MFR 3 Multi Function Relay: Manual
MFR 3 Multi Function Relay: Manual
MFR 3 Multi Function Relay: Manual
MFR 3
Multi Function Relay
Manual
Software Version 3.4xxx
Manual 37107F
Operation Manual 37107F MFR 3 - Multi Function Relay
WARNING
Read this entire manual and all other publications pertaining to the work to be performed before instal-
ling, operating, or servicing this equipment. Practice all plant and safety instructions and precautions.
Failure to follow instructions can cause personal injury and/or property damage.
The engine, turbine, or other type of prime mover should be equipped with an overspeed (overtempera-
ture, or overpressure, where applicable) shutdown device(s), that operates totally independently of the
prime mover control device(s) to protect against runaway or damage to the engine, turbine, or other
type of prime mover with possible personal injury or loss of life should the mechanical-hydraulic gov-
ernor(s) or electric control(s), the actuator(s), fuel control(s), the driving mechanism(s), the linkage(s),
or the controlled device(s) fail.
Any unauthorized modifications to or use of this equipment outside its specified mechanical, electrical,
or other operating limits may cause personal injury and/or property damage, including damage to the
equipment. Any such unauthorized modifications: (i) constitute "misuse" and/or "negligence" within
the meaning of the product warranty thereby excluding warranty coverage for any resulting damage,
and (ii) invalidate product certifications or listings.
CAUTION
To prevent damage to a control system that uses an alternator or battery-charging device, make sure
the charging device is turned off before disconnecting the battery from the system.
Electronic controls contain static-sensitive parts. Observe the following precautions to prevent dam-
age to these parts.
• Discharge body static before handling the control (with power to the control turned off, contact a
grounded surface and maintain contact while handling the control).
• Avoid all plastic, vinyl, and Styrofoam (except antistatic versions) around printed circuit boards.
• Do not touch the components or conductors on a printed circuit board with your hands or with
conductive devices.
OUT-OF-DATE PUBLICATION
This publication may have been revised or updated since this copy was produced. To verify that you
have the latest revision, be sure to check the Woodward website:
http://www.woodward.com/pubs/current.pdf
The revision level is shown at the bottom of the front cover after the publication number. The latest
version of most publications is available at:
http://www.woodward.com/publications
If your publication is not there, please contact your customer service representative to get the latest
copy.
Important definitions
WARNING
Indicates a potentially hazardous situation that, if not avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation that, if not avoided, could result in damage to equipment.
NOTE
Provides other helpful information that does not fall under the warning or caution categories.
Woodward reserves the right to update any portion of this publication at any time. Information provided by Woodward is believed to be
correct and reliable. However, Woodward assumes no responsibility unless otherwise expressly undertaken.
© Woodward
All Rights Reserved.
Revision History
Contents
CHAPTER 4. FUNCTIONAL DESCRIPTION ................................................................................... 31
Function ................................................................................................................................................. 31
Operating Conditions................................................................................................................... 31
Direction of Power ................................................................................................................................. 34
Power Factor Definition ......................................................................................................................... 34
Activation of the Circuit Breakers .......................................................................................................... 36
Operating Sequence for the MCB ............................................................................................... 36
Operating Sequence for the GCB ............................................................................................... 37
Analog Controller Outputs ..................................................................................................................... 38
Controller Setting ......................................................................................................................... 39
Load and/or Var Sharing ....................................................................................................................... 41
Language Manager ............................................................................................................................... 43
Alarms .................................................................................................................................................... 44
Alarm Class ................................................................................................................................. 44
Internally Detected Alarms .......................................................................................................... 44
Alarm Acknowledgement............................................................................................................. 45
CHAPTER 5. DISPLAY AND PUSH-BUTTONS .............................................................................. 46
Brief Description of LED and Push-Buttons .......................................................................................... 47
LEDs ............................................................................................................................................ 47
Push-Buttons ............................................................................................................................... 47
Miscellaneous .............................................................................................................................. 47
LEDs ...................................................................................................................................................... 48
Push-Buttons ......................................................................................................................................... 49
General / Configuration ............................................................................................................... 49
Control of the Power Circuit Breakers ......................................................................................... 51
Operating Mode Selector ............................................................................................................ 51
LC Display ............................................................................................................................................. 52
Automatic Mode (First Display Line: Measuring Values) ............................................................ 52
Automatic Mode (Second Display Line: Measuring Values) ....................................................... 53
Automatic Mode (Second Display Line: Alarm Display).............................................................. 54
CHAPTER 6. CONFIGURATION................................................................................................... 55
Introduction ............................................................................................................................................ 56
Basic Data ............................................................................................................................................. 56
Language Manager ..................................................................................................................... 56
Version Number .......................................................................................................................... 57
Service Display ............................................................................................................................ 57
Password Protection .............................................................................................................................. 59
Event Recorder ...................................................................................................................................... 60
Internal Events and Discrete Inputs ............................................................................................ 60
Analog Inputs .............................................................................................................................. 62
Direct Configuration ............................................................................................................................... 63
Basic Settings ........................................................................................................................................ 64
Generator and Mains Environmental .......................................................................................... 64
Change Passwords ..................................................................................................................... 72
Controller ............................................................................................................................................... 73
Constant and Interchange Real Power Controller ...................................................................... 73
Frequency Controller ................................................................................................................... 74
Voltage Controller........................................................................................................................ 77
Power Factor Controller .............................................................................................................. 80
Real Power Controller ................................................................................................................. 82
Load/var Sharing ......................................................................................................................... 86
Interface....................................................................................................................................... 87
Breaker ................................................................................................................................................... 88
Breaker Logic ............................................................................................................................... 88
Synchronization ........................................................................................................................... 91
Synchronization Time Monitoring ................................................................................................ 92
Dead Bus Start............................................................................................................................. 93
Breaker Monitoring ...................................................................................................................... 94
Mains Decoupling ........................................................................................................................ 94
Mains Settling Time ..................................................................................................................... 94
Protection ............................................................................................................................................... 95
Mains Power Monitoring .............................................................................................................. 95
Reverse/Reduced Power Monitoring ........................................................................................... 96
Generator Overload Monitoring ................................................................................................... 97
Generator Re-active Power Monitoring ....................................................................................... 98
Time-Overcurrent Monitoring (TOC)............................................................................................ 99
Inverse Time-Overcurrent Monitoring ........................................................................................ 100
Inverse Time-Overcurrent Monitoring with Voltage Restraint ................................................... 103
Earth Fault Monitoring ............................................................................................................... 105
Generator Load Imbalance Monitoring ...................................................................................... 106
Generator Overfrequency Monitoring ........................................................................................ 107
Generator Underfrequency Monitoring ...................................................................................... 108
Generator Overvoltage Monitoring ............................................................................................ 109
Generator Undervoltage Monitoring .......................................................................................... 110
Mains Frequency Monitoring ..................................................................................................... 111
Mains Voltage Monitoring .......................................................................................................... 112
Mains dϕ/dt Phase/Vector Shift Monitoring ............................................................................... 114
Mains df/dt Rate Of Change Of Frequency Monitoring (ROCOF) ............................................. 116
Mains Decoupling (Selection Between dϕ/dt and df/dt) ............................................................ 116
Battery Voltage Monitoring ........................................................................................................ 117
Discrete Inputs ..................................................................................................................................... 118
Blocking of Operation Mode Selector [D02] .............................................................................. 118
Selection of the Mains Decoupling via Discrete Input [D01]...................................................... 118
Breaker Logic via Discrete Input [D03] ...................................................................................... 119
Discrete inputs: Setting .............................................................................................................. 119
Discrete Inputs: Text .................................................................................................................. 120
Analog Inputs ....................................................................................................................................... 121
Analog Inputs: Setting ................................................................................................................ 121
Outputs ................................................................................................................................................. 125
Analog Outputs .......................................................................................................................... 125
Relay Manager........................................................................................................................... 126
Pulse Outputs ............................................................................................................................ 127
Drive ..................................................................................................................................................... 128
Delayed Monitoring and Ignition Speed..................................................................................... 129
Shutdown (Unload and Open GCB) .......................................................................................... 130
Counter ................................................................................................................................................ 131
Maintenance Call ....................................................................................................................... 131
Operating Hours Counter........................................................................................................... 132
Start Counter.............................................................................................................................. 133
kWh/kvarh Counter .................................................................................................................... 133
Resetting the Counters .............................................................................................................. 133
Real Time Clock ........................................................................................................................ 134
Current Slave Pointer ................................................................................................................ 134
CHAPTER 7. COMMISSIONING ................................................................................................. 135
APPENDIX A. DIMENSIONS ...................................................................................................... 137
APPENDIX B. TECHNICAL DATA .............................................................................................. 138
APPENDIX C. MEASURED QUANTITIES AND ACCURACY ........................................................... 140
Illustrations
Figure 3-1: Wiring diagram MFR 31 ........................................................................................................................................ 16
Figure 3-2: Wiring diagram MFR 32 ........................................................................................................................................ 17
Figure 3-3: Power supply .......................................................................................................................................................... 18
Figure 3-4: Measuring inputs - voltage - generator ................................................................................................................... 18
Figure 3-5: Measuring inputs - voltage - busbar ....................................................................................................................... 19
Figure 3-6: Measuring inputs - voltage - mains ........................................................................................................................ 19
Figure 3-7: Measuring inputs - current - generator ................................................................................................................... 20
Figure 3-8: Mains current transformer measuring inputs .......................................................................................................... 20
Figure 3-9: Discrete inputs - control inputs .............................................................................................................................. 21
Figure 3-10: Discrete inputs - alarm inputs - positive polarity ................................................................................................. 22
Figure 3-11: Discrete inputs - alarm inputs - negative polarity (examples) .............................................................................. 22
Figure 3-12: Analog inputs ....................................................................................................................................................... 23
Figure 3-13: Relay outputs - control outputs - CB control ........................................................................................................ 24
Figure 3-14: Relay outputs - relay manager .............................................................................................................................. 24
Figure 3-15: Analog outputs ..................................................................................................................................................... 25
Figure 3-16: Pulse outputs ........................................................................................................................................................ 25
Figure 3-17: Pulse output - wiring example .............................................................................................................................. 25
Figure 3-18: Controller - three-position controller.................................................................................................................... 26
Figure 3-19: Three-position controller - external RC wiring for relay manager ....................................................................... 27
Figure 3-20: Analog controller n/f/P - wiring and jumper setting ............................................................................................. 27
Figure 3-21: Analog controller V/Q - wiring and jumper setting.............................................................................................. 27
Figure 3-22: Interface - terminals ............................................................................................................................................. 28
Figure 3-23: Interface - CAN bus shielding .............................................................................................................................. 29
Figure 3-24: Interface - loop the CAN bus ............................................................................................................................... 29
Figure 4-1: Direction of power ................................................................................................................................................. 34
Figure 4-2: Activation of the circuit breakers - MCB ............................................................................................................... 36
Figure 4-3: Activation of the circuit breakers - GCB ................................................................................................................ 37
Figure 4-4: Closed loop ............................................................................................................................................................ 38
Figure 4-5: Step response (example)......................................................................................................................................... 38
Figure 4-6: Step response - controller setting ........................................................................................................................... 40
Figure 4-7: Load/var sharing - schematic ................................................................................................................................. 42
Figure 5-1: Front panel MFR 31 ............................................................................................................................................... 46
Figure 5-2: Front panel MFR 32 ............................................................................................................................................... 46
Figure 6-1: Characteristic of the time-overcurrent monitoring ................................................................................................. 99
Figure 6-2: Inverse time-overcurrent - characteristic "normal inverse" .................................................................................. 101
Figure 6-3: Inverse time-overcurrent - characteristic "high inverse" ...................................................................................... 102
Figure 6-4: Inverse time-overcurrent - characteristic "extremely inverse" ............................................................................. 102
Figure 6-5: Characteristic of the inverse time-overcurrent monitoring with voltage restraint (knee curve setting 20 %) ...... 103
Figure 6-6: Ignition speed - delayed monitoring ..................................................................................................................... 129
Figure 7-1: Dimensions ........................................................................................................................................................... 137
Figure 7–2: analog outputs – power factor scaling ................................................................................................................. 143
Tables
Table 3-1: Maximum CAN bus length...................................................................................................................................... 30
Table 4-1: Operating conditions - idle control and synchronization ......................................................................................... 31
Table 4-2: Operating conditions - idle control and synchronization - conditions ..................................................................... 31
Table 4-3: Operating conditions - dead bus start ...................................................................................................................... 32
Table 4-4: Operating conditions - dead bus start - conditions .................................................................................................. 32
Table 4-5: Operating conditions - isolated operation ................................................................................................................ 32
Table 4-6: Operating conditions - mains parallel operation ...................................................................................................... 33
Table 4-7: Alarms - text messages ............................................................................................................................................ 44
Table 4-8: Alarms - short acknowledgment .............................................................................................................................. 45
Table 4-9: Alarms - long acknowledgment ............................................................................................................................... 45
Table 5-1: Alarms - text messages ............................................................................................................................................ 54
Table 6-1: Event recorder - messages - Part 1 .......................................................................................................................... 61
Table 6-2: Event recorder - messages - Part 2 .......................................................................................................................... 62
Chapter 1.
General Information
Introduction
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
The MFR 3 has been designed to provide circuit breaker and load control and protection. It is possible to monitor
both the generator and mains simultaneously. The MFR 3 permits two circuit breakers to be synchronized and
control of the mains power.
The MFR 3 starts as a standard unit that may have additional functions added with each model. The model of the
MFR 3 is designated as follows:
Examples:
• MFR 31S45B/PSVX+Q (standard unit with one breaker logic for synchronous generators and is flush-
mounting, 400 Vac PT inputs as well as ../5 A CT measuring inputs; Option Q: analog or three-position con-
troller functionality selectable, and an event logger, T7 analog inputs, and real-time clock
• MFR 32S15B/PSVX+Q (standard unit with two breaker logic for synchronous generators and is flush-
mounting, 100 Vac PT inputs as well as ../5 A CT measuring inputs; Option Q: analog or three-position con-
troller functionality selectable, and an event logger, T7 analog inputs, and real-time clock
Intended Use: The control unit must only be operated as described in this manual. The prerequisite for a proper
and safe operation of the product is correct transportation, storage, and installation as well as careful operation
and maintenance.
NOTE
This manual has been developed for a unit fitted with all available options. Inputs/outputs, functions,
configuration screens and other details described, which do not exist on your unit may be ignored.
The present manual has been prepared to enable the installation and commissioning of the unit. Be-
cause of the large variety of parameter settings, it is not possible to cover every combination. The ma-
nual is therefore only a guide. In case of incorrect entries or a total loss of functions, the default set-
tings can be taken from the enclosed list of parameters at the rear of this manual.
Measuring
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Voltage
The control unit performs three-phase true RMS measurement of two star or delta voltage systems (generator
and mains). This unit can be delivered with the following measuring voltage ranges (rated values). The vol-
tage measuring is specific to the part number ordered (please note chapter "Technical Data", page 138):
- [1] 66/115 Vac
- [4] 230/400 Vac
Frequency
The measured voltages are digitally filtered for frequency measurement. The control unit performs three-
phase true RMS measurement of the frequency if the measured voltages exceed the rated value (100/400 Vac)
by 15 %. This ensures rapid and precise measurement of the frequency. Frequency is still measured correctly
if voltage is only measured in one phase.
Current
The control unit performs three-phase true RMS current measurement.
Real power
The control unit performs three-phase true RMS power measurement. This is accomplished by real-time mul-
tiplication of the wye voltage and instantaneous conductor current values (three-phase measurement) or the
phase voltage VL12 and the current IL1 (single-phase measurement).
Re-active power
The control unit performs single-phase true RMS re-active power measurement, which is calculated from ap-
parent power and active power.
Power factor
Power factor is determined as a time measurement between the filtered measured values of the voltage VL12
and the conductor current IL1.
Real energy
The positive real energy is integrated with a time measurement. The counter is controlled in the non-volatile
memory and has reverse counting protection. The data is saved in three-minute time frames with a resolution
of 1 Watt-hour. The display automatically updates the measured units when required to go to a larger refer-
ence. This permits the control unit to count up to 4,290 GWh. The counter is not PTB-calibrated.
Functional Range
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
The unit contains of the following features dependent upon the model:
PSVX+Q
Common features
1× ready for operation relay Standard
4(2) *× control relays (N.O. contact) Standard
7× freely configurable relay outputs (N.O. contact) Standard
2× three-position controller for n/f/V/P, power factor Standard
2× three-position controller for n/f/V/P, power factor and 2 analog controller for n/f/V/P/Q and PWM outp. Q
10(8) *× discrete control inputs * Standard
12× discrete alarm inputs Standard
7× analog inputs
1× analog input for mains real power (instead of current transducer)
2× analog outputs Standard
1× kWh pulse output Standard
1× kvarh pulse output Standard
Password system Standard
Configuration via PC and DPC cable possible (direct configuration) Standard
CAN bus interface Standard
Event recorder with real-time clock
Language manager for message texts Standard
Ignition speed relay function Standard
Running hours counter Standard
Maintenance call counter Standard
Start counter Standard
kWh- and kvarh counter Standard
Protection functions
Over-/undervoltage protection (2step), generator Vgen>/< Standard
Over-/undervoltage protection (1step), mains Vmains>/< Standard
Over-/underfrequency protection f>/< Standard
Voltage asymmetry protection Vas> Standard
dϕ/dt phase/vector jump protection dϕ/dt Standard
df/dt protection df/dt Standard
Reverse/reduced power protection +/-PGen< Standard
Overload protection PGen> Standard
Unbalanced load protection ΔP> Standard
Reactive power protection (loss of excitation) Q< Standard
Time-overcurrent protection Itime>/>> Standard
Inverse time-overcurrent protection, IEC 255 Iinv-time> Standard
Voltage restraint time-overcurrent protection IVtime> Standard
Ground fault protection Iearth> Standard
Battery monitoring VBat< Standard
* the lower number of control relays or inputs applies for units with one circuit breaker
PSVX+Q
Control/synchronization
Synchronization of 2 circuit breakers with V and f control Standard
Closing to a dead busbar (dead bus start) Standard
Voltage control Standard
Power factor control Standard
Speed/frequency control Standard
Real power control Standard
Mains interchange power control Standard
Load sharing Standard
var sharing Standard
Analog set point value for real power Standard
Analog set point value for power factor
Breaker logic "open transition" Standard
Breaker logic "closed transition" Standard
Breaker logic "soft loading" Standard
Breaker logic "parallel operation" Standard
Breaker logic "external" Standard
Remote control via interface Standard
Packages
MFR 3/PSVX+Q (7 analog inputs, event logger with real-time clock, setpoint value for cosϕ)
Chapter 2.
Electrostatic Discharge Awareness
All electronic equipment is static-sensitive, some components more than others. To protect these components
from static damage, you must take special precautions to minimize or eliminate electrostatic discharges.
1. Before performing maintenance on the electronic control, discharge the static electricity on your body to
ground by touching and holding a grounded metal object (pipes, cabinets, equipment, etc.).
2. Avoid the build-up of static electricity on your body by not wearing clothing made of synthetic materials.
Wear cotton or cotton-blend materials as much as possible because these do not store static electric
charges as much as synthetics.
3. Keep plastic, vinyl, and Styrofoam materials (such as plastic or Styrofoam cups, cup holders, cigarette
packages, cellophane wrappers, vinyl books or folders, plastic bottles, and plastic ash trays) away from
the control, the modules, and the work area as much as possible.
• Ensure that the device is completely de-energized (all connectors must be disconnected).
• Do not touch the electrical conductors, connectors, or components with conductive devices with your
hands.
• When replacing a PCB, keep the new PCB in the protective antistatic bag it comes in until you are
ready to install it. Immediately after removing the old PCB from the control cabinet, place it in the
protective antistatic bag.
CAUTION
To prevent damage to electronic components caused by improper handling, read and observe the pre-
cautions in Woodward manual 82715, Guide for Handling and Protection of Electronic Controls, Printed
Circuit Boards, and Modules.
Chapter 3.
Installation
CAUTION
A circuit breaker must be provided near to the device and in a position easily accessible to the opera-
tor. This must also bear a sign identifying it as an isolating switch for the unit.
NOTE
Connected inductive devices (such as operating current coils, undervoltage tripping devices, or aux-
iliary or power contacts) must be connected to a suitable interference suppressor.
Wiring Diagram
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
GND
[A2] Analog input 3 [T3]
IA 0/4 to 20 mA
Analog output
- Alarm input
0/4 to 20 mA
GND
[A1]
Control room
IA
Analog input 2 [T2]
SPS
PC
0/4 to 20 mA
- Setpoint: power factor
CAN-L
CAN-H
CAN bus interface
GND
Guidance level
74 75 76 77 78 79 80 81 82 83 37 38 47 48
Termination Relay [R7]
up to 14 additional generators
(each via one MFR 3)
Relay [R5]
Relaismanager
Analog input 5 [T5] Relay [R3]
Pt100
voltage
current
- Alarm input
PWM
DC
DC
Relay [R2]
GND
GND
PWM GND
Drive
SPEED / POWER
N/C
VA
GND
G
VA
6 7 33 34 35 36 60 61 62 63 64 65 66 67 68 69 70 71 72 73 18 19 43 44
Centralized alarm
Generator voltage L3
Generator voltage L2
3
Ready for operation
3/(4)
Generator voltage L1
NC
L1 Generator current L1
X2/S2 (L) x2/s2 (l) NO/#1
s2 (l) Alarm input [D07] 7
NC
NC
2 NO/#1
Operation mode selector locked NC
Command: open GCB
Alarm input [D01] or NO/#1
1
Mains decoupling via MCB NC
Common #2Battery
Mains voltage L1 N
0
Q Package
Control room
IA
Analog input 2 [T2]
SPS
PC
0/4 to 20 mA
- Setpoint: power factor
CAN-H
CAN bus interface
GND
Guidance level
74 75 76 77 78 79 80 81 82 83 37 38 47 48
Termination Relay [R7]
up to 14 additional generators
(each via one MFR 3)
Relay [R5]
Relaismanager
Analog input 5 [T5] Relay [R3]
Pt100
- Alarm input
Relay [R2]
lower SPEED / POWER
Drive
(three-position controller)
raise
or Relay [R1]
Analog controller output
50 51 52 27 28 39 40 16 17 53 54 23 24 41 42 14 15 3 4 25 26 29 30 31 32 20 21 22 11 12 13 8
(three-position controller)
raise
or
5 6 7 33 34 35 36 60 61 62 63 64 65 66 67 68 69 70 71 72 73 18 19 43 44
Analog controller output
Centralized alarm
Generator voltage L3
Generator voltage L2
3
Ready for operation
3/(4)
Generator voltage L1
2 NO/#1
Operation mode selector locked NC
Command: open GCB
Alarm input [D01] or NO/#1
1
Mains decoupling via MCB NC
Mains voltage L1 N
Subject to technical mocifications. 2005-10-10 | MFR 3 Packages Wiring Diagram r3ww-4105-ap.skf
Power Supply
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
9.5 to 32 Vdc
D1 = P600M
for 12 V DC systems C1 = 47,000 uF / 40 V
0 Vdc
2
C1 Power supply
9.5 to 32 Vdc
1
9.5 to 32 V DC (in normal operation)
D1 (min. 12 V DC to start)
N
0
Figure 3-3: Power supply
Measuring Inputs
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
NOTE
The three-phase system must have a dextrorotatory field (right-handed rotary field). If the unit is used
with a laevorotatory field (left-handed rotary field), the power factor measurement will not be correct.
Voltage
Generator
MCB GCB
L1
L2
L3
G
N
0 20 21 22
L3
L2
Generator voltage
L1
N
Busbar
MCB GCB
L1
L2
L3
G
N
Synchronous
23 24
L2
Busbar voltage
L1
Mains
MCB GCB
L1
L2
L3
G
N
50 51 52
L3
L2 Mains voltage
L1
NOTE
The mains voltage measuring inputs must be connected if the unit is used in mains parallel operation.
Current
CAUTION
Before disconnecting the secondary current transformer (CT) connections or the connections of the CT
at the device, make sure that the CT is short-circuited.
NOTE
Generally current transformers should be grounded on one side.
Generator
MCB GCB
L1
L2
L3
G
N
Detail:
Connection of the transducers
S2 S1
L.. G
s2 s1
s1 (k)
25 26 29 30 31 32
L3
s2 (l)
Generator
s1 (k) s1 (k) current
..
L.. L2
s2 (l) s2 (l)
..
Mains
S2 S1
MCB GCB
L1
G
s2 s1
L2
L3
N
s1 (k)
27 28
Mains current
L1
s2 (l) ../1A or ../5 A
Discrete Inputs
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
CAUTION
Please note that the maximum voltages which may be applied at the discrete inputs are defined as fol-
lows. Voltages higher than those specified will destroy the hardware!
Maximum input range: +/-18 to 250 Vac.
Control Inputs
+/-18 to 250 Vac/dc
Signal device
B A
Digital input
Reply CB 3
D C
Digital input
Positive Logic
B A
Discrete input
Negative Logic
Discrete input
Signal device
Analog Inputs
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
WARNING
The analog inputs of the MFR are not isolated. When using an isolation monitor, we recommend to use
two-pole, isolated transmitters.
The analog inputs for active transmitters (0 to 20 mA, 0 to 10V) should only be operated with two-pole,
isolated transmitters.
C B A
Analog input
Pt100 or Pt1000
only at Pt100
Ia
C B A
Analog input
GND
0/4 to 20 mA
Va
C B A
Analog input
GND
0 to 5 V, 0 to 10 V, 0 to 150 mV
C B A
Analog input
NTC, PTC, VDO
0 to 180/380 Ohm
Relay Outputs
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Control Outputs
max. 250 V AC
15 14
Command: close GCB
GCB
17 16
Command: close MCB
MCB
40 39
Command: open MCB
MCB
42 41
Command: open GCB
GCB
Relay Manager
max. 250 Vac
B A
Relay output
external device
Analog Outputs
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
IA
A
Analog output
0V
B
Figure 3-15: Analog outputs
Pulse Outputs
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Impuse output
B A
Open collector
Example
Impuse output
B A
Open collector
+
24 V DC
-
R > 1 kOhm
Impuse output
B A
V
Open collector
Controller Outputs
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
The controllers are configured in the standard version as three-position controllers (made up of a change-over
contact and a normally open contact]. With option Q these contacts can be used as different types of outputs de-
pending on the use of jumpers and the parameters selected.
9 10
Speed / power Lower
controller Higher
Speed / power
controller
Common
8
11 12 13
Voltage / power factor Lower
controller Higher
Voltage / power
factor controller
Common
Versions
Wiring of Controller
B A
Relay output
GND
9 10
GND
Governor
Current
Speed
Speed / power
N/C
controller
IA IA
8
GND
9 10
GND
Governor
Voltage
Speed
VA Speed / power
UA
controller
8
GND
9 10
GND
Governor
Speed
Speed / power
PWM
PWM PWM
controller
8
GND
11 12 13
GND
Current
Voltage / re-active
AVR
N/C
power controller
IA IA
GND
11 12 13
GND
Voltage
Voltage / re-active
AVR
UA VA
power controller
Interface
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Interface Wiring
Y1 Y2 Y3 Y4 Y5
Termination
GND
CAN-H
CAN-L
CAN bus
Interface
Figure 3-22: Interface - terminals
Wiring Description
Whether the terminals are designated X or Y depends on the configuration of the system. Please refer to the
wiring diagram (A = X/Y, B = X/Y, etc.)
all
A (X1) B (X2) C (X3) D (X4) E (X5)
[1] [1] GND CAN-H CAN-L CAN bus
[1]..can be used to loop the CAN bus or/and to connect the termination resistance.
0.01 µF
1 MOhm
400 Vac
NOTE
Please note that the CAN bus must be terminated at both ends with an impedance which corresponds
to the wave impedance of the cable (e.g. 120 Ohm). The Engine CAN bus is terminated between CAN-H
and CAN-L.
Terminal Terminal
CAN-L
CAN-L
CAN-L
CAN-L
CAN-H
GND
CAN-H
GND
CAN-H
CAN-H
GND
Termination
Termination
resistance resistance
Note:
The termination must be
effected with a resistor
which corresponds to the
wave impedance of the
used cable (e. g. 120 Ω )
If no data is transmitted on the CAN bus, check the following common reasons for CAN bus communication
problems:
The maximum length of the communication bus wiring is dependent on the configured Baud rate. Refer to Table
3-1 for the maximum bus length (Source: CANopen; Holger Zeltwanger (Hrsg.); 2001 VDE VERLAG GMBH,
Berlin und Offenbach; ISBN 3-8007-2448-0).
The maximum specified length for the communication bus wiring might not be achieved if wire of poor quality is
utilized, there is high contact resistance, or other conditions exist. Reducing the baud rate may overcome these is-
sues.
NOTE
To configure via the configuration interface (direct configuration) you need the configuration cable (or-
dering code "DPC"), the program LeoPC1 (delivered with the cable) and the corresponding configura-
tion files. Please consult the online help installed when the program is installed for a description of the
LeoPC1 program and its setup.
If the parameter "Direct config." is switched to ON, the communication via the interface on termin-
als X1-X5 is disabled.
Chapter 4.
Functional Description
Function
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Operating Conditions
Idle control: Generator voltage and frequency are adjusted to the configured set point values by raising and lo-
wering the controller outputs for voltage and speed/frequency as required.
Synchronization: Generator voltage and frequency are adjusted to the busbar values (synchronization GCB) or
to the mains values (synchronization MCB) by raising and lowering the controller outputs for voltage and speed
as required. The command to connect the appropriate circuit breaker is output with respect to the breaker connect
time so the breaker closes at the synchronization point.
Conditions
GCB is open [4]
Reply :
1 0 x x Idle control A
1 0 x x N/A B
1 1 x x Synchronization of the GCB C
0 x 1 1 Synchronization of the MCB D
0: "OFF" / 1: "ON" / x: signal has no significance (0 or 1)
Table 4-1: Operating conditions - idle control and synchronization
Voltage and frequency controllers as well as the synchronization can be switched ON or OFF by configuration.
Conditions Function
A Parameter "automatic idle control" is ON.
B Parameter "automatic idle control" is OFF.
C For the generator and for the busbar variables, the following must apply:
- 50 % Vset < voltage < 125 % Vset
- 80 % frated < frequency < 110 % frated
D For the busbar and for the mains variables, the following must apply:
- 50 % Vset < voltage < 125 % Vset
- 80 % frated < frequency < 110 % frated
- The "Command: GCB open" may not be apply.
Table 4-2: Operating conditions - idle control and synchronization - conditions
Dead bus start: Output of a connect command for the circuit breaker without synchronization.
Conditions
GCB is open [4]
Reply :
Condition Function
E The parameter "Dead bus start generator breaker" is ON and the generator voltage and fre-
quency are within the configured limits.
F The parameter "Dead bus start mains breaker" is ON and is valid for the mains values:
- 50 % Vset < voltage < 125 % Vset
- 42 Hz < frequency < 110 % frated
Table 4-4: Operating conditions - dead bus start - conditions
Isolated Operation
Isolated operation: Generator voltage and frequency are adjusted to the configured set point values by raising
and lowering the controller outputs for voltage and speed/frequency as required.
Conditions
GCB is open [4]
Reply :
An isolated operation only takes place if the generator frequency is greater than 42 Hz. Voltage control only
takes place if the generator voltage is at least 80 % of the secondary transformer rated voltage and the parameter
"Voltage controller isolated operation" is enabled. Voltage, frequency, and synchronization control may be
enabled or disable in the configuration menu.
NOTE
When using three-position controllers, these must be configured using the relay manager (see appen-
dix "Relay Manager").
Mains parallel operation: The controller outputs raise and lower speed/frequency and voltage to adjust real
power and power factor of the generator to the configured set point values.
Conditions
GCB is open [4]
Reply :
Mains parallel operation takes place only if the generator frequency is greater than 42 Hz. If during mains paral-
lel operation the generator frequency falls below 50 % of the rated value, the relay "Command: open GCB" is ac-
tivated.
Direction of Power
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
If the unit's current transformers are wired according to the pin diagram shown, the following values are dis-
played:
MAINS
MCB
mains circuit breaker
s2 (l) S2 (L)
27 P
pos
28 Q
s1 (k) S1 (K) ind
BUSBAR
MFR 3
GCB
generator circuit breaker
s2 (l) S2 (L)
25 P
pos
26 Q
s1 (k) S1 (K) ind
GENERATOR
G
Figure 4-1: Direction of power
Power Factor is defined as a ratio of the real power to apparent power. In a purely resistive circuit, the voltage
and current waveforms are instep resulting in a ratio or power factor of 1.00 (often referred to as unity). In an in-
ductive circuit the current lags behind the voltage waveform resulting in usable power (real power) and unusable
power (reactive power). This results in a positive ratio or lagging power factor (i.e. 0.85lagging). In a capacitive
circuit the current waveform leads the voltage waveform resulting in usable power (real power) and unusable
power (reactive power). This results in a negative ratio or a leading power factor (i.e. 0.85leading).
Inductive: Electrical load whose current waveform lags Capacitive: Electrical load whose current waveform
the voltage waveform thus having a lagging power fac- leads the voltage waveform thus having a leading pow-
tor. Some inductive loads such as electric motors have er factor. Some capacitive loads such as capacitor
a large startup current requirement resulting in lagging banks or buried cable result in leading power factors.
power factors.
+ (positive) - (negative)
lagging leading
The generator is …
a voltage lower "-" signal is output as long as the a voltage raise "+" signal is output as long as the meas-
measured value is "more inductive" than the reference ured value is "more capacitive" than the reference set
set point point
Example: measured = i0.91; set point = i0.95 Example: measured = c0.91; set point = c0.95
Phasor diagram:
inductive capacitive
Additional information can be obtained from the descriptions of the configuration screens.
Release 1
MCB (53/7)
Time/s
'Command: close 2 4
MCB' (16/17)
3
Time/s
'Reply: MCB is
open' (54/7)
Time/s
Connection time MCB
Shutdown: ON
Relay "Command: open GCB", logic: A (operating current; NO)
GCB continuous pulse: OFF
Additional information can be obtained from the descriptions of the configuration screens.
Release 1 5
GCB (3/7)
Time/s
'Command: close 2 4
GCB' (14/15)
3
Time/s
'Command: open 6 7
GCB' (41/42)
Time/s
'Reply: GCB is
open' (4/7)
Time/s
Connection time GCB
Between 5 and 6 the power is reduced. When the power is close to zero, the GCB is opened.
Influence
Kpr Tn Tv Tt Kp T1
quantity
If an abrupt disturbance variable is applied to the control loop, the reaction of the controlled system can be rec-
orded at the output as a function of time (step response).
x
xm
Tolerance band
xd
1
0
0 Trise Tsett t/s
Various values can be obtained from the step response; these are required for adjusting the controller to its opti-
mum setting:
Rise time Trise: The period of time starting when a control variable leaves its steady-state condition following a
disturbance variable being applied to it and ending the first time the value re-enters the new steady-state condi-
tion.
Transient time Tsett: The period of time starting when a control variable leaves its steady-state condition follow-
ing a disturbance variable being applied to it and ending when the value permanently re-enters the new steady-
state condition.
Overshoot xm: Highest transient deviation value during the transition from one steady-state condition to a new
steady-state condition following modification of the disturbance variable or reference input variable (xm Optimal ≤
10 %).
System deviation xd: Permanent deviation from the initial state value (PID controller: xd = 0).
By different conversions from these values, the values KPR, Tn and TV can be determined. Moreover, it is possi-
ble, by performing various calculations, to determine the optimal controller settings, e. g. by calculating compen-
sation or adjustment of the time constants, T-sum rule, symmetric optimum, Bode-diagram. Other setting proce-
dures and information may be obtained from current literature.
Controller Setting
CAUTION
The following must be observed regarding setting up the controller:
• Ensure that the emergency shutdown system is functional.
• While determining the critical frequency, monitor the amplitude and frequency.
• If either of the two values change uncontrollably:
EMERGENCY SHUTDOWN
Initial state: The start position of the controller is determined using the initial state of the controller. If the con-
troller is switched off, the basic setting can be used to output a fixed controller position. If the genset is not run-
ning, the controller automatically resets to the initial state.
General settings: The setting rule described below only serves as an example. Whether this method is suitable
for setting your particular controlled system has not been and cannot be taken into account as each controlled
system behaves uniquely.
There are various methods of setting a controller. The setting rules of Ziegler and Nichols are explained below
(determination for abrupt disturbances on the system input); this setting method assumes a pure lag element con-
nected in series with a first-order lag system.
CAUTION
If the engine starts to oscillate uncontrollably, perform an emergency shutdown and alter the screen
setting accordingly.
Step response
Controller setting Controller setting Uncontrolled oscillation of generator
Optimum (xm ≤ 10 %) Tcrit Controller setting wrong
x x x
1 1 1
0 0 0
0 t/s 0 t/s 0 t/s
Operating in mains parallel with mains interchange (import/export) real power control: Each controller
participating in load/var sharing controls the generator set that it is assigned so the real power set point at the
mains interchange remains constant. The real power set point for the mains interchange must be configured iden-
tically in each controller.
All controllers communicate via a CAN bus. This enables the controllers to adjust the real power generated by
the generator while remaining within the rated power of the generator. A smaller generator will contribute less
real power as compared to a large generator, but they will both be utilized to the same capacity factor. An exam-
ple of this would be a 100KW generator and a 1000KW generator and a mains interchange of 825KW. The
100KW generator would contribute 75KW and the 1000KW generator would contribute 750 KW or both genera-
tors would be at 75% of their rated capacity.
No reactive power sharing is performed when operating in parallel with the mains. The reactive power will be
defined by the configured power factor set point of the individual controllers.
The parameter "kW/kvar sharing: reference variable kW" can be used now to define the priority of the reference
variable (real power at interchange) for real power sharing. A higher percentage influences the control more to-
wards the real power set point for the interchange. A lower percentage influences the control more towards real
power sharing.
The parameter "kW/kvar sharing: reference variable kvar" has no influence here.
Isolated operation in parallel: Each controller participating in load/var sharing controls the generator set to
which it is assigned in such a manner that the set frequency and the set voltage at the bus remain constant. This
makes it imperative that the same frequency and voltage set points are configured for each controller.
All controllers communicate via a CAN bus. This enables the controllers to adjust the real power generated by
the generator while remaining within the rated power of the generator. A smaller generator will contribute less
real power as compared to a large generator, but they will both be utilized to the same capacity factor. An exam-
ple of this would be a 100KW generator and a 1000KW generator and a load of 825KW. The 100KW generator
would contribute 75KW and the 1000KW generator would contribute 750 KW or both generators would be at
75% of their rated capacity.
The reactive power will be allocated in a way that it is the same for all generators involved.
The parameter "kW/kvar sharing: reference variable kW" can be used now to define the priority of the reference
variable (frequency) for real power sharing. A higher percentage influences the control more towards frequency
control. A lower percentage influences the control more towards real power sharing.
The parameter "kW/kvar sharing: reference variable kvar" can be used now to define the priority of the reference
variable (voltage) for reactive power sharing. A higher percentage influences the control more towards voltage
control. A lower percentage influences the control more towards reactive power sharing.
Reverse synchronization of the busbar to the mains: Distribution is carried out according to the type of iso-
lated operation. The set point value for the bus frequency is determined by the mains frequency + dfmax/2.
Example: If dfmax = 0.2 Hz, this results for dfmax/2 = 0.1 Hz (i.e. in a system of 50 Hz, the busbar will be raised to
50.1 Hz).
Pre-requisites: It is imperative that the rated system frequencies (page 64) and the circuit breaker logic
(page 88) are set identically for all units participating in load/var sharing.
Description of the interface for load/var sharing: Load/var sharing is based on a multi-master-capable bus be-
tween the controls. This structure enables the parallel operation of up to 14 generators.
The following must be noted to ensure trouble-free operation of the CAN bus:
1. The maximum CAN bus length must not exceed 250 meters.
2. The CAN bus must be terminated at each end with terminating resistors that correspond to the wave im-
pedance of the CAN bus cable (approx. 120 ohm).
3. The CAN bus must be of a linear structure. Dead-end feeders are not permissible.
4. The recommended cable for use as the CAN bus cable is a "Twisted-shielded-pair" (Ex.: Lappkabel Uni-
tronic LIYCY (TP) 2×2×0.25, UNITRONIC-Bus LD 2×2×0.22).
5. The CAN bus cable must not be routed in the vicinity of high current power lines.
Frequency control is carried out via the measured voltage/frequency of the voltage system.
f actual [Hz]
P actual [kW]
f set
n actual [min-1]
Leading value 10..99 [%]
10 % = only P control
99 % = only f control
Σ P nominal (via CAN)
P diff [%]
Calculation
P actual [kW]
P Utilization factor of this engine [%]
Σ P actual (via CAN)
Calculation
P nominal [kW] 2001-08-06 Leistungsverteilung Blockschaltbild.skf
Language Manager
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
NOTE
Please also note the parameters to this option in chapter Language Manager at page 56.
In order to load a different language into the unit, please proceed as follows:
1. Establish a connection between your PC and the unit via the direct configuration cable (DPC) or via a Ga-
teway GW 4. To do this, connect the serial cable end to the COM port of your PC and insert the RJ45
plug in the socket on the side of the unit.
2. Enter the password for code level 2 into the unit. Also read chapter Password Protection at page 59.
3. Scroll down through the display to the configuration screen "load language".
5. Scroll down only until you reach the configuration screen "language number" and select the base language
in which you enter "0".
6. Enter in the "number of tool" screen the numbers (1 to 8) with which you operate the MFR via LeoPC1.
These numbers are identical to the unit numbers.
7. Now start the LeoPC1 and load the corresponding configuration file. Ensure, that direct configuration is
selected in the device settings in LeoPC1 and the connection between device and LeoPC1 has been
started.
8. Open the "Load Language" window and load the desired language file.
9. Go to the "Which texts have to be transferred?" area and select "All texts". Next click on the "Transfer
language" button to start loading the file into the control unit.
10. If, after transmission of the first language an additional language is to be loaded, the SECOND language
must be selected in the configuration screen "Sprache/language" of the unit or enter a "one" in the "Lan-
guage number" screen. Next repeat steps 6 through 9.
11. It is also possible to load a language via the CAN interface. If this method is utilized, the direct configura-
tion port is disabled in the device and the data communication settings in LeoPC1 must be changed to
CAN.
Alarms
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Alarm Class
The monitoring functions are divided into four alarm classes:
F0 - Warning alarm - This alarm does not lead to an interruption of the operation. An alarm message is dis-
played without a centralized alarm.
Alarm text.
F1 - Warning alarm - This alarm does not lead to an interruption of the operation. An alarm message is dis-
played and a centralized alarm will be output.
Alarm text + flashing LED "Alarm" + Relay "Centralized alarm" (horn).
F2 - Triggering alarm - This alarm leads to a soft shutdown. A power reduction is performed prior to the GCB
being opened. A cool down period is also carried out.
Alarm text + flashing LED "Alarm" + Relay "Centralized alarm" (horn) + cool down.
F3 - Triggering alarm - This alarm leads to the immediate opening of the GCB and a hard shutdown.
Alarm text + flashing LED "Alarm" + Relay "Centralized alarm" (horn) + immediate shutdown.
Alarm Acknowledgement
By pressing the "ACK" push button, the output of the centralized alarm and the alarm messages on the LC dis-
play are acknowledged according to the following logic:
Horn: After 2 minutes the horn is reset regardless of the acknowledgement of an alarm.
Interface: All internal alarms are communicated via the interface.
NOTE
The control unit does not differentiate between short and long alarm acknowledgements when given
through the interface. As soon as the acknowledgement bit is enabled via the interface, a "Long ac-
knowledgement" will be performed. A "Short acknowledgement " via the interface is not possible.
Action
• The "ACK" push-button is pressed for 0.5 s < t < 2.5 s
• The terminal 36 is energized for 0.5 s < t < 2.5 s
Result
The "Alarm" LED changes from blinking to continually illuminated and the horn is silenced.
Acknowledgment via …
Operating mode "ACK" button terminal 36 interface input
AUTO possible possible not possible
MANUAL possible not possible not possible
Table 4-8: Alarms - short acknowledgment
Action
• The "ACK" push-button is pressed for > 2.5 s
• The terminal 36 is energized for t > 2.5 s
• The acknowledge bit is enabled via the interface
Result
An alarm cannot be acknowledged if the fault condition still exists. If the fault condition is no longer
present:
• The "Alarm" LED turns off
• The F1, F2 and F3 alarm relays are reset
• The display messages are acknowledged
Acknowledgment via …
Operating mode "ACK" button terminal 36 interface input
AUTO possible possible possible
MANUAL possible not possible not possible
Table 4-9: Alarms - long acknowledgment
Chapter 5.
Display and Push-Buttons
The pressure-sensitive membrane of the front panel consists of a plastic coating. All keys have been designed as
touch-sensitive membrane switch elements. The display is an LC display, comprised of 2 lines with 16 characters
each, which are indirectly illuminated in red. The contrast of the display can be infinitely adjusted via a rotary
potentiometer positioned on the left side. The configuration plug is located on the left side of the unit. The direct
configuration cable (DPC) connects there.
2 V2 6 8 28
3 V3 7 9
Stop Operating and Alarm Messages
Automatic Manual Monitoring
5
14
10 ON Mains Parallel
13
11 12
MAN AUTO
Setpoint Setpoint
29 ACK
30
15 16 17 18 21 23 24 25 26 27
2 V2 6 8 28
3 V3 7 9
Operating and Alarm Messages
Automatic Manual Monitoring
5
14
10 ON ON
13
11 12
MAN AUTO
Setpoint Setpoint
29 ACK
30
15 16 17 18 19 20 21 23 24 25 26 27
Push-Buttons
No. Description Function
12 Message↓ Route messages
12 Select Confirm selection
13 Display V↓ Route voltage display
13 Digit↑ Increase digit
14 Set point Activate set point value
14 Cursor→ Move cursor one position right
15 Set point↑ Increase MANUAL set point value
16 Set point↓ Decrease MANUAL set point value
17 GCB ON Close GCB manually
18 GCB OFF Open GCB manually
19 MCB ON Close MCB manually
20 MCB OFF Open MCB manually
21 MAN Select operating mode MAN
23 LED TEST Execute LED test
24 ACK Acknowledge alarm messages
25 AUTO Select operating mode AUTOMATIC
26 Set point↑ Increase AUTO setpoint value
27 Set point↓ Decrease AUTO setpoint value
Miscellaneous
No. Description Function
28 LC display LC display
29 DPC plug Configuration plug
30 Potentiometer Adjust LCD contrast
LEDs
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
1 V1 - V2 - V3 Voltage control
2 Color: Green
3 The LED's "V1", "V2" and "V3" show which voltage (VL1N, VL2N, VL3N,
VL12, VL23 or VL31) is currently being displayed. This applies both to the ge-
nerator and the mains voltage display.
Generator 88 to 112 % fN
Mains 96 to 104 % fN
8 Monitoring Monitoring
Color: Green
If the "Monitoring" LED is illuminated, monitoring is enabled. The delayed
programmed alarm inputs are monitored in addition to the permanently mo-
nitored alarm inputs. Generator underspeed, underfrequency, undervoltage
and reverse power are also monitored.
9 Alarm Alarm
Color: Red
The unit has detected an alarm condition when the "Alarm" LED is illumi-
nated. The control unit reacts according to the alarm class. The alarm mes-
sage is shown in the LC display. If the alarm LED is flashing, a new alarm
condition has occurred within the last two minutes. By performing a short
acknowledgment, the alarm LED changes to continuous illumination and the
centralized alarm (horn) is terminated.
Push-Buttons
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
In order to facilitate configuring the parameters, the push buttons have an AUTOROLL function. It permits the
user to advance to the next setting, configuration screen, the digit, and/or cursor position by pressing and holding
the corresponding push button.
General / Configuration
12 Message↓ / Select Message↓ / Select
Color: Blue
Normal operation: Message↓ - By pressing this push button, the user my
advance through the operating and alarm messages.
Configuration: Select - The user advancesto the next configuration screen
by pressing this button. If the original displayed value has
been changed by pressing either the "Digit↑" or "Cursor→"
push buttons, the new value is saved by pressing the "Select"
push button once. By pressing this push-button again, the user
causes the system to display the next configuration screen.
NOTE
It is possible to block the MANUAL and AUTOMATIC operation mode push buttons by enabling the dis-
crete input [D02] (terminal 63), preventing the operating mode from being changed.
24 ACK Acknowledgment
Color: Blue
Alarm messages are acknowledged pressing the "ACK" push button. The
alarm messages on the LC display are cleared and the "Alarm" LED will
darken. The display is reset to the basic screen. Class F2 and F3 alarms can
only be acknowledged in the MANUAL operation mode. Refer to Alarm
Acknowledgement on page 45.
LC Display
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
28 LC display LC display
NOTE
Using push-button "Display V↓" the voltages can be displayed.
NOTE
The bottom line can be scrolled using the "Message↓" push button. It is also possible, to scroll
through any alarms that may be present using the "Message↓" push button.
These screens are displayed in succession by pressing the "Message↓" push button. When the last screen has
been reached, the basic screen is displayed. If alarms have occurred, the related message texts are displayed in
the sequence of their occurrence prior to the basic screen. If unit functions are active (e.g. synchronization of the
GCB), the basic screen is superimposed with the corresponding message (e.g. " synchronization"). Following the
termination of the unit function, the basic screen is displayed again.
NOTE
It is possible to scroll through any alarms that may be present using the "Message↓" push-button.
Chapter 6.
Configuration
Configuration can be performed via the front panel push buttons and LC display or using a PC and the LeoPC1
program with the serial interface. Additionally it is possible to configure the unit via CAN bus. The following
baud rates apply to each method:
CAUTION
Please note that configuration only should be performed when system is not operating.
Generator voltage must not be connected during configuration and the DI "Configuration blocked"
(terminal 34) must be de-energized.
Code level 2 access is required to select between direct configuration or configuration via CAN.
NOTE
Refer to Appendix B for a complete list of parameters at the end of this manual.
Introduction
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
The configuration screens have an AUTOROLL function when you are in configuration mode (simultaneously
pressing "Digit↑" and "Cursor→"). If the "Select" button is pressed and held, the scroll function will be activated
and the user will be able to rapidly advance through the parameter screens. It is possible to back-up four configu-
ration screens (exception: the break from the first to the last screen is not possible). To do this, simultaneously
press and release the "Select" and "Cursor→" buttons. If an action, entry, or modification, is not performed with-
in 60 seconds, the unit reverts to the automatic mode.
NOTE
There are two different hardware versions described in this manual: A 100 Vac version [1] and a
400 Vac version [4]. The two versions vary as far as the configuration screens, the input of the parame-
ters and the setting limits are concerned. The respective voltage values ([1]... or [4]...) are placed first to
differentiate the two types.
Basic Data
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Language Manager
Parameter 1 Language first/second
Sprache/language
---------------- first ...............All texts are displayed in the base/first language.
second...........All texts are displayed in the second language.
NOTE
Please also note chapter "Direct Configuration" on page 63.
Version Number
Parameter 6 Software version
Software version
Vx.xxxx Display of the current software version.
Service Display
Parameter 7 Service display ON/OFF
Service display
ON ON................ The following three screens are displayed:
• the generator and busbar voltages and frequencies
• the mains and busbar voltage and frequencies
• the controller breaker and relay statuses during synchronization
The specific displayed values are dependent upon the control unit
hardware.
OFF.............. The service display is disabled.
Password Protection
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
The unit is equipped with a three-level code and configuration hierarchy. This permits multiple levels of access
to configuration screens for different users. A distinction is made between:
NOTE
Access codes remain active for two hours after the last action is performed, even if the configuration
mode is accessed repeatedly. If an incorrect password is entered, the control unit reverts to code level
CS0 and external users are blocked from accessing the unit (setting of password on page 72). The de-
sired code level may be accessed again by entering the correct password for that code level.
Event Recorder
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
NOTE
The viewing and acknowledgment of alarms depends on access authorization:
# # #
Viewing of alarms Access authorization CS 0, CS 1 and CS 2
#
Acknowledgment of alarms Access authorization CS 2
#
CS = code level (see chapter "Alarm Class" on page 44.
If an alarm occurs in the unit, an entry into the event log is made. The following information is supported/stored:
Event
Date of occurrence
Time of occurrence
The event recorder stores the last 50 alarms in a FIFO (First In First Out) format, beginning with the most recent
event. By pressing the "ACK" push button, the displayed alarm condition is deleted from the event recorder. The
alarms are displayed on two lines. The top line indicates the date and time of the alarm occurred; the lower line
shows the type of alarm.
Analog Inputs
The name of the analog input is moved to the right according to the number of letters of the operating mode type.
The alarm type is written in the space that has become open.
WR Wire break
AL Limit 1
STOP Limit 2
Direct Configuration
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
NOTE
To carry out direct configuration, you require a direct configuration cable (order code "DPC"), the
LeoPC1 program (supplied with the cable) and the corresponding configuration files. After the program
has been installed, consult the online help utility for a description of the PC program and its setup.
Remote configuration: For remote configuration, the CS2 password must be entered via the parameter "pass-
word DPC", otherwise the values can only be read and not written. If the unit is at the CS0 pass code level it will
only permit the user to read the parameters. The control unit will not permit the user to modify any of the para-
meters. When the CS2 pass code is entered via LeoPC1 through the CAN bus, configuration of the unit will only
be able to be performed through the CAN bus. The pass code level will change back to CS0 after 2 hours of inac-
tivity, at which point the pass code will have to be entered again to modify any parameters. The password must
be input prior to loading a language file. If the CS2 password is entered directly into the control unit, configura-
tion via the CAN bus is automatically enabled.
NOTE
The direct configuration via LeoPC1 and the configuration using the control panel are independent of
each other and must be unlocked independent of each other. Unlocking the access via the control pan-
el does not permit a configuration via LeoPC1 and the other way round.
CAUTION
If the following parameter "direct para." is configured to "YES", communication via the CAN bus (ter-
minals X1 to X5) is disabled. If communication is to be re-established via the CAN bus after the unit is
configured (e.g. CAN bus connection to a Gateway GW 4), "Direct para." must be set to "NO"!
Direct configuration is disabled once the firing speed has been reached. This means that if further mo-
fifications to the control unit's parameters is desired, the only possible methods to do this is using the
display and push buttons manually or via the CAN bus interface. The parameter "Direct para." is auto-
matically changed from YES to NO (this is a function of the control unit software). The direct configura-
tion function is de-activated for safety reasons. This is to prevent the possibility of a simultaneous ge-
nerator start up and closing of circuit breakers to a dead bus in a multiple generator system (e.g.
emergency power situation).
Basic Settings
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
CAUTION
Failure to ensure correct configuration of parameters may lead to incorrect measurements and the con-
trol failing to respond properly!
CAUTION
If the following parameter values are modified, the values of the following parameters must be verified:
• generator voltage set point (at page 66)
• voltage controller dead band (at page 77)
• synchronization dVmax (at page 91)
• dead bus start GCB dVmax (at page 93)
• generator overvoltage tripping value (at page 109)
• generator undervoltage tripping value (at page 110)
Parameter 16 PTs. primary, generator [1] 0.005 to 65,000 kV; [4] 0.020 to 65,000 kV
Gen.volt.transf.
primary 00.000kV The primary voltage is set here in kV. This entry serves to indicate the primary vol-
tages in the display. If a potential transformer is not used, the measured voltage of
120V would be configured as "00.120kV" and 480V would be configured as
"00.480kV".
Parameter 18 PTs, primary, busbar [1] 0.005 to 65,000 kV; [4] 0.020 to 65,000 kV
Bus.volt.transf.
primary 00.000kV The primary voltage is set here in kV. This entry serves to indicate the primary vol-
tages in the display. If a potential transformer is not used, the measured voltage of
120V would be configured as "00.120kV" and 480V would be configured as
"00.480kV".
CAUTION
If the following parameter values are modified, the values of the following parameters must be verified:
• mains overvoltage tripping value (at page 112)
• mains undervoltage tripping value (at page 112)
Parameter 20 PTs, primary, mains [1] 0.005 to 65,000 kV; [4] 0.020 to 65,000 kV
Mains volt.trans
primary 00.000kV The primary voltage is set here in kV. This entry serves to indicate the primary vol-
tages in the display. If a potential transformer is not used, the measured voltage of
120V would be configured as "00.120kV" and 480V would be configured as
"00.480kV".
CAUTION
If the following parameter is configured to "singlephase" a phase/vector jump monitoring is not possi-
ble.
Generator Current, CT
NOTE
The following parameter is only available for units with a software version of 3.4006 or higher. Units
with a lower software version use the internal value “3”.
Example:
S = UGNPRIM * IGNPRIM * √3 = 10 kV * 200 A* √3 = 3,46 MVA
If this parameter is configured to "3" (default), the power format is 00.0 MW, if it is configured to "4", it is
0000 kW.
NOTE
If this parameter is configured for a higher resolution (higher value), large values (above the calculated
apparent power) might be displayed incorrectly. However, this parameter does not affect the monitor-
ing functions.
NOTE
When producing positive real power, a positive real current flows in the "k to l" direction in the current
transformer. Positive re-active power means that with a positive effective direction, inductive re-active
(lagging) current flows in the effective direction. If the unit is connected to the terminals of a generator
and the outgoing circuits of the current transformer facing the generator are connected to "k", the unit
shows a positive real power when the generator supplies real power. Refer to the "Direction of Power"
section on page 34.
Change Passwords
NOTE
Once the code level is entered, access to the configuration menus will be allowed for two hours after
the last function is performed or until another password is entered into the control. If a user needs to
exit a code level then code level CS0 should be entered. This will block any configuration of the con-
trol. A user may return to CS0 by allowing the entered password to expire after two hours or by chang-
ing any one digit on the random number generated on the password screen and entering it into the
unit. If power to the unit is cycled off, the unit starts up in CS0.
Controller
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
CAUTION
Entering incorrect values can lead to the control unit failing to function properly and destroy the gene-
rator!
NOTE
The fixed-value power controller does not monitor the mains interchange point. If excess power for the
load requirements is generated, the excess power is exported to the mains. If insufficient power for the
load requirements is generated, remaining power required is imported from the mains.
Frequency Controller
Parameter 37 f controller: initial state 0 to 100 %
Initial state
Frequency 000% This value is the initial state or start value for the frequency controller when the
control unit is not operating or changing from a real power controller to a frequen-
cy controller. This value relates to Parameter 46 "F/P contr. output".
NOTE
The following settings in the n/f controller area affect the P controller.
NOTE
The control logic of the PWM signal can be inverted by the following steps:
- Select "F/P contr.type" = ANALOG
- Select with parameter "F/P contr.output" any of the listed inverted control outputs
(10 to 0mA, 20 to 0mA, 20 to 4mA, 5 to 0V, 4.5V to 0.5V, or 10 to 0V outputs)
- Back-up one screen to "F/P contr.type" (by pressing "Select" and "Cursor→" simultaneously)
- Select "F/P contr.type" = PWM
Now the PWM signal is inverted.
Voltage Controller
Parameter 51 V controller: initial state 0 to 100 %
Starting point
voltage 000% This value is the intial state or start value for the frequency controller when the
control unit is not operating or changing from a power factor controller to a voltage
controller. This value relates to Parameter 57 "V/Q contr. output".
NOTE
The following settings in the V controller area affect the power factor (cosphi) controller.
Parameter 54 V controller: dead band [1] 0.1 to 15.0 V; [4] 0.5 to 60.0 V
Volt.controller
dead band 00.0V Isolated operation The generator voltage set point is controlled in such a manner,
that in a steady state, the actual value does not deviate from the gene-
rator voltage set point by more than the configured dead band value.
Synchronization The generator voltage is controlled in such a manner , that in its
steady state, the differential voltage does not exceed the configured
dead band value. The mains or busbar frequency is used as the set
point value.
Parameter 62 Power factor controller: internal set point value i0.70 to 1.00 to c0.70
Pow.fact.contr.
setpoint 0.00 When operating in mains parallel, the control regulates the re-active power in a
manner that results in the generator producing power at the power factor confi-
gured here. The designation "i" equals inductive (generator overexcited/leading)
and "c" capacitive (generator underexcited/lagging) re-active power. This set point
is enabled only in mains parallel operation.
NOTE
Please note the configured settings for the voltage controller (refer to Voltage Controller on page 77).
The settings for the voltage controller also affect the power factor controller.
Parameter 63 Power factor set point: external set point value ON/OFF
Power factor
external ON ON ................The power factor set point 2 value may be enabled via an external
signal. The subsequent screens of this function are displayed. This set
point 2 is enabled when terminal 5" ("Setpoint 1↔2) is energized.
OFF ..............If this function is configured as "OFF", the control unit utilizes set
point 1 only. The external set point value specification cannot be car-
ried out via the 0 to 20 mA input. The subsequent screens of this
function are not displayed.
Parameter 65 Power factor set point: minimum value i0.70 to 1.00 to c0.70
Ext. Pow.Factor
0mA 0.00 The minimum value of the power factor is defined here (e.g. i0.95).
Parameter 66 Power factor set point: maximum value i0.70 to 1.00 to c0.70
Ext. Pow.Factor
20mA 0.00 The maximum value of the power factor is defined here (e.g. c0.95).
Power Limitation
CAUTION
The interchange power set point (import/export power) can be scaled. When controlling interchange
power, it is vital to ensure that a constant power setting is not configured simultaneously with an Im-
port or Export power setting when scaling the external analog input.
Load/var Sharing
Parameter 88 Load sharing ON/OFF
Active power
load share ON ON ................Real power is shared between all generators operating in parallel.
The power output by each generator is dependent upon the indivi-
dually configured values. The subsequent screens of this function are
displayed.
OFF ..............Load sharing is not carried out, and the subsequent screens of this
function are not displayed.
Interface
Breaker
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Parameter 93 Configure breakers YES/NO
Configure
Breaker YES Various groups of parameters are grouped together in blocks to aid in the rapid na-
vigation through the large number of configuration screens. Selecting "YES" or
"NO" does not determine if control or monitoring is performed. The user’s selec-
tion has the following effect:
YES ..............The configuration screens in this block are displayed and can either
be viewed ("Select" push button) or modifications can be made to the
parameters ("Cursor→", "Digit↑" or "Select" push buttons). This
does not disable or enable individual parameters, only if the individ-
ual parameters in this parameter block may be accessed for modifica-
tions.
NO ................The parameters in this block are not displayed, cannot be modified
and are therefore skipped.
Breaker Logic
Parameter 94 Breaker logic see below
Breaker logic:
---------------- The unit automatically controls the two breakers (MCB and GCB). Up to five (5)
breaker logic modes may be selected from. These are: EXTERNAL and
PARALLEL for MFR-31 & MFR-32, and OPEN TRANSIT, CLOSED TRANSIT,
and INTERCHANGE for MFR-32.
NOTE
For a dead bus start it is necessary to enable the dead bus start function. To trigger the watchdogs
"generator underfrequency" as well as "generator undervoltage", terminal 6 (enable monitoring) must
be energized. It is possible to switch the breaker logic by energizing and de-energizing discrete input
[D03] (terminal 64). The second breaker logic may be configured during the configuration of the dis-
crete inputs. When discrete input [D03] is energized, the second breaker logic is enabled.
Logics
CAUTION
Following table is valid only if Parameter 241 "Download and open GCB" is configured "ON".
The MCB and the GCB can be manually opened and closed without All breaker control must be carried out via a master controller (e.g. a
synchronization. The circuit breakers are opened for decoupling PLC). The MFR 3 issues the breaker open commands under fault
from the mains. conditions.
Mains parallel operation can be initiated by pressing the "GCB ON" By energizing terminal 3 "Enable GCB", the GCB is synchronized
or "MCB ON" push-button. or closed to the dead busbar without synchronization and the gene-
rator initiates a mains parallel operation. When terminal 3 is de-
energized, the generator performs a power reduction and opens the
GCB.
The source of power can be changed from either the mains or gene- When terminal 3 "Enable GCB" is energized, the system changes to
rator without synchronization by pressing the "GCB ON" or "MCB generator operation. When terminal 3 "Enable GCB" is de-
ON" push-button. energized, the system changes back to mains operation. If termin-
al 53 is not energized, the MCB remains closed even if the busbar is
voltage-free - terminal 53 "Enable MCB" must be energized.
Via the "GCB ON" and "MCB ON" push-button, synchronization to The GCB is synchronized and closed via a signal "Enable GCB"
either generator or the mains operation is performed. (terminal 3 energized). The MCB is then opened. Following disabl-
ing the "Enable GCB" signal, the MCB is reverse synchronized and
closed. The GCB is then opened.
By pressing either the "GCB ON" or "MCB ON" push button, syn- When terminal 3 "Enable GCB" is energized, the GCB is synchro-
chronization to either generator or mains operation can be carried nized and the generator assumes load until a mains interchange
out. The power controller must be enabled. If during an interchange power = 0 kW is reached. The MCB is then opened. When termin-
synchronization "zero" import power is not achieved within the al 3 "Enable GCB" is de-energized, the MCB is reverse synchro-
configured time, a message and a class 1 alarm are issued. nized, the generator performs a power reduction, and the GCB is
then opened.
Parameter
Add-off: The maximum amount of time the generator has to shed load below 3%
of the generator load rating (Parameter 28) is configured here. If the generator has
not dropped below 3% of the generator load rating within this time period, the
GCB is opened.
Add-on with soft loading: If the mains interchange (import/export) real power
value does not reach 0kW in breaker logic "INTERCHANGE" within the time con-
figured here, a class F1 alarm and an alarm message are issued. In addition, the re-
lay manager relay programmed with relay manager function 93 (Appendix E) is
enabled and the MCB is prevented from opening.
Parameter 96 Max. permissible time with F2 prior to open the GCB 0 to 999 s
GCB open at F2
max.time 000s Prerequisite: Load sharing and automatic start/stop are configured "ON". The gene-
rator is in isolated operation and at least one additional generator is connected to
the busbar.
If a class F2 alarm occurs, shutting the generator down is delayed by the time con-
figured here. This gives another generator the opportunity to start and assume the
load. The generator is shut down when this time expires.
In both cases, the "Command: open GCB" relay energizes to open the breaker.
Synchronization
Parameter 99 Synch.: max. permissible differential frequency (pos. slip) 0.02 to 0.49 Hz
Synchronize
df max 0.00Hz This is the upper frequency differential limit for synchronization. The prerequisite
for a breaker closure command is that the positive frequency differential be lower
than the configured value. A positive value corresponds to positive slip. This
means that the generator frequency is higher than the busbar frequency for syn-
chronizing the GCB or the bus bar frequency is higher than the mains frequency for
synchronizing the MCB.
Parameter 100 Synch.: max. permissible differential frequency (neg. slip) 0.00 to -0.49 Hz
Synchronize
df min -0.00Hz This is the lower frequency differential limit for synchronization. The prerequisite
for a breaker closure command is that the negative frequency differential be lower
than the configured value. A negative value corresponds to negative slip. This
means that the generator frequency is lower than the busbar frequency for synchro-
nizing the GCB or the bus bar frequency is lower than the mains frequency for syn-
chronizing the MCB.
NOTE
The MCB is never opened except in a mains failure function.
Parameter 109 Dead bus start: max. permissible differential frequency GCB 0.05 to 5.00 Hz
GCB dead bus op.
df max 0.00Hz The prerequisite to issuing a close command is that the monitored generator fre-
quency does not deviate from the generator rated frequency by more than the value
configure here.
Parameter 110 Dead bus start: max. perm. differential voltage GCB 00.1 to 20.0 %
GCB dead bus op.
dV max 00.0% The prerequisite to issuing a close command is that the monitored generator voltage
does not deviate from the generator rated voltage by more than the percentage con-
figure here.
Parameter 111 Dead bus start: max. time to close the GCB 0 to 999 s
GCB dead bus op.
max.time 000s If the GCB is to be closed onto a dead busbar, this timer is initiated at the start of
the breaker closing sequence. If the breaker fails to close before the configured
time expires, a class F1 alarm is issued.
Tripping of class F1 alarm
Breaker Monitoring
Parameter 113 Breaker monitoring GCB ON/OFF
Supervision GCB
ON ON ................Monitoring of the GCB is performed (except in the "EXTERNAL"
CB logic). If the circuit breaker cannot be closed by the fifth attempt,
the relay manager function 89 relay is energized and a class F1 alarm
and message are issued. The control unit continues to attempt to
close the GCB. If, 2 seconds following a "Command: open GCB"
pulse, the "Reply: GCB is open" is detected, the relay manager func-
tion 91 relay is energized and an alarm message is displayed. If the
generator is load sharing, the add-on command is deleted so that
another control can close the breaker.
Tripping of class F1 alarm
OFF ..............Monitoring is not performed.
Mains Decoupling
If the application the control unit is being configured for is an isolated system, this configuration screen and its
settings do not apply. If the application is a single-breaker unit in a mains parallel operation, the GCB is confi-
gured as always open.
NOTE
The "Blocking of mains protection" input (terminal 61) disables mains monitoring and decoupling.
Protection
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Parameter 117 Configure monitoring YES/NO
Configure
Monitoring YES Various groups of parameters are grouped together in blocks to aid in the rapid na-
vigation through the large number of configuration screens. Selecting "YES" or
"NO" does not determine if control or monitoring is performed. The user’s selec-
tion has the following effect:
YES .............. The configuration screens in this block are displayed and can either
be viewed ("Select" push button) or modifications can be made to the
parameters ("Cursor→", "Digit↑" or "Select" push buttons). This
does not disable or enable individual parameters, only if the individ-
ual parameters in this parameter block may be accessed for modifica-
tions.
NO................ The parameters in this block are not displayed, cannot be modified
and are therefore skipped.
NOTE
This function does not issue a centralized alarm or output a message. Only a relay output is enabled,
which must be monitored externally.
CAUTION
Mains power monitoring is not designed as a generator protective function. If this function is to be
used for generator protection, it must be utilized in conjunction with an external circuit.
NOTE
All percentage indications of the power are in relation to the generator rated power (Parameter 28).
NOTE
All percentage indications of the power are in relation to the generator rated power (Parameter 28).
Parameter 126 Generator overload: limit MOP (Mains Operating in Parallel) 80 to 150 %
Gen.overload MOP
resp.value 000% The value configured in this screen is a percentage of the configured generator
rated power. If this level is reached or exceeded for the configured delay time, the
unit issues an alarm and opens the GCB.
Tripping of class F2 alarm
without load shedding
Parameter 128 Generator overload: limit IOP (Isolated Operating in Parallel) 80 to 150 %
Gen.overload IOP
resp.value 000% The value configured in this screen is a percentage of the configured generator
rated power. If this level is reached or exceeded for the configured delay time, the
unit issues an alarm and opens the GCB.
Tripping of class F2 alarm
without load shedding
NOTE
All percentage indications of the power are in relation to the generator rated power (Parameter 28).
NOTE
All percentage indications of the current are in relation to the generator rated current (Parameter 29).
Function: The user may configure two steps for time-overcurrent monitoring. The threshold values and delays
can be configured so that the individual set points are independent of each other. Overcurrent level 1 disconnects
lower overcurrent levels that are present over longer periods of time. Overcurrent level 2 disconnects the more
destructive higher currents quickly to protect against short circuit conditions.
I [%]
I >>
(I2)
I>
(I1)
t2 t1 t [s]
Figure 6-1: Characteristic of the time-overcurrent monitoring
NOTE
All percentage indications of the current are in relation to the generator rated current (Parameter 29).
Function: Monitoring of overcurrents including inversely proportional time dependent tripping characteristic.
The selected trip curve defines the tripping time according to the measured current. The tripping time will be de-
creased according to a defined curve the higher the measured current is. According to IEC 255 three different
characteristics are available.
0.14
normal inverse: t= * t p [s]
( I / I P ) 0.02 − 1
13.5
high inverse: t= * t p [s]
(I / I P ) −1
80
extreme inverse: t= * t p [s]
( I / I P )2 − 1
If t is greater than 650 s the system trips at 650 s. If t is lower than tmin the tripping time is tmin. The reaction time
for tmin depends on the time it takes to monitor the fault and the operating time of the relays. tmin is at least 20 ms.
Configuration Screens
Characteristics
Normal Inverse
Ip = 1 x In; I start = 1.1 x In
t[s]
1000
100
10
tp = 1.6 s
tp = 1.0 s
1 tp = 0.5 s
tp = 0.2 s
tp = 0.1 s
tp = 0.05 s
0,1
I start/Ip
0,01
1 10 I/Ip 100
Highly Inverse
Ip = In; I start = 1.1 x In
t[s]
1000
100
10
1 tp = 1.6 s
tp = 1.0 s
tp = 0.5 s
tp = 0.2 s
0,1
tp = 0.1 s
tp = 0.05 s
I start/Ip
0,01
1 10 I/Ip 100
Extremely Inverse
t[s]
Ip = In; I start = 1.1 x In
1000
100
10
tp = 1.6 s
tp = 1.0 s
0,1
tp = 0.5 s
tp = 0.2 s
I start/Ip
tp = 0.05 s tp = 0.1 s
0,01
1 10 I/Ip 100
NOTE
This monitoring function is an additional functionality for the inverse time overcurrent monitoring func-
tion. If the inverse time overcurrent monitoring is disabled (Parameter 140), time-overcurrent monitor-
ing with voltage restraint is disabled too.
All percentage indications of the current are in relation to the generator rated current (Parameter 29).
Function: This function is recommended for a generator that must be monitored with droop excitation and pre-
cautions for short-circuit excitation (e.g. supplementary components) are not available. A short-circuit close to
the terminal may be caused due to the low voltage excitation cannot be maintained. As a result, the unit cannot
maintain power in order to initiate a voltage independent overcurrent delay. The voltage restraint functionality
reduces the overcurrent threshold of the inverse time overcurrent monitoring function proportionally with the
monitored voltage if this function is enabled. If the monitored voltage falls below the threshold defined by the
knee curve setting (Parameter 146), the overcurrent threshold remains at the value of the knee curve setting. The
reduction of the inverse time threshold occurs according to Figure 6-5.
I a [%]
Ip
100
90
20
20 90 V [%]
Vn
Figure 6-5: Characteristic of the inverse time-overcurrent monitoring with voltage restraint (knee curve setting 20 %)
Example:
Initial conditions:
Rated voltage Vn = 100 V
Configured value Ip = 2.0*5 A = 10 A (rated current In = 5 A)
Case 2 (monitored voltage V < 90% Vn , but actual voltage V > knee curve setting):
If the monitored voltage falls below 90% of the rated voltage, the configured value is adjusted proportionally
with the ratio of monitored and rated voltage.
-> Ia = (V/Vn) * Ip
NOTE
All percentage indications of the current are in relation to the generator rated current (Parameter 29).
NOTE
Energizing terminal 6 ("monitoring") enables this monitoring.
NOTE
Energizing terminal 6 ("monitoring") enables this monitoring.
NOTE
The "Blocking of mains protection" input (terminal 61) disables mains monitoring and decoupling.
Monitoring of the mains frequency is absolutely vital if a generator is to be operated in parallel with a public util-
ity. In the event of a mains failure (e. g. short interruption) the generator which is in mains parallel operation,
must be automatically disconnected from the mains.
NOTE
The "Blocking of mains protection" input (terminal 61) disables mains monitoring and decoupling.
Monitoring the mains voltage is absolutely vital if a generator is to be operated in parallel with a public utility. In
the event of mains failure (e. g. short interruption) the generator which is in mains parallel operation must be au-
tomatically disconnected from the mains.
NOTE
The "Blocking of mains protection" input (terminal 61) disables mains monitoring and decoupling.
A dϕ/dt phase/vector jump is a sudden change in the voltage vector angle, and may be caused by a major genera-
tor load change. In this case, the measuring circuit detects a change in the cycle duration once. This change in the
vector angle is compared with a calculated mean value from previous measurements. Monitoring encompasses all
three phases. The threshold value in degrees specifies the difference in time between the mean and the current
value in reference to a full cycle. Monitoring can be set in various manners. The dϕ/dt phase/vector shift moni-
toring may be used as an additional method for decoupling from the mains. The minimum voltage at which the
phase shift monitoring is enabled is 70 % of the rated PT secondary voltage input.
Parameter 187 dϕ/dt phase/vector shift: type one/three-phase / three phase only
Monitoring
---------------- one/three-phase: During single-phase voltage phase shift monitoring, tripping oc-
curs if the phase shift exceeds the configured threshold value in any
one of the three phases. This type of monitoring is very sensitive, and
may lead to nuisance tripping if the configured phase angle settings
are too small.
three phase only: During three-phase voltage phase shift monitoring, tripping oc-
curs only if the phase shift exceeds the configured threshold value in
all three phases within 2 cycles.
Tripping of class F0 alarm
NOTE
If monitoring is configured to "three phase only", only the second screen will be displayed; if moni-
toring is configured to "one/three-phase", both screens are displayed.
NOTE
The "Blocking of mains protection" input (terminal 61) disables mains monitoring and decoupling.
Function: "Frequency change per time unit not within the permissible range"
The control unit determines a measuring value for the change in frequency per unit of time (Hz/s). In order to en-
able reliable differentiation between dϕ/dt phase/vector shift and df/dt, measurement is carried out over 4 cycles.
This results in a minimum tripping time of approx. 100 ms (at 50 Hz). The breaker configured as the mains de-
coupling breaker is opened. The requirement therefore is a mains parallel operation (both GCB and MCB are
closed). An alarm is issued if a fault condition is detected.
Note: Regardless of the configured battery voltage watchdog, readiness for opera-
tion is withdrawn and a message is displayed if the power supply falls below
9 Vdc.
Discrete Inputs
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Parameter 196 Configure discrete inputs YES/NO
Configure
Dig.input YES Various groups of parameters are grouped together in blocks to aid in the rapid na-
vigation through the large number of configuration screens. Selecting "YES" or
"NO" does not determine if control or monitoring is performed. The user’s selec-
tion has the following effect:
YES ..............The configuration screens in this block are displayed and can either
be viewed ("Select" push button) or modifications can be made to the
parameters ("Cursor→", "Digit↑" or "Select" push buttons). This
does not disable or enable individual parameters, only if the individ-
ual parameters in this parameter block may be accessed for modifica-
tions.
NO ................The parameters in this block are not displayed, cannot be modified
and are therefore skipped.
NOTE
For a dead bus start it is necessary to enable the dead bus start function. To trigger the watchdogs
"generator underfrequency" as well as "generator undervoltage", terminal 6 (enable monitoring) must
be energized. It is possible to switch the breaker logic by energizing and de-energizing discrete input
[D03] (terminal 64). The second breaker logic may be configured during the configuration of the dis-
crete inputs. When discrete input [D03] is energized, the second breaker logic is enabled.
NOTE
Operating current (NO, make contact): The discrete input is enabled by energizing it.
This does not provide wire break monitoring!
Closed circuit current (NC, break contact): The discrete input is enabled by de-energizing it.
This may provide wire break monitoring.
NOTE
It is possible to configure upper and lower case letters, numbers, and characters.
Analog Inputs
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Parameter 206 Configure analog inputs YES/NO
Configure
Analg.inp. YES Various groups of parameters are grouped together in blocks to aid in the rapid na-
vigation through the large number of configuration screens. Selecting "YES" or
"NO" does not determine if control or monitoring is performed. The user’s selec-
tion has the following effect:
YES .............. The configuration screens in this block are displayed and can either
be viewed ("Select" push button) or modifications can be made to the
parameters ("Cursor→", "Digit↑" or "Select" push buttons). This
does not disable or enable individual parameters, only if the individ-
ual parameters in this parameter block may be accessed for modifica-
tions.
NO................ The parameters in this block are not displayed, cannot be modified
and are therefore skipped.
Analog input 1 2 3 4 5 6 7
Type 0/4 to 20 mA Pt100
Terminals 93/94/95 96/97/98 99/100/101 102/103/104 105/106/107 108/109/110 111/112/113
Function Real power Power factor Alarm input
set point set point
The Pt100 temperature input is designed for temperatures up to 240 °C. A name may be assigned to each Pt100
input. Each input is displayed with its name, and can be monitored in two stages. The first stage initiates a class 1
alarm, and the second stage initiates a class 3 alarm.
Parameter 212 Analog input, Pt100: monitoring for high limit mon./low limit mon.
Monitoring for
---------------- The analog input is monitored in different manners:
high limit mon. .... The value must exceed the configured limit.
low limit mon....... The value must fall below the configured limit.
NOTE
If limit value monitoring is not required, a limit value which is higher than the expected level must be
configured in the corresponding screen (e. g. for the ambient temperature: 100 °C).
0/4 to 20 mA values can be read here. A name and a unit of measurement may be assigned to the input. The ana-
log input is displayed with its name, and can be monitored in two stages. The first stage initiates a class 1 alarm,
and the second stage initiates a class 3 alarm.
Parameter 216 Analog input, 0/4 to 20 mA: lower level value -9,999 to 9,999
Value at
0% 0000 The scaleable analog input must be assigned a numerical value which corresponds
to the lowest input value Definition of the lower value (0 % equals 0 kW, 0 V
etc.) with minimum analog input value (0 mA or 4 mA).
Parameter 217 Analog input, 0/4 to 20 mA: upper level value -9,999 to 9,999
Value at
100% 0000 The scaleable analog input must be assigned a numerical value which corresponds
to the highest input value Definition of the upper value (100 % equals 500 kW,
400 V etc.) with maximum analog input value (20 mA).
Parameter 218 Analog input, 0/4 to 20 mA: warning (limit 1) -9,999 to 9,999
Limit warning
value 0000 Threshold limit value at which a warning occurs is configured here.
Tripping of class F1 alarm
Parameter 219 Analog input, 0/4 to 20 mA: shutdown (limit 2) -9,999 to 9,999
Limit shutdown
value 0000 The limit value that a shutdown occurs is configured here.
Tripping of class F3 alarm
Parameter 221 Analog input, 0/4 to 20 mA: monitoring for high limit mon./low limit mon.
Monitoring for
---------------- The analog input is monitored in different manners:
high limit mon. .... The value must exceed the configured limit.
low limit mon. The value must fall below the configured limit.
Analog in. --.- This message appears when positive or negative deviation from the measuring
range occurs. The control assesses a fault condition depending on the values speci-
fied below.
NOTE
The control assesses that a wire break has occurred when the following values are measured for the
listed analog input types. When a wire break has been assessed by the control, the threshold limit
monitoring for the analog input is deactivated.
Measuring range monitoring, tripping at
4 to 20 mA 2 mA (negative deviation)
Pt100 240 °C (positive deviation)
Pt1000 150 °C (positive deviation)
PTC 16 kΩ (positive deviation)
180 Ω VDO, 0 to 5 bar 193 Ω (positive deviation)
180 Ω VDO, 0 to 10 bar 193 Ω (positive deviation)
180 Ω VDO temperature 400 Ω (positive deviation)
Outputs
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Parameter 225 Configure outputs YES/NO
Configure
Outputs YES Various groups of parameters are grouped together in blocks to aid in the rapid na-
vigation through the large number of configuration screens. Selecting "YES" or
"NO" does not determine if control or monitoring is performed. The user’s selec-
tion has the following effect:
YES .............. The configuration screens in this block are displayed and can either
be viewed ("Select" push button) or modifications can be made to the
parameters ("Cursor→", "Digit↑" or "Select" push buttons). This
does not disable or enable individual parameters, only if the individ-
ual parameters in this parameter block may be accessed for modifica-
tions.
NO................ The parameters in this block are not displayed, cannot be modified
and are therefore skipped.
Analog Outputs
The analog output manager can be used to apply specific measurement variables to the available analog outputs.
The outputs may be configured as 0 to 20 mA or as 4 to 20 mA. A list of the parameters, which may be confi-
gured, is located in Appendix D. Each parameter is assigned a unique number. The parameter may be scaled via
an upper and a lower input value. The analog outputs may also be assigned an engineering unit of measure (refer
to "Analog output manager" in Appendix D).
NOTE
The list of values and setting limits for the analog output manager is contained in chapter "Analog
Output Manager" starting on page 141.
Relay Manager
The relay manager enables the user to assign combinations of functions to each relay of terminals 37/38, 47/48.
and 74-83. In order to achieve this, each possible function has its own number. A text, which describes a logical
condition for this relay's picking up, must now be entered in the configuration menu for each relay. Up to three
numbers may be involved in this link. The length of the text must not exceed 16 characters. The unit detects in-
correct function numbers or incorrect formula constructions, and does not accept these. The user must enter the
logical combination to be performed.
NOTE
The list of function numbers for the relay manager is located in Appendix E"Relay Manager" starting on
page 126.
NOTE
If the user programs an illogical function, the entered line is deleted.
Pulse Outputs
NOTE
The pulse outputs of the energy counter are not calibrated!
These outputs issue pulses whose frequency is proportional to the measured real power or re-active
power. The frequency of the pulses can be adjusted. The length of a pulse is 50 ms to 100 ms. The
pulse frequency is adjustable so that the time between pulses does not fall under 100 ms at maximum
power.
Drive
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Parameter 237 Configure drive YES/NO
Configure
Drive YES Various groups of parameters are grouped together in blocks to aid in the rapid na-
vigation through the large number of configuration screens. Selecting "YES" or
"NO" does not determine if control or monitoring is performed. The user’s selec-
tion has the following effect:
YES ..............The configuration screens in this block are displayed and can either
be viewed ("Select" push button) or modifications can be made to the
parameters ("Cursor→", "Digit↑" or "Select" push buttons). This
does not disable or enable individual parameters, only if the individ-
ual parameters in this parameter block may be accessed for modifica-
tions.
NO ................The parameters in this block are not displayed, cannot be modified
and are therefore skipped.
Nominal frequency
Generator
frequency [Hz]
Minimum
frequency
Time [s]
Relay 4
'ON'
Time [s]
Case 1
'Release
Monitoring ON'
(Terminal 6)
Time [s]
LED Delay
'Monitoring ON' (configuration
(Watchdogs are active) screen B)
Time [s]
Case 2
'Release
Monitoring ON'
(Terminal 6/7)
Time [s]
LED Delay
'Monitoring ON' (configuration
(Watchdogs are active) screen B)
Time [s]
NOTE
Please note chapter "Breaker Logic" (starting page 88) for description of the breaker logics.
Counter
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Parameter 242 Configure counters YES/NO
Configure
Counters YES Various groups of parameters are grouped together in blocks to aid in the rapid na-
vigation through the large number of configuration screens. Selecting "YES" or
"NO" does not determine if control or monitoring is performed. The user’s selec-
tion has the following effect:
YES .............. The configuration screens in this block are displayed and can either
be viewed ("Select" push button) or modifications can be made to the
parameters ("Cursor→", "Digit↑" or "Select" push buttons). This
does not disable or enable individual parameters, only if the individ-
ual parameters in this parameter block may be accessed for modifica-
tions.
NO................ The parameters in this block are not displayed, cannot be modified
and are therefore skipped.
Maintenance Call
Parameter 243 Maintenance call ON/OFF
Service interval
ON ON................ Maintenance call counter is enabled and an alarm message will be
displayed when the counter expires. Refer to Parameter 244 for a de-
scription of the maintenance call function.
OFF.............. The maintenance call counter is disabled.
NOTE
If maintenance has been performed prior to the counter expiring, it is possible to reset the maintenance
counter to the configured value. The unit must be in code level 1 or 2 in order to achieve this. The
counter is reset in a 2-step procedure for safety reasons. The following procedure applies:
1. Step: Configure the desired number of hours for the maintenance call.
2. Step: Integration of the value which has been saved:
1. Exit the configuration mode and switch the controller into AUTOMATIC mode
2. Navigate to the display screen "Service interval in 000h" using the "Select" button
3. Press and hold the "Digit" push button for 7 seconds
NOTE
The operating hours counter can be set to a maximum value of 65,000 hours.
NOTE
If the control unit operating hours must be configured to a specific value, the unit must be in code lev-
el 2 in order to achieve this. The counter is reset in a 2-step procedure for safety reasons. The follow-
ing procedure applies:
1. Step: Configure and store the desired operating hours.
2. Step: Integration of the value which has been saved:
1. Exit the configuration mode and switch the controller into AUTOMATIC mode
2. Navigate to the display screen "Op.hours 000h" using the "Select" button
3. Press and hold the "Digit" push button for 7 seconds
Start Counter
Parameter 247 Start counter ON/OFF
Start counter
ON ON................ Start counter is enabled. Refer to Parameter 248 for a description.
OFF.............. The counter is not enabled.
NOTE
After 32,000 starts, the counter is automatically reset.
NOTE
If the control unit number of starts must be configured to a specific value, the unit must be in code lev-
el 2 in order to achieve this. The counter is reset in a 2-step procedure for safety reasons. The follow-
ing procedure applies:
1. Step: Configure and store the desired number of starts.
2. Step: Integration of the value which has been saved:
1. Exit the configuration mode and switch the controller into AUTOMATIC mode
2. Navigate to the display screen "Start counter 00000" using the "Select" button
3. Press and hold the "Digit" push button for 7 seconds
kWh/kvarh Counter
Parameter 249 Display kWh counter Y/N
Display kWh +-
on? YY It is possible to display the positive kWh counter (+) and/or the negative kWh
counter (-) by selecting "Y" or "N". It is possible to display no counters, one coun-
ter or both counters by making the appropriate entry
Y ................... The selected kWh counter is visible.
N ................... The selected kWh counter is not visible.
To reset the individual counters, the control unit must be in the AUTOMATIC mode. Navigate to the display
screen that is to be reset or changed. Press and hold the "Digit" button for at least 7 seconds.
For the start counter and the operating hours counter, the values that have been configured in the parameters
"Start counter set" or "Op.hours counter set” will be integrated into the display.
Chapter 7.
Commissioning
LIFE THREATENING
CAUTION
Only a qualified technician may commission unit. The "EMERGENCY-STOP" function must be opera-
tional prior to commissioning of the system and must not depend on the unit for its operation.
CAUTION
Prior to commissioning ensure that all measuring devices are connected in correct phase sequence.
The connect command for the unit circuit breaker must be disconnected at the unit circuit breaker. The
rotating field must be monitored for proper rotation. Any absence of or incorrect connection of voltage
measuring devices or other signals may lead to malfunctions and damage the unit, the engine, and/or
components connected to the unit!
CAUTION
Please consider that the unit does not have an internal rotating field monitoring.
The unit assumes always a clockwise phase rotation direction of all three voltage systems, which are
measured.
A rotating field monitoring must be provided by the customer in order to avoid a CB closure with a
counter-clockwise rotating field.
Procedure
1. After checking to ensure that all measuring voltages have been connected to the correct phases, the power
supply (12/24 Vdc) may be connected.
2. By simultaneously pressing the two push buttons "Digit↑" and "Cursor→", the configuration mode is ac-
cessed. After entering the access code number, the unit may be configured according to the application
requirements (refer to the Configuration section).
3. After the control unit has been configured, the unit will display the measured system values. These values
should be confirmed with a calibrated measuring instrument.
4. The initial operation should be performed in the MANUAL operation mode (press the "MANUAL" push
button). All measured generator values must be verified. Any alarm messages should be investigated to
determine the cause.
5. Operating mode AUTOMATIC (press the push button "AUTO"): A synchronization can now be carried
out for the GCB by energizing the "Enable GCB" discrete input.
Check-out of the synchronization: Disconnect the connect pulse "Command: close GCB".Check the ge-
nerator and the generator busbar phase rotation. Check the connect command with a zero voltmeter (de-
termination of the phase angle) at the GCB. If several pulses have been output at the correct synchronous
point, switch the operating mode to MANUAL and reconnect the connect pulse "Command: close GCB".
6. If steps 1 through 5 have been carried out successfully, mains parallel operations may commence. It is
recommended to start with a constant power/base load operation (approx. 25 % of the generator rated
power). While this operation is being performed, the displayed measuring values must be verified. Test
the GCB shutdown for proper operation. Check the real power controller and, if necessary, the power fac-
tor controller. Enter various set point values and verify proper operation.
7. If mains parallel operation performs in a satisfactory manner, the synchronization of the MCB must be
checked:
A power failure in the system must be simulated or monitored by the control Unit.. During mains parallel
operation, change the operating mode from AUTOMATIC to MANUAL. Open the MCB ("MCB ON"
LED will turn off). Press the AUTOMATIC pushbutton to return the control unit back to the
AUTOMATIC operating mode.
Check the generator busbar and the mains field rotation. Check the connect command with a zero voltme-
ter (determination of the phase angle) at the MCB. If several pulses have been output at the correct syn-
chronous point, switch the operating mode to MANUAL and reconnect the connect pulse "Command:
close MCB".
NOTE
The automatic operation mode is influenced by the input signals “Automatic 1” and “Automatic 2”. En-
sure that the power circuit breaker reply messages are processed as the opposite of the condition (i.e.
when the power circuit breaker is closed the reply message for the inputs: CB is open (terminal 54) is
0 volts. The CB auxiliary contact should be configured as normally closed contacts (NC)! Refer to the
description of the alarm and control inputs starting on page 22 of this manual). It is vital that these rep-
lies be connected!
Electrical isolation between voltage supply and discrete control and feedback inputs: By the use of correspond-
ing external wiring, the common reference point of the discrete inputs can be electrically isolated from the power
supply voltage (0 V, terminal 2). This is necessary if the discrete inputs are not to be enabled with 24 Vdc and an
electrically isolation of the control voltage (e. g. 220 Vdc, 220 Vac) from the supply voltage must be ensured.
Appendix A.
Dimensions
144.0 mm
32.0 mm
12.0 mm
Configuration plug
42.0 mm
8.0 mm
48 25
X1 X5 130 138
144.0 mm
136.0 mm
83 60
50 54
01 24
136.0 mm 111.0 mm
Appendix B.
Technical Data
Housing ----------------------------------------------------------------------------------------------------------
- Type ............................................................................................ APRANORM DIN 43 700
- Dimensions (W× H × D) ..................................................................... 144 × 144 × 118 mm
- Front cutout (W×H) ................................................................. 138 [+1.0] × 136 [+1.0] mm
Appendix C.
Measured Quantities and Accuracy
Appendix D.
Analog Output Manager
NOTE
The parameters listed below can only be output correctly if the existing version of the unit permits this.
1)
Note to parameter 1 and 2: The analog output is calculated according to the displayed real power without the
engineering unit of measure "kW" or "MW". The number of displayed digits is valid. Example: 20 mA corres-
ponds to "200".
The control unit automatically switches from "kW" to "MW" when the primary transformer real power of
3,000 kW is exceeded: Igen prim × Vgen prim × √ 3 ≥ 3,000 kW.
The description 0 % corresponds to the minimum input of 4 mA or 0 mA; the description 100 % corresponds to
the maximum input of 20 mA. The values can be entered with or without a leading sign (see parameter 1).
Definition of power factor scaling: According to the scaling of the analog output, the power factor can be out-
put within the range from capacitive values ranging from c0.00 to unity power factor = 1 to inductive values up
to i0.00.
Capacitive Inductive
(negative) (positive)
Lower distance Higher distance
eg. 0030 eg. 0030
Scalable range (0 to 20 mA)
c 0.00 eg. c0.70 to 1.00 to i0.70 i 0.00
Appendix E.
Relay Manager
No. Output
1 Class F1 alarm
2 Class F2 alarm
3 Class F3 alarm
4 Class F1, F2 or F3 centralized alarm
5 Class F2 or F3 centralized alarm
6 Ignition speed reached
7 Generator voltage within 88 to 112 % of the rated voltage
8 Busbar voltage within 88 to 112 % of the rated voltage
9 Mains voltage within 88 to 112 % of the rated voltage
10 AUTOMATIC operating mode
11 MANUAL operating mode
12 Mains overfrequency
13 Mains underfrequency
14 Mains overvoltage
15 Mains undervoltage
16 Mains phase/vector jump
17 Mains df/dt failure
18 Generator underfrequency 1
19 Generator overfrequency 1
20 Generator overspeed
21 Plausibility check: Generator frequency
22 Generator undervoltage 1
23 Generator overvoltage 1
24 Generator time-overcurrent 1
25 Generator time-overcurrent 2
26 Generator load imbalance
27 Generator overload 1
28 Generator reverse/reduced power
29 Time limit exceeded: Synchronization GCB
30 Generator re-active power, capacitive
33 Generator re-active power, inductive
32 Ground failure
33 Battery undervoltage
34 Interface failure terminals X1 to X5
35 Analog input [T1], terminals 93 - 95, level 1
36 Analog input [T1], terminals 93 - 95, level 2
37 Analog input [T2], terminals 96 - 98, level 1
38 Analog input [T2], terminals 96 - 98, level 2
39 Analog input [T3], terminals 99 - 101, level 1
40 Analog input [T3], terminals 99 - 101, level 2
41 Analog input [T4], terminals 102 - 104, level 1
42 Analog input [T4], terminals 102 - 104, level 2
43 Analog input [T5], terminals 105 - 107, level 1
44 Analog input [T5], terminals 105 - 107, level 2
45 Analog input [T6], terminals 108 - 110, level 1
46 Analog input [T6], terminals 108 - 110, level 2
47 Analog input [T7], terminals 111 - 113, level 1
48 Analog input [T7], terminals 111 - 113, level 2
49 Analog input, terminals 91 - 92, level 1
50 Analog input, terminals 91 - 92, level 2
51 Discrete input, terminal 34
52 Discrete input, terminal 35
53 Discrete input, terminal 36
54 Discrete input, terminal 37
55 Discrete input [D01], terminal 62
56 Discrete input [D02], terminal 63
57 Discrete input [D03], terminal 64
58 Discrete input [D04], terminal 65
No. Output
59 Discrete input [D05], terminal 66
60 Discrete input [D06], terminal 67
61 Discrete input [D07], terminal 68
62 Discrete input [D08], terminal 69
63 Discrete input [D09], terminal 70
64 Discrete input [D10], terminal 71
65 Discrete input [D11], terminal 72
66 Discrete input [D12], terminal 73
67 Reply: MCB is closed
68 Reply: GCB is closed
69 Mains parallel operation is desired
70 Power monitoring
71 Mains failure: mains voltage, mains frequency or mains phase/vector shift have been tripped
72 Dependent time-overcurrent
73 Class F1 alarm acknowledged
74 Class F2 or F3 alarm acknowledged
75 Generator undervoltage 2
76 Generator overvoltage 2
77 Generator underfrequency 2
78 Generator overfrequency 2
79 Internal
80 Generator overload 2
81 Interface failure terminals Y1 to Y5
82 Load shedding introduced: closing/synchronization GCB has happen or breaker is closed
83 Closing/synchronization MCB has happen or breaker is closed
84 Power monitoring mains incoming
85 Maintenance call
86 Time limit exceeded: Synchronization MCB
87 Synchronization MCB is happening
88 Lamp test activated
89 Malfunction "Reply: GCB is open" - failure during closing
90 Malfunction "Reply: MCB is open" - failure during closing
91 Malfunction "Reply: GCB is open" - failure during opening
92 Malfunction "Reply: MCB is open" - failure during opening
93 Mains interchange power <> 0
94 Closing time at dead bus start exceeded
95 Internal
96 Engine release
97 Push button "ACK" pressed
98 Class F1, F2 or F3 centralized alarm (pre-assigned to relay [8])
99 Three-position controller: raise n/f/P (external RC wiring required !!!)
100 Three-position controller: lower n/f/P (external RC wiring required !!!)
101 Three-position controller: raise V/Q (external RC wiring required !!!)
102 Three-position controller: lower V/Q (external RC wiring required !!!)
103 Engine running (f > 15Hz)
104 Internal
105 Rotation field generator/mains mismatch
106 Left rotation field mains
107 Right rotation field mains
108 Left rotation field generator
109 Right rotation field generator
110 Open GCB
111 Wire break analog input 1
112 Wire break analog input 2
113 Wire break analog input 3
114 Wire break analog input 4
115 Wire break analog input 5
116 Wire break analog input 6
117 Wire break analog input 7
NOTE
Rotation field monitoring (relay manager no. 105 through 109) is only active within the synchronization
limits (refer to Synchronization on page 91).
Appendix F.
Interface Telegram
Transmission Telegram
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Content (words) Unit Comment
MUX
No.
MUX
No.
4/1 13 Alarms 8 Bit 15 =1 F3: Generator overfrequency, level 2
Bit 14 =1 F3: Generator underfrequency, level 2
Bit 13 =1 F3: Generator overvoltage, level 2
Bit 12 =1 F3: Generator undervoltage, level 2
Bit 11 =1 F3: Reactive power, inductive
Bit 10 =1 F3: Reactive power, capacitive
Bit 9 =1 --Internal--
Bit 8 =1 --Internal--
FS: Control input, not active Bit 7 =1 --Internal--
F0: Class F0 alarm, not active Bit 6 =1 --Internal--
F1: Class F1 alarm, active until ac- Bit 5 =1 --Internal--
knowledged Bit 4 =1 --Internal--
F2: Class F2 alarm, active until ac- Bit 3 =1 --Internal--
knowledged Bit 2 =1 --Internal--
F3: Class F3 alarm, active until ac- Bit 1 =1 --Internal--
knowledged Bit 0 =1 --Internal--
4/2 14 Internal alarms 6 Bit 15 =1 --Internal--
Bit 14 =1 --Internal--
Bit 13 =1 Dead bus start error, time overrun
Bit 12 =1 --Internal--
Bit 11 =1 Switch fault "MCB open"
Bit 10 =1 Switch fault "GCB open"
Bit 9 =1 Synchronization time monitoring MCB
Bit 8 =1 Synchronization time monitoring GCB
FS: Control input, not active Bit 7 =1 --Internal--
F0: Class F0 alarm, not active Bit 6 =1 --Internal--
F1: Class F1 alarm, active until ac- Bit 5 =1 --Internal--
knowledged Bit 4 =1 --Internal--
F2: Class F2 alarm, active until ac- Bit 3 =1 --Internal--
knowledged Bit 2 =1 --Internal--
F3: Class F3 alarm, active until ac- Bit 1 =1 --Internal--
knowledged Bit 0 =1 Range alarm analog input [T1]
4/3 15 Generator voltage delta V23 V × 10VgenEXPO
5/1 16 Generator voltage delta V31 V × 10VgenEXPO
5/2 17 Generator voltage wye V1N V × 10VgenEXPO
5/3 18 Generator voltage wye V2N V × 10VgenEXPO
6/1 19 Generator voltage wye V3N V × 10VgenEXPO
6/2 20 Generator voltage delta V12 V × 10VgenEXPO
No.
6/3 21 Internal
7/1 22 Generator current in L1 A × 10IgenEXPO
7/2 23 Generator current in L2 A × 10IgenEXPO
7/3 24 Generator current in L3 A × 10IgenEXPO
8/1 25 Actual generator reactive power var × 10PgenEXPO positive = inductive
8/2 26 Generator power factor Example: FF9EH PF = c 0.98 (capacitive)
FF9DH PF = c 0.99 (capacitive)
0064H PF = 1.00
0063H PF = i 0.99 (inductive)
0062H PF = i 0.98 (inductive)
8/3 27 Internal
9/1 28 Internal
9/2 29 Number of participants on CAN bus
9/3 30 H.B. mains status FFH Voltage and frequency present
L.B. generator status 00H Voltage and frequency not present
10/1 31 Exponents High Byte: IgenEXPO generator current
Low Byte: --- free
10/2 32 Busbar frequency Hz / 100
10/3 33 H.B. busbar status FFH Voltage and frequency present
L.B. internal 00H Voltage and frequency not present
11/1 34 Mains voltage delta V23 V × 10VmainsEXPO
11/2 35 Mains voltage delta V31 V × 10VmainsEXPO
11/3 36 Mains voltage wye V1N V × 10VmainsEXPO
12/1 37 Mains voltage wye V2N V × 10VmainsEXPO
12/2 38 Mains voltage wye V3N V × 10VmainsEXPO
12/3 39 Mains frequency off VN12/VN23/VN31 Hz / 100
13/1 40 Mains current in L1 A × 10ImainsEXPO
13/2 41 Mains reactive power var × 10QmainsEXPO
13/3 42 Mains power factor Example: FF9EH PF = c 0.98 (capacitive)
FF9DH PF = c 0.99 (capacitive)
0064H PF = 1.00
0063H PF = i 0.99 (inductive)
0062H PF = i 0.98 (inductive)
14/1 43 Exponents High Byte: PmainsEXPO mains power
Low Byte: VmainsEXPO mains voltage
14/2 44 Exponents High Byte: ImainsEXPO mains current
Low Byte: VbusEXPO busbar voltage
14/3 45 Engine operating hours ( H.W.) h × 216 Double word
15/1 46 Engine operating hours ( L.W.) h
15/3 47 Hours until next maintenance h
15/3 48 Generator start number
16/1 49 Internal
MUX
No.
16/2 50 Generator active energy ( H.W.) kWh × 216 Double word
16/3 51 Generator active energy (L.W.) kWh
17/1 52 Battery voltage V / 10
17/2 53 Internal alarms 1 Bit 15 =1 \
F3: Generator overfrequency 1
Bit 14 =1 /
Bit 13 =1 \
F3: Generator underfrequency 1
Bit 12 =1 /
If both bits are set for double bits, the Bit 11 =1 \
F3: Generator overvoltage 1
input is activated. Bit 10 =1 /
Bit 9 =1 \
F3: Generator undervoltage 1
Bit 8 =1 /
FS: Control input, not active Bit 7 =1 \
--Internal--
F0: Class F0 alarm, not active Bit 6 =1 /
F1: Class F1 alarm, active until ac- Bit 5 =1 \
F1: Battery undervoltage
knowledged Bit 4 =1 /
F2: Class F2 alarm, active until ac- Bit 3 =1 \
F3: Generator overload
knowledged Bit 2 =1 /
F3: Class F3 alarm, active until ac- Bit 1 =1 \
F3: Generator reverse power
knowledged Bit 0 =1 /
17/3 54 Internal alarms 2 Bit 15 =1 \
F0: Mains overfrequency
Bit 14 =1 /
Bit 13 =1 \
F0: Mains underfrequency
Bit 12 =1 /
If both bits are set for double bits, the Bit 11 =1 \
F0: Mains overvoltage
input is activated. Bit 10 =1 /
Bit 9 =1 \
F0: Mains undervoltage
Bit 8 =1 /
FS: Control input, not active Bit 7 =1 \
Interface fault X1 to X5
F0: Class F0 alarm, not active Bit 6 =1 /
F1: Class F1 alarm, active until ac- Bit 5 =1 \
--Internal--
knowledged Bit 4 =1 /
F2: Class F2 alarm, active until ac- Bit 3 =1 \
F0: df/dt fault
knowledged Bit 2 =1 /
F3: Class F3 alarm, active until ac- Bit 1 =1 \
F0: Mains phase/vector jump
knowledged t Bit 0 =1 /
18/1 55 Internal alarms 3 Bit 15 =1 \ F3: Independent
Bit 14 =1 / time-overcurrent protection, level 2
Bit 13 =1 \
--Internal--
Bit 12 =1 /
Bit 11 =1 \
--Internal--
Bit 10 =1 /
Bit 9 =1 \
F3: Generator load imbalance
If both bits are set for double bits, the Bit 8 =1 /
input is activated. Bit 7 =1 \ F3: Independent
Bit 6 =1 / time-overcurrent protection, level 1
Bit 5 =1 \
--Internal--
FS: Control input, not active Bit 4 =1 /
F0: Alarm class 0, not active Bit 3 =1 \
F1: Maintenance call
F1: Alarm class 1, active until quit Bit 2 =1 /
F2: Alarm class 2, active until quit Bit 1 =1 \
--Internal--
F3: Alarm class 3, active until quit Bit 0 =1 /
No.
18/2 56 Internal
18/3 57 Internal
19/1 58 External alarms 1 Bit 15 =1 \ Terminal 34
Bit 14 =1 / DI "Configuration blocked"
Bit 13 =1 \ Terminal 35
Bit 12 =1 / DI "Isolated controller ON"
Bit 11 =1 \ Terminal 36
Bit 10 =1 / DI "External acknowledgement"
Bit 9 =1 \ Terminal 61
Bit 8 =1 / DI "Block mains protection"
Bit 7 =1 \ Terminal 62
Bit 6 =1 / Discrete input [D01]
Bit 5 =1 \ Terminal 63
Bit 4 =1 / Discrete input [D02]
Bit 3 =1 \ Terminal 64
Bit 2 =1 / Discrete input [D03]
If both bits are set for double bits, the Bit 1 =1 \ Terminal 65
input is activated. Bit 0 =1 / Discrete input [D04]
19/2 59 External alarms 2 Bit 15 =1 \ Terminal 66
Bit 14 =1 / Discrete input [D05]
Bit 13 =1 \ Terminal 67
Bit 12 =1 / Discrete input [D06]
Bit 11 =1 \ Terminal 68
Bit 10 =1 / Discrete input [D07]
Bit 9 =1 \ Terminal 69
Bit 8 =1 / Discrete input [D08]
Bit 7 =1 \ Terminal 70
Bit 6 =1 / Discrete input [D09]
Bit 5 =1 \ Terminal 71
Bit 4 =1 / Discrete input [D10]
Bit 3 =1 \ Terminal 72
Bit 2 =1 / Discrete input [D11]
If both bits are set for double bits, the Bit 1 =1 \ Terminal 73
input is activated. Bit 0 =1 / Discrete input [D12]
19/3 60 Internal alarms 7 Bit 15 =1 --Internal--
Bit 14 =1 --Internal--
Bit 13 =1 Ground current failure
Bit 12 =1 F3: ground current failure
Bit 11 =1 --Internal--
Bit 10 =1 --Internal--
Bit 9 =1 --Internal--
Bit 8 =1 --Internal--
Bit 7 =1 MCB close malfunction
Bit 6 =1 GCB close malfunction
Bit 5 =1 --Internal--
Bit 4 =1 --Internal--
Bit 3 =1 --Internal--
Bit 2 =1 --Internal--
Bit 1 =1 --Internal--
Bit 0 =1 --Internal--
20/1 61 Analog input 1 (terminals 93-95)
20/2 62 Analog input 2 (terminals 96-98)
20/3 63 Analog input 3 (terminals 99-101)
21/1 64 Analog input 4 (terminals 102-104)
21/2 65 Analog input 5 (terminals 105-107)
21/3 66 Analog input 6 (terminals 108-110)
22/1 67 Analog input 7 (terminals 111-113)
22/2 68 Internal
MUX
No.
23/3 69 Speed detection Bit 15 =1 --Internal--
Bit 14 =1 --Internal--
Bit 13 =1 --Internal--
Bit 12 =1 --Internal--
Bit 11 =1 --Internal--
Bit 10 =1 --Internal--
Bit 9 =1 --Internal--
Bit 8 =1 --Internal--
Bit 7 =1 \
Bit 6 =1
Firing speed exceeded
Bit 5 =1
Bit 4 =1 /
Bit 3 =1 \
Bit 2 =1
Machine is running
Bit 1 =1
Bit 0 =1 /
Receiving Telegram
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
A Gateway GW 4 may be used for start/stop synchronizing the MFR. The following three data words can be re-
ceived by the MFR. Refer to the GW 4 manual on how to control several MFR units.
No.
1/1 1 Set point value for the generator real power kW with control argument; see below
1/2 2 Set point value for the generator power fac- Example: FF9EH cos ϕ = c 0.98 (capacitive/lagging)
tor cos ϕ FF9DH cos ϕ = c 0.99 (capacitive/lagging)
0064H cos ϕ = 1.00
0063H cos ϕ = i 0.99 (inductive/leading)
0062H cos ϕ = i 0.98 (inductive/leading)
1/3 3 Control word Bit 15 = 1 --Internal--
Bit 14 = 1 --Internal--
Bit 13 = 1 --Internal--
Bit 12 = 1 --Internal--
Bit 11 = 1 --Internal--
Bit 10 = 1 --Internal--
Bit 9 = 1 --Internal--
Bit 8 = 1 --Internal--
Bit 7 = 1 --Internal--
Bit 6 = 1 --Internal--
Bit 5 = 1 --Internal--
Bit 4 = 1 Remote acknowledgement
Bit 3 = 1 Always "0"
Bit 2 = 1 Always "0"
Remote stop synchronization (high priori-
Bit 1 = 1
ty)
Bit 0 = 1 Remote start synchronization
Transmission Telegram
The data in the following table can be processed using a Gateway GW 4 or a PLC and transmitted to other com-
munication busses. The MFR 3 sends its data via cyclic CAN messages with this.
(The ID number is a parameter, which can be set at the MFR 3, which influences the CAN ID directly on which
the item sends its visualization messages.)
A visualization message, which is sent by an MFR 3, consists of 8 bytes and is assembled as follows:
In a visualization message the byte 0 is always used to show the hexadecimal value DD. This one defines the
message as a visualization message. Since the complete transmission telegram of the MFR 3 includes more than
three data words, byte 1 sends an additional MUX number starting with 0 in addition. Therefore it is theoretically
possible to send (256 × 3 = 768) words via the CAN ID. The whole telegram is built up as follows:
n depends on the total length of the item-specific telegram and cannot be larger than H’FF.
Example:
C power of 150 kW is to be compensated. The value transmitted is then:
01/00 0000 1001 0110 B 4096 H
I power of 600 kW is to be compensated. Negative power is transmitted. The value transmitted is then:
11/11 1101 1010 1000 B FDA8 H
CAN-ID in
[hex] [decimal]
MFR sends
Distribution message to other MFRs 180 + GENNO 384 + GENNO
Visualization 320 + GENNO 800 + GENNO
MFR receives
Distribution message from other MFR 180 + GENNO 384 + GENNO
Configuration messages from a higher control 33F 831
Appendix G.
List of Parameters
Project ____________________________________________________________
Level
Parameter Standard
Option Setting range Customer settings
100/400V; 5 A setting
CONFIGURE GENERAL
Sprache/language first /second first
Software version V 3.3xxx
Enter code 0 to 9999
Load language YES/NO NO Y N Y N
Language number 0/1
Number of tool 1 to 14
Direct para. YES/NO NO Y N Y N
Service display ON/OFF ON on off on off
Check event list YES/NO NO Y N Y N
CONFIGURE BASIC SETTINGS
Configure Measuring YES/NO NO Y N Y N
Generator number 1 to 14 01
Generator freq. f set 40.0 to 70.0 Hz 50.0 Hz
Rated system frequency 50/60 Hz 50.0 Hz
Gen.volt.transf. secondary 50 to 125 V; 50 to 480 V 100 V
Gen.volt.transf. primary 0.005 to 65.000 / 0.020 to 65.000kV 10.000 kV
Bus.volt.transf. secondary 50 to 125 V; 50 to 480 V 100 V
Bus.volt.transf. primary 0.005 to 65.000 / 0.020 to 65.000kV 10.000 kV
Mains volt.trans secondary 50 to 125 V; 50 to 480 V 100 V
Mains volt.trans primary 0.005 to 65.000 / 0.020 to 65.000kV 10.000 kV
Gen.voltage U set 25 to 125 V; 50 to 480 V 100 V
Rated voltage System 25 to 125 V; 50 to 480 V 100 V
Voltage systems phase to phase/Phase to neutral phase to
phase
Voltage measuring Main threephase / singlephase threephase
Current transf. generator 10 to 7,000/5 A 0100/5
Power measuring Gen. singlephase/threephase threephase
Rated power gen. 5 to 16,000 kW 02000 kW
Rated current generator 10 to 7,000 A 0100 A
Current transf. mains 5 to 7,000/5 A 0200/5
Angle adjustment Mainscurr. -180 to 0 to 180 ° 000 °
Define level 1 code 0 to 9999 0001
Define level 2 code 0 to 9999 0002
Level
Parameter Standard
Option Setting range Customer settings
100/400V; 5 A setting
CONFIGURE CONTROLLER
Configure Controller YES/NO NO Y N Y N
Power controller Pset1 C/E/I 0 to 16,000 kW C000200kW
Power controller Pset2 C/E/I 0 to 16,000 kW C000100kW
Initial state Frequency 0 to 100 % 50 %
Freq.controller ON/OFF ON on off on off
f-contr. active at: 0.0 to 70.0 Hz 30,0 Hz
Delay time for f to contr. 0 to 999 s 005 s
Freq.controller ramp 1 to 50 Hz/s 05 Hz/s
F/P contr.type THREEST. / ANALOG / PWM ANALOG
Freq.controller dead band 0.02 to 1.00 Hz 0.10 Hz
Freq.controller time pulse> 10 to 250 ms 080 ms
Freq.controller gains.Kp 0.1 to 99.9 10.0
F/P contr.output see table +/-10V
Level PWM 3.0 to 10.0 V 3.0V
Freq.controller gain.Kpr 1 to 240 20
Freq.controller reset Tn 0.0 to 60.0 s 1.00 s
Freq.controller derivat.Tv 0.00 to 6.00 s 0.00 s
Starting point voltage 0 to 100 % 50%
Volt.controller ON/OFF ON on off on off
V/Q contr.type THREESTEP / ANALOG ANALOG
Volt.controller dead band 0.1 to 15.0 V / 0.5 to 60.0 V 00.5%
Volt.controller time pulse> 20 to 250 ms 080 ms
Volt.controller gain.Kp 0.1 to 99.9 10.0
V/Q contr.output see table +/-10V
Volt.controller gain.Kpr 1 to 240 20
Volt.controller reset Tn 0.0 to 60.0 s 1.00 s
Volt.controller derivat.Tv 0.00 to 6.00 s 0.00 s
Pow.fact.contr. ON/OFF OFF on off on off
Pow.fact.contr. setpoint i0.70 to 1.00 to c0.70 1.00
Power factor external ON/OFF OFF on off on off
Analog input 0 to 20 / 4 to 20 mA 4 to 20 mA
Ext. Pow.Factor 0mA i0.70 to 1.00 to c0.70
Ext. Pow.Factor 20mA i0.70 to 1.00 to c0.70
Pow.fact.contr. dead band 0.5 to 25.0 % 01.0 %
Pow.fact.contr. gain Kp 0.1 to 99.9 10.0
Pow.fact.contr. gains Kpr 1 to 240 20
Pow.fact.contr. reset Tn 0.0 to 60.0 s 1.00 s
Pow.fact.contr. derivat.Tv 0.00 to 6.00 s 0.00
Power controller ON/OFF ON on off on off
Power controller ramp 0 to 100 %/s 005 %/s
Power controller ramp 1 to 100 kW/s 20 %/s
Power limit P max. 10 to 120 % 100 %
Power limit P min. 0 to 50 % 00 %
Power setpoint external ON/OFF ON on off on off
Analog input 0 to 20 / 4 to 20 mA 4 to 20 mA
Ext.setpoint 0mA C/E/I 0 to 16,000 kW C00000kW
Ext.setpoint 20mA C/E/I 0 to 16,000 kW C00200kW
Power controller dead band 0.1 to 25.0 % 01.0 %
Power controller gain Kp 0.1 to 99.9 20.0
Powercontr. dead band ratio 1.0 to 9.9 *2.0
Power controller gain Kpr 1 to 240 20
Power controller reset Tn 0.0 to 60.0 s 1.00 s
Power controller derivat.Tv 0.00 to 6.00 s 0.00
Warm up load limit value 5 to 110 % 015 %
Warm up load time 0 to 600 s 000 s
Active power load share ON/OFF ON on off on off
Act.load share factor 10 to 99 % 50 %
Reactive power load share ON/OFF OFF on off on off
React.load share factor 10 to 99 % 50 %
Level
Parameter Standard
Option Setting range Customer settings
100/400V; 5 A setting
Level
Parameter Standard
Option Setting range Customer settings
100/400V; 5 A setting
Level
Parameter Standard
Option Setting range Customer settings
100/400V; 5 A setting
Level
Parameter Standard
Option Setting range Customer settings
100/400V; 5 A setting
CONFIGURE OUTPUTS
Configure Outputs YES/NO NO Y N Y N
Analg.out.130131 OFF / 0 to 20 / 4 to 20 mA OFF
Analg.out.130131 parameter 0 to 23 01
Analg.out.130131 0% 0 to 9,990 0000
Analg.out.130131 100% 0 to 9,990 0200
Analg.out.132133 OFF / 0 to 20 / 4 to 20 mA OFF
Analg.out.132133 parameter 0 to 23 01
Analg.out.132133 0% 0 to 9,990 0000
Analg.out.132133 100% 0 to 9,990 0200
Pulse output 1 +kWh / -kWh
Pulse output 1 logic positive/negative negative
Active energy Pulse/kWh 0.1 to 150.0 001.0
Pulse output 2 +kvarh / -kvarh
Pulse output 2 logic positive/negative negative
Reactive energy Pulse/kvah 0.1 to 150.0 001.0
CONFIGURE DRIVE
Configure Drive YES/NO YES Y N Y N
Automatic idle Running ON/OFF OFF on off on off
Download and open GCB ON/OFF ON on off on off
Monitoring on at f gen > 15 to 70 Hz 15 Hz
Monitoring on after 0 to 99 s 08 s
CONFIGURE COUNTER
Configure Counters YES/NO NO Y N Y N
Service interval ON/OFF ON on off on off
Service interval in 0 to 9.999 h 0300 h
Op.hours counter ON/OFF ON on off on off
Op.hours counter set 0 to 65,000 h 00000 h
Start counter ON/OFF ON on off on off
Start counter set 0 to 32,000 00000
Display kWh +- on? Y/N YY
Display kvarh +- on? Y/N YY
Time 00:00 to 23:59 00:00
Year,month 00 to 99, 1 to 12 00,00
Day,weekday 01 to 31, 1 to 7 00,0
Appendix H.
Service Options
CAUTION
To prevent damage to electronic components caused by improper handling, read and observe the pre-
cautions in Woodward manual 82715, Guide for Handling and Protection of Electronic Controls, Printed
Circuit Boards, and Modules.
Packing a Control
Use the following materials when returning a complete control:
NOTE
We highly recommend that you make arrangement in advance for return shipments. Contact a
Woodward customer service representative at +49 (0) 711 789 54-0 for instructions and for a Re-
turn Authorization Number.
Replacement Parts
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
When ordering replacement parts for controls, include the following information:
• the part numbers P/N (XXXX-XXX) that is on the enclosure nameplate
• the unit serial number S/N, which is also on the nameplate
Woodward GmbH
Handwerkstrasse 29
70565 Stuttgart - Germany
Phone: +49 (0) 711 789 54-0 (8:00 - 16:30 German time)
Fax: +49 (0) 711 789 54-100
eMail: stgt-info@woodward.com
For assistance outside Germany, call one of the following international Woodward facilities to obtain the address
and phone number of the facility nearest your location where you will be able to get information and service.
You can also contact the Woodward Customer Service Department or consult our worldwide directory on
Woodward’s website (www.woodward.com) for the name of your nearest Woodward distributor or service fa-
cility. [For worldwide directory information, go to www.woodward.com/ic/locations.]
Engineering Services
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Woodward Industrial Controls Engineering Services offers the following after-sales support for Woodward
products. For these services, you can contact us by telephone, by e-mail, or through the Woodward website.
• Technical support
• Product training
• Field service during commissioning
Technical Support is available through our many worldwide locations, through our authorized distributors, or
through GE Global Controls Services, depending on the product. This service can assist you with technical ques-
tions or problem solving during normal business hours. Emergency assistance is also available during non-
business hours by phoning our toll-free number and stating the urgency of your problem. For technical engineer-
ing support, please contact us via our toll-free or local phone numbers, e-mail us, or use our website and refer-
ence technical support.
Product Training is available on-site from several of our worldwide facilities, at your location, or from GE
Global Controls Services, depending on the product. This training, conducted by experienced personnel, will as-
sure that you will be able to maintain system reliability and availability. For information concerning training,
please contact us via our toll-free or local phone numbers, e-mail us, or use our website and reference customer
training.
Field Service engineering on-site support is available, depending on the product and location, from our facility
in Colorado, or from one of many worldwide Woodward offices or authorized distributors. Field engineers are
experienced on both Woodward products as well as on much of the non-Woodward equipment with which our
products interface. For field service engineering assistance, please contact us via our toll-free or local phone
numbers, e-mail us, or use our website and reference field service.
Technical Assistance
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
If you need to telephone for technical assistance, you will need to provide the following information. Please write
it down here before phoning:
Contact
Your company____________________________________________________
Your name_______________________________________________________
_______________________________________________________________
_______________________________________________________________
_______________________________________________________________
_______________________________________________________________
_______________________________________________________________
Please be sure you have a list of all parameters available. You can print this using LeoPC1. Additionally you can
save the complete set of parameters (standard values) and send them to our Service department via e-mail.
Woodward GmbH
Handwerkstrasse 29 - 70565 Stuttgart - Germany
Phone +49 (0) 711 789 54-0 • Fax +49 (0) 711 789 54-100
stgt-info@woodward.com
Homepage
http://www.woodward.com/power
2008/12/Stuttgart