This document provides an operation manual for the ADVR-12 hybrid universal analog-digital voltage regulator. The ADVR-12 is a 12 amp regulator compatible with many common regulators. It features voltage sensing without potential transformers up to 520 volts and new DIP and TRIM adjustments compatible with automatic paralleling and power factor controllers. The manual provides specifications, installation guidelines, adjustment procedures, connection terminal explanations, and wiring instructions for the ADVR-12 regulator.
This document provides an operation manual for the ADVR-12 hybrid universal analog-digital voltage regulator. The ADVR-12 is a 12 amp regulator compatible with many common regulators. It features voltage sensing without potential transformers up to 520 volts and new DIP and TRIM adjustments compatible with automatic paralleling and power factor controllers. The manual provides specifications, installation guidelines, adjustment procedures, connection terminal explanations, and wiring instructions for the ADVR-12 regulator.
This document provides an operation manual for the ADVR-12 hybrid universal analog-digital voltage regulator. The ADVR-12 is a 12 amp regulator compatible with many common regulators. It features voltage sensing without potential transformers up to 520 volts and new DIP and TRIM adjustments compatible with automatic paralleling and power factor controllers. The manual provides specifications, installation guidelines, adjustment procedures, connection terminal explanations, and wiring instructions for the ADVR-12 regulator.
This document provides an operation manual for the ADVR-12 hybrid universal analog-digital voltage regulator. The ADVR-12 is a 12 amp regulator compatible with many common regulators. It features voltage sensing without potential transformers up to 520 volts and new DIP and TRIM adjustments compatible with automatic paralleling and power factor controllers. The manual provides specifications, installation guidelines, adjustment procedures, connection terminal explanations, and wiring instructions for the ADVR-12 regulator.
Digital Voltage Regulator Operation Manual Self Excited Automatic Voltage Regulator For use in Brushless PMG and Auxiliary Winding 4501 NW 27 Ave Miami Florida 33142 305.634.1511
______________________________________________________________________________________ 2 ADVR-12 1. SUMMARY The ADVR-12 is a totally new hybrid 12 Amp universal voltage regulator with a comparable footprint as the Basler* AVC63-12 and AVC125-10, CAT* VR6, KATO* K65-12B and K125-10B, and the Leroy Somer* 202-8634, and many other. To simplify installation, voltage sensing without PTs up to 520 volts was added, also new DIP & TRIM adjustment compatible with many automatic paralleling and PF controllers in the market. The new CPU design makes the ADVR-12 exceedingly stable, however keeping the analog power circuit for fast response. 2. SPECIFICATION Sensing Input 1 Voltage 220 / 440VAC 50 / 60Hz (SW5 Selectable) 180 ~ 260VAC @ 220VAC 330 ~ 520VAC @ 440VAC Power Input 1 or 3 Voltage 100 ~ 300VAC, 40 ~ 500Hz Output 63VDC @ 110VAC input 125VDC @ 220VAC input Output Current Continuous 12ADC Maximum 25ADC for 10 sec Frequency 50 / 60Hz (SW4 Selectable) 40 ~ 51Hz @ 50Hz Preset 47Hz 50 ~ 61Hz @ 60Hz Preset 57Hz Voltage Regulation < 0.5% ( with 4% engine governing ) Voltage Build-up Residual voltage at AVR terminal > 6 VAC @ 25Hz Thermal Drift 0.03% per
C change in AVR ambient
Over Excitation Protection 60% of Input Voltage External Volts Adjustment VR 10K ohm 0.5 watt trimmer Excitation Resistance > 10 ohm Current Compensation 1 or 5A > 0.2VA Max 7% @ P.F 0.5 Analogue Voltage Input Un0 ~ 10% @ 5VDC <2mA Respond Time < 1 Cycle Unit Power Dissipation Max. 12 watt Dimensions 214mm L * 163mm W * 45.7mm H Weight 1130g 2%
ATTENTION 1. AVR can be mounted directly on the engine, genset, switchgear, control panel, or any position that will not affects operation. For dimension reference, please see Figure 1. 2. All voltage readings are to be taken with an average-reading voltmeter Meggers and high-potential test equipment must not be used. Use of such equipment could damage the AVR. 3. Secure all wiring connection. Do not install AVR at a place with high vibrations to prevent loose connections. For safety do not touch the heat sink while in operation. 4. Fuse specification12A / 250V slow blow type.
Outline and Drilling Diagram Figure 1 UNITS : mm
______________________________________________________________________________________ ADVR-12 3 3. DIP SWITCH ADJUSTMENT (SW) KW SW <90KW 90~500KW >500KW 1 OFF ON ON 2 OFF OFF ON
SW ON OFF 3 O/E Deactivated O/E Activated 4 50Hz 60Hz 5 440V 220V
ATTENTION When 60Hz frequency setting is selected on a 50Hz generator, it could result in under voltage. When 50Hz frequency setting in selected on a 60Hz generator, it could result in over excitation current when stopping the generator and cause sever damage to the generator or AVR. After adjusting SW1 or 2, the STAB must be recalibrated to ensure maximum performance. All adjustment of SW must be conducted when engine is not in operation. 4. ADJUSTMENT 4.1 VOLT Voltage setting adjusting the genset rated output voltage. When SW5 is OFF (220V) adjustable range is 175 ~ 260VAC. When SW1 is ON (440V) adjustable range is 350 ~ 520VAC. When terminal 7 & 4 are bridged together, voltage adjustment is on the AVR VOLT VR. When connect a 10k ohm external VR to terminal 7 & 6a the voltage adjustment can be adjusted remotely (When terminal 7 & 4 is open circuit the AVR VOLT VR is ineffective. ATTENTION AVR AC voltage readings are all average value. 4.2 STAB Adjust STAB fully clockwise, the generator voltage will begin to fluctuate, whereas if adjust fully counterclockwise the voltage becomes stable. The correct stability setting is at a knee point, where the voltage is stable yet on the brink of becoming unstable. If Stability is over adjusted, it can result in high voltage fluctuation when load is connected. 4.3 U/F Under frequency protection adjustment. When generator frequency falls below the knee point, the under frequency protection circuit will begin to intervene and voltage and frequency begin to decrease in linear descend. Coordinate with the DIP switch SW4 frequency selection 50/60Hz. When selecting 50Hz the adjustable range is from 40 to 51Hz and the factory presets at 47Hz. When selecting 60Hz the adjustable range is from 50 to 61Hz and the factory presets at 57Hz. 4.4 U/F LED When under frequency protection is activated, the RED LED will light up. 4.5 DIP When under frequency protection is activated, the voltage droop ratio is adjusted via the DIP VR. The adjustable range is 3 ~ 10 V/Hz. 4.6 DROOP Droop adjustment. When paralleling, the AVR compensate the input rating and voltage shifting basis on load current, through internal circuit calculation and increase or decrease the voltage. When phase current lag the voltage, it decreases original voltage setting and if the phase current lead the voltage then it increases the original voltage setting. The increase and decrease range can be preset by the DROOP adjustment. 4.7 TRIM Analogue voltage Input sensitivity. When terminal 2 and 3 is added with a DC input (0 ~ 5V), the TRIM is used to adjust the influence level from the DC input to the rated voltage. If the TRIM potential (POT) is adjusted fully counter-clockwise, and then the additional signal will not cause any influence. On the contrary if the TRIM is adjusted fully clockwise, then the additional signal will produce a maximum effect. 4.8 O/E The protection is enabled by selecting DIP SW 3 to OFF position (Protection disabled when DIP SW 3 select to ON). The O/E voltage setting is at 125VDC 5V. If generator excitation voltage exceeds the setting the AVR will shutdown the excitation output and illuminate the O/E LED. To reset the protection, stop generator for 30 seconds before restart. The higher the excitation voltage the faster the AVR enables the protection from 0.1 ~ 20 seconds. If O/E is disabled, (DIP SW 3 to OFF position) the AVR does not shutdown the generator excitation output but only illuminate the O/E LED.
______________________________________________________________________________________ 4 ADVR-12 5. CONNECTION TERMINAL PIN NO. NOTES CH GND Ground 2 Analogue voltage input 3 4 For onboard voltage adjustment 4 & 7 Shorted For external voltage adjustment (Connect 10K ohm VR to 6a & 7) 4 & 7 Open 5 CT (Current Transformer) 1A input 5a CT (Current Transformer) 5A input 6 CT (Current Transformer) common 6a Bridge selection common 7 For onboard voltage adjustment 4 & 7 Shorted For external voltage adjustment (Connect 10K ohm VR to 6a & 7) 4 & 7 Open 8 Null 9 9 & 6a Open for single phase sensing 20 R phase sensing input 22 S phase sensing input 26 3 power input 28 1 or 3 power input 30 1 or 3 power input F1 Positive + excitation output F2 Negative excitation output 5.1 Manual excitation / Flash (None PMG system) A newly assembled generator, a exciter with incorrect polarity or with field residual voltage less than 6VAC, please disconnect the AVR wiring connection with engine at rest and follow the steps below : Series a limiting resistor at F1 (Positive) & F2 (Negative) and apply a DC input (Do not exceed 24VDC). The resistance is 1ohm per volt with 1 watt per volt at power. For example : If the DC input is 24VDC with 24ohm the resistor should be 24 watt. Remove DC power input from exciter after 5 seconds. Reconnect wiring. Start up engine, and if the measured residual voltage is still below 6Vac, repeat step 1 and 2. 5.2 Under frequency protection Knee point setting 50Hz adjustable range 40 ~ 51Hz Factory preset at 47Hz 60Hz adjustable range 50 ~ 61Hz Factory preset at 57Hz Adjustment steps as follow : From DIP select generator frequency. Startup generator and adjust to rated speed. Adjust UF VR to maximum (Clockwise), adjust voltage to rated. Decrease engine speed to required knee point activation frequency. Slowly ad SW4 just UF VR counterclockwise until voltage begins to decrease (UF LED illuminates). The under frequency protection only activate when generator frequency falls under the knee point setting, to prevent AVR from over excitation and causing damage. The V/Hz decrease margin is adjusted via DIP VR. 5.3 Wiring 1. Power Input (26, 28, 30) Terminals 26, 28, 30 are for 3 phase power input and terminals 28, 30 are for single phase power input. The input voltage 100 ~ 300VAC, 40 ~ 500Hz from PMG, Auxiliary winding, generator power input. If a switch is required to shutdown the excitation output, add a switch at terminals 26, 28, 30 to shut down AVR power. 2. Sensing Input (20, 22) 20, 22 are for single phase sensing input. In a single phase sensing input, terminals 9, 6a will need to be opened. Terminals 22, 24 need to be shorted and connect sensing input to terminals 20, 22, incorporating the DIP SW5 voltage setting. In a 220V SHUNT type generator, the power input and sensing input can be combined together.
______________________________________________________________________________________ ADVR-12 5 3. Analogue Voltage Input (2, 3) Terminal 2 & 3 are Analogue Voltage Input, for connecting to remote voltage control (Paralleling Controller) of Var / PFC (Power Factor Controller). When TRIM is adjust to maximum, entering 5VDC will effectively change the generators rated voltage by 10%, and if adjust to minimum, the analogue voltage input becomes ineffective. 4. Droop Compensation (5, 5a, 6) When paralleling, connecting a N : 1A CT at terminal 5 & 6 or connection a N : 5A CT at terminal 5a & 6 enables DROOP VR to adjust the generator voltage droop rate (Adjust clockwise to increase). The CT must never install on the same phase as the sensing input (Terminal 20 & 22). Circuit Voltage Compensation.
If CT input signal is reversed (K, L), it can become current compensation for the generator output, therefore the generator will voltage increase with the load current. The increase ratio is adjusted via the DROOP VR (Adjust clockwise to increase). 5. External VR (7, 6a) Terminal 4 & 7 must be shorted if external voltage adjustment is not required. When external voltage adjustment is required, connect one 10K ohm 1/2W VR to terminal 7 & 6a (The onboard VR then becomes ineffective). WARNING Please make sure you have read and understand the contents of the instruction manual prior to installation. Incorrect wiring connection may result in irreversible damage to the product and other equipments.
Figure 6 CT Input 5 & 6 for 1Amps, 5a & 6 for 5Amps
ADVR-12 Testing Procedure : 1. Setup ADVR-12 as shown in Figure 7. and switch SW5 to OFF position. 2. Turn VOLT VR fully counterclockwise then connect to power. Lamp should be off at this time. 3. Slowly adjust VOLT VR clockwise, the lamp will illuminate, then adjust counterclockwise the lamp should turn off. 4. If lamp is constantly illuminating or unable to illuminate then change to another AVR. Figure 7 AVR Testing Wiring Diagram
Figure 8 PMG Wiring Diagram If generator rated voltage differs from ADVR-12 : sensing voltage, add PT1 CT = 1A connect to 5 & 6, CT = 5A connect to 5a & 6 Figure 9 AUX. Wiring Diagram If generator rated voltage differs from ADVR-12 : sensing voltage, add PT1 power input voltage, add PT2 CT = 1A connect to 5 & 6, CT = 5A connect to 5a & 6 Use only original supplied spare protection fuse for fuse replacement. Please accept our sincere apology if any modification in performance, specification or appearance is made without prior notice. T7 T8 PMG Almost all Cat generators even if they work at 480/277v are sensing at 240Volts So be careful how you set up Voltage sensing on the ADVR-12 SW -5 T9 Use Jumper for 3 Phase sensing Open for single Phase sensing
Terminals 2 & 3 are normally not used. But come in handy if you need to correct PF. SW1 & SW2 SET GENERATOR SIZE (see Manual) SW3 OFF (Over Excitation Protection ON SW3 ON (Over Excitation Removed) SW4 OFF (60Hz) ON (50Hz) SW5 OFF (220V) ON (480 V) Sensing When using Single Phase Sensing Jumper 22 and 24 and remove Jumper from 6a to 9 L1 L2 L3 Connect 10k Ohm remote voltage adjust from 6a to 7 and remove bridge from 4 and 7. Keep bridge when using internal voltage adjust 6a 7 10k CT 1A 5A No more then 300Vac on the power input terminals T7 L1 Almost all Cat generators even if they work at 480/277v are sensing at 240Volts So be careful how you set up Voltage sensing on the ADVR-12 SW -5 T8 T9 Use Jumper for 3 Phase sensing Open for single Phase sensing
Terminals 2 & 3 are normally not used. But come in handy if you need to correct PF. SW1 & SW2 SET GENERATOR SIZE (see Manual) SW3 OFF (Over Excitation Protection ON SW3 ON (Over Excitation Removed) SW4 OFF (60Hz) ON (50Hz) SW5 OFF (220V) ON (480 V) Sensing When using Single Phase Sensing Jumper 22 and 24 and remove Jumper from 6a to 9 L2 L3 Connect 10k Ohm remote voltage adjust from 6a to 7 and remove bridge from 4 and 7. Keep bridge when using internal voltage adjust 6a 7 10k CT 1A 5A
Terminals 2 & 3 are normally not used. But come in handy if you need to correct PF. SW1 & SW2 SET GENERATOR SIZE (see Manual) SW3 OFF (Over Excitation Protection ON SW3 ON (Over Excitation Removed) SW4 OFF (60Hz) ON (50Hz) SW5 OFF (220V) ON (480 V) Sensing When using Single Phase Sensing Jumper 22 and 24 and remove Jumper from 6a to 9 Connect 10k Ohm remote voltage adjust from 6a to 7 and remove bridge from 4 and 7. Keep bridge when using internal voltage adjust 6a 7 10k CT 1A 5A L1 L2 Remove Jumper from 6a to 9 for Single Phase sensing 240/120Vac Field Set SW 1 & 2 to Proper Genset Size Set SW 3 to OFF Activate O/E -- ON Deactivate (when Paralleling) O/E Set SW 4 to OFF for 60 Hz ON for 50 Hz Set SW 5 to OFF Cat genset always sense at 220 V P12 = 12 Pin Plug P6 = 6 Pin Plug