Mportant Roduct Nformation: Read This Information First Product: Remote IO Manager Software Release 2.04
Mportant Roduct Nformation: Read This Information First Product: Remote IO Manager Software Release 2.04
Mportant Roduct Nformation: Read This Information First Product: Remote IO Manager Software Release 2.04
GFK-1867E
Caution
This tool shares many components used by the VersaPro™ software package; therefore
VersaPro and all its components must be uninstalled before this tool can be installed on a
particular computer. Version 2.0x of VersaPro incorporates the functionality supplied by this
tool.
Do not attempt to open configurations created with this tool with the hardware configuration
software supplied with VersaPro 1.1x and earlier. Doing so could corrupt the configurations.
Configurations created with the released version of this tool will be compatible with VersaPro
release 2.0x.
Note
When using SNP protocol, it is recommended that the communications settings be changed to the
settings described in “Serial Parameter Settings ” on page 5.
Installation
Note
The tool must be installed on a hard drive in your computer. Do not attempt to install the tool on
removable media such as Jaz® or Zip® drives.
1. It is recommended that you close all applications including virus checking, Internet Explorer 5.0,and CIMPLICITY
HMI software that might be running in the background. You may need to check the task manager to determine if
other applications are running.
2. Put the CD in CD-ROM Drive.
3. Select the CD drive from Windows Explorer.
4. Double click Setup.exe
Follow the user prompts to complete the installation. If you have a previous version of the tool or
VersaPro installed, the installation tool will first uninstall the previous version. During this uninstall
process, you may be asked whether you would like remove shared files. It is recommended that you
always answer “No to All” to ensure that no files are deleted that might be needed by another application.
Installation Issues
1. After installing VersaPro 2.0x and then subsequently installing VersaPro 1.0x or 1.1x, you may receive the
following error during the installation process:
In addition, you may not be able to connect to PLCs after the installation completes and the following error
message may appear.
Resolution: A VersaPro 2.0x user wishing to install VersaPro 1.0x or VersaPro 1.1x can avoid this problem by
following these steps:
a. Uninstall VersaPro 2.0x: In the Windows Start menu, select Programs\GE Fanuc
Software\VersaPro\Uninstall. You can also open the Control Panel's Add/Remove Programs, then select
"VersaPro 2.0x" for removal. (Uninstalling VersaPro 2.0x by letting the VersaPro 1.1x installer perform
the uninstall should be avoided.)
b. After the uninstall, shutdown and restart the computer.
c. After the computer has started up, delete the "\Program Files\Common Files\GE Fanuc
Automation\PLCServer" directory on the hard drive that contains the computers operating system. If you
don’t delete this directory and instead choose to delete all the files in the directory, you should make sure
Important Product Information 4
GFK-1867E
that the “Show All Files” option is selected under Folder options in Windows explorer. This is to ensure
that all files including hidden files are deleted from the directory.
Important Product Information 5
GFK-1867E
d. Delete the following files from the directory \Windows (Win95/98) , \WinNT (NT4.0 Win2000, Win ME,
Win XP):
ccu_enu.dll
egdservice.exe
gefccl32.dll
gefccu32.exe
gefegd32.dll
gefhct32.dll
gefsnp32.dll
gefsrx32.dll
geftcp32.dll
hctpxyif.dll
hdrvsnp.exe
hdrvtcp.dll
e. Install VersaPro 1.0x/1.1x
2. When installing on Windows 95/98, you may receive the following error: “Isuninst has performed an illegal
operation and will be shutdown.”.
Resolution: You should simply close the dialog and the install will proceed normally and VersaPro will be
installed correctly.
3. When installing on Windows 95/98 and selecting “Yes” to re-boot the PC to complete the installation, the PC
may lock-up rather than power down correctly.
Resolution: You can reset or power cycle the PC. The PC may run scan disk on power-up but will power up
correctly and VersaPro will install normally.
4. VersaPro loses default CCU settings if HMI project exists. VersaPro loses all the default CCU settings if HMI
has been installed prior to it and an HMI project has already been created. The gef_cfg.ini file created by HMI does
not put information about the serial devices used in the project.
Resolution: Using a text editor, such as Notepad, open the file gef_cfg.snp and copy and paste its contents into
gef_cfg.ini. Edit gef_cfg.ini to provide the correct defaults.
Communications Issues
Many communication issues can be resolved by properly setting the communications timing parameters which
may have been altered from previous programmer sessions on the same PC. Here are some guidelines which
can sometimes help when experiencing communication problems:
and usually C:\WinNT for Windows NT). Since this location is always in your path, you do not need to specify
the path when invoking the CCU.
If a password has been defined for the CCU, the Password dialog box will appear. To view the communications
parameters in Read-Only mode (not making changes), click the "View Only" button. The password can be
changed by the clicking the Change Password button on the Password dialog box or choosing Password from
the File menu in the CCU.
Modem Issues
The NIU does not support serial connections through modems.
Important Product Information 7
GFK-1867E
ID Description
CR74424 Loading Autoconfigured VersaMax modules Results in Similar but Wrong module
Details: The following list of modules have the same board IDs and VersaPro is unable to distinguish
between them when loading an autoconfigured module.
IC200MDL650 loads as IC200MDL636
IC200MDL750 loads as IC200MDL742
IC200MDL331 loads as IC200MDL329
IC200MDD844 loads as IC200MDD842
IC200MDL141 loads as IC200MDL140
Resolution: After loading the listed autoconfigured VersaMax modules, you should change the
configuration to the proper module in VersaPro and then store the configuration to VersaMax. After
storing the configuration, you will be able to load the configuration properly.
CR74778 Double clicking on a hardware configuration folder causes an error message.
Details: When you double click on a hardware configuration folder in Windows Explorer, an error
message box is displayed stating that "the *.hwcfg file or one of it's components could not be found."
Resolution: Configuration files should be opened from within the Remote I/O Manager using the
File, Open menu item.
Installation/Licensing Issues:
ID Description
CR73074 Settings.reg error on VersaPro 2.0x install after manually deleting files
Steps to reproduce:
1) Install VersaPro 1.0.
2) Manually delete the files from "\Program Files\Common Files\GE Fanuc Automation\PLCServer"
and the files from "\Program Files\GE Fanuc Automation\VersaPro"
3) Install VersaPro 2.0x from the CD
4) Upon Installation the following error was received: "Cannot import settings.reg: Error opening the
file. There may be a disk or a file system error.
After dismissing this error, install continues but it also appears that the license tag on the subsequent
dialog is missing.
Resolution: You should not delete files in order to perform an uninstall of VersaPro. In order to
correct the problem after deleting the files and receiving this error, you should re-install VersaPro and
it will install correctly.
CR73136 VersaPro Install problem when logged onto a Novell network
Details: When attempting to install VersaPro when also logged onto a Novell network, the following
errors will be reported:
RUNDLL has performed an illegal operation and will be shut down
NWPOPUP has performed an illegal operation.......
MSGSRV32 " "
ESSVC " "
MNTASK " "
Installation aborted
Resolution: You should re-boot the computer and not log onto a Novell network. VersaPro will
then install successfully.