE :


SPD.1 Y16 Y24 Y11 0 1 1 1 INVERTER
RST Y17 Y11 Y12 - - - - DRAWING NO. : REV.
Low Middle I/008/NL-S/V-11
JOG Creep 0
Speed Speed
SPEED Speed
≤ 60mpm > 60mpm
UNIT : SCALE : A4 (210 x 297)
L0 L1
F3/6A

Stop kontak
SW1
PIT

Stop kontak
230 VAC

230 VAC
Lamp
Lamp.
Panel
Top Car
N0 Lamp

N1
Top Car Pit Room

TRAFO
STEP
DOWN B110 110
A

+
AC
F2/6A F4/4A F5/4A VDC
A1
D1
A110
0
_
N AC
VDC

BC BC
110
VDC T1 L1 T2 L2 BK-

BR MB
BC A1 L11
BK+ F6/4A
0
VDC T3 L3
OPTIONAL

A1 POWER P24
SUPPLY 2
SWITCHING 1
0 -------- AJI DJH BI
24VDC
N N24 REV. DATE
DRAWING CHECKED APPROVED
BY BY BY
PROJECT :
HOTEL SANTIKA 4/4

PREPARED BY :

D1 : DIODE RECTIFIER 35A/1000V


LINE ®
ELEVATOR

BR : COIL BRAKE DRAWING TITLE :


POWER
MB : MECHANICAL BRAKE
KC : RUNNING CONTACTOR DRAWING NO. : REV.
I/008/NL-S/V-11
BC : BRAKE CONTACTOR 0

UNIT : SCALE : A4 (210 x 297)


100 100A 101 102
B110
FLU FLD SSW1
E.S 1
SAFETY MACHINE ROOM
SAFETY HOISTWAY

102 104 105 106

SSW5 E.S 3 E.S 4


E.S 2

SAFETY CAR SAFETY PANEL

X33

110
X32
GS

111
X31
1DS 2DS nDS

BC1
A1 BC N

MC1
MC
GS : Car Door Lock
1DS : Hall Door Lock for 1 st Floor
2DS : Hall Door Lock for 2 nd Floor
nDS : Hall Door Lock for n Floor 2
1
FLD : Final Limit Down 0 -------- AJI DJH BI
DRAWING CHECKED APPROVED
FLU : Final Limit Up REV. DATE
BY BY BY
SSW1 : Governoor PROJECT :
HOTEL SANTIKA 4/4
SSW5 : Emergency Exit
E.S 1 : Emergency Stop Pit Room PREPARED BY :

E.S 2 : Emergency Stop Car Top


LINE ®
ELEVATOR

E.S 3 : Emergency Stop In Car (COP) DRAWING TITLE :


SAFETY & GATE S/W
E.S 4 : Emergency Stop Control Panel
BC : Brake Contactor DRAWING NO. : REV.
I/008/NL-S/V-11
0

UNIT : SCALE : A4 (210 x 297)


P24 N24

HOISTWAY
M1

CAR

CABINET
X00
Running Feedback KC1
X01
Inverter Running
X02 M2
Inverter Zero Speed
X03 M3
Inverter Monitor
X04 M1
X05
Ins.Slow Down
X06
Ins.Slow Up
X07
X10
X11
Brake Feedback BC
X12
X13
X14

M3 A110
Hall Door
X31 DL111
Car Door
X32 DL110
Safety Circuit
X33 S106

M3
ARM

2
1
0 -------- AJI DJH BI
DRAWING CHECKED APPROVED
REV. DATE
BY BY BY
PROJECT :
HOTEL SANTIKA 4/4
PREPARED BY :
LINE ®
ELEVATOR

DRAWING TITLE :
INPUT 1

DRAWING NO. : REV.


I/008/NL-S/V-11
0

UNIT : SCALE : A4 (210 x 297)


P24 N24

M2

HOISTWAY

CAR

CABINET
X15
Leveling LVL
X16
Ins. / Normal
X17
Fire FS
X20
Parking PRK
X21
Down Limit DNL
X22
Up Limit UPL
X23
Slow Down 2 SLD 2 ( Speed > 60 MPM )
X24
Slow Up 2 SLU 2 ( Speed > 60 MPM )
X25
Slow Down 1 SLD1
X26
Slow Up 1 SLU1
X27
UPS EMC
X30

A+ IP

B+ INV.

A- A0

B- B0

M3
ARM

2
1
0 -------- AJI DJH BI
DRAWING CHECKED APPROVED
REV. DATE
BY BY BY
PROJECT :
HOTEL SANTIKA 4/4
PREPARED BY :
LINE ®
ELEVATOR

DRAWING TITLE :
INPUT 2

DRAWING NO. : REV.


I/008/NL-S/V-11
0

UNIT : SCALE : A4 (210 x 297)


P24 N24
COM1
-
Y00
-
Y01 BC1 14
13

-
Y02 KC1 14
13

-
Y03 MC1 14
13

COM3 SN

Y11 S7

Y12
Y13
-
Run Down Dir.
Y15 REV
Run Up Dir.
Y16 FWD

Y17
INV
COM4 YASKAWA
L1000A
Y20
Y21
JOG SPEED
Y22 S4 High Speed ≥ 120 MPM
Low Speed Medium Speed ≥ 90 MPM
Y23 S5
Creep Speed Low Speed ≤ 60 MPM
Y24 S6

2
Y25 1
0 -------- AJI DJH BI
DRAWING CHECKED APPROVED
0V N24 REV. DATE
BY BY BY
PROJECT :
+ 24V P24 HOTEL SANTIKA 4/4

PREPARED BY :
M3 LINE ®
ELEVATOR

ARM DRAWING TITLE :


OUTPUT 1
DC : LOCK LIFT CONTACTOR
DRAWING NO. : REV.
LR : RELAY LAMP & FAN I/008/NL-S/V-11
DOR : DOOR OPEN CONTACTOR 0

DCR : DOOR CLOSE CONTACTOR UNIT : SCALE : A4 (210 x 297)


P24 N24

HOISTWAY

CAR
M4 Input power public terminal

--
X34 Leveling point for security module input
(for ahead open door)
X35 Monitering point for security module input
(for ahead open door)

GND N24
+24V
GND
+24V P24

VCC H
CAN5 CAN bus interface for Car Call
GND L

VCC H
CAN4 CAN bus interface for Hall Call
GND L

VCC H
CAN3 CAN bus interface for Hall Call
GND L

VCC H
CAN2 Control or paraller connection
GND L

VCC H
CAN1 Control or paraller connection
GND L

M3
ARM

2
1
0 -------- AJI DJH BI
DRAWING CHECKED APPROVED
REV. DATE
BY BY BY
PROJECT :
HOTEL SANTIKA 4/4

PREPARED BY :
LINE ®
ELEVATOR

DRAWING TITLE :
OUTPUT 2

DRAWING NO. : REV.


I/008/NL-S/V-11
0

UNIT : SCALE : A4 (210 x 297)


GND

GND
VCC

VCC
H

H
L

L
L.1C 1C
LED01 IN01
L.2C 2C
LED02 IN02
L.3C 3C
LED03 IN03
L.4C 4C
LED04 IN04
LED05 IN05
LED06 IN06
LED07 IN07
LED08 IN08

BOARD
ICAL-08C
(Ada di COP)
X01
X02
X03
X04
X05
X06
DCB
X07
DOB
X08
GND
VCC
Q1
Q2
Q3
Q4
Q5
Q6
Q7
Q8
Light for Close
Light for Open

BUZZER

2
1
0 -------- AJI DJH BI
DRAWING CHECKED APPROVED
REV. DATE
BY BY BY
PROJECT :
HOTEL SANTIKA 4/4

PREPARED BY :
LINE ®
ELEVATOR

DRAWING TITLE :
ICAL-08C

DRAWING NO. : REV.


I/008/NL-S/V-11
0

UNIT : SCALE : A4 (210 x 297)


N24

INS1

311

INS2

310

INS3
DINS1

UINS1

DINS2

UINS2

DINS3

UINS3
INS DN

INS UP
X06

X17
XO7

INS
CONTROL
TO MICO

INS1 : INS/AUTO TOP CAR


2
INS2 : INS/AUTO IN CAR 1
0 -------- AJI DJH BI
INS3 : INS/AUTO CONTROL PANEL REV. DATE
DRAWING CHECKED APPROVED
BY BY BY
UINS1 : INS.UP TOP CAR PROJECT :
UINS2 : INS.UP IN CAR HOTEL SANTIKA 4/4
UINS3 : INS.UP CONTROL PANEL PREPARED BY :
DINS1 : INS.DN TOP CAR LINE ®
ELEVATOR

UINS2 : INS.DN TIN CAR DRAWING TITLE :


UINS3 : INS.DN CONTROL PANEL Rangkaian Inspection

DRAWING NO. : REV.


I/008/NL-S/V-11
0

UNIT : SCALE : A4 (210 x 297)


BOARD PM 709
(Ada di Maintenance Box)
DOOR

GND
GND

VCC
VCC
MOTOR
FERMATOR P24

H
H

L
L
9 COM2 N24
12 b00
8 b01 COM1
11 b02 Door Open Limit1 A00
b03 Door Close Limit1 A01
10
Door Open Limit2 A02
Door Close Limit2 A03
Over Load (110%) A04
COM3
Full Load (100%) A05
b04
Half Load (20%) A06
b05
Safety Edge A07
A10
ArrivalGong
A11
A12
Level A13
L1
L2 COM4
b06 C110
Fan Lamp X16
switch switch
(COP) (COP)

L2a L2b
Car Car
Fan Lamp

N1
A00 = DOOR OPEN LIMIT 1
A01 = DOOR CLOSE LIMIT 1
A02 = DOOR OPEN LIMIT 2
A03 = DOOR CLOSE LIMIT 2
A04 = OVER LOAD
2
A05 = FULL LOAD
1
A06 = LIGHT LOAD / ANTI-NUISANCE 0 -------- AJI DJH BI
DRAWING CHECKED APPROVED
A07 = SAFETY SHOE 1 REV. DATE
BY BY BY
A10 = SAFETY SHOE 2 PROJECT :
A11 = SPARE HOTEL SANTIKA 4/4
A12 = SPARE
PREPARED BY :
A13 = LEVELING SENSOR
b00 = door open 1
LINE ®
ELEVATOR

b01 = door close 1 DRAWING TITLE :


b02 = door open 2 PM709
b03 = door close 2
DRAWING NO. : REV.
b04 = arrival gong
I/008/NL-S/V-11
b05 = spare 0

b06 = lighting UNIT : SCALE : A4 (210 x 297)


RANGKAIAN MAINTENANCE BOX & DOOR MOTOR

INS1
TB2 TB11
UINS1
TB9

COM DINS1
TB10

Lamp
TB7
TB6 TB8 TA1 TA2
SSW5
E.S 2
Stop kontak

230 VAC

INVERTER DOOR INVERTER DOOR


MOTOR MOTOR
L11/TB3
Fermator Fermator
5
L11/TB3
5
6
56 M PG
56 M PG
PE 6
PE
7
7
N/TB4 55 N/TB4 55
b01 8
b03 8
COM2 9
30 A00 COM2 9
30 A02
10 31
PM709 COM1 10 31 COM1
11 PM709
34 PM709 11
34 PM709
b00 12
33 A01 b02 12
33 A03

2
1
0 -------- AJI DJH BI
DRAWING CHECKED APPROVED
REV. DATE
BY BY BY
E.S 2 : Emergency Stop on Top Car PROJECT :
HOTEL SANTIKA 4/4
SSW5 : Emergency Exit (Optional)
PREPARED BY :
INS1 : SWITCH INS./AUTO TOP CAR
LINE ®
ELEVATOR

UINS1/DINS1 : Switch Up/Down Ins.Top Car


DRAWING TITLE :
M/B & DOOR MOTOR
DOR : DOOR OPEN RELAY (PANEL) DRAWING NO. : REV.
I/008/NL-S/V-11
0
DCR : DOOR CLOSE RELAY (PANEL)
UNIT : SCALE : A4 (210 x 297)
TERMINAL A
NO NAME MARK
1 POWER 220 VAC L1
2 POWER 0 VAC N0
3 POWER DOOR MOTOR 220 VAC L11
4 POWER DOOR MOTOR 0 VAC N
5 FAN L2a
6 POWER 0 VAC (FAN) N 220 VAC
7 LAMPU L2b
8 POWER 0 VAC (LAMPU) N 220 VAC
9 LAMPU N 220 VAC
10 POWER 0 VAC (LAMPU) L2b
11 POWER 220 VAC L2
12 -------- ---

TERMINAL B
NO NAME MARK
1 +24 VDC P24
2 -24 VDC N24
3 -24 VDC N24
4 -24 VDC N24
5 LEVELING X16
6 ES TOP CAR 102
7 ES TOP CAR 104
8 105
9 INS.UP X07
10 INS.DOWN X06
11 311
12 310

TERMINAL C

NO NAME MARK
1 DOOR LOCK SWITCH 106
2 DOOR LOCK SWITCH 110
3
4
5
6
7 2
8 1
0 -------- AJI DJH BI
9 REV. DATE
DRAWING CHECKED APPROVED
BY BY BY
10 PROJECT :
11 HOTEL SANTIKA 4/4
12
PREPARED BY :
LINE ®
ELEVATOR

DRAWING TITLE : Terminal Maintenance


Box
DRAWING NO. : REV.
I/008/NL-S/V-11
0

UNIT : SCALE : A4 (210 x 297)


P24
N24
P24
N24
INTERKOM
UPL(X23)
INTERKOM
DNL(X22)
INTERKOM
SLU1(X27)

SLD1(X26)
BK+
FIRE(X20)
BK-
PARK(X21)

LEVEL(X16)
L.220VAC(L0)
INPUT POWER 310
N.220VAC(N0)
INS.UP(X07)

INS.DN(X06)
L220VAC(L1)
POWER
B110 B110
PIT ROOM
N220VAC(N1) Safety Hoistway
101 101

101 101
L.220VAC(L1) Safety Machine Room
POWER CAR 102 102
N220VAC(N1)
102 102
Safety Car
105 105
L220VAC(L11)
POWER
106 106
DOOR MOTOR
N220VAC(N1) Car Door
110(X32) 110

106 106
A110 Hall Door
111(X31) 111

2
1
0 -------- AJI DJH BI
DRAWING CHECKED APPROVED
REV. DATE
BY BY BY
PROJECT :
HOTEL SANTIKA 4/4

PREPARED BY :
LINE ®
ELEVATOR

DRAWING TITLE : TERMINAL


PANELCONTROL
DRAWING NO. : REV.
I/008/NL-S/V-11
0

UNIT : SCALE : A4 (210 x 297)


No. Fungsi Keterangan

1 SAFETY B110

2 SAFETY 101

3 PINTU 106

4 PINTU 111

5 SLD X26

6 N24 N24

7 LSD X22

8 N24 N24

9 LSU X23

10 N24 N24

11 SLU X27

12 N24 N24

13 FIRE X20

14 N24 N24

15 PARKING X21

16 N24 N24

17 L220 L220 VAC

18 N220 N220 VAC

19
20
21
22
23
24

No. Fungsi Keterangan

1 - 24VDC N24
KABEL
2 + 24VDC P24

3 DATA H
DATA
4 DATA L
4Core

2
1
0 -------- AJI DJH BI
DRAWING CHECKED APPROVED
REV. DATE
BY BY BY
PROJECT :
HOTEL SANTIKA 4/4
PREPARED BY :
LINE ®
ELEVATOR

DRAWING TITLE :
Cable Hoistway

DRAWING NO. : REV.


I/008/NL-S/V-11
0

UNIT : SCALE : A4 (210 x 297)


CABLE TRAVELLING 24 CORE DARI C/P
No WARNA TUJUAN FUNGSI
1 KUNING M/B L1
VCC
2 KUNING M/B L11
GND
3 KUNING M/B N SERIAL CABLE
H
4 KUNING M/B GROUND
L
5 KUNING M/B SAFETY(102)
6 KUNING M/B SAFETY(105) L1 / N0 : Power Service (220 VAC)
7 KUNING M/B DOOR(110) L11 / N : Power Door Motor
8 KUNING M/B DOOR(106) M/B : Maintenance Box
9 KUNING M/B P24 SE/PHS : Safety Edge/Photo Sensor
10 KUNING M/B N24 C/P : Control Panel
11 KUNING M/B -- P24/N24 : + 24 VDC / - 24 VDC
12 KUNING M/B --
13 KUNING M/B GROUND
14 KUNING M/B INTERPHONE -
15 KUNING M/B INTERPHONE
16 KUNING M/B INTERPHONE -
17 KUNING M/B INS.DN(X06)
18 KUNING M/B INS.UP(X07)
19 KUNING M/B 310
20 KUNING M/B LEVEL(X16)
21 KUNING M/B VCC
22 KUNING M/B GND
23 KUNING M/B L
24 KUNING M/B H

CABLE DARI M/B KE COP

No FUNGSI
1 M/B COP VCC
2 M/B COP GND
3 M/B COP H
4 M/B COP L
5 M/B COP Ins.Dn(X06)
6 M/B COP Ins.Up(X07)
7 M/B COP ---
8 M/B COP INTERPHONE
9 M/B COP INTERPHONE
10 M/B COP INTERPHONE
2
11 M/B COP 310 1
0 -------- AJI DJH BI
12 M/B COP 311 DRAWING CHECKED APPROVED
REV. DATE
BY BY BY
13 M/B COP SAFETY(104)
PROJECT :
14 M/B COP SAFETY(105) HOTEL SANTIKA 4/4
15 M/B COP L2
PREPARED BY :
16 M/B COP L2a LINE ®
ELEVATOR
17 M/B COP L2b
18 M/B COP GROUND
DRAWING TITLE : TRAVELLING CABLE
24
DRAWING NO. : REV.
I/008/NL-S/V-11
0

UNIT : SCALE : A4 (210 x 297)


CONTROL PANEL M3 ARM

X26
X24

X21
X22

X20

X27
X25
X23
101

111

106
N0

N24
N24
L1

FLU
N24/100

UPL
X23/N24

SLU 1 nDLS
X25/N24

SLU 2
X27/N24
#

5DLS
100
4DLS

3DLS

2DLS

1DLS

nDLS : SWITCH PINTU LANTAI ke n


2DLS : SWITCH PINTU LANTAI 2
1DLS : SWITCH PINTU LANTAI 1
SLD1 : SLOW DOWN 1
SLD2 : SLOW DOWN 2
SLU1 : SLOW UP 1
SLU2 : SLOW UP 2
PARKING DNL : DOWN LIMIT
X21/N24
UPL : UP LIMIT
FIRE FLD : FINAL LIMIT DOWN
X20/N24
FLU : FINAL LIMIT UP
SLD 2 # # : Untuk speed diatas 60 mpm
X24/N24
2
SLD 1 1
--------
X26/N24 0 AJI DJH BI
DRAWING CHECKED APPROVED
REV. DATE
BY BY BY
DNL PROJECT :
X22/N24 HOTEL SANTIKA 4/4
FLD
101 PREPARED BY :
100/100A LINE ®
ELEVATOR
100A
E.S PIT DRAWING TITLE :
100A/101 Safety Hoistway
POWER PIT DRAWING NO. : REV.
L1/N0 I/008/NL-S/V-11
0

UNIT : SCALE : A4 (210 x 297)


HOP DP003M
CABLE
LT N 4 CORE
VCC H VCC H VCC H
CONTROL PANEL
GND L GND L GND L

VCC H
GND L

UPB TRAVELLING
24 CORE
UPL
COM
COM

DNB MAINTENANCE BOX


DNL
COM PM709
COM
VCC H
GND L

VCC H
GND L

COP
HOP DP003M
LT.2 VCC H
ICAL-08C
GND L

VCC H VCC H
GND L GND L

VCC H
UPB
GND L
UPL
COM
DP003L
COM
VCC H
DNB
GND L
DNL
VCC H
COM
GND L
COM

HOP DP003M
LT.1 VCC H
GND L

VCC H
2
GND L 1
0 -------- AJI DJH BI
DRAWING CHECKED APPROVED
UPB REV. DATE
BY BY BY
UPL PROJECT :
HOTEL SANTIKA 4/4
COM
COM PREPARED BY :
LINE ®
ELEVATOR

DNB DRAWING TITLE :


DNL ------------------
COM DRAWING NO. : REV.
COM I/008/NL-S/V-11
0

UNIT : SCALE : A4 (210 x 297)


FLU 150 MM FLU

UP LIMIT UP LIMIT
Up Limit harus aktif ketika Lift
berada 5 cm di atas sill luar
lantai teratas.
1550 MM

SLU

LANTAI CAR

5 CM
SLU

LANTAI
TERATAS

SLD

1550 MM

SLD

LANTAI 1
SILL LANTAI 5 CM
LANTAI CAR Down Limit harus aktif ketika
DOWN LIMIT Lift berada 5 cm di bawah sill 150 MM DOWN LIMIT
luar lantai 1.

FLD FLD

2
1
0 -------- AJI DJH BI
DRAWING CHECKED APPROVED
REV. DATE
BY BY BY
PROJECT :
HOTEL SANTIKA 4/4

PREPARED BY :
LINE ®
ELEVATOR

DRAWING TITLE :
Ukuran Switch Safety

DRAWING NO. : REV.


I/008/NL-S/V-11
0

UNIT : SCALE : A4 (210 x 297)


DUTY ROOM MACHINE ROOM
MAIN-PHONE MAIN-PHONE CAR SUB-PHONE
XL-DJMN01 XL-DJMN01
XL-DJMN
YELLOW

YELLOW

YELLOW
BLUE

BLUE
BLUE

GREEN
RED

RED

CALLING
BLACK

BLACK

WHITE
+

_
DC SUPPLY
~
220 VAC

XL-YD-12

2
1
0 -------- AJI DJH BI
DRAWING CHECKED APPROVED
REV. DATE
BY BY BY
PROJECT :
HOTEL SANTIKA 4/4

PREPARED BY :
LINE ®
ELEVATOR

DRAWING TITLE :
Interphone

DRAWING NO. : REV.


I/008/NL-S/V-11
0

UNIT : SCALE : A4 (210 x 297)


MACHINE ROOM CAR SUB-PHONE
MAIN-PHONE (COP)
NKT12(1-1)A NKT12(1-1)B

R
L

L
EB1

CALLING
+

EB2
-

+
-
R
+

L
-

CAR SUB-PHONE
(M/B)
~

+
220 VAC

NKT12(1-1)B1
~

DC SUPPLY
RKP 220/12
2
1
0 -------- DJH DJH BI
DRAWING CHECKED APPROVED
REV. DATE
BY BY BY
PROJECT :
HOTEL SANTIKA 4/4

PREPARED BY :
LINE ®
ELEVATOR

DRAWING TITLE :
INTERPHONE

DRAWING NO. : REV.


I/008/NL-S/V-11
0

UNIT : SCALE : A4 (210 x 297)


TRAVO

INVERTER

POWER SUPLY

M3ARM

2
1
0 -------- AJI DJH BI
DRAWING CHECKED APPROVED
REV. DATE
BY BY BY
PROJECT :
HOTEL SANTIKA 4/4

PREPARED BY :
LINE ®
ELEVATOR

DRAWING TITLE :
TATA LETAK KOMPONEN