Air Heater
Air Heater
Air Heater
Fault Finder
for Warm Air Heating
R E L I A B I L I T Y Y O U C A N T R U S T
2. Modairflow Series 1 4
3. Modairflow Series 2 8
5. System E-T 16
6. Economaire 20
7. Proportional Balancing 24
9. Spillage Test 27
www.johnsonandstarley.co.uk
GENERAL VENTILATION INFORMATION
From the 1st June 2008, all installations providing less than
90% of the ventilation requirements will be regarded as AR.
Models
1
J15-22 Mk 1, 2 & 3
J25-32 Mk 1, 2 & 3
JA33-43
J54-64
JT19-25
JTRS22-25
JWD38-50
www.johnsonandstarley.co.uk
MAIN BURNER NOT OPERATING
Check Pilot Burner is lit, Time Control is ON, Thermista-stat turned UP
6
5
4
PLEASE NOTE: The unit will have either 2
3
Models
2
OPERATIONAL CHECKS
J70-90
J55-65
JB40-50
JU40-50
JB16-20
JB25-30
Q44
HI-SPEC J30
HI-SPEC J50
HI-SPEC J65
HI-SPEC J90
HI-SPEC JU55
www.johnsonandstarley.co.uk
MAIN BURNER NOT OPERATING
Check Pilot Burner is lit, Time Control is ON, Thermista-stat turned UP
10 www.johnsonandstarley.co.uk
MAIN BURNER ON FOR BRIEF PERIOD ONLY
Check Thermista-stat control knob is on maximum setting
Bridge out Thermista-stat connection at heater
Models
2
OPERATIONAL CHECKS
J70-90
J55-65
JB40-50
JU40-50
JB16-20
JB25-30
Q44
HI-SPEC J30
HI-SPEC J50
HI-SPEC J65
HI-SPEC J90
HI-SPEC JU55
12 www.johnsonandstarley.co.uk
SYMPTOM POSSIBLE CAUSE REMEDY
Check for gas at inlet pressure
No gas supply to heater test point on Multifunctional
Control
Purge gas supply pipe in
Gas supply pipe not purged
Pilot will not light accordance with BS 6891
Clear pilot orifice or replace
Pilot orifice restricted
pilot injector
Check ignitor, lead and
Piezo system faulty
electrode
Connection between
Thermocouple and
Check connection is secure
Multifunctional Control not
Pilot lights but goes secured
out on releasing START Faulty power unit on Replace Multifunctional
button during initial Multifunctional Control Control
light-up, or after normal
Faulty Thermocouple Replace Thermocouple
operation
Pilot flame of insufficient
Adjust
length
Pilot orifice restricted Replace pilot injector
Loose electrical connection
Check connections
fan delay control
Fan control set incorrectly Check for correct settings
Main burner lights but
Replace, taking care not to
fan fails to run after Faulty fan assembly
damage impeller
approx 3 minutes
Faulty fan control Replace fan control
Burner setting pressure not
Adjust pressure as necessary
correct
Gas rate or burner pressure Check gas rate and burner
setting high pressure setting
Adjust fan speed or gas rate
Temperature rise excessive
accordingly
Air filter or return air path Check filter is clean and air
Main burner operating restricted path is clear
intermittently with fan
running Excessive number of outlets
Open additional outlets
closed
Carry out spillage test and
Spillage of flue gases
rectify
Spillage monitoring device
Replace spillage device
(TTB) faulty
14 www.johnsonandstarley.co.uk
Non-MODAIRFLOW CIRCUIT DIAGRAM
Models
OPERATIONAL CHECKS
HI-SPEC J25
HI-SPEC J25RS
HI-SPEC J25SC
HI-SPEC J32
HI-SPEC M31
HI-SPEC J40
16 www.johnsonandstarley.co.uk
MAIN BURNER NOT OPERATING
Fan runs Fan does not run Fan runs Fan does not run
Replace replace FDC/ Replace electronic Replace capacitor Replace fan
limit control module
Models
OPERATIONAL CHECKS
ECONOMAIRE 25
ECONOMAIRE 31
ECONOMAIRE 32
ECONOMAIRE 50
ECONOMAIRE 65
ECONOMAIRE 90
NOTE:
FAULTS 4, 5 & 6 RELATE TO THE AIR HEATER, WHILST
FAULTS 7, 8 & 9 RELATE TO THE WATER CIRCULATOR
20 www.johnsonandstarley.co.uk
NO DISPLAY
Check mains electrical supply
NO DISPLAY
Heater continually cycles in rest sequence Disconnect main supply & check continuity
across terminals 3 & 4
Reset button stuck or
broken approx. 2.1k Ω Open circuit
Check reset button & Replace Economaire
replace if broken module
22 www.johnsonandstarley.co.uk
DISPLAY F
Ignites on rest Fails to ignite
Air heater overheat Ignition controller lockput
Check filter for blockage Check wiring at pin 7
Check ductwork for restrictions Check limit switch wiring
Check return air path Fails to ignite
Check heat load for property Replace Economaire module/ignition
controller
DISPLAY H
Ignites on reset Fails to ignite on reset
Water circulator overheat Ignition controller lockout
Check water circulation Check wiring at pin 10
Check thermostat Check limit switch wiring
Fails to ignite
Replace Economaire module
ignition controller
YES NO
Rewire thermista-stat Replace Economaire
Thermista-stat
Telephone: 01604 762881 23
PROPORTIONAL BALANCING
A B C D
Warm air Room Guide Measured Column B Balancing velocities
outlet number balancing Velocities Column A Column A x Av Column C
velocities
24 www.johnsonandstarley.co.uk
Temperature rise checking across the heater
The temperature rise between the nearest available point in the
return air duct and the nearest available point on the supply air
duct must be between 45˚C and 55˚C; check as follows.
26 www.johnsonandstarley.co.uk
SPILLAGE TEST
Carry out a full test as follows, and ensure that the flue
operates effectively with all doors and windows closed and any
extractor fans in operation.