Instruction Manual: MX322 Automatic Voltage Regulator (AVR)
Instruction Manual: MX322 Automatic Voltage Regulator (AVR)
Instruction Manual: MX322 Automatic Voltage Regulator (AVR)
INSTRUCTION MANUAL
English
Original Instructions A062V276 (Issue 1)
Table of Contents
1. DESCRIPTION ...................................................................................................................... 1
2. SPECIFICATION ................................................................................................................... 3
3. CONTROLS........................................................................................................................... 5
The AVR provides closed loop control by sensing the alternator output voltage at the main stator
windings and adjusting the exciter stator field strength. Voltage induced in the exciter rotor, rectified by
the rotating diodes, magnetises the rotating main field which induces voltage in the main stator
windings. A separately-excited AVR is independently powered from a separate permanent magnet
generator (PMG), mounted on the main alternator rotor shaft. Voltage is induced in the stator of the
PMG by a rotor of permanent magnets.
1
De-rate linearly from 4.2 A at 50 °C to 3.2 A at 70 °C
2
With 4% engine governing. The stated voltage regulation may not be maintained in the presence of certain transmitted
radio signals. Any change in regulation will fall within the limits in Criteria B of BS EN 61000-6-2: 2001
3
After 10 minutes
4
Alternator de-rate may apply. Check with factory.
5
Factory set, semi-sealed, jumper selectable
6
Any device connected to the analogue input must be fully floating (galvanically isolated from ground), with an
insulation strength of 500 VAC
7
Non-condensing.
DANGER
Live Electrical Conductors
Live electrical conductors at output, AVR and AVR accessory terminals, and AVR heat sink
can cause serious injury or death by electric shock and burns.
To prevent injury, take suitable precautions to prevent contact with live conductors including
personal protective equipment, insulation, barriers and insulated tools.
NOTICE
Refer to alternator wiring daigram for connection details.
The AVR controls are set at the factory for initial running tests. Check that the AVR settings are
compatible with your required output. Do not adjust controls that have been sealed. To set up a
replacement AVR, follow these steps:
1. Stop and isolate the generator set.
2. Install and connect the AVR.
3. Turn the AVR [VOLTS] volts control Section 3.3 on page 7 fully counter-clockwise.
4. Turn the hand trimmer (if fitted) to 50%, the midway position.
5. Turn the AVR [STAB] stability control Section 3.4 on page 8 to 50%, the midway position.
6. Connect a suitable voltmeter (0 to 300 VAC range) between one output phase and neutral.
7. Start the generator set with no load.
8. Adjust speed to nominal frequency (50 to 53 Hz or 60 to 63 Hz).
9. If the LDE is lit, adjust the AVR [UFRO] control Section 3.5 on page 8.
10. Carefully turn AVR [VOLTS] control clockwise until the voltmeter shows rated voltage.
11. If voltage is unstable, adjust the AVR [STAB] stability control.
12. Re-adjust the AVR [VOLTS] control, as needed.
NOTICE
Hand trimmer terminals may be above earth potential. Do not ground any of the hand trimmer
terminals. Grounding hand trimmer terminals could cause equipment damage.
3. Check that the remote hand trimmer is fitted or terminals 1 and 2 are linked.
NOTICE
If a remote hand trimmer is connected, set it to 50%, the midway position.
NOTICE
If the voltage is unstable set the AVR stability before proceeding Section 3.4 on page 8.
NOTICE
0% to 100% rotation corresponds to 90% to 110% VAC
NOTICE
If the voltage is unstable go immediately to step 5.
6. Adjust the AVR [STAB] control slowly counter-clockwise until the output voltage becomes
unstable.
7. Adjust the AVR [STAB] control slowly clockwise until the voltage is stable.
8. Adjust the AVR [STAB] control a further 5% clockwise.
NOTICE
Readjust the voltage level if necessary (see Section 3.3 on page 7).
NOTICE
If the voltage is high / low / unstable, use method Section 3.3 on page 7 or Section 3.4
on page 8 before proceeding.
6. Reduce the alternator speed to approximately 95% of correct operating speed. i.e. 47.5 Hz for 50
Hz operation, 57.0 Hz for 60 Hz operation.
7. Adjust the AVR [UFRO] control slowly counter-clockwise until the AVR LED lights.
8. Adjust the AVR [UFRO] control slowly clockwise until the AVR LED is just OFF.
NOTICE
Do not go past the point at which the LED is just OFF.
9. Adjust the alternator speed back to 100% nominal. The LED should be off.
An analog input (-5 VDC to +5 VDC) modifies the AVR excitation voltage, by adding to, or subtracting
from, the sensed alternator voltage. A Stamford Power Factor Controller (PFC3) can provide such an
input. The AVR [TRIM] control adjusts the effect.
1. Connect the analog input from the PFC3, or similar, to terminals A1 and A2 of the AVR. Terminal
A1 is connected to AVR zero volts. Positive voltage connected to A2 increases AVR excitation,
negative voltage connected to A2 decreases AVR excitation.
2. Turn the AVR [TRIM] control to the desired position. The analog signal has no effect on
excitation when the AVR [TRIM] control is fully counter-clockwise, and maximum effect when
fully clockwise.
The AVR protects the alternator by removing excitation if it senses that the alternator output voltage
exceeds a threshold set by the AVR [OVER V] control.
1. If the alternator output voltage exceeds the over-voltage setting, the red LED on the AVR turns
on.
2. After a short time, the AVR removes the excitation voltage and the red LED flashes (which can
also indicate an over-excitation trip or UFRO operation).
3. Stop the alternator to reset the over-voltage condition.
The AVR protects the alternator by removing excitation if it senses that the excitation voltage exceeds
a threshold set by the AVR [EXC] control.
1. If the excitation voltage exceeds the over-excitation trip setting, the red LED on the AVR turns
on.
2. After a short time, the AVR removes the excitation voltage and the red LED flashes (which can
also indicate an over-voltage trip or UFRO operation).
3. Stop the alternator to reset the over-excitation condition.