Friction loss calculation

Pumped fluid Static head Layout


Water, pure 6 Wet well installation

Flow Number of pumps Calculation model


80 l/s 2 Colebrook-White

Viscosity Nature of system


1.569 mm²/s Single pumps as parallel circuit

Type Ø ? or L Qty. v k ΔH
(mm) (m/s) (mm) (m)
Ø = Diameter v = Velocity k = Pipe roughness ΔH = Head loss
Individual discharge side pipe - Plastic / PE100 (HDPE) PE 4710
SDR 17 (PN 10) / DN 200 (200x11,9 mm) / DIN 8074/75 /EN 13244
Pipe length 176.2 8m 1 1.64 0.01 0.1016
Elbows 176.2 0.6 2 1.64 0.08229
Inlet 176.2 1 1 1.64 0.1372
Non-return valves 176.2 0.9 1 1.64 0.1234
T-piece 176.2 0.4 1 1.64 0.05486
VALVE 176.2 0.3 1 1.64 0.04115
Total friction head 0.5405
Common discharge side pipe - Plastic / PE100 (HDPE) PE 4710
SDR 17 (PN 10) / DN 200 (250x14,8 mm) / DIN 8074/75 /EN 13244
Pipe length 220.4 450 m 1 2.097 0.01 6.849
Discharge Connection 220.4 0.3 1 2.097 0.06723
Outlet 220.4 1 1 2.097 0.2241
T-piece 220.4 0.4 1 2.097 0.08964
VALVE 220.4 0.3 1 2.097 0.06723
Elbow 45° 220.4 1.08 10 2.097 0.2946
Elbow 90° 220.4 0.678 4 2.097 0.1941
Total friction head 7.786

Friction loss head 8.326 m


Total static head 6m
Total head 14.33 m

Project Created by Last update 6/6/2020


Block AW.ITEMNAME Created on 6/6/2020 Page 1 / 1