Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Equipotential Bonding Required For Multi-Level Buildings Lightning Rods

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

R - EMC guidelines

2 Earthing principles and


structures

7KHUHFRPPHQGHGFRQ¿JXUDWLRQIRUWKHHDUWKLQJQHWZRUNDQGHOHFWURGHVLVWZRRU
three dimensional (see Fig. R5). This approach is advised for general use, both
in terms of safety and EMC. This recommendation does not exclude other special
FRQ¿JXUDWLRQVWKDWZKHQFRUUHFWO\PDLQWDLQHGDUHDOVRVXLWDEOH

Equipotential bonding required for


multi-level buildings
lightning rods

"Electrical" and "communication"


earthing as needed

Multiple interconnected earth electrodes

Fig. R5 : Installation with multiple earth electrodes

In a typical installation for a multi-level building, each level should have its
own earthing network (generally a mesh) and all the networks must be both
interconnected and connected to the earth electrode. At least two connections are
required (built in redundancy) to ensure that, if one conductor breaks, no section of
the earthing network is isolated.
Practically speaking, more than two connections are made to obtain better symmetry
LQFXUUHQWÀRZWKXVUHGXFLQJGLIIHUHQFHVLQYROWDJHDQGWKHRYHUDOOLPSHGDQFH
between the various levels in the building.
The many parallel paths have different resonance frequencies. If one path has a high
impedance, it is most probably shunted by another path with a different resonance
frequency. On the whole, over a wide frequency spectrum (dozens of Hz and MHz),
a large number of paths results in a low-impedance system (see Fig. R6).
Each room in the building should have earthing-network conductors for equipotential
Fig. R6 : Each level has a mesh and the meshes are bonding of devices and systems, cableways, trunking systems and structures. This
interconnected at several points between levels. Certain system can be reinforced by connecting metal pipes, gutters, supports, frames, etc.
JURXQGÀRRUPHVKHVDUHUHLQIRUFHGWRPHHWWKHQHHGVRI ,QFHUWDLQVSHFLDOFDVHVVXFKDVFRQWUROURRPVRUFRPSXWHUVLQVWDOOHGRQIDOVHÀRRUV
certain areas ground reference plane or earthing strips in areas for electronic systems can be used
to improve earthing of sensitive devices and protection interconnection cables.

R4
Schneider Electric
ll rights reserved

You might also like