Indura® Wet Location: Features & Specifications
Indura® Wet Location: Features & Specifications
Indura® Wet Location: Features & Specifications
Number
Notes
INDL
plications. It is 5VA flame rated, impact-resistant, scratch-resistant and corrosion proof. The UV-stable resin
resists discoloration from natural and man-made light sources. There is a low-profile, integrated and back-lit
test switch with an easily visible multi-color LED status indicator. The back-plate contains a universal j-box
mounting pattern to facilitate ease of installation on a wide variety of j-boxes and the front housing allows
tool-less access for ease of maintenance. The lamp heads have a unique track-and-swivel arrangement Indura®
permitting full range of direction of optical aiming.
OPTICS — The SP640L features four high-performance LEDs rated at 6.6 watts and delivers a total of 640 Wet Location
lumens in a spot pattern.
The SP1100L features six high-performance LEDs rated at 10.6 watts and delivers a total of 1,100 lumens in
a spot pattern.
The SP2200L features twelve high-performance LEDs rated at 22 watts and delivers a total of 2,200 lumens
in a spot pattern.
The typical life of an LED is 10 years. The LED light sources typically never need to be replaced under normal
conditions for normal off applications.
CCT: 5000K.
ELECTRICAL — UVOLT (120 thru 347V, 50/60hz). Current-limiting charger maximizes battery life and
minimizes energy consumption to provide low operating costs. Small battery chargers Certified in the CA
Title 20 Appliance Efficiency Database.
Short-circuit protection — current-limiting charger circuitry protects printed circuit board from shorts.
EXTL
Regulated charge voltage maintains a stable charge voltage over a wide range of line voltages. Extreme®
Prevents over/undercharging that shortens battery life and reduces capacity. Filtered charger input mini-
mizes charge voltage ripple and extends battery life. NEMA 4X
BATTERY: Lithium Iron Phosphate battery. Optional High-Output (HO option) and Extra High Output (EHO
option), LTP battery type only, provides a wide variety of remote capacities and/or extended run time.
SELF-DIAGNOSTICS AND REMOTE TEST (SDRT OPTION): Automatic 24-hour recharge after a 90-min-
ute discharge. Advanced electrical design provides constant light output throughout the entire discharge
period. Brownout protection is automatically switched to emergency mode when supply voltage drops
below approximately 80 percent nominal of 120, 220, 277 or 347. Other input voltages may vary. AC/LVD re-
set allows battery connection before AC power is applied and prevents battery damage from deep discharge. TM
EMERGENCY INDL_EXTL
Pg. 1 of 4
INDL-EXTL Industrial LED Emergency Lights
INDURA® WET LOCATION
ORDERING INFORMATION For shortest lead times, configure product using bolded options. Example: INDL SP1100L UVOLT LTP SDRT
Series Lamp Type Housing Color Voltage Battery Type Automatic Testing Options
INDL Indura® Wet SP640L 640 lumen, 6.6 watt, (blank) Gray UVOLT 120-347VAC, LTP Lithium Iron SDRT Self- (blank) Not Required
location Spot distribution 50/60hz Phosphate Diagnostics, HO High-Output Battery
SP1100L 1100 lumen, 10.6 watt, Remote
Testing EHO Extra High-Output Battery
Spot distribution
CW Cold Weather (-30 - 50c)
SP2200L 2200 lumen, 22 watt,
Spot distribution1 USPOM Assembled in the US
Notes
1 SP2200L lumen package only available with EHO option.
EXTREME® NEMA 4X
ORDERING INFORMATION For shortest lead times, configure product using bolded options. Example: EXTL SP1100L UVOLT LTP SDRT
Series Lamp Type Housing Color Voltage Battery Type Automatic Testing Options
EXTL Extreme® SP640L 640 lumen, 6.6 watt, (blank) Gray UVOLT 120-347VAC, LTP Lithium Iron SDRT Self- (blank) Not Required
NEMA 4X Spot distribution 50/60hz Phosphate Diagnostics, HO High-Output Battery
SP1100L 1100 lumen, 10.6 watt, Remote
Testing EHO Extra High-Output Battery
Spot distribution
CW Cold Weather (-30 - 50c)
SP2200L 2200 lumen, 22 watt,
Spot distribution1 USPOM Assembled in the US
Notes
1 SP2200L lumen package only available with EHO option.
RTKIT Remote test kit, up to 40' away (includes goggles, laser and battery)
INDL_EXTL
EMERGENCY: One Lithonia Way, Conyers, GA 30012 Phone: 1-800-705-SERV (7378) techsupport-emergency@acuitybrands.com www.lithonia.com © 2018-2020 Acuity Brands Lighting, Inc. All rights reserved. Rev. 02/04/20
Pg. 2 of 4
INDL-EXTL Industrial LED Emergency Lights
INDL SPACING GUIDELINES EXTL SPACING GUIDELINES
128' 110'
1 FC average 1 FC average
Example of multiple Example of multiple
INDL luminaires EXTL luminaires
illuminating a 3' path illuminating a 3' path
of egress. of egress.
3' 3'
1 FC average 1 FC average
Example of single INDL illuminating a 3' path of egress. Example of single EXTL illuminating a 3' path of egress.
7.5' 7.5'
* Application image examples are using SP2200L lamp at 10' MH. * Application image examples are using SP2200L lamp at 10' MH.
124' 110'
3' 3'
Maximum Spacing Guidelines — INDL SP640L Maximum Spacing Guidelines — EXTL SP640L
Single Luminaire Multiple Luminaire Single Luminaire Multiple Luminaire
Mounting Illumination Application Mounting Illumination Application
Height Level 3' Path of 6' Path of 3' Path of 6' Path of Notes Height Level 3' Path of 6' Path of 3' Path of 6' Path of Notes
Egress Egress Egress Egress Egress Egress Egress Egress
7.5' 1FC Avg1 58' 56' 63' 57' 7.5' 1FC Avg1 54' 48' 57' 50'
10' 1FC Avg 1
56' 50' 59' 54' 10' 1FC Avg1 52' 48' 56' 50'
Open Open
12' 1FC Avg1 56' 50' 58' 53' warehouse: 12' 1FC Avg1 48' 42' 50' 45' warehouse:
200'x15'x30' 200'x15'x30'
16' 1FC Avg1 52' 48' 54' 50' 10/10/10 16' 1FC Avg1 46' 40' 48' 43' 10/10/10
20' 1FC Avg 1
48' 44' 50' 46' reflectances 20' 1FC Avg1 42' 38' 44' 40' reflectances
24' 1FC Avg1 44' 40' 46' 42' 24' 1FC Avg1 36' 34' 38' 36'
Notes: Notes:
1. Also meets the additional illumination requirements of NFPA 101: 1FC minimum and max/min ratio of 40:1. 1. Also meets the additional illumination requirements of NFPA 101: 1FC minimum and max/min ratio of 40:1.
Maximum Spacing Guidelines — INDL SP1100L Maximum Spacing Guidelines — EXTL SP1100L
Single Luminaire Multiple Luminaire Single Luminaire Multiple Luminaire
Mounting Illumination Application Mounting Illumination Application
Height Level 3' Path of 6' Path of 3' Path of 6' Path of Notes Height Level 3' Path of 6' Path of 3' Path of 6' Path of Notes
Egress Egress Egress Egress Egress Egress Egress Egress
7.5' 1FC Avg 1 76' 74' 82' 75' 7.5' 1FC Avg 1 69' 67' 72' 67'
10' 1FC Avg 1
76' 72' 79' 75' 10' 1FC Avg 1 69' 62' 72' 66'
Open Open
12' 1FC Avg 1 72' 70' 78' 74' warehouse: 12' 1FC Avg 1 68' 61' 70' 65' warehouse:
200'x15'x30' 200'x15'x30'
16' 1FC Avg 1 68' 66' 73' 69' 10/10/10 16' 1FC Avg 1 62' 60' 66' 62' 10/10/10
20' 1FC Avg 1
64' 62' 67' 64' reflectances 20' 1FC Avg 1 60' 56' 63' 60' reflectances
24' 1FC Avg 1 60' 58' 63' 60' 24' 1FC Avg 1 54' 54' 58' 55'
Notes: Notes:
1. Also meets the additional illumination requirements of NFPA 101: 1FC minimum and max/min ratio of 40:1. 1. Also meets the additional illumination requirements of NFPA 101: 1FC minimum and max/min ratio of 40:1.
Maximum Spacing Guidelines — INDL SP2200L Maximum Spacing Guidelines —EXTL SP2200L
Single Luminaire Multiple Luminaire Single Luminaire Multiple Luminaire
Mounting Illumination Application Mounting Illumination Application
Height Level 3' Path of 6' Path of 3' Path of 6' Path of Notes Height Level 3' Path of 6' Path of 3' Path of 6' Path of Notes
Egress Egress Egress Egress Egress Egress Egress Egress
7.5' 1FC Avg 1 124' 114' 128' 115' 7.5' 1FC Avg 1 110' 100' 110' 104'
10' 1FC Avg 1 118' 116' 122' 114' 10' 1FC Avg 1 106' 100' 108' 104'
Open Open
12' 1FC Avg 1
120' 116' 121' 114' warehouse: 12' 1FC Avg 1
104' 100' 108' 104' warehouse:
200'x15'x30' 200'x15'x30'
16' 1FC Avg 1 116' 112' 119' 114' 10/10/10 16' 1FC Avg 1 102' 98' 104' 101' 10/10/10
20' 1FC Avg 1
112' 108' 115' 111' reflectances 20' 1FC Avg 1
98' 94' 104' 100' reflectances
24' 1FC Avg 1 106' 104' 108' 107' 24' 1FC Avg 1 94' 90' 100' 92'
Notes: Notes:
1. Also meets the additional illumination requirements of NFPA 101: 1FC minimum and max/min ratio of 40:1. 1. Also meets the additional illumination requirements of NFPA 101: 1FC minimum and max/min ratio of 40:1.
INDL_EXTL
EMERGENCY: One Lithonia Way, Conyers, GA 30012 Phone: 1-800-705-SERV (7378) techsupport-emergency@acuitybrands.com www.lithonia.com © 2018-2020 Acuity Brands Lighting, Inc. All rights reserved. Rev. 02/04/20
Pg. 3 of 4
INDL-EXTL Industrial LED Emergency Lights
COMPATIBLE REMOTES
BATTERY CAPACITY AND LOADING
# of Remote SP640L # of Remote SP1100L # of Remote SP2200L
Total Capacity Lamp Heads* Lamp Heads* Lamp Heads*
INDL SP640L / EXTL SP640L 11W 1 0 0 INDRE SP640L T INDRE SP1100L T INDRE SP2200L T
4.66 11.76 11.76 5.03 5.03 11.76 11.76 6.06 6.06 11.76 11.76 6.06 6.06
11.76 11.76 4.66 [29.9] [29.9]
[29.9] [29.9] [11.8] [11.8] [12.8] [12.8] [29.9] [29.9] [15.4] [15.4] [29.9] [29.9] [15.4] [15.4]
SPECIFICATIONS
Lamp Wattage 7.02 7.02
Battery
7.02 Capacity and Loading — Extended Run-Times
7.02
[17.8] [17.8] [17.8]
Lamp Type [17.8] Watts per Lamp Head Battery Option Total Capacity* 2 hours Total Capacity* 4 hours
11.76 SP640L
11.76 6.06 3.3W
6.06 11.76 11.76 INDL
6.06 6.06 8.25W 4.125W
[29.9] [29.9] [15.4] [15.4] [29.9] [29.9] [15.4] [15.4]
SP1100L 5.3W INDL HO 15.37W 7.68W
SP2200L 11W INDL EHO 24W 12W
* *Total capacity including the lamp types
EXTL 8.25W 4.125W shipped standard on luminaire. SP640L LED
ELECTRICAL lamp heads are 3.3 watts each, SP1100L
EXTL HO 15.37W 7.68W
Unit Battery Input Input LED lamp heads are 5.3 watts each, and the
Watts (W) EXTL EHO 24W 12W
Type Type Voltage(V) Current (A) SP2200L LED lamp heads are 11 watts each.
Lithium Iron 120 0.108 12.84
Phosphate BATTERY
(STD) 347 0.087 15.2
Lithium Iron Phosphate
Cold
Lithium Iron 120 0.157 18.69
weather- Type Voltage Typical Shelf Life Typical Life 1 Maintenance 2 Optimum Temperature Range 3,4
Phosphate
With 347 0.119 23.57
(HO) STD 9.6V 1 year 7-9 years none 32°F - 122°F (0°C - 50°C)
Heater
Lithium Iron 120 0.202 23.95
Phosphate
HO 9.6V 1 year 7-9 years none 32°F - 122°F (0°C - 50°C)
(EHO) 347 0.157 27.74 EHO 12.8V 1 year 7-9 years none 32°F - 122°F (0°C - 50°C)
Lithium Iron 120 0.028 2.72 CW 9.6V , 12.8V
5 5
1 year 7-9 years none -22°F - 122°F (-30°C - 50°C)
Phosphate
(STD) 347 0.041 3.84 Notes
Non Cold
Lithium Iron 120 0.042 4.56 1 At 77°F ambient temperature, charge/discharge cycles and prolonged full discharge may reduce useful life.
weather-
Phosphate 2 All life safety equipment, including emergency lighting for path of egress must be tested in accordance with all National Fire Protection As-
Without 347 0.043 6.62
(HO) sociation (NFPA) and local codes. Failure to perform the required testing could jeopardize the safety of occupants and will void all warranties.
Heater
Lithium Iron 120 0.05 5.69 3 Optimum ambient temperature range where unit will provide capacity for 90 minutes. Higher and lower temperatures affect life and capacity.
Phosphate
(EHO) 347 0.047 7.65 4 Battery life is negatively impacted by many variables including temperature, charging rates, number of cycles and deep discharges due to long
periods of time without AC power.
5 CW battery type is compatiable with 9.6V (STD and HO) and 12.8V (EHO) options.
INDL_EXTL
EMERGENCY: One Lithonia Way, Conyers, GA 30012 Phone: 1-800-705-SERV (7378) techsupport-emergency@acuitybrands.com www.lithonia.com © 2018-2020 Acuity Brands Lighting, Inc. All rights reserved. Rev. 02/04/20
Pg. 4 of 4