System Application of Datatech
System Application of Datatech
western.nl
DATATECH
INDEX
Example image 3
Technical features 5
DATATECH - technical data 10
Ed unit - direct expansion
DATATECH - electrical data 14
Ed unit - direct expansion
DATATECH - technical data 16
Ed dc version (direct expansion + chilled water coil)
DATATECH - electrical data 18
Ed dc version (direct expansion + chilled water coil)
DATATECH - technical data 20
Edw/fc version
DATATECH - electrical data 22
Edw/fc version
DATATECH - technical data 24
Cw unit
DATATECH - electrical data 26
Cw unit
DATATECH - technical data 27
Dw unit
DATATECH - electrical data 29
Unità dw
DATATECH - functioning limits 30
DATATECH - sound spectrums 32
Installations recommendations location 41
2
DATATECH
EXAMPLE IMAGE
3
DATATECH
EXAMPLE IMAGE
4
DATATECH
TECHNICAL FEATURES
DATATECH
The electronic appliances are products of a developing technology that generates constant changes. This leads to continuously
more advanced and compact technological devices, which however need a precise control of environmental conditions in order
to work.
The DATATECH air conditioners have been expressly designed to create “an ideal atmosphere” for electronic systems, removing
the excess heat and maintaining humidity within the tolerance limits with higher levels of reliability and safety.
CONFIGURATIONS
DATATECH O LED A 22.1 CO --
1 2 3 4 5 6 7
• 1. Series
• 2. Air flow direction
O = OVER upward
U = UNDER downward
• 3. Type of unit
ED = expansion
CW = cooled water
DW = double coil with cooled water
• 4. Type of condenser
A = remote air
W = incorporated water
• 5. Indicative capacity
• 6. Version
CO = cooling
CH = cooling + heating
HH = cooling + heating + humidification + dehumidification
• 7. Set-ups
DC = Dual Cooling
FC = Free Cooling
Set-up type
5
DATATECH
7
DATATECH
ELECTRIC ACCESSORIES
--Humidity signal probe
--Serial boards for supervision and tele-assistance
8
DATATECH
By means of the installation of a serial board, it is possible to • Stainless steel unit containment tank
connect the unit to
supervision and tele-assistance systems.
Depending on the requested communication protocol, dif-
ferent options are available:
--RS485 serial board allows the communication with Carel
and Modbus networks.
--Serial board for the communication to LonWorks® net-
works (FTT10 interface).
--Connection board to BACnet™ RS485 type networks.
--RS232 serial board that allows to connect the control to
a modem
both for standard PSTN and GSM telephone connections to
send SMS messages.
--pCO Web board for the connection to Ethernet networks
with SNMP protocol,
http,BACnet™ over IP.
VARIOUS ACCESSORIES
• Fire detection sensors
For the detection of fire with sensors located on the unit. The
sensor is the heat differential type and can perceive the speed
with which the temperature increases in a way to react rapidly
to the currents of hot air of a fire. It can protect and area of
49 m2 (7x7).
• Smoke detection sensors
For the detection of smoke with sensors located on the unit.
The sensor is the optical type and is approved at national level
by the Home Office while at international level it is has been
type-approved in compliance with CEN EN 54 part 7 and 8
Harmonised European Standards. It can protect an area of 81
m2 (9x9).
• Under floor flooding sensor
For the detection of water leaks, complete with sensor to be
positioned in the zone to control. Further sensors can be con-
nected on request to allow the control of several areas.
9
DATATECH
10
DATATECH
11
DATATECH
12
DATATECH
13
DATATECH
Maximum compressor absorbed current (1) A 12,9 19,1 7,7 9,4 12,0 9,8
Compressor in-rush current (3) A 58,0 97,0 48,0 66,0 69,0 63,0
Maximum AC fan absorbed current (1) A 1,1 1,1 1,5 1,5 1,5 5,0
Maximum EC fan absorbed current (1) 2,6 2,6 2,2 2,2 2,2 3,6
Standard electrical heaters maximum absorbed current (1) 13,0 13,0 6,5 6,5 6,5 6,5
Enhanced electrical heaters maximum absorbed current (1) 17,4 17,4 10,1 10,1 10,1 10,1
Humidifier maximum absorbed current (1) A 9,8 9,8 3,2 3,2 3,2 8,7
Maximum compressor absorbed current (1) A 14,2 15,9 18,8 20,5 22,2 19,6
Compressor in-rush current (3) A 73,0 100,0 75,4 100,0 100,0 72,8
Maximum AC fan absorbed current (1) A 5,0 5,0 5,0 5,0 5,0 10,0
Maximum EC fan absorbed current (1) 3,6 3,6 3,6 3,6 3,6 7,2
Standard electrical heaters maximum absorbed current (1) 6,5 13,0 13,0 13,0 13,0 13,0
Enhanced electrical heaters maximum absorbed current (1) 10,1 18,8 18,8 18,8 18,8 20,2
Humidifier maximum absorbed current (1) A 8,7 8,7 8,7 8,7 8,7 8,7
(1) Current at maximum permissible operating conditions. Please refer to wiring diagram for suggested cable size.
(2) With remote condenser arrangement, mains supply MUST comprise neutral.
(3) For twin compressor unit: one compressor at maximum load and one at startup
14
DATATECH
Maximum compressor absorbed current (1) A 22,2 24,0 28,4 30,6 36,2 41,0
Compressor in-rush current (3) A 100,0 81,0 87,2 174,0 118,1 120,5
Maximum AC fan absorbed current (1) A 10,0 10,0 10,0 10,0 10,0 10,0
Maximum EC fan absorbed current (1) 7,2 7,2 7,2 7,2 7,2 7,2
Standard electrical heaters maximum absorbed current (1) 13,0 13,0 13,0 13,0 13,0 13,0
Enhanced electrical heaters maximum absorbed current (1) 20,2 20,2 20,2 20,2 20,2 20,2
Humidifier maximum absorbed current (1) A 8,7 8,7 8,7 8,7 8,7 8,7
(1) Current at maximum permissible operating conditions. Please refer to wiring diagram for suggested cable size.
(2) With remote condenser arrangement, mains supply MUST comprise neutral.
(3) For twin compressor unit: one compressor at maximum load and one at startu
15
DATATECH
16
DATATECH
17
DATATECH
Maximum compressor absorbed current (1) A 9,8 14,2 15,9 20,5 19,6 22,2
Compressor in-rush current (3) A 63,0 73,0 100,0 100,0 72,8 100,0
Maximum AC fan absorbed current (1) A 5,0 5,0 5,0 5,0 10,0 10,0
Maximum EC fan absorbed current (1) 3,6 3,6 3,6 3,6 7,2 7,2
Standard electrical heaters maximum absorbed current (1) 6,5 6,5 13,0 13,0 13,0 13,0
Enhanced electrical heaters maximum absorbed current (1) 10,1 10,1 18,8 18,8 20,2 20,2
Humidifier maximum absorbed current (1) A 8,7 8,7 8,7 8,7 8,7 8,7
(1) Current at maximum permissible operating conditions. Please refer to wiring diagram for suggested cable size.
(2) With remote condenser arrangement, mains supply MUST comprise neutral.
(3) For twin compressor unit: one compressor at maximum load and one at startup
18
DATATECH
Maximum compressor absorbed current (1) A 24,0 28,4 30,6 36,2 44,4 50,9 61,2
Compressor in-rush current (3) A 81,0 87,2 174,0 118,1 122,2 165,4 204,6
Maximum AC fan absorbed current (1) A 10,0 10,0 10,0 10,0 15,0 15,0 15,0
Maximum EC fan absorbed current (1) 7,2 7,2 7,2 7,2 10,8 10,8 10,8
Standard electrical heaters maximum absorbed current (1) 13,0 13,0 13,0 13,0 19,5 19,5 19,5
Enhanced electrical heaters maximum absorbed current (1) 20,2 20,2 20,2 20,2 30,3 30,3 30,3
Humidifier maximum absorbed current (1) A 8,7 8,7 8,7 8,7 8,7 8,7 8,7
(1) Current at maximum permissible operating conditions. Please refer to wiring diagram for suggested cable size.
(2) With remote condenser arrangement, mains supply MUST comprise neutral.
(3) For twin compressor unit: one compressor at maximum load and one at startu
19
DATATECH
20
DATATECH
21
DATATECH
Maximum compressor absorbed current (1) A 9,8 14,2 15,9 20,5 19,6 22,2
Compressor in-rush current (2) A 63,0 73,0 100,0 100,0 72,8 100,0
Maximum AC fan absorbed current (1) A 5,0 5,0 5,0 5,0 10,0 10,0
Maximum EC fan absorbed current (1) 3,6 3,6 3,6 3,6 7,2 7,2
Standard electrical heaters maximum absorbed current (1) 6,5 6,5 13,0 13,0 13,0 13,0
Enhanced electrical heaters maximum absorbed current (1) 10,1 10,1 18,8 18,8 20,2 20,2
Humidifier maximum absorbed current (1) A 8,7 8,7 8,7 8,7 8,7 8,7
(1) Current at maximum permissible operating conditions. Please refer to wiring diagram for suggested cable size.
(2) With remote condenser arrangement, mains supply MUST comprise neutral.
(3) For twin compressor unit: one compressor at maximum load and one at startup
22
DATATECH
Maximum compressor absorbed current (1) A 24,0 28,4 30,6 36,2 44,4 50,9 61,2
Compressor in-rush current (2) A 81,0 87,2 174,0 118,1 122,2 165,4 204,6
Maximum AC fan absorbed current (1) A 10,0 10,0 10,0 10,0 15,0 15,0 15,0
Maximum EC fan absorbed current (1) 7,2 7,2 7,2 7,2 10,8 10,8 10,8
Standard electrical heaters maximum absorbed current (1) 13,0 13,0 13,0 13,0 19,5 19,5 19,5
Enhanced electrical heaters maximum absorbed current (1) 20,2 20,2 20,2 20,2 30,3 30,3 30,3
Humidifier maximum absorbed current (1) A 8,7 8,7 8,7 8,7 8,7 8,7 8,7
(1) Current at maximum permissible operating conditions. Please refer to wiring diagram for suggested cable size.
(2) With remote condenser arrangement, mains supply MUST comprise neutral.
(3) For twin compressor unit: one compressor at maximum load and one at startu
23
DATATECH
Unit size 6 9 14 18 22 30 35 45
Total cooling capacity (1) kW 6,7 8,2 13,3 16,7 21,2 30,9 37,0 45,8
Sensible cooling capacity (1) kW 6,1 6,9 12,4 14,5 17,1 27,5 31,5 36,6
SHR 0,90 0,85 0,93 0,87 0,81 0,89 0,85 0,80
Maximum total cooling capacity (6) kW 8,4 10,5 13,7 17,2 22,0 33,6 40,4 50,1
Maximum sensible cooling capacity (6) kW 7,5 8,7 12,8 14,9 17,7 29,6 34,3 39,8
Fans
Number n° 1 1 1 1 1 1 1 1
Nominal air capacity m3/h 1.800 1.800 4.000 4.000 4.000 8.400 8.400 8.400
Maximum allowable airflow (6) m3/h 2.520 2.520 4.170 4.170 4.170 9.450 9.450 9.450
AC fans power input - UNDER version (2) kW 0,21 0,22 0,55 0,59 0,67 1,58 1,65 1,78
EC fans power input - UNDER version (2) kW 0,14 0,15 0,38 0,41 0,51 0,96 1,02 1,14
AC fans power input - OVER version (2) kW 0,21 0,22 0,55 0,59 0,67 1,37 1,45 1,60
EC fans power input - OVER version (2) kW 0,14 0,15 0,38 0,41 0,51 0,81 0,87 0,98
Maximum available static pressure - Downflow units AC fans (3) Pa 85 70 130 105 60 275 255 220
Maximum available static pressure - Downflow units EC fans (3) Pa 355 310 335 310 265 325 305 265
Maximum available static pressure - Upflow units AC fans (3) Pa 85 70 130 105 60 315 300 260
Maximum available static pressure - Upflow units EC fans (3) Pa 355 310 335 310 265 365 350 310
Hydraulic circuit
Total pressure drop kPa 33 34 48 72 71 66 67 74
Connections G1/2" G1/2" G3/4" G3/4" G1" G1"1/4 G1"1/4 G1"1/4
Electric heating (CH-HH version)
Standard capacity kW 3 3 5 5 5 9 9 9
Enhanced capacity kW 4 4 7 7 7 13 13 13
Operation stages n° 1 1 1 1 2 2 2 2
Hot water coil (CH-HH version)
Potential (4) kW 5,9 5,9 13,1 13,1 13,1 24,5 24,5 24,5
Total pressure drop kPa 21,0 21,0 11,0 11,0 11,0 28,0 28,0 28,0
Humidifier (HH version)
Standard steam production kg/h 1,5 1,5 3,0 3,0 5,0 5,0 5,0 5,0
Maximum steam production kg/h 3,0 3,0 3,0 3,0 8,0 8,0 8,0 8,0
Sound level
Sound pressure levels (5) dB(A) 47 47 50 50 50 56 56 56
Dimensions and weight of basic unit
Cabinet size 607,0 607,0 705,0 705,0 705,0 1100,0 1100,0 1100,0
Length mm 607 607 705 705 705 1.100 1.100 1.100
Depth mm 500 500 650 650 650 850 850 850
Height mm 1.850 1.850 1.990 1.990 1.990 1.990 1.990 1.990
Under/over (HH) operating weight kg 165/158 167/160 222/212 225/215 231/221 329 335 347
24
DATATECH
25
DATATECH
Unit size 6 9 14 18 22 30 35 45
AC fan maximum power input kW 0,25 0,25 0,71 0,71 0,71 2,40 2,40 2,40
EC fan maximum power input kW 0,44 0,44 1,00 1,00 1,00 2,30 2,30 2,30
Standard electrical heaters maximum power input kW 3,00 3,00 4,50 4,50 4,50 9,00 9,00 9,00
Enhanced electrical heaters maximum power input kW 4,00 4,00 7,00 7,00 7,00 13,00 13,00 13,00
Humidifier maximum power requirement kW 2,3 2,3 2,3 2,3 6,0 6,0 6,0 6,0
Maximum AC fan absorbed current (1) A 1,1 1,1 1,5 1,5 1,5 5,0 5,0 5,0
Maximum EC fan absorbed current (1) A 2,6 2,6 2,2 2,2 2,2 3,6 3,6 3,6
Standard electrical heaters maximum absorbed current (1) A 13,0 13,0 6,5 6,5 6,5 13,0 13,0 13,0
Enhanced electrical heaters maximum absorbed current (1) A 17,4 17,4 10,1 10,1 10,1 18,8 18,8 18,8
Humidifier maximum absorbed current (1) A 9,8 9,8 3,2 3,2 8,7 8,7 8,7 8,7
Maximum AC fan absorbed current (1) A 10,0 10,0 10,0 15,0 15,0 - - - -
Maximum EC fan absorbed current (1) A 7,2 7,2 7,2 10,8 10,8 14,7 14,7 19,6 19,6
Standard electrical heaters maximum absorbed current (1) A 13,0 13,0 13,0 19,5 19,5 43,3 43,3 43,3 43,3
Enhanced electrical heaters maximum absorbed current (1) A 20,2 20,2 20,2 30,3 30,3 56,3 56,3 56,3 56,3
Humidifier maximum absorbed current (1) A 8,7 8,7 8,7 8,7 8,7 16,2 16,2 16,2 16,2
(1) Current at maximum permissible operating conditions. Please refer to wiring diagram for suggested cable size.
26
DATATECH
Unit size 10 12 15 25 30 40
Total cooling capacity (1) kW 10,4 12,4 14,6 25,2 31,8 37,1
Sensible cooling capacity (1) kW 9,1 10,6 12,1 22,0 26,6 30,3
SHR 0,9 0,9 0,8 0,9 0,8 0,8
Fans
Number n° 1 1 1 1 1 1
Nominal air capacity m3/h 3.340 3.340 3.340 8.000 8.000 8.000
AC fans power input - UNDER version (2) kW 0,6 0,6 0,6 1,7 1,8 1,9
EC fans power input - UNDER version (2) kW 0,4 0,4 0,4 1,0 1,2 1,3
AC fans power input - OVER version (2) kW 0,6 0,6 0,6 1,5 1,6 1,7
EC fans power input - OVER version (2) kW 0,4 0,4 0,4 0,9 1,0 1,1
Maximum available static pressure - Downflow units AC fans (3) Pa 165 120 75 285 245 220
Maximum available static pressure - Downflow units EC fans (3) Pa 320 280 235 316 277 253
Maximum available static pressure - Upflow units AC fans (3) Pa 165 120 75 332 293 269
Maximum available static pressure - Upflow units EC fans (3) Pa 320 280 235 362 323 299
Hydraulic circuit
Total pressure drop kPa 64 39 52 45 48 51
Connections G1/2" G3/4" G3/4" G1" G1"1/4 G1"1/4
Electric heating (CH-HH version)
Standard capacity kW 4,5 4,5 4,5 9,0 9,0 9,0
Enhanced capacity kW 7,0 7,0 7,0 13,0 13,0 13,0
Operation stages n° 1 1 1 2 2 2
Humidifier (HH version)
Standard steam production kg/h 3 3 3 5 5 5
Maximum steam production kg/h 3 3 3 8 8 8
Sound level
Sound pressure levels (5) dB(A) 50 50 50 56 56 56
Dimensions and weight of basic unit
Cabinet size XS XS XS S S S
Length mm 702 702 702 1100 1100 1100
Depth mm 650 650 650 850 850 850
Height mm 1990 1990 1990 1990 1990 1990
Under/over (HH) operating weight 232 235 237 336 345 352
27
DATATECH
28
DATATECH
Unit size 10 12 15 25 30 40
AC fan maximum power input kW 0,7 0,7 0,7 2,4 2,4 2,4
EC fan maximum power input kW 1,0 1,0 1,0 2,3 2,3 2,3
Standard electrical heaters maximum power input kW 4,5 4,5 4,5 9,0 9,0 9,0
Enhanced electrical heaters maximum power input kW 7,0 7,0 7,0 13,0 13,0 13,0
Humidifier maximum power requirement kW 2,3 2,3 6,0 6,0 6,0 6,0
Maximum AC fan absorbed current (1) A 1,5 1,5 1,5 5,0 5,0 5,0
Maximum EC fan absorbed current (1) A 2,2 2,2 2,2 3,6 3,6 3,6
Standard electrical heaters maximum absorbed current (1) A 6,5 6,5 6,5 13,0 13,0 13,0
Enhanced electrical heaters maximum absorbed current (1) A 10,1 10,1 10,1 18,8 18,8 18,8
Humidifier maximum absorbed current (1) A 3,2 3,2 8,7 8,7 8,7 8,7
Maximum AC fan absorbed current (1) A 10,0 10,0 10,0 15,0 15,0 - -
Maximum EC fan absorbed current (1) A 7,2 7,2 7,2 10,8 10,8 10,8 10,8
Standard electrical heaters maximum absorbed current (1) A 13,0 13,0 13,0 19,5 19,5 43,3 43,3
Enhanced electrical heaters maximum absorbed current (1) A 20,2 20,2 20,2 30,3 30,3 56,3 56,3
Humidifier maximum absorbed current (1) A 8,7 8,7 8,7 8,7 8,7 16,2 16,2
(1) Current at maximum permissible operating conditions. Please refer to wiring diagram for suggested cable size.
29
DATATECH
35
30
28
Environment temperature [°C]
Cooling
25
20
16
15
-40 -35 -30 -25 -20 -15 -10 -5 0 +5 +10 +15 +20 +25 +30 +35 +40 +45 +50 +55 +60
(1) With condenser supply by Blue Box (complete with revs. regulator)
(2) With condensation control kit (LAK-Low Ambient Kit)
30
28
Environment temperature [°C]
25
Cooling
21,5
20
16
15
30
DATATECH
30
28
Environment temperature [°C]
25
Cooling
21,5
20
16
15
31
DATATECH
We present the sound spectrums in air flow rate and nominal useful pressures conditions for the DATATECH series.
The tables differ as follows:
1) Sound pressure levels at 2m
2) Intake side sound power levels
3) Flow side sound power levels
a) Unit with downward flow, upward with return from downwards and upwards with rear return
b) Unit with upward flow (only in the basic version with front intake)
I) ED unit
II) CW unit
III) DW unit
ED Lp
Sound pressure level octave-band - air intake from the front, air dicharge from the top
A-weighted 2m free field
Model Central frequency [Hz]
sound pressure level
31,5 63 125 250 500 1000 2000 4000 8000
OED* 6.1 35,0 36,0 40,0 45,5 43,0 42,5 40,0 36,0 29,0 47
OED* 8.1 35,0 34,5 39,5 43,0 41,0 43,0 40,5 37,5 29,5 47
OED* 11.1 53,5 49,0 52,0 50,5 45,0 43,0 43,0 41,5 35,0 50
OED* 15.1 50,0 47,5 50,0 49,0 46,0 44,5 44,0 44,0 38,0 51
OED* 18.1 49,0 46,0 50,0 48,0 44,5 44,5 44,5 44,0 40,5 51
OED* 17.1 56,5 52,5 55,5 49,5 46,5 47,5 44,5 42,0 32,5 52
OED* 22.1 56,0 52,0 56,5 51,0 47,5 48,5 45,5 42,5 33,0 53
OED* 26.1 60,0 58,5 61,0 56,0 50,5 48,5 48,0 43,0 34,0 55
OED* 30.2 56,5 54,5 56,5 53,0 49,0 49,5 49,0 46,0 37,5 55
OED* 32.1 56,5 54,5 57,0 53,5 49,0 49,5 49,0 45,0 37,0 55
OED* 36.1 54,5 53,0 54,0 53,5 51,5 52,5 51,5 46,0 39,0 57
OED* 34.2 62,0 60,0 58,0 60,0 54,0 54,5 51,5 47,5 37,5 59
OED* 38.1 63,0 61,0 58,5 60,5 55,0 56,0 51,5 48,0 38,5 60
OED* 38.2 58,5 58,0 56,5 58,0 53,0 53,5 53,5 49,0 39,0 59
OED* 46.2 61,5 59,0 59,0 60,5 55,5 56,0 55,0 49,5 40,5 61
OED* 49.1 61,5 59,0 59,0 60,5 55,5 56,0 55,0 49,0 39,5 61
OED* 56.2 60,5 58,0 58,0 60,5 54,0 57,0 57,0 50,5 41,5 62
OED* 66.2 58,0 55,5 57,0 60,5 54,0 57,5 57,0 50,5 42,5 62
OED* 72.2 65,5 65,0 64,0 61,5 60,5 58,5 54,5 48,5 39,0 63
OED* 85.2 60,5 60,5 62,0 60,0 60,0 60,5 56,5 50,0 40,0 64
OED* 95.2 64,5 60,0 60,5 59,5 60,0 60,5 56,5 51,0 44,0 64
OED* 104.2 61,5 58,5 60,0 59,5 59,5 61,0 56,0 51,5 45,0 64
Conditions: nominal air flow and 20Pa external static pressure Air discharge under raised floor or ducted
Sound pressure level octave-band - air discharge from the bottom and air intake from the top, or air discharge from the top and air intake from the
bottom/rear A-weighted 2m free field
Model
Central frequency [Hz] sound pressure level
31,5 63 125 250 500 1000 2000 4000 8000
*ED* 6.1 36,5 39,0 42,5 47,0 44,0 42,0 39,5 35,0 27,5 47
*ED* 8.1 36,5 37,5 42,0 46,0 42,5 42,5 40,0 36,5 28,0 47
*ED* 11.1 55,0 52,0 54,5 52,0 46,0 42,0 42,0 40,5 33,5 50
*ED* 15.1 51,5 50,5 52,5 50,5 47,0 44,0 43,5 43,0 36,5 51
*ED* 18.1 50,5 49,0 52,5 49,5 45,5 44,0 44,5 43,0 39,0 51
*ED* 17.1 58,0 55,5 58,0 51,0 47,5 47,0 44,0 40,5 31,0 52
*ED* 22.1 57,5 55,0 59,0 52,5 48,5 48,0 45,0 41,0 31,5 53
*ED* 26.1 60,0 58,5 61,0 56,0 50,5 48,5 48,0 43,0 34,0 55
*ED* 30.2 58,0 57,5 59,0 54,5 50,0 49,0 48,5 45,0 36,0 55
*ED* 32.1 58,0 57,5 59,5 55,0 50,0 49,0 48,5 44,0 35,5 55
*ED* 36.1 56,0 56,0 56,5 55,0 52,5 52,0 51,0 45,0 37,5 57
*ED* 34.2 63,5 63,0 60,5 61,5 55,0 53,5 50,5 46,0 36,0 59
*ED* 38.1 64,5 64,0 61,0 62,0 56,0 55,5 51,0 46,0 37,0 60
*ED* 38.2 60,0 61,0 59,0 59,5 54,0 53,0 53,0 48,0 37,5 59
*ED* 46.2 63,0 62,0 61,5 62,0 56,5 55,5 54,5 48,5 39,0 61
*ED* 49.1 63,0 62,0 61,5 62,0 56,5 55,5 54,5 48,0 38,0 61
*ED* 56.2 62,0 61,0 60,5 62,0 55,0 56,5 57,0 49,5 40,0 62
*ED* 66.2 59,5 58,5 59,5 62,0 55,0 57,0 56,5 50,5 41,0 62
*ED* 72.2 67,0 68,0 66,5 63,0 61,5 57,5 53,5 47,0 37,5 63
*ED* 85.2 62,0 63,5 64,5 61,5 61,0 60,0 56,0 49,0 38,5 64
*ED* 95.2 63,0 61,5 62,5 61,0 60,5 60,5 55,5 50,5 43,5 64
*ED* 104.2 63,0 61,5 62,5 61,0 60,5 60,5 55,5 50,5 43,5 64
Conditions: nominal air flow and 20Pa external static pressure Air discharge under raised floor or ducted
32
DATATECH
ED lw - flow
Condizioni: portata d'aria nominale e pressione statica utile 20Pa. Mandata dell'aria canalizzata o sottopavimento
Condizioni: portata d'aria nominale e pressione statica utile 20Pa. Mandata dell'aria canalizzata o sottopavimento
33
DATATECH
ED lw - intake
Condizioni: portata d'aria nominale e pressione statica utile 20Pa. Mandata dell'aria canalizzata o sottopavimento
Condizioni: portata d'aria nominale e pressione statica utile 20Pa. Mandata dell'aria canalizzata o sottopavimento
34
DATATECH
CW Lp
Sound pressure level octave-band - air intake from the front, air dicharge from the top
A-weighted 2m free field
Model Central frequency [Hz] sound pressure level
31,5 63 125 250 500 1000 2000 4000 8000
OCW 6 38 36,5 42 46 45 42,5 37,5 34 28 47
OCW 9 38,5 36,5 41,5 45,5 45 44 39,5 36,5 31,5 48
OCW 14 53 52 53,5 50 44,5 42,5 43,5 41 37,5 50
OCW 18 50 49,5 51 47,5 44 43 44 42 38 50
OCW 22 48,5 48 49,5 46 43 43,5 44 42,5 40 50
OCW 30 55 53,5 56 50 48,5 52,5 50,5 41,5 34 56
OCW 35 52 52 53 48,5 48,5 53 49,5 43 35 56
OCW 45 51 50 52,5 47,5 49 53 49,5 44 35,5 56
OCW 55 65 64,5 61,5 63 58 58 57 49 39,5 63
OCW 65 63 63 61 63 57 58 57,5 49,5 40 63
OCW 85 61 62,5 59,5 61 56,5 58,5 57,5 51 43 63
OCW 100 65,5 66 65,5 63,5 62 61 57 48 40,5 65
OCW 130 66 65,5 64 60,5 60,5 61,5 58,5 49 42 65
Conditions: nominal air flow and 20Pa external static pressure Air discharge under raised floor or ducted
Sound pressure level octave-band - air discharge from the bottom and air intake from the top, or air discharge from the top
and air intake from the bottom/rear A-weighted 2m free field
Model
Central frequency [Hz] sound pressure level
31,5 63 125 250 500 1000 2000 4000 8000
*CW 6 41 40 44,5 48 46 41,5 36 32,5 25 47
*CW 9 39 38,5 44 48 45,5 43,5 38,5 35 28,5 48
*CW 14 52 50,5 53,5 51,5 47 42 42,5 39,5 35 50
*CW 18 51,5 50,5 52,5 50,5 46,5 42,5 42,5 41 36 50
*CW 22 50,5 49 52,5 49,5 45 43 43,5 41 37 50
*CW 30 58,5 57,5 60 53 50,5 52,5 49,5 40 32 56
*CW 35 59 57,5 59,5 55 51,5 51 49,5 40,5 34 56
*CW 45 58 57 58,5 55 51,5 51 50 41 35 56
UCW 55 66,5 66 64 66 59 57 55,5 47 37 63
*CW 65 65 64 63,5 64,5 58,5 57,5 56,5 48,5 38,5 63
*CW 85 63,5 62,5 62 63,5 56,5 58 57,5 49,5 39,5 63
*CW 100 65,5 67,5 67 64 63 60,5 56 46,5 38 65
*CW 130 62,5 60,5 60,5 61 62 62 56,5 50 44 65
UCW 140 67,5 68,5 68 65 64 63 59 50 42 67
UCW 170 65 66,5 65,5 63 62,5 63 61 52 44,5 67
Conditions: nominal air flow and 20Pa external static pressure Air discharge under raised floor or ducted
35
DATATECH
CW lw - flow
Sound pressure level octave-band - air intake from the front, air dicharge from the top
Central frequency [Hz] A-weighted sound power
Model
level discharge side
31,5 63 125 250 500 1000 2000 4000 8000
OCW 6 65,5 63,5 67 70,5 71 70,5 68,5 66,5 64 75,5
OCW 9 62,5 61 65,5 69 68,5 71 70,5 68,5 67,5 76,5
OCW 14 72 71,5 74 70,5 69 70,5 71,5 71 69,5 77,5
OCW 18 68 69 71,5 69 68,5 71 71,5 70,5 69,5 77,5
OCW 22 66 66,5 69,5 67 68 71,5 71 70,5 70 77,5
OCW 30 74,5 72,5 75,5 79 75,5 76 73 67,5 53,5 80
OCW 35 70,5 70 73 78 75 76 73,5 67,5 54 80
OCW 45 69,5 68 72 77,5 74 76,5 73,5 68 55,5 80
OCW 55 73 71,5 78,5 80 77,5 76,5 72 65,5 54,5 80,5
OCW 65 71 70 77 79 76 77 73 66,5 55 80,5
OCW 85 69 68,5 76 78,5 75 77,5 73 67 57 80,5
OCW 100 76 78 78,5 82,5 80 79 70,5 68 57 82,5
OCW 130 74 74,5 76 81,5 79 79,5 71,5 70 59,5 82,5
Conditions: nominal air flow and 20Pa external static pressure Air discharge under raised floor or ducted
Sound pressure level octave-band - Air discharge to the bottom and air intake from the top, or air discharge to the top and
air intake from the bottom/rear A-weighted sound power
Model
Central frequency [Hz] level discharge side
31,5 63 125 250 500 1000 2000 4000 8000
UCW 6 68 66,5 69,5 72,5 73 70 68 65 61,5 75,5
UCW 9 66,5 65,5 69 69,5 71,5 71 70,5 68 65 76,5
UCW 14 76,5 75 78 75 71,5 70 71,5 69,5 67 77,5
UCW 18 75 73 76,5 75 71 70 71,5 69,5 68 77,5
UCW 22 74,5 70,5 75,5 71 68,5 70 72 70,5 69,5 77,5
UCW 30 78 75 78,5 82,5 76,5 75,5 71 65 51 80
UCW 35 75,5 74,5 78 80,5 76 76,5 71 66 53,5 80
UCW 45 75,5 73 76,5 79,5 75,5 76,5 72 66,5 54 80
UCW 55 73 74 80 81,5 79 75,5 70 63,5 51,5 80,5
UCW 65 70 72 79 81,5 78,5 76 70 65 53,5 80,5
UCW 85 67,5 70,5 78,5 80 77 77 71,5 65,5 54 80,5
UCW 100 78,5 80 79,5 83,5 80,5 78,5 70 67 55,5 82,5
UCW 130 75 76,5 78 82 80 79 71,5 67,5 58 82,5
UCW 140 85 86,5 83 90,5 85,5 82,5 75,5 71,5 59,5 87,5
UCW 170 85 85 82,5 89 84,5 83,5 77,5 73,5 62,5 87,5
Conditions: nominal air flow and 20Pa external static pressure Air discharge under raised floor or ducted
36
DATATECH
CW lw - intake
Sound pressure level octave-band - air intake from the front, air dicharge from the top
Central frequency [Hz] A-weighted sound power
Model
level discharge side
31,5 63 125 250 500 1000 2000 4000 8000
OCW 6 56,5 55,5 60,5 65 64,5 64 61,5 58 54,5 68,5
OCW 9 54 53 59 63 62,5 65 63 61 57,5 69,5
OCW 14 65,5 65 67,5 66 64,5 65 64,5 63,5 61 71
OCW 18 62,5 64 66,5 64 64,5 65,5 64 64 61,5 71
OCW 22 60,5 61,5 65 63 64 65,5 65,5 64,5 62 71
OCW 30 71,5 69 71,5 76 71 65,5 66,5 59,5 52 73,5
OCW 35 69,5 68,5 70 74 71 66,5 67 60,5 53,5 73,5
OCW 45 68 66,5 69 73,5 68,5 67,5 68 62 54,5 73,5
OCW 55 68,5 68,5 74,5 76,5 70,5 66 66,5 56,5 48,5 73,5
OCW 65 69,5 67 73 76,5 70 67 66,5 56,5 48,5 73,5
OCW 85 69,5 66 72,5 76,5 69 67 67 57,5 50 73,5
OCW 100 67,5 67,5 72 77,5 73,5 69 67,5 61,5 50 75,5
OCW 130 62,5 64 70,5 75,5 73,5 69,5 68 63 51,5 75,5
Conditions: nominal air flow and 20Pa external static pressure Air discharge under raised floor or ducted
Sound pressure level octave-band - Air discharge to the bottom and air intake from the top, or air discharge to the top and
air intake from the bottom/rear A-weighted sound power
Model
Central frequency [Hz] level discharge side
31,5 63 125 250 500 1000 2000 4000 8000
UCW 6 60 57,5 64 67 66 64 60,5 56 52 68,5
UCW 9 58 56 63 66,5 65,5 65,5 62 58 54,5 69,5
UCW 14 73,5 71,5 74 69 64,5 63 65,5 63 58,5 71
UCW 18 70,5 70,5 72 68 63 63,5 65 64,5 59 71
UCW 22 69,5 69,5 71,5 66,5 62 64,5 65 64 60 71
UCW 30 75 71,5 73,5 77 71,5 66,5 64 57,5 48,5 73,5
UCW 35 71 69 73 76 70,5 67,5 65,5 58,5 49,5 73,5
UCW 45 70,5 68 71,5 76 69,5 68 65,5 60,5 50,5 73,5
UCW 55 69,5 70 76 76,5 72 66,5 63,5 54,5 45,5 73,5
UCW 65 69 69,5 76 76,5 71,5 67,5 63,5 55 46 73,5
UCW 85 68,5 69 76 75,5 71,5 67,5 64,5 56 47 73,5
UCW 100 68,5 69 74 78,5 73,5 68,5 67 60,5 48 75,5
UCW 130 65,5 65,5 71,5 77 72,5 69,5 68,5 62,5 51 75,5
UCW 140 77,5 76,5 80,5 85,5 76 75 72 66,5 55,5 81
UCW 170 72,5 72 78 84 73,5 76,5 73,5 69 59 81
Conditions: nominal air flow and 20Pa external static pressure Air discharge under raised floor or ducted
37
DATATECH
DW lp
Sound pressure level octave-band - air intake from the front, air dicharge from the top
Central frequency [Hz] A-weighted 2m free field
Model
sound pressure level
31,5 63 125 250 500 1000 2000 4000 8000
ODW 10 54 51 53 51,5 47 42,5 42,5 39 34 50
ODW 12 52,5 50 52,5 51,5 46,5 43 42,5 39 34,5 50
ODW 15 50,5 49,5 52 51 46 43 42,5 40,5 36 50
ODW 25 55 54,5 56,5 51 48,5 52,5 50,5 41 34 56
ODW 30 56,5 54 55 50,5 48,5 52,5 50,5 41,5 34,5 56
ODW 40 57 53 53 49,5 48,5 52,5 50,5 42 35,5 56
ODW 50 67 65 62,5 66,5 57 57,5 56 47 37,5 63
ODW 60 66,5 63,5 62,5 66,5 56,5 57,5 56,5 47 38 63
ODW 70 66 63 62 66 56,5 57 57 47,5 38,5 63
ODW 85 67 68 67,5 64 63 60,5 56 46 37 65
ODW 100 66 68,5 66 63,5 62,5 61 56,5 46,5 38 65
Conditions: nominal air flow and 20Pa external static pressure Air discharge under raised floor or ducted
Sound pressure level octave-band - air discharge from the bottom and air intake from the top, or air discharge from the top
and air intake from the bottom/rear A-weighted 2m free field
Model
Central frequency [Hz] sound pressure level
31,5 63 125 250 500 1000 2000 4000 8000
*DW 10 55 52,5 54 52,5 47,5 41,5 42 38 32,5 50
*DW 12 52,5 52 52,5 52 47 42 42,5 39 33 50
*DW 15 50,5 49,5 52 51 46 42,5 43 40,5 34 50
*DW 25 56,5 56 58 51,5 49,5 52,5 50 40,5 33 56
*DW 30 56 55 57 50,5 49 52,5 50,5 41 33,5 56
*DW 40 57 54,5 55,5 50 48,5 52,5 50,5 41,5 34,5 56
*DW 50 66,5 67,5 63,5 67 57,5 57 55,5 46 36 63
*DW 60 65 65,5 63,5 66,5 56,5 57,5 56 47 36,5 63
*DW 70 63,5 64 63 65,5 56,5 57,5 57 48 38,5 63
*DW 85 65,5 70 68,5 65 63,5 60 55 45 36,5 65
*DW 100 62,5 60,5 60,5 61 62 62 56,5 50 44 65
UDW 115 67,5 70 69 66,5 65 62,5 58 49 40,5 67
UDW 130 65 68 66,5 64,5 63,5 63,5 59 51 43 67
Conditions: nominal air flow and 20Pa external static pressure Air discharge under raised floor or ducted
38
DATATECH
DW lw - flow
Sound power level in octave band - front air intake, ducted upward flow.
Central frequency [Hz] A-weighted sound power
Model
level discharge side
31,5 63 125 250 500 1000 2000 4000 8000
ODW 10 76,5 75 77,5 74,5 71 70,5 71,5 70 67 77,5
ODW 12 76,5 75 75,5 72,5 71 70,5 71,5 70 67,5 77,5
ODW 15 76 74,5 74,5 71 70,5 70,5 71,5 70,5 68 77,5
ODW 25 76 76 78 80,5 76 76 72 65,5 52 80
ODW 30 76 75 77,5 80 75,5 76 72,5 66,5 53 80
ODW 40 75,5 74,5 77 78,5 75 76,5 72,5 67 53,5 80
ODW 50 72,5 74,5 80 82 79 75,5 70,5 62,5 50,5 80,5
ODW 60 71,5 73,5 79 81,5 78,5 76 71 62,5 52 80,5
ODW 70 70,5 73,5 78,5 80,5 78 76,5 71,5 63,5 52 80,5
ODW 85 78,5 79,5 78,5 83 80,5 78,5 71 67,5 56 82,5
ODW 100 77 77,5 77,5 82 80 79 71,5 68,5 57 82,5
Conditions: nominal air flow and 20Pa external static pressure Air discharge under raised floor or ducted
Sound pressure level octave-band - Air discharge to the bottom raised floor and air intake from the top ducted, or air
discharge to the top ducted and air intake from the bottom/rear A-weighted sound power
Model
Central frequency [Hz] level discharge side
31,5 63 125 250 500 1000 2000 4000 8000
*DW 10 78 77,5 80 76,5 72,5 70 71 69 65,5 77,5
*DW 12 77 76,5 79,5 75 71,5 70,5 71,5 69 66,5 77,5
*DW 15 76 75 78,5 74 70 70,5 71,5 70,5 67 77,5
*DW 25 77,5 77,5 79,5 83 77 75 70 64 50 80
*DW 30 76 77 78,5 81,5 76,5 75,5 71,5 65 51 80
*DW 40 75 76,5 77,5 81 76 76 71,5 65,5 52,5 80
*DW 50 72,5 74,5 80 82 79 75,5 70,5 62,5 50,5 80,5
*DW 60 71 74 80 82 78,5 75,5 70,5 63 51 80,5
*DW 70 69 72,5 79 81 78,5 76 71 64 52,5 80,5
*DW 85 80,5 82 80,5 84 81 78 69,5 66 54 82,5
*DW 100 79,5 80,5 79,5 83,5 80,5 78,5 70,5 67 56 82,5
UDW 115 86,5 88 84 90,5 86 82 74,5 71 58,5 87,5
UDW 130 85 85,5 83 89 85,5 83 76 72 60 87,5
Conditions: nominal air flow and 20Pa external static pressure Air discharge under raised floor or ducted
39
DATATECH
DW lw - intake
Sound power level in octave band - front air intake, ducted upward flow.
Central frequency [Hz] A-weighted sound power
Model
level suction side
31,5 63 125 250 500 1000 2000 4000 8000
ODW 10 69 70,5 74 68,5 64,5 63 65,5 63 58,5 71
ODW 12 69 70 73,5 67 63 63 66 63 59,5 71
ODW 15 70 69,5 72,5 66 62,5 63 66 64 60 71
ODW 25 72,5 71,5 73 76,5 71 65,5 64 57 48 73,5
ODW 30 70 70 72 76,5 70,5 66,5 64,5 57 48,5 73,5
ODW 40 69 68,5 70,5 76 70,5 66,5 64,5 58 49,5 73,5
ODW 50 72,5 71 76 77,5 71,5 66 63 55 45,5 73,5
ODW 60 71,5 71 76 77,5 71,5 66 63 55 46,5 73,5
ODW 70 70 70,5 76,5 77,5 71,5 66 63 55 47 73,5
ODW 85 66,5 69 74 78,5 73,5 68,5 67 60 47,5 75,5
ODW 100 68 67,5 72,5 77,5 73 69 68 61,5 49,5 75,5
Conditions: nominal air flow and 20Pa external static pressure Air discharge under raised floor or ducted
Sound pressure level octave-band - Air discharge to the bottom raised floor and air intake from the top ducted, or air
discharge to the top ducted and air intake from the bottom/rear A-weighted sound power
Model
Central frequency [Hz] level suction side
31,5 63 125 250 500 1000 2000 4000 8000
*DW 10 74 73 75,5 70,5 66 62,5 65 62,5 57 71
*DW 12 72,5 71,5 75 70 65 63 65 63 58 71
*DW 15 70 70,5 73 67,5 64 63,5 65 64 58,5 71
*DW 25 75 73,5 74,5 78 72 65 63 55,5 46 73,5
*DW 30 73,5 73 74 77,5 72 65 63,5 56,5 47 73,5
*DW 40 73 72 74 77,5 71,5 65,5 64 57 48 73,5
*DW 50 69,5 72 77,5 78 72 65 62 53,5 44 73,5
*DW 60 70 71 77 77,5 72 65,5 63 55 46 73,5
*DW 70 70 70,5 76,5 77,5 71,5 66 63 55 47 73,5
*DW 85 70 70,5 75,5 79 74 67,5 66 59 46,5 75,5
*DW 100 69 68 74,5 78,5 73,5 68,5 67 60 48 75,5
UDW 115 77 78,5 82 86,5 76,5 74 70,5 65,5 54 81
UDW 130 75,5 78,5 80,54 86 75 75 72 66 55 81
Conditions: nominal air flow and 20Pa external static pressure Air discharge under raised floor or ducted
40
DATATECH
INSTALLATIONS RECOMMENDATIONS
LOCATION
Strictly allow clearances as indicated in the catalogue.
Please check that there isn’t any obstructions on the suction of
the finned coil and on the discharge of the fans
Locate the unit in order to be compatible with environmental
requirements (sound level, integrationinto the site, etc.).
ELECTRICAL CONNECTIONS
Check the wiring diagram enclosed with the unit, in which are
always present all the instructions necessary to the electrical
connections.
Supply the unit at least 12 hours before start-up, in order to
turn crankcase heaters on. Do notdisconnect electrical supply
during temporary stop periods (i.e. weekends).
Before opening the main switch, stop the unit by acting on the
suitable running switches or, if lacking, on the remote control.
Before servicing the inner components, disconnect electrical
supply by opening the main switch.
The electric supply line must be equipped with an automatic
circuit breaker (to be provided by theinstaller.
HYDRAULIC CONNECTIONS
Carefully vent the system, with pump turned off, by acting
on the vent valves. This procedure is fundamental: little air
bubbles can freeze the evaporator causing the general failure
of thesystem.
Drain the system during seasonal stops (wintertime) or use pro-
per mixtures with low freezing point. Incase of temporary stop
periods an electric heater should be installed on the evaporator
and hydraulic circuit.
Install the hydraulic circuit including all the components indica-
ted in the recommended hydraulic circuitdiagrams (expansion
vessel, flow switch, strainer, storage tank, vent valves, shut off
valves, flexibleconnections, etc.).
Connect the flow switch, which is furnished on all units, not
fitted. Follow the instructions enclosed with the units.
41
10260001502 DATATECH_07-2017