DSE555 Data Sheet
DSE555 Data Sheet
FEATURES
DESCRIPTION
Enhanced
power
measurement
module provides all the functions of
the Basic unit but also includes full
power monitoring instrumentation
(detailed right) and powerful auto-sync
functions as standard. The inclusion
of auto-sync now allows the OEM to
offer the choice of clean break or
Bumpless no break transfers to and
from the gen-set.
No need for
complex sync panels etc. Simply use
the 555 Power measurement module
and interface to the engine governor
and AVR.(No break transfer using the
555 module requires connecting to a
suitable electronic governor and AVR.)
Generator Frequency Hz
Mains Frequency Hz
Engine Temperature
AMF AND
INSTRUMENTATION
MODULE
Issue 6
VH 18/03/03
Status Page
Alarm Page
Engine Instruments Page
Generator Instruments Page
Mains Instruments Page
Event Log Page
DESCRIPTION
CONTINUED
SPECIFICATION
DC Supply:
8 to 35 V Continuous.
Cranking Dropouts:
Able to survive 0 V for 50 mS, providing
supply was at least 10 V before dropout
and supply recovers to 5V. This is
achieved without the need for internal
batteries.
Max. Operating Current:
513mA at 12 V. 263 mA at 24 V.
Max. Standby Current:
370 mA at 12 V. 210 mA at 24 V.
Alternator Input Range:
15 V(ph-N) to 277 V(ph-N) AC (+20%)
Alternator Input Frequency:
50 - 60 Hz at rated engine speed
(Minimum: 15V AC Ph-N)
Magnetic Pick-up Voltage Input
Range:
+/- 0.5 V to 70 V Peak
Magnetic Input Frequency: 10,000 Hz
(max)
Mains Sensing Input Range:
15V(ph-N) to 277V(ph-N) AC (+20%)
Mains Sensing Input Frequency:
50 - 60 Hz at rated engine speed
(Minimum: 15V AC Ph-N)
Start Relay Output:
16 Amp DC at supply voltage.
Fuel Relay Output:
16 Amp DC at supply voltage.
Auxiliary Relay Outputs:
5 Amp DC at supply voltage.
Generator loading Relay Output:
8 Amp AC 250V.
Mains loading Relay Output:
8 Amp AC 250V
Charge Fail / Excitation Range:
0 V to 35 V
Operating Temperature Range:
-30 to +70C
Dimensions:
192mm x 144mm x 138mm
7.6 x 5.7 x 5.5
NOTE
An Automatic Start version of the 555
is also available (Model 550).
Please refer to Deep Sea Electronics
for details
Warm-up timer
Cooling timer
TELEMETRY
The 555 module provides the user with
the option of full telemetry facilities via
the optional communications software.
The module can be either connected to
the PC using the 810 interface or via a
suitable modem (Optional: Remote
Communications output version only).
The PC software is MS-Windows TM
based and allows the operator to
control the module from a remote
location.
The remote operator can also view the
instrumentation, Alarm and Data log
details, and the relay and input status.
All access is password controlled so
unauthorised
operators cannot log
onto the system.
Additionally in the event of the module
detecting an alarm condition, it will
initiate a modem dial out to the host PC
to inform the remote operator of the
problem, giving identification of the
module followed by the alarm event
and the time and date of occurrence.
(Optional: Remote Communications
output version only).
If using a GSM modem, the module is
also able to send text messages to a
GSM cell phone to indicate gen-set,
site and alarm condition.
ENVIRONMENTAL
TESTING STANDARDS
EVENT CAPTURE
The standard module features event
capture facilities, this records the last
25 shutdown alarms allowing the
operator to view the recent operating
history of the module to assist in fault
finding, etc.
Event Log:
19 Apr2000 14:34:14
CONFIGURATION
BUILT-IN FUNCTIONS
SYNCHRONISING
AND LOAD CONTROL
OPTIONS
Sync check
Governor/engine speed control
AVR/voltage control
Dead bus sensing
Synchroscope
No break change-over
Parallel running with the mains
KW/kVAr load control with mains
Hz +0.9
V +0.2
Electromagnetic Compatibility
BS EN 50081-2 EMC Emission
Standard for the Industrial Environment
BS EN 50082-2 EMC Immunity
Standard for the Industrial Environment
Vibration
BS EN 60068-2-6 Ten sweeps (up and
back down) at 1 octave/minute in each
of the three major axes.
5Hz to 8 Hz @ +/-7.5mm constant
displacement.
8Hz to 500 Hz @ 2gn constant
acceleration
Temperature
Cold:
BS EN 60068-2-1-to -300 C
Hot:
BS EN 60068-2-2 to 700 C
Humidity
BS EN 2011 part 2.1 93% RH @ 400 C
for 48 hours
Shock
BS EN 60068-2-27 Three half sine
shocks in each of the three major axes
15gn amplitude. 11mS duration.
Electrical Safety
BS EN 60950 Low Voltage
Directive/Safety of information
technology equipment, including
electrical business equipment.
CASE DIMENSIONS
144.0mm
5.7
137mm
5.4
155.0mm
110mm
4.3
185.0mm
7.3
192.0mm
7.6
Panel Cut-out:138mmx185mm
5.5 x 7.3
7.5mm
0.3
TYPICAL CONNECTIONS
LOAD
L1
L2
L3
Current
Transformers
ALTERNATOR
MAINS
Generator
Contactor
Mains
Contactor
Electrical Interlock
29 34 33
25 26 27
32
31
36
35
Generator Loading
Relay
38
40 39
Mains Loading
Relay
42
43
44 45
18
19
FCC68 - 8 Way
1
20 21
22
24
9 10 11 12 13 14 15 16 17
23
30
4
Oil
Sender
810
Configuration
Temp
Sender
MPU
NOTE:When connected to a
completed Panel / Gen-set
Real-time diagnostic display
is available
5
These Ground connections must be
on the engine block and must
be a sound electrical connection
to the sender bodies.
The wire to Terminal 24 must not
be used to provide a ground
connection to any other device
6
7
8
9
Configurable inputs