A. Lightning Current and Impedance
A. Lightning Current and Impedance
A. Lightning Current and Impedance
B. AC source voltage
An ac source voltage is often neglected in a lightning surge simulation. It, however, has been found that the ac
source voltage affects a flashover phase of an archorn especially in the case of a rather small lightning current. Fig. 4 is a
measured result of archorn flashover phases as a function of the ac source voltage on a 77kV transmission line in Japan for a
summer [26]. The measurements were carried out in two 77 kV substations by surge recorders installed in the substations.
From the recorded voltages and currents, Fig. 4 was obtained. The figure clearly shows that the archorn flashover phase is
quite dependent on the ac source voltage, i.e. a flashover occurs at a phase of which the ac voltage is in the opposite polarity
of a lightning current. Table 2 shows a simulation result of archorn peak voltages (archorn not operating) on (a) the
77kV line and (b) a 500kV line [27]. The simulation was carried out in a similar circuit to Fig. 1, but another five towers
were added instead of the gantry and the substation.
The parameters are the same as those in Table 1 for a 77 kV system except the lightning current of 40 kA based on the
field measurement[26]. The lower phase archorn voltage is relatively smaller than the other phase archorn voltages on the
500kV line compared with those on the 77kV line. Thus, an archorn flashover phase on an EHV line is rather independent
from the ac source voltage, and the lower phase flashover is less probable than the other phase flashover. On the contrary,
flashover probability is rather same on each phase and a flashover is dependent on the ac source voltage on a low voltage
line.
C. Tower model
(1) Problem of recommended tower model
Fig. 5 shows simulation results of archorn flashover phases by a simple distributed line “tower model” i.e. neglecting
the RL circuit in Fig. 2 with the parameters in Table1, and by the recommended model illustrated in Fig. 2. The simulation
circuit is the same as that described for Table 2 in the previous section. This figure should be compared with the field test
result shown in Fig. 4. It is clear that the recommended model can not duplicate the field test result, while the simple
40
voltage [kV]
20
angle [deg.]
0
0 30 60 90 120 150 180 210 240 270 300 330 360
-20
-40
-60
-80
L1-4
80 Lower Middle Upper 80 Lower Middle Upper
60 60
Voltage[kV] 40 40
Voltage[kV]
20 Phase [deg.] 20 Phase [deg.]
0 0
0 30 60 90 120 150 180 210 240 270 300 330 360 0 30 60 90 120 150 180 210 240 270 300 330 360
-20 -20
-40 -40
-60 -60
-80 -80
(a) A simple distributed line model (b) Recommended tower model
distributed line model shows a good agreement with the field test result. The reason for the poor accuracy of the
recommended model is that the model was developed originally for a 500kV line on which the lower phase flashover was
less probable as explained in the previous section. Thus, the recommended tower model tends to result in lower flashover
probability of the lower phase archorn. An R-L parallel circuit between two distributed lines in Fig. 2 represents traveling
wave attenuation and distortion along a tower. The R and L values were determined originally based on a field
measurement ( α in eq. (4)), and thus those are correct only for the tower on which the measurement was carried out.
Sometimes, the R-L circuit generates unreal high frequency oscillation. This indicated a necessity of further investigation of
the R-L circuit.
The recommended value of a tower surge impedance for each voltage class in Table 1 was determined by field
measurements in Japan. Although the surge impedance is a representative value, it can not be applied to every tower as is
clear in Table 3.
Wave deformation on tower structures (L- or T-shape iron conductor) can be included in a lightning surge analysis, if
required, based on the approach in Reference [30].
It should be pointed out that the influence of the surge impedance and the frequency-dependent effect of a tower is
heavily dependent on the modeling of a tower footing impedance, which will be discussed in the following section. When
the footing impedance is represented by a resistive model as recommended in Japan or by a capacitance model, then the
influence of the tower surge impedance and the frequency-dependent effect of a traveling wave along the tower becomes
rather noticeable. On the contrary, those cause only a minor effect when the footing impedance is represented either by an
inductive model or by a nonlinear resistance. Fig. 6 shows an example [7], [33]. The measurement was carried out on a
500 kV tower by applying a current in Fig. 6(a-1) to the top of the tower. The tower top voltage predicted by a
distributed-line model with a constant tower surge impedance and no R-L circuit, Fig. 6(c-1), differs from that by the
frequency-dependent tower model, Fig. 6(b) which agrees with the measured result, in the case of the footing impedance
being a resistance. On the contrary, in the case of an inductive footing model, the tower top voltage obtained by the
distributed-line model shows a rather good agreement with the measured result. It should be also noted that some 10%
variation of the tower surge impedance does not affect the result in the inductive footing impedance case.
L1-5
Table 3 Measured and calculated surge impedances of vertical conductors
Ref. height radius measured Ametani Jordan*1 Wagner*2 Sargent*3 Hara*4
h [m] r [mm] Zmes [Ω] Ref. [27] Ref. [28] Ref. [29] Ref. [30] Ref. [31]
[31] 15.0 25.4 320.0 323.0 322.9 445.2 385.2 325.2
15.0 2.5 459.0 462.0 462.0 584.4 524.4 464.4
9.0 2.5 432.0 431.3 431.3 553.7 493.7 433.7
6.0 2.5 424.0 407.0 407.0 529.4 469.4 409.4
3.0 50.0 181.0 187.2 185.7 308.0 248.0 188.0
3.0 25.0 235.0 228.0 227.2 349.6 289.6 229.6
3.0 2.5 373.0 365.5 365.4 487.8 427.8 367.8
2.0 2.5 345.0 341.2 341.1 463.5 403.5 343.5
[30] 0.608 43.375 112.0 104.7 98.4 220.8 160.8 100.8
0.608 9.45 180.0 191.2 189.8 312.2 252.2 192.2
0.608 3.1125 250.0 256.9 256.5 378.9 318.9 258.9
average of absolute error [%] 2.5 2.7 44.8 22.6 2.8
300
Voltage [V]
200
100
0
0 1 2 3 4
(1) Applied current (2) Tower top voltage Time [µs]
Voltage [V]
Voltage [V]
0 0 0
Thus, it is concluded that the frequency-dependent effect of wave propagation along a tower can be neglected and the
value of the surge impedance is not significant unless a tower footing impedance is represented by a resistive or a capacitive
model.
Z t1 Vt1 l1 = 12.5m
L1 R1
Z t 2 Vt 2 l 2 = 20. 0m
L2 R2
1 1
Voltage [pu]
Voltage [pu]
0.5 0.5
500Ωm 500Ωm
1000Ωm 1000Ωm
0 2000Ωm 0 2000Ωm
4000Ωm 4000Ωm
実測波形 実測波形
0 10 20[µsec] 30 40 0 10 20 30 40
Time Time [µsec]
(c) Simulation results by Marti model (d) Simulation results by Dommel model. (f=3.348kHz)
Fig.7 Surge characteristics on an 1100kV line
L1-7
4
f=1MHz 2.5
Carson 50Hz
2 fin Carson
log10Ri [Ω/km]
Carson 10kHz fin
Li [mH/km]
2
0 fin Carson 10kHz
On the contrary, the per unit length admittance of an infinitely long line is smaller than that of a finite length line.
From the above discussion, it should now be clear that Carson’s and Pollaczek’s earth return impedances may not be
applied to a lightning surge analysis, because the separation distance x between adjacent towers is the same order as the
line height. The same is true for a gas-insulated bus, because its length, height and radius are in the same order. This
requires further work which is interesting and significant.
It is noteworthy that the propagation constants of a finite line is nearly the same as that of an infinitely long line, but
the characteristic (surge) impedance is smaller, because of a smaller series impedance and a greater shunt admittance of the
finite line. Furthermore the ratio of the surge impedances of two finite lines is nearly the same as that of two infinitely
long lines. Finally, traveling wave reflection, refraction and deformation on the finite line is not much different from those
on the infinitely long line.
normalized K [pu]
normalized K [pu]
0.8
Rg=7Ω , Rp=500Ω
6 Rg=7Ω , Rp=70Ω 0.6
Rg=∞ , Rp=∞
4 0.4 Rg=7Ω , Rp=∞
Rg=7Ω , Rp=500Ω
2 0.2 Rg=7Ω , Rp=70Ω
0 0
0 200 400 600 800 1000 0 200 400 600 800 1000
applied voltage E0 [kV] applied voltage E0 [kV]
(a) Without back-flashover (b) With back-flashover
Fig. 9 Measured result of normalized voltage ratio K – Effect of corona wave deformation
800
phase a a-b
b a-c
600 b-c
c
Voltage [kV]
400
200
C is an integration path along the wire axis, Einc denotes the incident electric field that induces current I, R=r -r’, r and
t denote the observation location (a point on the wire surface) and time, respectively, r’ and t’ denote the source location (a
point on the wire axis) and time, respectively, s and s’ denote the distance along the wire surface at r and that along the wire
axis at r’, ŝ and ŝ' denote unit vectors tangent to path C in (12) at r and r’, µ0 is the permeability of vacuum, and c is the
speed of light. Through numerically solving (12), which is based on Maxwell’s equations, the time-dependent current
distribution along the wire structure (lightning channel), excited by a lumped source, is obtained.
The thin-wire time-domain (TWTD) code [52] (available from the Lawrence Livermore National Laboratory) is based
on the MoM in the time domain. One of the advantages of the use of the time-domain MoM is that it can incorporate
nonlinear effects such as the lightning attachment process [54], although it does not allow lossy ground and wires buried in
lossy ground to be incorporated.
L1-10
I (s’ )
^
s’
^
s
r
r’
C(r)
Origin
Fig. 11 Thin-wire segment for MoM-based calculations. Current is confined to the wire axis,
and the tangential electric field on the surface of the wire is set to zero.
jη ⎛ 2 ∂2 ⎞
− ŝ ⋅ E inc ( r ) = ∫C I ( s ′ )⎜⎜ k ŝ ⋅ ŝ ′ − ⎟g ( r , r ′ )ds ′ (13)
4πk ⎝ ∂s∂s ′ ⎟⎠
⎛ − jk r − r ′ ⎞ µ0
where g( r , r ′ ) = exp⎜ ⎟, k = ω µ0 ε 0 , η =
⎜ r − r′ ⎟ ε0
⎝ ⎠
ω is the angular frequency, µ0 is the permeability of vacuum, and ε0 is the permittivity of vacuum. Other quantities in
eq.(13) are the same as those in eq.(12). Current distribution along the lightning channel can be obtained numerically
solving eq.(13).
This method allows lossy ground and wires in lossy ground (for example, grounding of a tall strike object) to be
incorporated into the model. The commercially available numerical electromagnetic codes [56], [57], are based on the MoM
in the frequency domain.
n⎛ 1 ⎞ 1 − σ (i, j, k + 1 2) ∆ t [2 ε (i, j, k + 1 2) ] n −1 ⎛ 1⎞
E z ⎜ i, j, k + ⎟ = × E z ⎜ i, j, k + ⎟
⎝ 2 ⎠ 1 + σ (i, j, k + 1 2) ∆ t [2 ε (i, j, k + 1 2) ] ⎝ 2⎠
⎡ n− 1 1
⎤
H y 2 (i + 1 2 , j, k + 1 2)∆y − H y 2 (i − 1 2 , j, k + 1 2)∆y ⎥
n−
∆t ε(i, j, k + 1 2) 1 ⎢ (14)
+ ×
1 + σ(i, j, k + 1 2)∆t [2ε(i, j, k + 1 2)] ∆x∆y ⎢ 1 1 ⎥
⎢⎣− H x 2 (i, j + 1 2 , k + 1 2)∆x + H x 2 (i, j − 1 2 , k + 1 2)∆x ⎥⎦
n− n−
n+
1
⎛ 1 1⎞ n− ⎛
1 1 1⎞ ∆t 1
Hx 2 ⎜ i, j − , k + ⎟ = H x 2 ⎜ i, j − , k + ⎟ + (15)
⎝ 2 2⎠ ⎝ 2 2 ⎠ µ(i, j − 1 2 , k + 1 2) ∆y∆z
⎡− E z n (i, j, k + 1 2)∆z + E z n (i, j − 1, k + 1 2)∆z ⎤
×⎢ ⎥
⎢⎣+ E y (i, j − 1 2 , k + 1)∆y − E y (i, j − 1 2 , k )∆y⎥⎦
n n
Equation (14) , which is based on Ampere’s law, is an equation updating z component of electric field, Ez(i, j, k+1/2),
at point x=i∆x, y=j∆y, and z=(k+1/2)∆z, and at time t=n∆t. Eq. (15), which is based on Faraday’s law, is an equation
updating x component of magnetic field, Hx(i, j-1/2, k+1/2), at point x=i∆x, y=(j-1/2)∆y, and z=(k+1/2)∆z, and at time
t=(n+1/2)∆t. Equations updating x and y components of electric field, and y and z components of magnetic field can be
written in a similar manner. Note that σ(i, j, k+1/2) and ε(i, j, k+1/2) are the conductivity and permittivity at point x=i∆x,
y=j∆y, and z=(k+1/2)∆z, respectively, µ(i, j-1/2, k+1/2) is the permeability at point x=i∆x, y=(j-1/2)∆y, and z=(k+1/2)∆z. By
updating electric and magnetic fields at every point using eq.(14) and (15), transient fields throughout the computational
domain are obtained. Since the material constants of each cell can be specified individually, a complex inhomogeneous
medium can be analyzed easily.
In order to analyze fields in unbounded space, an absorbing boundary condition has to be set on each plane which
limits the space to be analyzed, so as to avoid reflections there. The FDTD method allows one to incorporate wires buried in
lossy ground, such as strike-object grounding electrodes [59], and nonlinear effects.
L1-11
E-field cell
Ez (i, j, k+1/2)
∆y
E-field cell
∆x Hy (i-1/2, j, k+1/2) Ey (i, j-1/2, k+1)
Ez (i, j-1, k+1/2)
Hx (i, j+1/2, k+1/2)
∆z Hx (i, j-1/2, k+1/2) Hx (i, j-1/2, k+1/2)
measured result
simulation result
(a) (b)
Fig. 13 Simulation of the transient response of a
grounding electrode by the FDTD method.
B. Application Examples
(1) A transient response on a grounding electrode
The impedance and admittance of a given electrical circuit are essential to analyze its steady and transient
characteristics by a circuit-theory based approach such as the Electromagnetic Transients Program (EMTP) [1, 2]. Sunde’s
formula of the admittance of a grounding electrode [60] is well-known and has been widely used in the world. However, the
formula is only for a steady state. Sunde also proposed impedance and admittance formulas for a transient, but those require
iterative calculations and the accuracy is found not satisfactory enough [61].
An electromagnetic interference due to mutual coupling between a grounding mesh and a control cable becomes a
significant subject in power stations and substations [4, 62-64]. To analyze this problem, a transient impedance and
admittance are indispensable. Unfortunately no formula is available, and numerical identification from a measured result
looks only a promised method presently as far as the circuit-theory based approach concerns, although many grounding
electrode models have been proposed [65]. On the contrary, an NEA approach requires no impedance and admittance,
because those are evaluated as a part of an NEA calculation.
Fig.13 (a) illustrates the geometrical configuration of a tested grounding electrode and the experimental circuit, where
only geometrical and physical parameters are required in the NEA calculation [37]. Fig.13 (b) is a comparison of an FDTD
simulation result with the measured one. A satisfactory accuracy of the FDTD method is confirmed from the results. This
example shows that the numerical electromagnetic analysis can solve a problem of which the impedance and admittance are
not known, for the method requires no circuit parameter. Also, the mode of wave propagation may not be TEM, while the
circuit-theory based approach is restricted only for the TEM propagation. Also, it should be noted that the phenomenon is
three-dimensional as is clear from Fig.13 (a).
measurement point
of tower-top 21.7 V
77 m 600 ns
voltage rise 1.37
A
67.8 V
600 ns
(a) injected current (b) tower-top voltage rise
0
0
voltage [V]
current [A]
−20
−1 −40
1.37 A
1.5 A −60
69.2 V
−2 −80
0 200 400 600 800 0 200 400 600 800
time [ns] time [ns]
(c) FDTD simulation result
Fig. 15 Simulation of tower-top voltage rise of a 500-kV transmission tower
bus due to electromagnetic wave scattering. The scattering at the corner can not be simulated by a circuit-theory based
method. The approach is applied to develop life estimation of a power apparatus [5].
150
measured
FDTD
voltage [V]
100
50
0
0 100 200 300 400 500
time [ns]
(a) EMTP simulation (b) FDTD simulation
Fig. 17 Comparison of measured and simulation results
r1=1mm, d=0.2m, x=8m
It is observed that the simulation results in Fig.19 by the EMTP and in Fig. 20 by the FDTD agree reasonably well
with the measured result in Fig. 19. A difference observed between the measured and the EMTP simulation results is
estimated due to mutual coupling between the tower, the pipeline and measuring wires. Also, the frequency-dependent
effect of the conductor affects the difference. A difference between the measured and the FDTD simulation results seems
to be caused by a perfect conductor assumption of the FDTD method.
160 60
EXP
120 EMTP
40
80
Voltage[V]
Voltage[V]
40 20
0
0
-40 EXP
EMTP
-80 -20
0 50 100 150 200 0 50 100 150 200
Time[ns] Time[ns]
60 40
20
40
Voltage[V]
Voltage[V]
0
20
-20
0
EXP -40 EXP
EMTP EMTP
-20 -60
0 50 100 150 200 0 50 100 150 200
Time[ns] Time[ns]
160 80
FDTD FDTD
120
40
Voltage[V]
Voltage[V]
80
40
0
0
-40 -40
0 50 100 150 200 0 50 100 150 200
Time[ns] Time[ns]
60 40
FDTD FDTD
20
40
Voltage[V]
Voltage[V]
0
20
-20
0
-40
-20 -60
0 50 100 150 200 0 50 100 150 200
Time[ns] Time[ns]
L1-15
29.0m
r = 20mm
4 5
8.0m
4.0m
Measured [6] 4 Measured [6]
16.0m 11.2m 3 Calculated Calculated
3
Voltage [MV]
Current [kA]
11.6m 4.0m 2
12.0m 2
12.0m 4.0m 1
80.0m 1
r = 0.373m
0 (1) (2)
44.0m 0
-1 -1
0 1 2 3 0 1 2 3
Time [µs] Time [µs]
(a) The structure of a model tower subject to analysis. (b) Measured waveforms of the voltage of a 3 m gap
and the current flowing through it [2], and those
computed with the TWTDA code including
Motoyama’s flashover model. (1) Voltage. (2) Current.
Voltage [MV]
Voltage [MV]
4 4
2 2
(1) (2)
0 0
0 1 2 0 1 2
Time [µs] Time [µs]
(c) Waveforms of archorn voltages computed by (1) TWTDA and by (2) EMTP, in the
case of a middle-phase back-flashover. ( 150 kA, 1.0 µs ramp current injection )
Fig.21 Archorn voltages during a back-flashover
To analyze such a very-fast transient electromagnetic field around a three-dimensional conductor system,
electromagnetic modeling codes are appropriate. Among many available codes, the Thin-Wire Time-Domain Analysis
(TWTDA) code [52, 68] based on the method of moments [53] is chosen in the present work, for this code allows to
incorporate nonlinear effects into the analysis [6].
In this section, archorn voltages of a simulated 500 kV twin-circuit tower in Fig.21 (a) hit by lightning, in the case of
one-phase back-flashover, are analyzed by a modified TWTDA code that includes a recently proposed flashover model [69,
70]. A similar analysis is also carried out by EMTP [1], and the results are compared with those computed by the modified
TWTDA code.
Fig.21 (b) shows measured waveforms of the voltage of a 3 m gap representing an archorn and the current flowing
through it [70], and those computed by the TWTDA code. Fig.21 (c) are the archorn voltages computed by (1)TWTDA and
(2)EMTP. In the EMTP simulation, the multistory tower model [13] is used, and Motoyama’s flashover model is represented
by a general-purpose description language ‘MODELS’ [71] in EMTP. The archorn voltages computed by EMTP agree well
with those computed by TWTDA before the back-flashover on one phase. On the other hand, after the back-flashover, the
archorn voltages of the other two phases computed by EMTP decay more steeply than those computed by TWTDA, and
they deviate from the results computed by TWTDA during about 1 µs after that. The deviation is noticeable particularly in
the case of the middle- or the lower-phase back-flashover although the settling values of both results are in good agreement.
One of the reasons for these discrepancies may be attributed to somewhat high lumped resistors of the multistory
tower model, which are employed to reproduce the peak values of archorn voltages for step current injection into the tower
top. A very steep wave, injected into the top of this tower model, propagates downward without reflection at nodes, but an
upward propagating wave, which may be a reflected wave at the ground or the associated with the middle- or lower-phase
back-flashover, attenuates much at these nodes. The difference of induction or coupling between the actual dynamic
electromagnetic field around a tower struck by lightning and the TEM mode, which is a basis of an EMTP multiconductor
model, must be another reason.
VI. Conclusion
This paper has presented a lightning surge analysis by the EMTP and by numerical electromagnetic analysis methods.
Because the EMTP is based on a circuit theory assuming TEM mode propagation, it can not give an accurate solution
for a high frequency transient which involves non-TEM mode propagation. Also, the EMTP can not deal with a circuit of
which the parameters are not known.
On the contrary, a numerical electromagnetic analysis method can deal with a transient associated with both TEM and
non-TEM mode propagation. Furthermore, it requires not circuit parameter but geometrical and physical parameters of a
given system. However, it other results in numerical instability if the analytical space, the boundary conditions, the cell
size etc are not appropriate. Also, it requires a large amount of computer resources, and existing codes are not general
enough to deal with various type of transients especially in a large network.
L1-16
VII. References
[1] W. Scott-Meyer: EMTP Rule Book, B.P.A., 1980.4
[2] H. W. Dommel: EMTP Theory Book, B.P.A., 1986.8
[3] A. Ametani and T. Kawamura: A method of a lightning surge analysis recommended in Japan using EMTP, IEEE Trans. PWRD, vol.20, no.2,
pp.867-875, 2005.4
[4] A. Ametani, H. Motoyama, K. Ohkawara, H. Yamakawa and N. Suga: Electromagnetic disturbances of control circuits in power station and
substation experienced in Japan, IET Proc. GTD, vol.3, no.9, pp.801-815, 2009
[5] S. Sakaguch and M. Oyama: Application of Maxwell solvers to PD propagation Part III: PD propagation in GIS, IEEE EI Magazine, vol.19, no.1,
pp.6-12, 2003
[6] T. Mozumi, Y. Baba, M.Ishii, N. Nagaoka and A. Ametani: Numerical electromagnetic field analysis of archon voltages during a back flashover on a
500kV twin-circuit line, IEEE Trans. PWRD, vo.18, no.1, pp.207-213, 2003.1
[7] IEE Japan WG: Numerical Transient Electromagnetic Analysis Methods, IEE Japan, 2008.3
[8] A. Ametani, T. Hoshino, M. Ishii, T. Noda, S. Okabe and K. Tanabe: Numerical electromagnetic analysis method and its application to surge
phenomena, CIGRE 2008 General Meeting, Paper C4-108, 2008.8
[9] A. Ametani: Distributed-Parameter Circuit Theory, Corona Pub. Co., Tokyo, 1990
[10] Japanese standard, ‘High-voltage testing method’, JEC-0102-1994, IEE Japan, 1994
[11] IEE Japan WG Report, ‘A new method of a lightning surge analysis in a power system’, Technical Report No. 244, March 1987
[12] L. V. Bewley, ‘Traveling Waves on Transmission Systems’, Dover (N.Y.), 1963
[13] M. Ishii, T. Kawamura, T. Kouno, E. Ohsaki, K. Shiokawa, K. Murotani and T. Higuchi, “Multistory transmission tower model for lightning surge
analysis” IEEE Trans. Power Delivery, vol.6, no.3, July, pp.1327-1335, 1991
[14] IEEE Working Group Report, ‘A simplified method for estimating lightning performance of transmission lines’, IEEE Trans., Vol. PAS-104, 919,
1985
[15] IEEE Working Group Report, ‘Estimating lightning performance of transmission lines, II-Update to analytical models’, IEEE Trans., Vol. PWRD-8,
1254, 1993
[16] IEEE Guide for Improving the Lightning Performance of Transmission Lines, IEEE Standard1243-1997, 1997
[17] CIGRE SC33-WG01, ‘Guide to Procedures for Estimating Lightning Performance of Transmission Lines’, Technical Brochure, Oct. 1991
[18] T. Shindo and T. Suzuki, ‘A new calculation method of breakdown voltage-time characteristics of long air gaps’, IEEE Trans., Vol. PAS-104, 1556,
1985
[19] N. Nagaoka, ‘An archorn flashover model by means of a nonlinear inductance’, Trans. IEE Japan, Vol. B-111(5), 529, 1991
[20] IEEE Working Group 3. 4. 11, ‘Modeling of metal oxide surge arresters’, IEEE Trans., Vol. PWRD-7(1), 302, 1992
[21] I. Kim et al., ‘Study of ZnO arrester model for steep front wave’, IEEE Trans., Vol. PWRD-11(2), 834, 1996
[22] A. Ametani at el : Modeling of a buried conductor for an electromgnetic transient simulation, IEE Japan Trans. EEE, vol.1, no.1, pp.45-55, June
2006
[23] R. B. Anderson and A. J. Eriksson, ‘Lightning parameters for engineering application’, Electra, No. 69, 65, 1980
[24] S. Yokoyama: “Development of lightning observation methods for current waveforms and discharge progressing manner”, Asia-Pacific EMC,
Beijing, China, Paper TH-PM-E1-1, April 2010.
[25] W. Diesendorf, ‘ Insulation Co-ordination in High Voltage Electric Power Systems‘, Butterworths, 1974.
[26] T. Ueda, M. Yoda and I. Miyachi, ‘Characteristics of lightning surges observed at 77kV substations’, Trans. IEE Japan, Vol. 116-B(11), 1422, 1996
[27] A. Ametani, et al., ‘Investigation of flashover phases in a lightning surge by new archorn and tower models’, Proceedings of IEEE PES T&D
Conference 2002, Yokohama, pp. 1241-1246, 2002
[28] A. Ametani, et al., ‘A frequency-dependent impedance of vertical conductors on a multiconductor tower model’, IEE Proc.-GTD, Vol. 141(4), pp.
339-345, 1994
[29] T. Hara, O. Yamamoto, M. Hayashi and C. Uenoson: “Empirical formulas of surge impedance for a single and multiple vertical cylinder”, Trans.
IEEJ, vol.B-110, pp.129-136, 1990
[30] A. Ametani, et al., ‘Wave propagation characteristics of iron conductors in an intelligent building’, Trans. IEE Japan, Vol. 120-B(1), 31, 2000
[31] A. Semlyen and A. Dabuleanu, ‘Fast and accurate switching transient calculations on transmission lines with ground return using recursive
convolutions‘, IEEE Trans., Vol. PAS-95(5), 561, 1975
[32] J. R. Marti, ‘ Accurate modeling of frequency-dependent transmission lines in electromagnetic transient simulations‘, IEEE Trans., Vol. PAS-101(1),
147, 1982.
[33] N. Nagaoka, ‘Development of frequency-dependent tower model’, Trans. IEE Japan, vol. 111-B, 51, 1991
[34] M.Ishii and Y. Baba: Numerical electromagnetic field analysis of tower surge response, IEEE Trans. PWRD, vol.12, no.1, pp.483-488, Jan. 1997
[35] A. K. Mishra, A. Ametani, Y. Baba, N. Nagaoka and S. Okabe: “Nonuniform characteristics of a horizontal grounding electrode”, IEEE Trans.
PWRD, vol.22 (4), pp. 2327-2334, Oct. 2007
[36] M. Loboda: “Essential requirements for earthing system determining the efficiency of lightning protection”, Asia-Pacific EMC, Beijing, China,
Paper WE-PM-E2-1, April 2010
[37] K. Tanabe “Novel method for analyzing dynamic behovior of grounding systems based on the finite-difference time-domain method“, IEEE Power
Engineering Review, vol.21, no.9, pp.55-57, 2001
[38] N. Nagaoka and A. Ametani, ‘A lightning surge analysis considering multiphase flashovers’, IEE Japan, Research Meeting, Paper HV-95-50, 1995.
10
[39] CRIEPI: Visual Surge Test Lab. (VSTL), http://criepi.denken.or.jp/jp/electric/substance/09.pdf, 2007
[40] A. Ametani, K. Adachi and T. Narita, ‘An investigation of surge propagation characteristics on an 1100 kV transmission line’, IEEJ Trans. PE, vol.
123(4), 513, 2003
[41] J. R. Carson : Wave propagation in overhead wires with ground return, Bell Syst. Tech. J., vol.5, pp539-554, 1926
[42] F. Pollaczek : Uber das Feld einer unendlich langen wechselstromdurchflossenen Einfachleitung, ENT, Heft 9, Band 3, pp.339-359, July 1926
[43] A. Ametani, ‘Wave propagation on a nonuniform line and its impedance and admittance’, Sci. Eng. Review, Doshisha Univ., Vol. 43(3), 136, 2002
[44] A. Ametani, T. Yoneda, Y. Baba and N. Nagaoka : An investigation of earth-return impedance between overhead and underground conductors and its
approximation, IEEE Trans. EMC, vol.51, no.3, pp.860-867, Aug. 2009
[45] A. Ametani and A. Ishihara, ‘Investigation of impedance and line parameters of a finite-length multiconductor system’, Trans. IEE Japan, Vol.
113-B(8), 905, 1993.
[46] A. Deri et al., ‘The complex ground return plane : a simplified model for homogeneous and multi-layer earth return’, IEEE Trans. Vol. PAS-100(8),
3686, 1981
[47] A. Ametani and A. Ishihara, ‘Impedance of a non-parallel conductor system and its circuit analysis’, IEE Japan, Research Meeting, Paper PE-92-173,
1992. 10
[48] Celia de Jusus and M. T. Correia de Barros, ‘ Modeling of corona dynamics for surge propagation studies’, IEEE Trans, Vol, PWRD-9(3), 1564,
1994
[49] J. F. Guiller, M. Poloujadoff and M. Rioul, ‘ Damping model of traveling waves by corona effect along extra high voltage three phase line’, IEEE
Trans. Vol. PWRD-10(4), 1851, 1995
[50] A. Ametani, et al., ‘A study of phase-wire voltage variations due to corona wave-deformation’, Proceeding of the IPST ’99, Budapest, Hungary, pp.
433-438, June, 1999
[51] A. Ametani, et al., ‘A basic investigation of substation entrance voltage variation due to corona wave deformation’, Trans. IEE Japan, Vol. 120-B(3),
L1-17
403, 2000
[52] M. Van Baricum, and E. K. Miller, “TWTD --- A Computer Program for Time-Domain Analysis of Thin-Wire Structures“ UCRL-51-277, Lawrence
Livermore Laboratory, California, 1972
[53] E. K. Miller, A. J. Poggio, and G. J. Burke, “An integro-differential equation technique for the time-domain analysis of thin wire structures” J.
Computational Phys., vol. 12, pp. 24-48, 1973
[54] A. S. Podgorski, and J. A. Landt, “Three dimensional time domain modelling of lightning” IEEE Trans. Power Delivery, vol. PWRD-2, no. 3, Jul.,
pp.931-938, 1987
[55] R. F. Harrington, Field Computation by Moment Methods Macmillan Co., New York, 1968
[56] G. J. Burke, and A. J. Poggio, “Numerical Electromagnetic Code (NEC) --- Method of Moments“ Technical Document 116, Naval Ocean Systems
Center, San Diego, 1980
[57] G. J. Burke, “Numerical Electromagnetic Code (NEC-4) --- Method of Moments“ UCRL-MA-109338, Lawrence Livermore National Laboratory,
California, 1992
[58] K. S. Yee, “Numerical solution of initial boundary value problems involving Maxwell’s equations in isotropic media,”(IEEE Trans. Antennas
Propagat., vol. AP-14, no. 3, Mar., pp. 302-307, 1966
[59] T. Noda, A. Tetematsu, and S. Yokoyama, “Improvements of an FDTD-based surge simulation code and its application to the lightning overvoltage
calculation of a transmission tower” IPST05-138-24c, Montreal, Canada, Jun. 2005
[60] E. D. Sunde “Earth Conduction Effects in Transmission Systems“ Dover Publications, New York, 1968
[61] A. K. Mishra, A. Ametani, N. Nagaoka, and S. Okabe “A study on frequency-dependent parameters and Sunde’s formula of a counterpoise“ IEEJ
Trans. PE, vol.127, no.1, pp.299-305, 2007
[62] CIGRE WG36.04 “Guide on EMC in power plants and substations“ CIGRE Pub.124, Paris, France, Dec. 1997
[63] S. Agematu et al, “High-frequency switching surge in substation and its effects on operation of digital relays in Japan” CIGRE 2006, General
Meeting, Paper C4-304, Sept.2006
[64] A.Ametani et al “Electromagnetic disturbances of control circuits in power stations and substations experienced in Japan “UPEC 2007, 12-31/12-32,
Brightion, UK, Sept.2007
[65] A. K. Mishra, N. Nagaoka and A. Ametani “Frequency-dependent distributed-parameter modeling of counterpoise by time-domain fitting“ IEE Proc.
GTD, vol.153, no.4, July, pp.485-492, 2006
[66] A. Aemtani, T. Chikara, Y. Baba, N. Nagaoka and S. Okabe : “A characteristic of a grounding electrode on the earth sargace “, IWHV 2008/Kyoto,
Paper HV-08-76, 2008-10
[67] A. Ametani, K. Oshio, N. Nagaoka and Y. Baba: “Lightning surge characteristics in a chemical plant”, EEUG 2010 / Helsinki, 2010.8
[68] R. Moini, B. Kordi and M. Abedi, “Evaluation of LEMP effects on complex wire structures located above a perfectly conducting ground using
electric field integral equation in time domain,” IEEE Trans. Electromagnetic Compatibility, vol.40, no.2, May, pp.154-162, 1998
[69] H. Motoyama, K. Shinjo, Y. Matsumoto and N. Itamoto, “Observation and analysis of multiphase back flashover on the Okushishiku test
transmission line caused by winter lightning” IEEE Trans. Power Delivery, vol.13, no.4, October, pp.1391-1398, 1998
[70] H. Motoyama, “Development of a new flashover model for lightning surge analysis” IEEE Trans. Power Delivery, vol.11, no.2, April, pp.972-979,
1996
[71] L. Dube and I. Bonfanti, “MODELS: A new simulation tool in the EMTP” European Trans. Electrical Power Engineering, vol.2, no.1,
January/February, pp.45-50, 1992
A. Ametani, (M’71-SM’84-F’92-LF’10) received the Ph.D. degree from the University of Manchester Institute of Science and Technology, Manchester, U.
K., in 1973. Currently, he is a Professor at Doshisha University, Kyoto, Japan.
L1-18