UPS Guide PDF
UPS Guide PDF
UPS Guide PDF
Business-Critical Continuity™
USER MANUAL
10H52179UM10 - rev. 3
Chloride 80-NET
1. INTRODUCTION .................................................................................. 5
1.1. Notes to the CE Declaration of Conformity ........................................................... 5
1.2. Symbols and pictograms ...................................................................................... 5
1.3. Terms used .......................................................................................................... 6
1.4. Documentation structure..................................................................................... 6
1.5. Information about the presence of foreign materials in the vicinity of UPS
equipment installations .............................................................................................. 6
2. PREPARATION FOR USE ....................................................................... 9
2.1. Transport ............................................................................................................. 9
2.2. Delivery and storage ............................................................................................ 9
2.3. Unpacking and unloading the cabinets from the pallet......................................... 9
2.4. Environmental conditions .................................................................................... 10
2.5. Access to service area and cooling system............................................................ 11
2.6. Installation and footprint...................................................................................... 12
3. INSTALLATION .................................................................................... 21
3.1. Electrical preparations.......................................................................................... 21
3.2. Currents and suggested cable sizes ...................................................................... 22
3.3. Physical appearance ............................................................................................. 23
3.4. External protection devices .................................................................................. 27
3.5. Backfeed protection............................................................................................. 31
3.6. External electrical connections ............................................................................. 32
3.7. Power connections............................................................................................... 32
3.8. Connecting the batteries...................................................................................... 39
3.9. Connections between battery compartments and UPS ........................................ 41
3.10. Handling the batteries ....................................................................................... 43
4. CONNECTIVITY PANEL......................................................................... 45
4.1. Slot for Connectivity Products - XS3 ..................................................................... 47
4.2. Slot for LIFE.net Products - XS6............................................................................. 47
4.3. Serial Interface for Service (serial input/output) - X3............................................. 47
4.4. Serial Interface for Connectivity Products (serial input/output) - X6 ..................... 47
4.5. Connector for external battery disconnector - XT1/2............................................ 47
4.6. Ethernet RJ-45 Interface for Service and Placement into service - X9 .................... 48
4.7. Connector for RPO (input and output) - XT3/8 ..................................................... 48
4.8. Customizable output/input contact - TB1 ............................................................ 49
4.9. SUB-D connector for parallel UPS connection - X19A, X19B.................................. 51
4.10. RJ-45 Ethernet interface for synchronization with external signal - X20 .............. 51
4.11. Battery Area Temperature sensor (input) - XT1 .................................................. 51
4.12. Connector for backfeed status (output) - XT2 .................................................... 52
5. NORMAL AND SAFE OPERATION.......................................................... 53
5.1. Function............................................................................................................... 53
5.2. Special features.................................................................................................... 54
5.3. Block diagram ...................................................................................................... 55
5.4. Maintenance Bypass............................................................................................. 56
1. INTRODUCTION
This User’s Manual contains information on the installation, operation and use of the
Chloride 80-NET Uninterruptible Power System (UPS).
We recommend reading this document before installing the equipment, which must be
operated only by qualified personnel.
Afterwards, the manual must be kept and referred to whenever work must be done on the
UPS.
However, it is not possible for Chloride to ensure that foreign bodies will not be
introduced during on-site installation, or when the UPS doors & covers are "open"
and the electrical terminals are exposed to allow power line connections to be
made by the electrical contractor/installer.
It is also not uncommon to have other personnel working in the same (UPS
equipment) room during on-site installation. Such personnel sometimes work
above the UPS equipment and associated auxiliary equipment/components.
To prevent major disruption to site operations and risk to property and
personnel, including the possibility of a fatality, each site's facility manager
or construction manager must prevent foreign bodies from being
introduced into the UPS module and associated auxiliary equipment/
components.
All UPS modules and associated auxiliary equipment/components are thoroughly
inspected by Chloride engineers prior to placement into service and testing on-
site. When conductive foreign bodies are identified, our engineers are instructed
to interrupt all work until the equipment and the area have been thoroughly
cleaned of any contaminants.
However, the person responsible for the site must ensure that the UPS module
and associated auxiliary equipment/components, and the immediate
surroundings, are kept clean and free from any possible conductive material such
as metal foil, food wraps, cable shields, washers and other hardware, scrap metal,
swarf and dust.
If the UPS system is shut down after placement into service & testing are
completed, the UPS room must be kept clean to avoid the possibility (during
restart) of the considerable volume of air-flow produced by UPS operation to
dislodge and/or drag any foreign bodies into the equipment, which would result
in system failure and possible supply interruption to the critical site load, and
several hours of downtime resulting from the damage typically associated with
such events.
If the UPS is left running/operational at the completion of placement into service
and testing, the room similarly needs to be kept clean to prevent foreign bodies
from entering the UPS module via its forced air-flow.
Chloride will not accept liability or pay damages deriving from accidents caused
by the introduction of conductive foreign bodies into the UPS module or
associated auxiliary equipment/components, which occured before or after the
unit is placed into service in its operating environment.
Figure 1 - Unpacking
If you do not plan to use the UPS within seven days of delivery, be sure to store it under the
conditions that meet product standard.
• If the batteries or the equipment are to be stored, they must be kept in a clean, dry
environment and away from extreme temperatures.
Installation altitude in m
AIR FLOW
INTAKE
FRONT
CABLE ENTRY
AREA
Figure 5 - Chloride 80-NET 60/80 kVA - UPS upper view (door open)
FRONT
CABLE ENTRY
AREA
Figure 7 - Chloride 80-NET 100/120 kVA - UPS upper view (door open)
FRONT
GLAND
PLATE
CABLE ENTRY
AREA
Figure 9 - Chloride 80-NET 160 kVA - UPS upper view (door open)
Figure 10 - Chloride 80-NET 200 kVA - UPS upper view (door open)
FRONT
CABLE ENTRY
AREA
GLAND
PLATE
Figure 12 - Chloride 80-NET 300 kVA - UPS upper view (door open)
Figure 13 - Chloride 80-NET 400 kVA - UPS upper view (door open)
FRONT
CABLE ENTRY
AREAGLAND
PLATE
Figure 15 - Chloride 80-NET 500 kVA - UPS upper view (door open)
3. INSTALLATION
3.1. Electrical preparations
Warning
For reasons of safety, the secondary access panel MUST NOT BE REMOVED.
If, for any reason, it is necessary to remove this panel, the entire
installation must be switched off and de-energized; otherwise complete
safety cannot be guaranteed.
The UPS is connected to 400/230 V three-phase power lines; DC voltages
above 500 V are also found in the battery circuit. Installation must only be
carried out by qualified personnel in accordance with these operating
instructions and both national and local electrical codes. Since UPS devices
create a large leakage current, connect the device to ground prior to
placement into service. Improper connection can damage the device and
lead to injuries and even death.
Warning
With regard to electromagnetic conformance, the device was developed in
accordance with product standard IEC/EN 62040-2. The UPS must be
protected against overvoltages in line power in excess of those at which it was
tested. Over voltages in the power supply system may occur for several
reasons, including lightning strikes, ON/OFF switching of inductive or
capacitive loads (such as power transformers or capacitor banks), and short-
circuit shutdowns.
Notice
QS1, QS2 and QS4 are used for disconnecting.
Warning
Do not operate the battery switch QS9 when the inverter is ON.
Notice
For different conditions, it will be necessary to verify whether cable
dimensions meet the requirements of IEC 60287.
Notice
When selecting the cable, it is important to take into account the voltage
drop due to the cable length (if the voltage drop exceeds 3%, increase the
cross section).
Notice
If the UPS supplies predominantly non-linear loads, the cross section of the
PEN conductor must be oversized by a factor of 1.7 for 60-200 kVA or 1.5 for
300-500 kVA.
Notice
To avoid electrical interference:
• - power cables (primary input, bypass input, battery, output load cables)
should be routed separately
• - communication and data lines should be routed using proper conduits
and kept separate from all power cables.
Notice
The cross section of the ground cables indicated in Table 1 on page 29 and
Table 3 on page 30 is indicative. It must be selected in accordance with
national and local rules, and coordinated with protection devices installed
ahead of the UPS.
Connectivity panel
INVERTER MODULE
INVERTER MODULE
RECTIFIER MODULE
RECTIFIER MODULE
Connectivity panel
RECTIFIER MODULE
PHASE U
INVERTER MODULE
PHASE U
QS1
INVERTER MODULE
PHASE V
RECTIFIER MODULE
PHASE V
QS2
RECTIFIER MODULE
INVERTER MODULE PHASE W
QS3
PHASE W
QS4
STATIC SWITCH
BOOST MODULE MODULE
QS9
QS4
PHASE U
RECTIFIER 1 RECTIFIER 2
MODULE MODULE
PHASE U PHASE U
QS1
RECTIFIER 2
RECTIFIER 1 QS2 MODULE
MODULE PHASE V
PHASE V
INVERTER 2
QS9 BOOST 1
MODULE
RECTIFIER 1
MODULE
STATIC
MODULE
25
Installation
26
Connectivity panel
RECTIFIER 1
Installation
RECTIFIER 1 MODULE
MODULE PHASE V
PHASE U
RECTIFIER 2
RECTIFIER 2 MODULE
MODULE PHASE V
PHASE U
INVERTER 1 QS1
MODULE RECTIFIER 1
PHASE U MODULE
PHASE W
INVERTER 2 QS2
MODULE
PHASE U RECTIFIER 2
MODULE
PHASE W
STATIC QS3
MODULE
INVERTER 1
MODULE
INVERTER 1 PHASE V
MODULE QS4
PHASE W
INVERTER 2
MODULE
INVERTER 2 PHASE V
MODULE QS9
PHASE W
A differential device installed on the primary and bypass inputs supply senses the sum of all
ground leakage currents in both the UPS and the load it supplies.
To avoid spurious operation, the following must be taken into consideration when selecting
differential protection devices for installation on input lines:
1 The nominal value of ID must take into account the ground leakage current of the UPS
and the load under normal operating conditions: ID = IDUPS + load leakage current.
N.B. The maximum limit for UPS ground leakage current is 5% of nominal input current
(see IEC/EN62040-1)
2 Be of a delayed operation type (greater than 30 0mS);
3 The type of differential switch used must conform to product regulation
IEC/EN62040-1.
Table 1: 60-200KVA
UPS devices 60 kVA 80 kVA 100 kVA 120 kVA 160 kVA 200 kVA
Primary Power line:
Max. current [A] 98 130 162 195 260 327
3) 35 50 70 95 120 2x70
Conductor cross section [mm2]
Screw size M8x25 M8x25 M10x30 M10x30 M10x30 M10x30
1) For a nominal voltage of 380V multiply the current value by 1.05; for 415V, multipily by 0.96
2) Overload current specified in chap. 10.?on page?113
3) To select the cross section refer to the actual installation data and national and local codes
The following table lists the tightening torque for the hex-head terminal connection screws
supplied with the UPS.
Table 2: Tigthening torque 60-200 kVA
Table 3: 300-500KVA
UPS devices 300 kVA 400 kVA 500 kVA
Primary Line power :
Max. current [A] 486 644 805
3) 2x120 2x180 2x240
Conductor cross section [mm2]
Screw size M12x35 M12x35 M12x40
1) For a nominal voltage of 380V multiply the current value by 1.05; for 415V, multipily by 0.96
2) Overload current specified in chap. 10.?on page?113
3) To select the cross section refer to the actual installation data and national and local codes
The following table lists the tightening torque for the hex-head terminal connection screws
supplied with the UPS.
Table 4: Tigthening torque 300-500KVA
Notice
For a TN-C distribution system, connect an insulated jumper between UPS
ground and the UPS Neutral connector.
Refer to local Standards and regulations for the correct jumper cross
section.
Connect line power cable PEN to the UPS Neutral connector (N).
Notice
Ensure that the line power and load conductors are connected to the UPS as a
clockwise (right hand) 3 phase system.
The distance between the power connection holes is 36 mm, unless otherwise specified.
Figure 21 - Chloride 80-NET 60/80 kVA - Customer power connections (front view)
The distance between the power connection holes is 50 mm, unless otherwise specified.
Figure 22 - Chloride 80-NET 100/120 kVA - Customer power connections (front view)
Figure 23 - Chloride 80-NET 160/200 kVA - Customer power connections (front view)
Figure 24 - Chloride 80-NET 160/200 kVA - Customer power connections (side view)
Figure 25 - Chloride 80-NET 300 kVA - Customer power connections (front view)
Figure 26 - Chloride 80-NET 400/500 kVA - Customer power connections (front view)
Figure 27 - Chloride 80-NET 300/400/500 kVA - Customer power connections (side view)
Notice
Full safety instructions on the use and maintenance of UPS batteries are
provided in the appropriate battery manufacturers' manuals. The battery
safety information contained in this section consists of key considerations
which must be taken into account when designing the installation and may
affect its outcome, depending on local conditions.
Warning
Special care should be taken when working with the batteries associated with
the Chloride 80-NET. When all batteries are connected together the overall
voltage exceeds 500V.
It is very important to make sure that the batteries are separately installed in a
specially designed, lockable, dedicated battery cabinet or battery room.
Battery cabinet specifications can be found in para 9.5. on page 105 of this
manual.
Warning
In the event of malfunction, the battery shelves and/or cabinet or battery
holders may become live!
Notice
The requirements of EC directives are met when battery compartments with
original accessories are used. If other batteries are used, make sure that the
applicable EC directives are met and that conformance is declared. The UPS
must still be parameterized with the service software and equipped with an all-
pole disconnecting device and fuses, as per Table 1 on page 29 and Table 3 on
page 30. When dimensioning your battery cables, note the connection
tolerances at terminals +/-.
Warning
ENSURE CORRECT POLARITY!
Notice
The most common battery type used in UPS installations is the valve
regulated battery.
Valve regulated cells are not sealed.
The amount of gas given off is less than for flooded cells, but when planning
the battery installation, allowance must be made for adequate ventilation
and heat dissipation.
Valve-regulated cells are not completely maintenance-free. They must be
kept clean and their connections checked periodically to ensure they are
tight and that there is no evidence of corrosion.
It is inevitable that batteries will lose some charge during transportation and
storage. Before attempting a capacity test, make sure the batteries are fully
charged, as this may take several hours.
Cell performance typically improves after a few discharge/recharge cycles.
Notice
The battery charger can be configured for different types of batteries and
different numbers of cells. In the technical data table (chap. 10. on page 113)
lists the type of batteries that can be used and the number of the cells for which
the battery charger is configured. The maximum charging current is selectable
and depends on the rating of the UPS and its operating conditions (chap. 10. on
page 113). Several charging methods (depending on the type of battery) are
available and can be configured by authorized personal only.
• The battery area temperature sensor should be installed adjacent to the UPS (see Fig.
21-Fig. 27 for the position of the input battery connections inside the UPS).
• Make the ground connections (PE).
• Connect the batteries with cables, as suggested in Table 1 on page 29 and Table 3 on
page 30 to terminals + (positive pole) and - (negative pole), and in accordance with the
connection diagram.
• Connect the battery area temperature sensor to connector XT1 in the connectivity
panel (Fig. 29, Fig. 30, Fig. 31, Fig. 32, Fig. 33).
• The wires that connect the temperature probe must be shielded and routed in
dedicated conduits that are separate from the power cables.
• Connect the two wires (if installed) that monitor the status of the external battery
disconnector to XT1/2 in the connectivity panel (Fig. 29, Fig. 30, Fig. 31, Fig. 32, Fig.
33). These wires must be routed in a dedicated conduit that is separate from the power
cables. To improve noise immunity, use twisted pairs or shielded wires.
Warning
Before the system starts, ensure that UPS battery connection polarity is correct.
Wrong connections can damage the system and endanger operator safety.
Notice
When recharging, follow the instructions printed on the packaging
Notice
Before replacing batteries, make sure the new batteries are fully charged.
Warning
If a battery has been disconnected and must be reconnected, the battery
isolator may be reconnected only after you have made certain that voltage
with the correct polarity is present in the intermediate circuit (see Connecting
the Batteries).
4. CONNECTIVITY PANEL
Chloride 80-NET is equipped with the following interfaces:
• XS3) Slot for Connectivity Products (X3 will be switched to XS3 to parameterize
Connectivity Products);
• XS6) Slot for LIFE.net modem;
• X3) Serial Interface for Service;
• X6) Serial Interface for external LIFE.net;
• XT1/2) 4-pole screw connector. Pin 1 and 2 to monitor the external battery
disconnector;
• X9) RJ-45 Ethernet Interface for Service and Placement into service only;
• XT3/8) 4-pole screw connector for RPO Input and Output;
• XT4) not used;
• TB1) 2x16-pole screw connector for input and output contacts;
• X19A/B) 2x15-pole connectors for parallel UPS connection;
• X20) RJ-45 Interface for synchronization with external signal;
• XT1) 2-pole Battery Area Temperature sensor (input);
• XT2) 2-pole screw connector for Backfeed output contact;.
X19/A
RS232-1 XT1
XS3 XS6 X3 X9 X20
XT1/2 XT4
XT2
RS232-2 XT3/8 TB1 X19/B
X6
RS232-2 X19/A
X9 X20 XT2 XT1
XS3 XS6 X6 XT4
XT1/2 XT3/8 TB1 X19/B
RS232-1
X3
X19/A
RS232-2 XT1
XS3 XS6 X6 X9 X20
XT4
XT2
RS232-1 XT1/2 XT3/8 TB1 X19/B
X3
RS232-2 X19/A
XT1
XS3 XS6 X6 X9 X20
XT4 XT2
XS3
XT1
X19/A
RS232-2 TB1
XS6 X9 X20 XT2
X6 XT4
CONNECTOR/TERMINAL IDENTIFICATION
X3) SUB-D 9-pin female X6) SUB-D 9-pin male
XT1/2 and XT3/8) screw connector, 4-poles XT1, XT2) screw connector, 2-poles
upper row
lower row
4.6. Ethernet RJ-45 Interface for Service and Placement into service - X9
This interface is a 10/100 MBit autonegotiation full/half duplex Ethernet Interface for LAN
communication with Chloride service software. This allows the setup and implementation of
UPS parameters such as Battery detail and performance of the UPS.
The Interface is SELV - isolated from UPS primary circuits.
Warning
The output of the external backfeed circuit connected to XT2 must not exceed:
• 24 VDC, 1A
• 160 VAC, 3A
Warning
XT2 are voltage free contacts fully isolated from UPS primary circuits.
If a voltage higher than 40 V is applied to control an external disconnection
device, XT2 can no longer be considered safe.
carrying out a manual reset to restore initial conditions, it is necessary to remove the root
cause of the fault. It is strongly recommended you contact customer support for more
information.
5.1.4. Communication
The UPS offers several interfaces for communication with computers. Further information is
included in chap. 4. on page 45.
Maintenance Bypass
Static Switch
Rectifier Inverter
Battery converter
Warning
Do not connect any devices that may overload the UPS or draw direct current
from it.
Notice
If these instructions are not observed correctly, problems may occur with the
supply of power.
Warning
This operation must be carried out by authorized personnel.
To prevent damage to the system, before closing QS9, use a suitable
instrument to make sure that the polarity of the battery voltage measured on
the external side of QS9 matches the polarity indicated in (see Fig. 21-Fig. 27).
Warning
Close QS9 only after battery polarity has been carefully checked.
DISPLAY
2
1
4
3
5 6
9
7
8 10
6.1.2. Display
The Display provides the user with a range of information and functions that can be accessed
using control panel navigation keys 1 to 4 (see Fig. 40 on page 63).
UPS modifications and settings must be made by qualified technicians, only. Settings should
be tested only if the loads connected to the UPS are non-critical.$
The Main Page displays a block diagram of the UPS and uses standard technical symbols to
indicate current operating status (e.g. on-line operation, battery operation, Bypass
operation, etc.), load level, and remaining backup time. To access the Main Menu page from
the Main (default) page, press the Right soft key (key 4 - see Fig. 40 on page 63). From this
menu, you can scroll through the various sub-menus using the Up and Down soft keys (2 and
3). Press the Right soft key to select any menu from the list, and the Left soft key (1) to return
to the Main Menu page.
The table on the following page provides a summary of the sub-menus.
When the UPS is not in the normal operating mode, you can access the "Warning and Alarm"
summary page directly from the Main (default) page. Warnings and alarms are identified by
text strings and codes (see Table 6 on page 72 and Table 7 on page 75). During battery
powered operation, the display switches between warning code and estimated backup time
(minutes).
6.1.3. Sample guided procedure for switching the UPS from Normal Mode to
Maintenance Bypass - Manual Bypass
When the desired procedure is selected from the Guided Procedures menu (in this case the
Single UPS Manual Bypass procedure), the following window appears in the display and
shows the principle UPS components and their current status:
Manual Bypass
Stop
Exit Inverter
The various UPS switches are also shown. The Maintenance Bypass switch, QS3, is shown in
the open (OFF) position in the above example. Flashing icons inform the operator that the
corresponding switch must be opened or closed.
In the event of a fault, a warning message is displayed (see para 6.1.4. on page 71 for full list
of warning messages). Exit the procedure, correct the fault and reset before proceeding.
Pressing the button identified by the “Exit” message at any time interrupts the procedure.
In this example, the “Stop Inverter" message appears in the bottom right of the display, and
the Stop symbol flashes over the Inverter, indicating that the user must shut down the
Inverter by pressing the corresponding button on the panel. (See “Instruction messages” on
page 71 for full list of instruction messages).
PROCEDURE:
Manual Bypass
3 The message “Close QS3” is displayed, and the symbol representing QS3 on the display
begins to flash.
4 The message “Open QS4” is displayed, and the symbol representing QS4 on the display
begins to flash.
Manual Bypass
QS4
Manual Bypass
QS2
6 The message “Open QS9” is displayed, and the symbol representing QS9 on the display
begins to flash.
Manual Bypass
QS9
Exit Open QS9
Manual Bypass
QS1
Manual Bypass
Instruction messages
Stop Inverter Open QS1 Close QS1
Start Inverter Open QS2 Close QS2
Press Exit Open QS3 Close QS3
Reset Fault Open QS4 Close QS4
Open QS9 Close QS9
Fault indications
If a fault occurs, the affected UPS component is always switched off, and the UPS
automatically switches to the best possible operating mode for supplying the loads; the red
FAULT LED lights up on the control panel. A number appears on the Warning/Fault Diagnosis
page of the display indicating the type of fault. Fault indicators are also indicated by a
continuous tone from the buzzer. If a fault occurs, proceed as follows:
Acknowledge horn
First, acknowledge the horn by pressing the TEST/RESET button
Correct fault
Next, correct the fault by following the indications in para 6.1.6. on page 79.
If the fault cannot be corrected:
Call Customer Service: The customer service addresses are given on the last page of this
manual.
Acknowledge correction of fault
After the fault has been corrected, the corrected condition must be acknowledged by
pressing the TEST/RESET button again.
Displayed Faults
The various possible fault indicators are listed in the table below:
Table 7: Fault Indications
DSP STAGE
ID MESSAGE
F1 EPO
F2 Incorrect power class config.
F3I1 Incorrect state in main SM
F3I2 Bypass illegal software state
F3I3 Rectifier illegal software state
F3I4 Inverter illegal software state
F3I6 Incorrect state in state-machine
F3I7 Generic software error
F3I8 Too many parameters for EEPROM
F3I9 Insuff. RAM space for EEPROM par.
F3I10 Parameter init. called runtime
F3I11 Parallel node ident. timeout
F3I12 Error during parallel node ident.
F3I13 Parallel node ident. not possible
F4I6 EPROM checksum fault
F4I7 I2C I/O expander init. failed
F4I8 I2C multiple error I/O expander
F4I9 I2C multiple error ID card
F4I10 Par.-cable-fitted signal missing
6.1.6. Troubleshooting
Rectification of Errors
Despite the high reliability of this device, problems may occur. If you are having a problem,
please check the following points before contacting your customer service representative:
Is there line power on the UPS input?
Has the input fuse blown or have circuit breakers tripped?
If you contact your customer service representative, please have the following information
ready:
• Device information = model, order no., series no. as shown on the identification plate
• An exact description of the problem (what loads are being powered, whether the
problem occurs regularly or sporadically, etc.)
Problem Possible cause Action
No display Main switch switched off Switch on main switch
No alarm No line power Have line power inspected by
(UPS switched off) qualified electrician
Input fuse blown or input Replace with fuse of same
circuit breaker tripped type or reset circuit breaker. If
the problem persists, contact
your customer service
representative.
Green “OK” LED does No line power UPS operation
not light up, buzzer
sounds at intervals
Green “OK” LED does Input fuse blown or input Replace with fuse of same
not light up when circuit breaker tripped type or reset circuit breaker. If
line power is present, the problem persists, contact
buzzer sounds at your customer service
intervals representative.
ALARM indicator UPS error Contact your customer service
lights up, buzzer representative
sounds continuously Overheating Reduce ambient temperature
Backup time less The fuse switch of the battery Move the fuse switch to the
than that specified extension(s) is in "OPEN" "ON" position.
position.
Batteries are not completely Charge batteries, and test
charged backup time. If the problem
persists, contact your
customer service rep.
Batteries are defective Contact customer service
Charging device is defective Contact customer service
1 8 5 3
Fault Indicator (Alarm Condition): when the red circle with white cross appears,
immediate attention should be given to the severity of the alarm, and service should be
called promptly. A description of the active alarm(s) can be viewed by clicking on the
warning and fault button at the bottom of the page.
Regardless of which indicator is active, all available diagnostic information on the unit can be
displayed by touching this area.
6. Control Buttons:
Start Inverter and Stop Inverter : the touch screen display features two separate
buttons for starting and shutting down the inverter. The start/stop control incorporates a
safety feature for preventing accidental operation. In fact, when the start or stop functions
for the inverter are selected, a pop-up window appears asking for confirmation of the action
selected. This pop up feature is run at every command that results in a permanent change to
UPS settings.
Reset Fault : for resetting faults (this becomes red when there is a system fault)
Buzzer Mute : for silencing the buzzer in the case of an alarm.
7. Menu Buttons:
Warning/Fault: this page contains information regarding various abnormal conditions
concerning the unit, as subdivided into the specific converters such as the Bypass, rectifier,
inverter, booster charger and battery . In addition, there are also several "Info" statements
that are catagorized by status. These provide further details about the condition of the unit.
Diagnostic classification :
• FAULT
• WARNING
• INFO
Event Log: displays the date and time of all UPS events.
Measures: this page contains the full set of measurements for each functional block
(rectifier, Bypass, booster/charger, batteries, inverter and load).
Battery: displays battery status/parameters such as temperature, cell voltage, capacity and
run time, as well as commands that enable the user to configure and execute the battery
test.
LIFE: contains information about the status of Chloride LIFE.net connections, calls and call
types and allow certain specific commands to be executed. This button is not active if the
LIFE.net option is not available on UPS.
Settings: this page allows users to customize the settings of the touch screen display and to
select the desired language. Each of these sub pages is programmed to revert back to the
main page after 30 seconds of inactivity. The text displayed by the touch screen is available
in 15 languages: English, Italian, French, German, Spanish, Portuguese, Turkish, Polish,
Swedish, Norwegian, Finnish, Czech, Russian, Arabic and Chinese - all selectable by the user.
Measures menu
This menu item displays the measurements for each functional block (see below figure)
Battery menu
This menu manages the status of the battery (see below figure).
1 2 3
1. Battery Status:
1.1 Battery Status. Specify whether battery is charging or not
1.2 Charger Status. Specify Battery Charger status
1.3 Battery Test Status. Specify details of the last battery test executed
1.4 Automatic Battery Test Status. Specify details related to Automatic battery test
2. Battery Test: The following commands can be set using this page
2.1 Enable automatic battery test. Using this command, the Automatic Battery test is
enabled using the existing parameter configuration. These parameters can be
modified only by PPvis
2.2 Configure and manage Manual Battery test. Features:
2.2.1 Test duration and Min Voltage can be modified using the + and - button
2.2.2 Start battery using dedicated command button (Start Battery Test)
2.2.3 Test duration can be monitored on a dedicated progress bar (Battery test
progress bar )
2.2.4 While the test is running, it can be aborted with a dedicated Stop command
button (Stop Battery Test)
2.2.5 Battery test status provides immediate information about test status
3. Battery measures: This section monitors variables applicable to the battery.
LIFE menu
This menu displays the status of Chloride LIFE.net communications and allows the User to
issue certain commands (see figure below).
1 3
2 4
1. LIFE.net status
• LIFE.net option (Present/Not present) Shows whether the "LIFE.net" option is
available on the UPS.
• LIFE.net (Enabled/Disabled) Shows whether the LIFE.net option has
been started.
• Current UPS dd.mm.yy hh:mm:ss Displays the time used by the UPS to
date/time time-stamp the Life data
• ‘Set Sampling Set sampling/service mode Toggles LIFE.net operating modes
Mode’ button between 'service' and 'sampling':
service is used when UPS maintenance is
in progress.
4. Call Type
• Routine call The UPS is making its regular call.
• Emergency call The UPS is making an Emergency call.
• Manual call The UPS is making a Manual Call or an automatic extra call to
reset an emergency condition which is no longer active.
• Buffer full call The UPS is making a call to empty its diagnostics history
buffer, which is full and cannot store any more data.
• ‘Manual call request’ When this button is pressed, the UPS is forced manually to
button make an immediate call to the LIFE station.
Settings menu
This menu item displays the LCD settings and selected language (see below figure)
8. Animated One Line Mimic: this area displays all the functional blocks in the UPS. Touch
any icon to obtain detailed information about the corresponding functional block. The color
of the block identifies its functional status:
• normal conditions
• warning conditions
• fault conditions
9. About button: this button displays the Type and Size of the unit. When this area is
touched, you will obtain Serial Number, FW details and IP and MAC addresses.
This page displays detailed information about the UPS S/, size and model, FW revision and
system time.
6.2.1. Troubleshooting
Rectification of Errors
Despite the high reliability of this device, problems may occur. If you are having a problem,
please check the following points before contacting your customer service representative:
Is there line power on the UPS input?
Is the input fuse blown or have circuit breakers tripped?
If you contact your customer service representative, please have the following information
ready:
• Device information = model, order no., series no. as per identification plate.
• An exact description of the problem (what loads are being powered, whether the
problem occurs regularly or sporadically, etc.)
7. MAINTENANCE
7.1. Maintenance intervals
Chloride recommends that regular maintenance checks be carried out on-site by an
authorized customer service. The UPS informs the user when the normal service life of a fan
has ended. A replacement fan is recommended.
7.4. Decommisioning
7.4.1. Taking out of service
N.B. Switch to service Bypass
• Switch the UPS to Maintenance Bypass operation (see para 5.7.3. on page 61)
N.B. Disconnect the batteries
• Open the battery isolator or battery switch if other external batteries are used.
• Before continuing work, measure the voltage on the battery terminals and on the line
power input, and wait until these have dropped to 0 V; or wait at least 5 min. Failure to
do so may cause severe electrical shock and possibly death.
The UPS is now in the maintenance Bypass operating mode. The only voltage present is at
the line power and load terminals. Qualified personnel may now carry out maintenance work
while taking the corresponding safety measures.
N.B. Disconnect line power
If the loads no longer need power, you may open the external line power separation device
for the UPS.
8. PARALLEL CONFIGURATION
Up to 8 Chloride 80-NET units can be connected in parallel to increase power capacity and
thus to provide more secure power to the load (redundancy).
The modules in parallel exchange information via a 15-wire shielded cable.
The total load current is shared between the modules.
For optimum performance of the parallel system and proper current sharing, especially in
the Bypass mode, make sure that the series impedance of the modules in parallel is the
same.
The cross section and length of the power cables used to connect the inputs of each UPS
module must be the same. The same applies to the output cables and the battery cables, if
the modules are connected to the same DC source.
Differences of 20% are allowed for power cable lengths of up to 20 m. For larger distances,
cable lengths may not vary by more than 10%.
System
Bypass
To
Load
STATIC
SWITCH
STATIC
SWITCH
STATIC
SWITCH
STATIC
SWITCH
UPS 4
X19/A 1)
X19/B
1)
UPS 3
X19/A
X19/B
1)
UPS 2
X19/A
X19/B
1)
UPS 1
X19/A
X19/B
9. OPTIONS
Some of the options listed in this section may modify the data on the standard technical data
tables (see chap. 10. on page 113). It may not be possible to use certain options
simultaneously on the same UPS.
9.10. Connectivity
The following table gives details of the various combinations of connectivity solutions which
can be used in association with Chloride 80-NET. Only one of the combinations may be used
at a time; other combinations may be possible. For port numbers, please refer to chap. 4. on
page 45. For further information, please see Chloride Connectivity. The following interfaces
can be found on Chloride 80-NET:
FRONT
UNIT RATING
DESCRIPTION
kVA 60 80 100/120 160 200
Depth mm 851
Width mm 570 845 1375
Height mm 1780
Floor area INPUT/
OUTPUT (depth
without handle: 830 m2 0,47 0,70 1,14
mm)
Net Weight INPUT Kg 600 815 1200 1320
Floor loading INPUT kg/m2 1277 1164 1053 1158
Net Weight OUTPUT Kg 585 810 1250 1420
Floor loading OUTPUT kg/m2 1245 1157 1096 1246
Heat dissipation of the
transformer option at
kW 1,67 2,23 3,34 4,45 5,57
nominal load and
input conditions
Note:
the total heat dissipation of the UPS is the sum of the UPS dissipation on chap. 10.?on
page?113 and transformer heat dissipation.
U1, V1, W1
U, V, W
N U2, V2, W2
U1, V1, W1
U2, V2
U, V, W W2
N N1
N
N.B.: If Primary Line power and Bypass Line power are supplied from separate sources, the
jumper cables connected between UPS terminals U and U1, V and V1, W and W1 must be
removed.
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Tel: +1 614 8880246
Asia
7/F, Dah Sing Financial Centre
108 Gloucester Road, Wanchai
Hong Kong
Tel: +852 2572220
Fax: +852 28029250
Emerson, Business-Critical Continuity and Emerson Network Power are trademarks of Emerson Electric Co. or one of its affiliated companies. ©2011 Emerson Electric Co.