Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Warning: 35 3.6 Changing Direction of Display Unit

Download as pdf or txt
Download as pdf or txt
You are on page 1of 37

<3.

Installation> 35
3.6 Changing Direction of
Display Unit
(1) Removing the Cover
• The following tool is required. (1)
Hexagonal wrench (nominal size 3)
• Turn off the power to the flowmeter.
• Using the wrench, loosen the cover locking screw
(1) (See Figure 3.6.1 and Figure 3.6.2) clockwise
to unlock the cover. Upon shipment from the
manufacturing plant, the cover is locked. Hold the
Cover locking screw
flowmeter with your hand. Remove the cover by F0341.ai

rotating it counterclockwise. Figure 3.6.1 Removing the Display Cover


(Integral Flowmeter)

WARNING
• For explosion protection type products, please
confirm that it is “no explosive atmosphere”.
(1)

3
WARNING

Installation
• When opening and closing the cover, be sure to
handle the cover carefully so that there are no
Cover locking screw
damage and foreign matter adhesion at its threads F0342.ai

and O-ring. Keep checking their condition and clean Figure 3.6.2 Removing the Display Cover
the threads in case of adhering the foreign matter. (AXG4A Remote Transmitter)
• Replace the cover in case the treads receive
damages.
• Replace the O-ring if there is any scarring or
transformation. And apply silicone based grease at
the O-ring in case of the shortage and exhaustion of
grease.

IMPORTANT
• When closing the cover, close it with both hands
until the cover does not turn in order to bring the
housing and cover into tight contact.
• Tighten while confirming that the cover rotates
smoothly.

IM 01E22A01-01EN
<3. Installation> 36
(2) Changing Display Unit Direction 90 degrees (3) Installing the Cover
• Hold the display unit with your hand and loosen • Install the cover to the flowmeter by rotating the
the two mounting screws. cover clockwise.
• Rotate the display unit 90 degrees clockwise and • Tighten cover locking screw (1) (See Figure
confirm the assembling position, taking care of the 3.6.1 and Figure 3.6.2) counterclockwise using
connector and wire of the display unit. a hexagonal wrench (nominal size 3) to lock the
At this time, do not remove the connector. cover.
• Secure the display unit using its two mounting
screws.
IMPORTANT
Safety cover
• When closing the cover, close it with both hands
until the cover does not turn in order to bring the
housing and cover into tight contact.
• Tighten while confirming that the cover rotates
smoothly.

Mounting screw
(two screws)
WARNING
• When opening and closing the cover, be sure to
handle the cover carefully so that there are no
damage and foreign matter adhesion at its threads
and O-ring. Keep checking their condition and clean
the threads in case of adhering the foreign matter.
• Replace the cover in case the treads receive
damages.
Clockwise 90 degrees
F0343.ai
• Replace the O-ring if there is any scarring or
Figure 3.6.3 Changing Display Unit Direction 90 degrees
transformation. And apply silicone based grease at
the O-ring in case of the shortage and exhaustion of
grease.

IMPORTANT
To preserve the safety, do not touch the electrical circuit
and cable of shaded area.

WARNING
• To prevent electric shocks and maintain
performance, do not remove safety cover.

IM 01E22A01-01EN
<4. Wiring> 37

4. Wiring
WARNING CAUTION
The wiring of the magnetic flowmeter must be • Terminate all the cable finish with crimp terminal of
performed by expert engineer or skilled personnel. a round or rod shape (depending on the shape of
No operator shall be permitted to perform procedures the terminal block), and connect them reliably.
relating to wiring. • Always route the power and output signal cables
in separate steel conduit tubes, except when the
power supply voltage is 24 V and four-core cables
are used for wiring. For the remote type, route the
WARNING excitation cable and the signal cable in separate
steel conduit tubes. Keep conduits or flexible tubes
For explosion protection type products, please be sure watertight using sealing tape.
to read the user's manual of the applicable explosion
protection type as listed in Table 1.1 before wiring.

CAUTION
CAUTION • If there is any unused cable entry, use the blanking
plug to cover which comes with this product or
Once all wiring is completed, check the connections which is supplied by YOKOGAWA. The blanking
before applying power to the product. Improper plug should be fastened into the unused cable
arrangements or wiring may cause a unit malfunction or entry without any mistake. If not, stated enclosure
4
damage. protection is not applicable. One or two blanking

Wiring
plug is provided depending on the specifications (24
V for power supply voltage or I/O selection).
• The signal cables must be routed in separate steel
4.1 Wiring Precautions conduit tubes 16 (JIS C 8305) or flexible conduit
Be sure to observe the following precautions when wiring: tubes 15 (JIS C 8309).
• When waterproof glands or union equipped
waterproof glands are used, avoid tightening the
CAUTION glands with an excessive torque.
• For the instruction of removing/installing the housing
• In order to maintain performance, wiring according covers and handling the locking screws, read
to regulations is necessary. Section 4.4 and Section 4.5.
• When opening the cover, wait for more than 20 • Explosion protected types must be wired in
minutes after turning off the power. accordance with specific requirement (and, in
• In cases where the ambient temperature exceeds certain countries, legal regulations) in order to
50°C, use external heat resistant wiring with a preserve the effectiveness of their explosion
maximum allowable temperature of 70°C or above. protected features.
• Do not connect cables outdoors in wet weather in
order to prevent damage from condensation and to
protect the insulation, e.g. inside the terminal box of IMPORTANT
the flowmeter.
• Before turning the power on, tighten the terminal For the remote type, prepare the excitation cable
box cover securely. (supplied by customer) and the signal cable of almost
• For the remote type, do not splice the cable the same length. It is recommended to lay them
between the transmitter and the sensor terminal together closely.
when it is too short. Replace it with a complete
cable of the appropriate length.
• For the remote type, ground the remote sensor and
the transmitter separately.

IM 01E22A01-01EN
<4. Wiring> 38
4.2 Cables
NOTE
4.2.1 Recommended Cable for Excitation, • For excitation cable and power cable, always use a
Power and Input/Output: crimp terminal with an insulation cover.
JIS C 3401 control cable equivalent • Use crimp tools supplied by the manufacturer of the
JIS C 3312 power cable equivalent crimp terminal you want to use to connect the crimp
14 AWG Belden 8720 equivalent terminal and cable.
• Use crimp tools that are appropriate for the diameter
Outer Diameter:
of the cable to be connected.
With no gland option:
6.5 to 12 mm (0.26 to 0.47 in.)
With waterproof gland (optional code EG, EG, EU, 4.2.2 Dedicated Signal Cable (AX01C)
EU, EW):
Unit : mm
For excitation cable: Conductors (A and B) (approx. inch)
10.5 or 11.5 mm (0.41 or 0.45 in.) Shields (SA and SB)
Tape
For power and input/output cable:
7.5 to 12 mm (0.30 to 0.47 in.)
With plastic gland (optional code EP, EP: Outer jacket 10.5 (0.413)

6 to 12 mm (0.24 to 0.47 in.)


Shield (C)
Nominal Cross Section: Inner jacket
Single wire; 0.5 to 2.5 mm2 Inner jacket F0402.ai

Stranded wire; 0.5 to 1.5 mm2 Figure 4.2.2  Dedicated Signal Cable

Excitation cable for submersible use and optional


The flow signal is transmitted via this dedicated cable.
code DHC:
The cable is constructed with double shielding over the
Heat resistant vinyl resin sheath cable
two conductors, and heat-resistant vinyl is used for the
Outer diameter ø 10.5 mm
outer jacket material.
In case of power cable, Green/Yellow covered conductor
Finished diameter: 10.5 mm (0.413 in.)
shall be used only for connection to PROTECTIVE
Maximum length:
CONDUCTOR TERMINALS. Conform to IEC227,
Combination with the AXFA11 transmitter: 200 m (660 ft)
IEC245 or equivalent national authorization.
Combination with the AXG4A transmitter: 100 m (330 ft)
Unit : mm
(approx. inch) Maximum temperature: 80°C (176°F)
Crimp terminal
IMPORTANT
EX1
EX2

EX2
EX1

If the cable is longer than required, cut off any extra


85 (3.35) 85 (3.35) length rather than coiling it up, and terminate the
conductors as shown in Figure 4.2.3.
Avoid using junction terminal boards to extend the cable
length, as this will interrupt the shielding.
On the transmitter side On the sensor side

F0401.ai

Figure 4.2.1  Cable Finish for Excitaiton Cable

IM 01E22A01-01EN
<4. Wiring> 39
Cable Finish: Finished Unit: mm (approx. in.)
4.3 Cable Entries

55(2.17)
E

B
A

B
WARNING
SA

SB

90(3.54)
90(3.54)
F

G
For explosion protection type products, please be sure

D
(WHITE) (BLACK) (RED) (WHITE) (BLACK) (RED) to read the user's manual of the applicable explosion
protection type as listed in Table 1.1.

8(0.31)Max.
8(0.31)Max.
150 ±5

150 ±5
(5.91)

(5.91)
This product is of watertight construction as stipulated in
TRANSMITTER

JIS C 0920. It is shipped with a wiring bracket (waterproof

SENSOR
gland, waterproof gland with union or a

ø10.5(0.41)
L (Specified Length)
plastic gland attached), only in cases where an optional
20(0.79)
specification is selected for the cable entry.
F0403.ai
Cable gland has the following kinds depending on the
Length type and size.
Specification Code Description
D E F G
AX01C-C 60 (2.4) 25 (1.0) 70 (2.8) 50 (2.0) For AXG4A
AX01C-D 70 (2.8) 25 (1.0) 50 (2.0) 60 (2.4) For AXFA11
Integral Type Flowmeter
AXG (Size: 2.5 to 400 mm (0.1 to 16 in.))
Cable Finish: Unfinished
Optional
Description
ø10.5(0.41)

Code

CAP EG2 2 pcs. of waterproof gland, and a blanking plug


EG3 3 pcs. of waterproof gland
2 pcs. of waterproof gland with union joint, and a blanking
EU2
plug
4
L (Specified Length) + 340(13.39) (Length for Cable Finish)

F404.ai EU3 3 pcs. of waterproof gland with union joint


Figure 4.2.3  Cable Finish for Signal Cable EP2 2 pcs. of plastic gland, and a blanking plug

Wiring
EP3 3 pcs. of plastic gland

CAUTION Remote Sensor


AXG (Size: 2.5 to 500 mm (0.1 to 20 in.))
• As crimp terminals A, B, SA, SB and C have their
Optional
own electrical potentials, securely insulate them so Description
Code
as not to come in contact with one another.
EW 2 pcs. of waterproof gland with JIS G3/4 female
• To prevent a shield from coming in contact with
EG 2 pcs. of waterproof gland
another shield or the case, cover each shield with a
vinyl tube or wrap it in vinyl tape. EU 2 pcs. of waterproof gland with union joint
EP 2 pcs. of plastic gland

4.2.3 Recommended Cable for Modbus Remote Transmitter


communication AXG4A
3-Wire cable (twisted pair and Common) with shield Optional
Description
should be used. Code

Wire gauge: AWG24 or wider EG4 4 pcs. of waterproof gland, and a blanking plug
Characteristic Impedance of cable: 100Ω or more EG5 5 pcs. of waterproof gland
4 pcs. of waterproof gland with union joint, and a blanking
EU4
plug
EU5 5 pcs. of waterproof gland with union joint
EP4 4 pcs. of plastic gland, and a blanking plug
EP5 5 pcs. of plastic gland

IM 01E22A01-01EN
<4. Wiring> 40
Remote Transmitter (1) Waterproof Gland
AXFA11G Integral Flowmeter
Optional
Description Optional code: EG2, EG3
Code
EW 5 pcs. of waterproof gland with JIS G3/4 female
EG 5 pcs. of waterproof gland
EU 5 pcs. of waterproof gland with union joint
EP 5 pcs. of plastic gland

Washer

IMPORTANT
Apply a blanking plug to the unused cable entry. Seal
the cable entries properly comply to usage state. Gasket
Waterproof gland
Cable F0405.ai

4.3.1 When waterproof property is neces- Remote Sensor


sary (Wiring using waterproof glands) Optional code: EG

IMPORTANT
To prevent water or condensation from entering the Washer
transmitter housing, waterproof glands are recommended.
Do not over-tighten the glands or damage to the cables
may result. Tightness of the gland can be checked by
confirming that the cable is held firmly in place. Gasket
Waterproof gland
For working on the conduit or the flexible tubes (G1/2), Cable F0406.ai

remove the waterproof gland and attach them directly to Remote Transmitter (AXG4A)
the cable entry. Optional code: EG4, EG5

Washer

Gasket
Waterproof gland
Cable
F0407.ai

Remote Transmitter (AXFA11)


Optional code: EG

Washer

Gasket
Waterproof gland
Cable F0408.ai

IM 01E22A01-01EN
<4. Wiring> 41
(2) Waterproof Gland with Union Joint (3) Plastic Gland
Integral Flowmeter Integral Flowmeter
Optional code: EU2, EU3 Optional code: EP2, EP3

Gasket

Gasket
G1/2

Washer
Tightening gland

Cable
Plastic gland
F0413.ai
When working on conduit or flexible tube (G1/2 only)
F0409.ai
Remote Sensor

Remote Sensor Optional code: EP

Optional code: EU

Gasket Gasket

G1/2

Washer 4
Tightening gland Plastic gland F0414.ai

Wiring
Remote Transmitter (AXG4A)
Cable
Optional code: EP4, EP5
When working on conduit or flexible tube (G1/2 only)
F0410.ai

Remote Transmitter (AXG4A)


Optional code: EU4, EU5
Gasket

Gasket

G1/2 Plastic gland F0415.ai

Remote Transmitter (AXFA11)


Washer
Optional code: EP
Tightening gland

Cable

When working on conduit or flexible tube (G1/2 only)


F0411.ai

Remote Transmitter (AXFA11)


Optional code: EU
Washer

Plastic gland
G1/2
F0416.ai

Gasket

Tightening gland
Cable
When working on conduit or flexible tube (G1/2 only)
F0412.ai

IM 01E22A01-01EN
<4. Wiring> 42
(4) Waterproof Gland with JIS G3/4 Female 4.3.2 Conduit Wiring
Remote Sensor When wiring the conduits, utilize the waterproof gland to
Optional code: EW prevent water from flowing in through the conduit. Place
the conduit pipe on an angle as shown in the following
Gasket figures.
Washer Install a drain valve at the low end of the vertical pipe, and
open the valve regularly.
To prevent noise, do not use the same conduit for signal
Conversion plug (x2)* cable and power cable.
Cable

G1/2

G3/4

When working on conduit or flexible tube (G3/4)

* When connecting G1/2, remove the conversion plug and


connect directly to cable entry.
F0417.ai Drain valve
Remote Transmitter (AXFA11)
F0419.ai
Optional code: EW
Figure 4.3.1  Integral Flowmeter
When working on conduit or
flexible tube (G3/4)

G1/2

G3/4

Gasket
Washer Drain valve
Extension plug (x2)
F0420.ai
Conversion plug (x5)*
Cable Figure 4.3.2  Remote Sensor
* When connecting G1/2, remove the conversion plug
and connect directly to cable entry.
F0418.ai

Drain valve

F0421.ai

Figure 4.3.3  Remote Transmitter (AXG4A)

Drain valve

F0422.ai

Figure 4.3.4  Remote Transmitter (AXFA11)

IM 01E22A01-01EN
<4. Wiring> 43
4.4 Connecting to External Wiring Procedure
1. Check the product’s power is off, then remove the
Products of Integral terminal cover (transparent).
Flowmeter and Remote 2. Wire the power supply cable and the functional
grounding cable to the power supply terminals.
Transmitter 3. Install the terminal cover.
Functional grounding cable
4.4.1 Wiring Precautions for Power Supply
Cables
When connecting to the power supply, observe the points
below. Failure to comply with these warnings may result
in an electric shock or damage to the product. Power supply
cable

WARNING
• Ensure that the power supply is off in order to prevent M4 Screw Type
electric shocks.
• When opening the cover, wait for more than 20 Functional grounding cable
minutes after turning off the power.
• Ensure the protective grounding terminal is grounded
before turning on the power.
• Terminate all the cable finish with round or rod
shaped crimp terminal (depending on the shape of
the terminal block) with insulation cover, and connect Power supply

them reliably.
cable 4
• Install an external switch or circuit breaker as a

Wiring
means to turn the power off (capacitance: 15A,
conforming to IEC60947-1 and IEC60947-3).
Clamp Type
Locate this switch either near the product or in other F0423.ai
places facilitating easy operation. Affix a “Power Off Figure 4.4.1  Power Cable Wiring
Equipment” label to this external switch or circuit
breaker.
4.4.2 DC Power Connection
When using DC power as the power supply for the
WARNING transmitter, pay attention to the following points.

For explosion protection type products, please be sure (1) Connecting Power Supply
to read the user's manual of the applicable explosion
protection type as listed in Table 1.1.
IMPORTANT
Do not connect power supply with reversed polarities.
L/+ terminal: connect to + (power supply)
N/– terminal: connect to - (power supply)

IMPORTANT
For the 24 V power supply version (power supply code
-2), power supply with 100 to 240 V AC and 100 to 120
V DC cannot be connected.
The wrong connection results in a damage to the
transmitter.

IM 01E22A01-01EN
<4. Wiring> 44
(2) Required Power Supply Voltages 4.4.3 Grounding

IMPORTANT WARNING
• For the 24 V power supply version (power supply For the wiring of protective grounding, terminate the
code -2), the specification of 24 V (–15% to +20%) cable finish with round shaped crimp terminal with
is the supply voltage between the terminals on insulation cover (for M4 screw), and connect it to the
the transmitter. Because of voltage drop by cable protective grounding terminal reliably.
resisitance, the supply voltage must be applied
within the range of Figure 4.4.2.
• For AXFA11, read the applicable user’s manual as
CAUTION
listed in Table 1.1.
• The grounding should satisfy grounding resistance
700 (2290) requirement, 100 Ω or less (Class D grounding).
Allowable cable length m(ft)

603 (1970)
600 (1960) • For explosion protection type, the grounding must
500 (1640) satisfy the domestic electrical requirements as
400 (1310) regulated in each country
338 (1100)
300 (980)

200 (650)

100 (320)
IMPORTANT
0
28.8 A lightning protector is built-in for integral flowmeter
20 22 24 26 28 30
Usable voltage range (V)
or AXG4A remote transmitter. When the lightning
Cable cross section area: 1.25 mm2 protection is needed, the ground should satisfy Class C
Cable cross section area: 2 mm2 requirements (grounding resistance, 10 Ω or less).
F0424.ai For AXFA11, read the applicable user’s manual as listed
Figure 4.4.2 Supply Voltage and Power Supply Cable in Table 1.1.
Length (Integral Flowmeter and AXG4A
Remote Transmitter)
• The protective grounding terminals are located on
the inside and outside of the terminal area.
(3) Setting Power Supply Frequency
Either terminal can be used.
• Use 600 V vinyl insulation wires as the grounding wires.
IMPORTANT
Set the local commercial power frequency in order to
eliminate the effect of induction noise from the power
supply.
For detailed parameter setting, read the user’s manual
of the applicable communication type (for AXG/AXG4A)
or the hardware/software edition (for AXFA11) as listed Protective
in Table 1.1. grounding
terminals

Display Menu Path (AXG/AXG4A):


Device setup ► Detailed setup ► AUX calculation ► Power sync on/off
Device setup ► Detailed setup ► AUX calculation ► Set power freq

Protective grounding terminals F0425.ai

Figure 4.4.3 Position of Protective Grounding Terminal

IM 01E22A01-01EN
<4. Wiring> 45
4.4.4 Connecting to External Products
IMPORTANT
Improper grounding may result in an adverse effect WARNING
on the flow measurement. Ensure that the product is
properly grounded. • Before wiring with external products, be sure to turn
off the power supply of the magnetic flowmeter.
• Be sure the power supply of the external products is
The electromotive force of the magnetic flowmeter
turned off, and then start wiring.
is minute and it is easily affected by noise, and the
reference electric potential is the same as that of the
measuring fluid. Therefore, the reference electric Read Section 4.6 for connection to external products.
potential (terminal potential) of the sensor and transmitter
also need to be the same as that of the measuring fluid.
4.4.5 Wiring Procedures
Moreover, the potential must be the same as the ground.
The magnetic flowmeter is equipped with an grounding
(1) For Integral Flowmeter and AXG4A Remote
ring that makes a connection with the charge of the
measured fluid for grounding and protects the lining. Transmitter
Grounding rings are supplied with the products when 1) Removing the Cover
specified with dedicated optional code. Loosen the cover locking screw (1 and 3) (See
Figure 4.4.5 and Figure 4.4.6) clockwise using a
600 V vinyl-insulated cable hexagonal wrench (nominal size 3) to unlock the
Cable cross section area:
2 mm2, and cross section cover. Upon shipment from the manufacturing
area larger than power cable plant, the cover is unlocked. Hold the flowmeter
with your hand and remove the cover by turning it
in the direction of the arrow as shown below.
4
WARNING

Wiring
grounding ring
• When opening and closing the cover, be sure to
handle the cover carefully so that there are no
Grounding Resistance: 10 Ω or less (Class C requirements) damage and foreign matter adhesion at its threads
Note: When lightning protection performance by the built-in lightning and O-ring. Keep checking their condition and clean
protectors is not required, grounding resistance 100 Ω or less
the threads in case of adhering the foreign matter.
(Class D requirements) can be applied.
F0426.ai • Replace the cover in case the treads receive
damages.
• Replace the O-ring if there is any scarring or
CAUTION transformation. And apply silicone based grease at
the O-ring in case of the shortage and exhaustion of
• The grounding should satisfy grounding resistance grease.
requirement, 100 Ω or less (Class D grounding).
• For explosion protection type, the grounding must
satisfy the domestic electrical requirements as IMPORTANT
regulated in each country.
• When closing the cover, close it with both hands
until the cover does not turn in order to bring the
housing and cover into tight contact.
• Tighten while confirming that the cover rotates
smoothly.

In case grounding rings In case grounding rings are not used.


are used. (Available only for metal piping)
F0427.ai

Figure 4.4.4  Grounding (Integral Flowmeter)

IM 01E22A01-01EN
<4. Wiring> 46
(2) Terminal Configuration
(Integral Flowmeter and AXG4A Transmitter)
Protective Protective
Grounding Terminal Grounding Terminal

(2)
(1)

Cover locking screws


F0428.ai
Integral Flowmeter AXG4A Remote Transmitter
Figure 4.4.5 Removing the Terminal Box Cover for Integral
Flowmeter Integral Type/AXG4A Remote Transmitter:
<To be wired to Power Supply and I/Os>
Cover locking screws

M4 Screw Type

(1)

(3)
(2)

Clamp Type
F0429.ai

Figure 4.4.6 Removing the Terminal Box Cover for AXG4A


Remote Transmitter

2) Terminal Configuration
When the cover is removed, the connection
terminals will be visible.
The description of the terminal symbols is shown in
Figure 4.4.7 or Figure 4.4.8.
3) Wiring Procedure
1. Check the product’s power is off.
2. Wire the signal cable and excitation cable to
each terminal. Terminal Symbol Description
3. Install the terminal cover. Shorting Screw
(Need to be fixed for normal operation)
4) Installing the Cover Functional Grounding
Install the cover to the flowmeter by turning N/- Power Supply
it clockwise. Tighten the cover locking screw L/+
I/O4 -
(1 and 3) (See Figure 4.4.5 and Figure 4.4.6) I/O4 +
counterclockwise using a hexagonal wrench I/O3 -
I/O3 + Refer to
(nominal size 3) to lock the cover. I/O2 - Input/Output Table
I/O2 +
I/O1 -
I/O1 +
Protective Grounding
(Inside and outside of the terminal box)
F0430.ai

Figure 4.4.7 Terminal Configuration (Integral Flowmeter and


AXG4A Remote Transmitter)

IM 01E22A01-01EN
<4. Wiring> 47
AXG4A Remote Transmitter:  BRAIN, HART
<To be wired to Remote Sensor> Communication
Connection Terminal
and I/O code
BRAIN HART I/O1 I/O2 I/O3 I/O4
Iout1 P/Sout1
DA JA - -
Active Passive
Iout1 P/Sout1 P/Sout2 Iout2
DB JB
Active Passive Passive Active
Iout1 P/Sout1 Sin Iout2
DC JC
Active Passive No-voltage Active
Iout1 P/Sout1 Sout P/Sout2
DD JD
Active Passive Passive Passive
Iout1 P/Sout1 Sin P/Sout2
DE JE
Active Passive No-voltage Passive
P/Sout2
Iout1 P/Sout1 Sin
DF JF Active
Active Passive No-voltage
(With resistor)
P/Sout2
Iout1 P/Sout1 Sin
DG JG Active
Active Passive No-voltage
(Without resistor)
Iout1 P/Sout1 Iout2 Iin
DH JH
Active Passive Passive Active
Iout1 P/Sout1 P/Sout2 Iin
DJ JJ
Active Passive Passive Active
Terminal Symbol Description Iout1 P/Sout1 Sin Iin
DK JK
Active Passive No-voltage Active
SA
SB
A Flow Signal Input  Modbus
B
C Communication
Connection Terminal
and I/O code
EX1 Excitation Current Output Modbus I/O1 I/O2 I/O3 + I/O3 - I/O4 + I/O4 -
EX2
M0 -
F0431.ai
Iin
M2 P/Sout1 Modbus Modbus Modbus
Figure 4.4.8 Terminal Configuration Active -
Passive C(Common) B(D1) A(D0)
Iout2
(AXG4A Remote Transmitter) M6
Active 4
Iout1: Current output with BRAIN/HART communication

Wiring
Iout2: Current output
Iin: Current input
P/Sout1: Pulse output or status output
P/Sout2: Pulse output or status output
Sin: Status input
Sout: Status output
Modbus: Modbus communication
The position of Communication and I/O code:
Integral Type:
AXG--
Remote Transmitter:
AXG4A-

IM 01E22A01-01EN
<4. Wiring> 48
(3) For AXFA11 Remote Transmitter Table 4.4.1 Terminal Symbols
(AXFA11 Remote Transmitter)
1) Removing the Cover
Terminal Symbol Description
While supporting the front of the cover with your
C
hand, flip the connecting screw protective cover
SA
over, and remove the four connecting screws. SIGNAL A Flow signal input
B
SB
AL+
ALARM OUT Alarm output
AL-
SO1+
STATUS OUT SO2+ Status output (Two outputs)
COM
I+ Current output
CURRENT OUT
I- 4−20 mA DC
Sl1+
F0432.ai STATUS IN Sl2+ Status input (Two inputs)
COM
Figure 4.4.9 Removing the Front Cover
(AXFA11 Remote Transmitter) P+
PULSE OUT Pulse output
P-
EX1
2) Terminal Configuration EXCITATION Excitation current output
EX2
When the cover is removed, the connection
L /+
terminals will be visible as shown below. POWER SUPPLY
N/-
Power supply

Functional grounding

Protective grounding (Outside of


the terminal)

IMPORTANT
Do not wire the terminal without terminal symbols in
terminal layout labels.
I+ I– SO1+ SO2+ COM AL+ AL– C SA A B SB
N/– L/+ EX1 EX2 P+ P– SI1+ SI2+ COM

F0433.ai
3) Installing the Cover
While supporting the front of the cover with your
hand, flip the connecting screw protective cover
over, and tighten the four connecting screws.

I+ I– SO1+ SO2+ COM AL+ AL– C SA A B SB


CURRENT OUT STATUS OUT ALARM OUT SIGNAL

N/– L/+ EX1 EX2 P+ P– SI1+ SI2+ COM


POWER SUPPLY EXCITATION PULSE OUT STATUS IN

F0434.ai

Figure 4.4.10 Terminal Configuration


(AXFA11 Remote Transmitter)

IM 01E22A01-01EN
<4. Wiring> 49
4.5 Connecting to Remote (2) Terminal Configuration
When the cover is removed, the connection
Sensor and Remote terminals will be visible as shown below.
Transmitter (Sensor Side) Remote Sensor:
<To be wired to Remote Transmitter>

WARNING Non Explosion Protection Use

For explosion protection type products, please be sure


to read the user's manual of the applicable explosion
protection type as listed in Table 1.1.

WARNING
Before wiring, be sure that the power supply to magnetic
flowmeter has been turned off to prevent an electrical
shock.

(1) Removing the Cover


Loosen the cover locking screw (1) (See Figure
4.5.1) clockwise using a hexagonal wrench (nominal
size 3) to unlock the cover. Upon shipment from the
manufacturing plant, the cover is unlocked. Hold
the sensor with your hand and remove the cover Explosion Protection Use 4
by turning it in the direction of the arrow as shown
below.

Wiring
(1)

Terminal Symbol Description


A
B Flow Signal Output
F0435.ai
C
Figure 4.5.1 Removing the Terminal Box Cover EX1 Excitation Current Input
(Remote Sensor) EX2
Protective Grounding
(Outside of the terminal box)

Functional Grounding
F0436.ai

Note: When submersible use or optional code DHC is selected,


waterproof glands with union joints and cables are
attached.
Figure 4.5.2  Terminal Configuration (Remote Sensor)

IM 01E22A01-01EN
<4. Wiring> 50
(3) Wiring of Remote Sensor and Remote 2) Connection with AXFA11 Remote Transmitter
Transmitter Connect wiring as shown in the figure below.

1) Connection with AXG4A Remote Transmitter I+ I– SO1+ SO2+ COM AL+ AL– CC SA A B SB

Connect wiring as shown in the figure below.


CURRENT OUT STATUS OUT ALARM OUT SIGNAL

FUSE
AXFA11 transmitter
Non Explosion Protection Use 2.5A 250V
N/– L/+
POWER SUPPLY
EX1 EX2
EXCIT ATION
P+ P–
PULSE OUT
SI1+ SI2+
STATUS IN
COM

AXG4A transmitter

AX01C dedicated A AX01C dedicated


signal cable signal cable
SA Excitation
cable Remote
B Transmitter
sensor
SB SA Taping*
A A
C B B
SB Taping*
EX1 C C
A EX2 EX1 EX1
EX2 EX2 EX2
B
Excitation cable * Individually tape and insulate
the shields corresponding to
EX1 SA and SB on the remote
sensor side.
C
A Remote sensor F0438.ai
EX2
B Figure 4.5.4  Wiring Diagram (AXFA11 Remote Transmitter)

EX1
C (4) Grounding
Remote sensor

Explosion Protection Use WARNING


AXG4A transmitter
For the wiring of protective grounding, terminate the
AX01C dedicated A
signal cable cable finish with round shaped crimp terminal with
SA
insulation cover (for M4 screw), and connect it to the
B
proctective grounding terminal reliably.
SB
C
EX1

EX2
CAUTION
Excitation cable
• The grounding should satisfy Class D requirements
(grounding resistance, 100 Ω or less).
• For explosion protection type, the grounding must
A EX2 satisfy the domestic electrical requirements as
B regulated in each country.

EX1
C

Transmitter
Remote sensor
Remote sensor
IMPORTANT
SA Taping*
A A Improper grounding may result in an adverse effect
B B
SB Taping* on the flow measurement. Ensure that the product is
C C properly grounded.
EX1 EX1
EX2 EX2
* Individually tape and insulate the shields corresponding to SA and SB on the
remote sensor side.
F0437.ai

Figure 4.5.3  Wiring Diagram (AXG4A Remote Transmitter)

IM 01E22A01-01EN
<4. Wiring> 51
The electromotive force of the magnetic flowmeter (5) Installing the Cover
is minute and it is easy to be affected by noise.
Install the cover to the terminal box by turning it
Therefore, be sure to ground according to Figure
clockwise. Tighten the cover locking screw (1) (See
4.5.5. The reliable grounding equalize the reference
Figure 4.5.1) counterclockwise using a hexagonal
electric potentials (terminal potential) of the sensor
wrench (nominal size 3) to lock the cover.
and the transmitter, the measuring fluid potential and
the ground potential, and then reduce the affection
by noise.
The grounding rings make a connection between WARNING
the measured fluid and the ground and protects the
• When opening and closing the cover, be sure to
flared face of lining.
handle the cover carefully so that there are no
Grounding rings are supplied with the products
damage and foreign matter adhesion at its threads
when specified with dedicated optional code.
and O-ring. Keep checking their condition and clean
600 V vinyl-insulated cable
Cable cross section area: the threads in case of adhering the foreign matter.
2 mm2 or larger • Replace the cover in case the treads receive
damages.
• Replace the O-ring if there is any scarring or
transformation. And apply silicone based grease at
the O-ring in case of the shortage and exhaustion of
grease.

Grounding ring

• Grounding Resistance: IMPORTANT


100 Ω or less (Class D requirements)
• When closing the cover, close it with both hands 4
until the cover does not turn in order to bring the
CAUTION housing and cover into tight contact.

Wiring
• Tighten while confirming that the cover rotates
• The grounding should satisfy grounding resistance smoothly.
requirement, 100 Ω or less (Class D grounding).
• For explosion protection type, the grounding must
satisfy the domestic electrical requirements as
regulated in each country.

In case grounding rings In case grounding rings are not used.


are used. (Available only for metal piping)
F0439.ai

Figure 4.5.5  Grounding (Remote Sensor)

IM 01E22A01-01EN
<4. Wiring> 52
4.6 Input and Output
This section provides descriptions of the specificaiton and wiring of the input and output signals.
In accordance with the communication and I/O code specified, the function assigned to each terminal is different. For the
specification and terminal configuration, read Section 4.4 and the applicable general specifications as listed in Table 1.1.
For AXFA11, read the applicable user’s manual as listed in Table 1.1.

(1) Output Signal


Galvanic isolation:
All circuits for inputs, outputs and power supply are galvanically isolated from each other.
Output signal type Specification
Active current output One or two current outputs are available depending on the specification.
[Iout]: Depending on the measured value, the active current output delivers 4 to 20 mA.
Output current 4 to 20 mA DC
Load resistance 750 Ω or less
Load resistance for BRAIN communication 250 to 450 Ω
Load resistance for HART communication 230 to 600 Ω
Current output accuracy ±8 μA (±0.05% of span)

Transmitter
Iout+
Receiver

Iout-
F0440.ai

Figure 4.6.1  Connection diagram: Active current output [lout]


Passive current output Current output: 4 to 20 mA
[Iout]: Output current 4 to 20 mA DC
External power supply 10.5 to 32 V DC
Load resistance 911 Ω or less
Load resistance for BRAIN communication 250 to 450 Ω
Load resistance for HART communication 230 to 600 Ω
Current output accuracy ±8 μA (±0.05% of span)
R: Load Resistance (Ω)

911
U - 10.5
R=
0.0236

0
10.5 32
U: External Power Supply (V)
F0441.ai

Figure 4.6.2 Load Resistance as External Power Supply

Figure 4.6.2 shows the relation between external power supply and load resistance. The
higher supply voltage allows the higher load resistance.
Transmitter
Iout+
U: External Power Supply

R: Load Resistance

Iout- F0442.ai

Figure 4.6.3  Connection diagram: Passive current output [lout]

IM 01E22A01-01EN
<4. Wiring> 53
Output signal type Specification
Active pulse output Connection of an electronic counter
[P/Sout]: Observe that maximum allowable voltage and voltage polarity are correct when wiring.
Load resistance 1 kΩ or more
Internal power supply 24 V DC ±20%
Maximum pulse rate 10,000 pulses/s
Maximum frequency output rate 12,500 Hz

Transmitter
24 V P/Sout+ Electronic
Load Counter
Resistance

P/Sout-
0V
F0443.ai

Figure 4.6.4  Connection diagram: Active pulse output [P/Sout] (Electronic counter)

Connection of an electromechanical counter


Maximum current 150 mA or less
Average current 30 mA or less
Internal power supply 24 V DC ±20%
Maximum pulse rate 2 pulses/s
Pulse width 20, 33, 50, 100 ms

Transmitter
24 V P/Sout+ Electromechanical
Protective Counter
Diode

P/Sout- 4
0V
F0444.ai

Wiring
Figure 4.6.5 Connection diagram: Active pulse output [P/Sout] (Electromechanical counter)
When Communication and I/O code DG or JG is specified, upon shipment from the
manufacturing plant, the output is set for electromechanical counter. If the output is set for
electronic counter, the following parameter is change from “For magnetic counter” to “Normal”.
For detailed parameter setting, read the user’s manual of the applicable communication type
as listed in Table 1.1.
Display Menu Path (AXG/AXG4A):
Device setup ►Detailed setup ►Pulse/Status out ►PO2/SO2 ►Active pulse

Active pulse output Internal power supply 24 V DC ±20%


[P/Sout] with internal Internal pull-up resistor 2.2 kΩ
resistor: Maximum pulse rate 10,000 pulses/s
Maximum frequency output rate 12,500 Hz

Transmitter
Internal Resistor
24 V P/Sout+
Electronic
Counter

0V P/Sout-
F0445.ai

Figure 4.6.6 Connection diagram: Active pulse output [P/Sout] (with internal resistor)

IM 01E22A01-01EN
<4. Wiring> 54
Output signal type Specification
Passive pulse output Connection of an electronic counter
[P/Sout]: Maximum voltage and correct polarity must be observed for wiring.
Maximum load current 200 mA or less
Power supply 30 V DC or less
Maximum pulse rate 10,000 pulses/s
Maximum frequency output rate 12,500 Hz

Transmitter
P/Sout+
Load Electronic
Resistance Counter

P/Sout-
F0446.ai

Figure 4.6.7 Connection diagram: Passive pulse output [P/Sout] (Electronic counter)

Connection of an electromechanical counter


Transmitter
P/Sout+
Protective Electromechanical
Diode Counter

P/Sout-
F0447.ai

Figure 4.6.8 Connection diagram: Passive pulse output [P/Sout] (Electromechanical counter)


Active status output Because of connecting to a transisiter, observe that maximum allowable current, voltage
[P/Sout]: polarity and output current level are correct.
Load resistance (External instruments) 1 kΩ or more
Internal power supply 24 V DC ±20%

Transmitter
24 V P/Sout+ Load
Resistance

P/Sout-
0V
F0448.ai

Figure 4.6.9  Connection diagram: Active status output [P/Sout]


Active status output Internal power supply 24 V DC ±20%
[P/Sout] with internal Internal resistor 2.2 kΩ
resistor:
Transmitter
Internal Resistor
24 V P/Sout+
External
Instruments

0V P/Sout-
F0449.ai

Figure 4.6.10 Connection diagram: Active status output [P/Sout] (with internal resistor)

IM 01E22A01-01EN
<4. Wiring> 55
Output signal type Specification
Passive status output Because of connecting to a transisiter, observe that maximum allowable voltage, voltage
[P/Sout or Sout]: polarity and maximum allowable current are correct.
Maximum load current 200 mA or less
Power supply 30 V DC or less

Transmitter
P/Sout+ or Sout+
External
Instruments

P/Sout- or Sout-
F0450.ai

Figure 4.6.11 Connection diagram: Passive status output [P/Sout or Sout]

A relay must be connected in series to switch alternating voltage.


Transmitter
Relay
P/Sout+ or
Sout+ Protective Solenoid
Valve
Diode

P/Sout- or AC Power Supply


Sout-
F0451.ai

Figure 4.6.12 Connection diagram: Passive status output [P/Sout or Sout] (Solenoid valve)

(2) Input signals

Input signal type Specification


Active current input The active current signal is used for connecting to an external device with a passive current
4
[Iin]: output, e.g. two-wire transmitter.

Wiring
Input current 2.4 to 21.6 mA
Internal power supply 24 V DC ±20%
Internal load resistance 160 Ω or less

Transmitter
24 V Iin+
External Instruments
(passive current output)
Internal Load Resistance

0V Iin-
F0452.ai

Figure 4.6.13  Connection diagram: Active current signal [Iin]


Status input [Sin]:
IMPORTANT
The status input detects a signal without voltage.
Loading voltage during the switching status "Close" may result in damage on the electrical
circuit.

The status input is used for connecting to the following no-voltage contacts.
Switching status Resistance
Closed 200 Ω or less
Open 100 kΩ or more
Transmitter
Sin+

Sin-
F0453.ai

Figure 4.6.14  Connection diagram: Status input [Sin]

IM 01E22A01-01EN
<5. Basic Operating Procedures> 56

5. Basic Operating Procedures


5.1 Operation by Display unit
NOTE
The parameter settings from display unit can be carried
out using the three IR (infra-red) switches - namely, the The language on the display is set to “English” as default
[SET] [SHIFT] and [▼] switches. The IR switches enable at the factory shipment. Select the adequate language
the user to set parameters from the outside of the glass of referring to the Subsection 5.2.2. The menu pass of the
the display cover. display on this manual is selected to “English”.
This section provides descriptions of basic parameter
configuration and operation procesures of IR switches.
This product can be also operated using the dedicated
handheld terminal or the FieldMate (Versatile Device
5.2 Display and Basic
Management Wizard). For operation in details, read the Configuration
user’s manual of the applicable communication type
The display unit of AXG Integral Flowmeter and AXG4A
(for AXG/AXG4A) or the hardware/software edition (for
Remote transmitter has various functions below.
AXFA11) as listed in Table 1.1.
5.2.1 Display

WARNING microSD card


(Optional code: /MC)
Be sure to enable the write protect function to prevent
the overwriting of parameters after finishing parameter 00 : 00 Status icon and time
setting. 0.00000m/s VEL
Data display
(Abbreviation:
In rare cases, the IR switches may respond 0.0% FLP
see Table 5.2.1)
22.000mA A01
unexpectedly to water drops or extraneous substances SET SFT INC Switch On/Off status
sticking on the surface of display panel, due to the (On: inverted)
IR switches
operating principal. The possibility of malfunction arises
after rain or cleaning operation near the place where the
flowmeter is installed. Turning on and off the flashlight
F0501.ai
etc. towards the IR switch may also be a cause of
malfunction. (1) Basic operation of IR switches
Read Section 6.3 for the hardware write protect The operation from display panel is done by using
function, and the user's manual of applicable the three IR switches; [SET], [SHIFT] and [▼]. The
communication type as listed in Table 1.1 for the combination of the two switches provides a different
software write protect function. function, and the function is indicated on the display.
Indicate
IR switch
of switch Function
(Note 1)
IMPORTANT (Note 2)
▪ Apply parameter (Note 3)
[SET►] SET ▪ Enter data (Note 3)
Operate the display unit under the condition where ▪ Move to next menu
direct sunlight, etc... do not shine to the IR switches ▪ Move cursor right
[SHIFT] SFT
(Numeric type parameter)
directly when the parameter setting operation is carried ▪ Move cursor down
out. (Select type parameter)
▪ Increment value
[▼] INC
(Numeric type parameter)
▪ Change position of decimal point
NOTE (Numeric type parameter)
▪ Move cursor up
[SHIFT] + [▼] (Select type parameter)
DEC
• Always keep the cover closed and operate the (=[▲]) ▪ Decrement value
setting switches from the outside of the glass (Numeric type parameter)
SHIFT + SET► ▪ Cancel
window. (=[ESC◄])
ESC
▪ Back to previous menu
• If dirt, dust or other substances surfaces on the
Note 1: [A] + [B] (=[C]): The function is changed to switch [C]
glass of display cover, wipe them clean with a soft when switch [B] is pushed while pushing switch [A].
dry cloth. Note 2: [SET], [SFT], [INC], [DEC] and [ESC] indicate the
• The operation with dirty gloves may cause a switch assigned function in accordance with display mode at
that time.
response error. Note 3: “Apply” and “Enter” are executed by pushing a switch
twice. If a switch after first pushing a switch.

IM 01E22A01-01EN
<5. Basic Operating Procedures> 57
(2) Status icons 5.2.2 Basic Configuration for Display
Icon Contents Icon Contents For paramter setting from display panel, configurable
Write protect Invalid Write protect Valid parameters differ by the three operational levels specfied
in Table 5.2.2, and a passcode is needed to enter into
Device Busy Device Fault
Setting mode. No passcode requires for “Operator”, and
Ready for microSD Accessing microSD
card card a passcode corresponding to each level requires for
Disable to access
Uploading parameters
“Maintenance” or “Specialist”.
microSD card
For parameter in details, read the user’s manual of
Downloading
parameters
Trend graph executing applicable communication type as listed in Table 1.1.

BRAIN communication HART communication Table 5.2.2 Parameter setting from display panel and
operation level
Modbus
System alarm occurs Operation Reading
communication Writing parameters
Level parameters
Setting alarm occurs Process alarm occurs Operator All parameters Parameters related with basic display
settings including display language.
Information occurs Warning occurs Maintenance All parameters Parameters allowed for Operator level.
Parameters related with Zero adjustment.
Operation level: Specialist All parameters All Parameters
Display Damping Valid
Operator
Operation level: Operation level:
Specialist Maintenance The following parameters are available to “Operator” level
without passcode.
(3) Data indication part
The process values are available to select 8 items (1) Display Language Setting
maximum on the display. It is possible to indicate 4 items Display Menu Path:
Device setup ► Language
maximum on the display at the same time, and the rest 4
The language on the display is set to “English” as default
items are able to show by scrolling.
at the factory shipment. Select the adequate language.
Table 5.2.1 Abbreviation table of process values to be
indicated on the display. The selectable display language is different by the model 5
Abbreviation Contents and suffix code (display code) specified when ordering.

Basic Operating Procedures


FLP(*1) Flow rate % Position of the display code:
PRV(*1) Process value Integral type:
VEL(*1) Flow velocity
AXG--
VFL(*1) Volumetric flow
MFL(*1) Mass flow
Remote transmitter:
FLB Flow rate in % bar graph AXG4A-
CAL(*1) Calorie Display code Selectable display language
TL1(*1) Totalization value 1 1 English, French, German, Italian, Spanish,
TL2(*1) Totalization value 2 Portuguese, Japanese, or Russian
TL3(*1) Totalization value 3 2 English or Chinese
TAG Tag No.
LTG Long Tag (for HART communication type only)
COM Communication protocol (2) Display Contrast Setting (shading)
ADH Adhesion diagnostic Level (Alarm at Level 4)
Display Menu Path:
AO1(*1) Analog output value 1
Device setup►Detailed setup►Display set►Optional config►Contrast
AO2(*1) Analog output value 2
FNL Flow Noise Level (Alarm at Level 4) Available to change the contrast of the display.
TC1 Count value of totalizer 1
Setting item Contents
TC2 Count value of totalizer 2
-5 to +5 Set the contrast of the display
TC3 Count value of totalizer 3
(The value is small: Low, and the value is big: High)
MOD Information of Modbus communication setting
Display example (*2): R/001/19200/E/1

*1: Available to display the online trend graph.


*2: Explanation of display example
Example: R/001/19200/E/1

Transmission mode Stop bit


•R: RTU •1: 1 bit
•A: ASCII •2: 2 bit
Device address Parity
Baud rate •N: None
•O: Odd
•E: Even
F0502.ai

IM 01E22A01-01EN
<5. Basic Operating Procedures> 58
(3) Display Line Setting (4) Date Display Formant Setting
Display Menu Path: Display Menu Path:
Device setup ► Detailed setup ► Display set ► Optional config ► Device setup ► Detailed setup ► Display set ► Optional config ►
Line mode Format date
Available to select the number of lines of process value to The date display format can be specified below.
be indicated on the display. Setting item Contents
Up to four lines can be displayed at the same time. The MM/DD/YYYY Displays the date in "month/day/year".
character size changes depending on the number of line. DD/MM/YYYY Displays the date in "day/month/year".
YYYY/MM/DD Displays the date in "year/month/day".
Setting item Contents
1 line(big) Number of displayable process value : One (without The date needs to be set every time when the power is
unit) turned on.
1 line Number of displayable process value : One (with unit) In case the date is not set:
2 line Number of displayable process values : Two • BRAIN communication: Date counting starts from the
3 line Number of displayable process values : Three
date stored in the memory.
4 line Number of displayable process values : Four
• HART communication: Date counting starts
from 1900/01/01 00:00:00, according to HART
Table 5.2.3 Display line setting and display example
specification.
Lines of
Example 1 Example 2
display (5) Inverse Display Setting
00 : 00 00 : 00
VEL FNL
Display Menu Path:

0.50000 Device setup ► Detailed setup ► Display set ► Optional config ►


Inversion
1 line(big) SET SFT INC SET SFT INC
Available to change from normal diplay to white/black
F0503.ai F0508.ai

* Not indicate the Flow noise reverse display.


status.
* Indicate 32 characters of the Setting item Contents
Long Tag. Normal Characters in the display is Black.
00 : 00 00 : 00
Inverse Outline characters
0.50000
VEL FNL

1 line m/s Normal


SET SFT INC SET SFT INC
F0504.ai F0509.ai

* Indicate 32 characters of the


Long Tag.
00 : 00 00 : 00

0.5000m/s VEL
Normal
FNL

50.0% Long tag 1234567


FLP LTG

2 line 89ABCDEFGabcdefg
SET SFT INC SET SFT INC
F0505.ai F0510.ai

* Indicate 32 characters of the


Long Tag.
00 : 00 00 : 00

0.50000 m/s VEL


Normal
FNL

50.0% FLP
AO1
Long tag 1234567... LTG
TAG
12.00SFT
mA
TAG12345
SET INC SET SFT INC
F0506.ai F0511.ai
3 line
* Indicate 32 characters of the
Long Tag in the first line.
* Indicate 16 characters in the
first half of 32 characters of the
Long Tag in the second and
third lines.
0.50000m/s 00 : 00
VEL
Normal
00 : 00
FNL
50.0% FLP
Long tag 1234567...
LTG

12.000mA
AO1 TAG
FNL TAG12345
Normal
4 line SET SFT INC SET SFT INC
F0507.ai F0512.ai

* Indicate 16 characters in the


first half of 32 characters of the
Long Tag only

IM 01E22A01-01EN
<5. Basic Operating Procedures> 59
5.3 Display Mode and Setting [Passcode Confirmation and Change]
The confirmation and change of the passcode are
Mode allowed only by parameter setting from the display unit.
Display Menu Path:
The device runs in the Display Mode when the power Device setup ► Detailed setup ► Access cfg ► Chg mainte
is turned on. For check or change of parameters, the Device setup ► Detailed setup ► Access cfg ► Chg special
Setting Mode must be activated. The following procesure (1) Passcode for “Maintenance” operation level
explains how to change to the Setting Mode. For the To change the passcode (Maintenance code),
function of IR switches, read Subsection 5.2.1. “Maintenance” or “Specialist” as the operational level
is required.
[Procedure]
1) Turn on the power and wait for several seconds to (2) Passcode for “Specialist” operation level
move to display mode. To change the passcode (Specialist code),
00 : 00
“Maintenance” or “Specialist” as the operational level
0.00000l/min
PRV

0.00000m/s VEL
is required.
FLB
SET SFT INC
F0513.ai

2) Keep touching [SET] switch for two seconds. The


IMPORTANT
screen moves to the menu of Operation Level.
00 : 00
Display Menu Path:
Operation level Device setup ► Wizard
Maintenance
When parameters are changed in the Wizard of

Specialist
▼Exit
SET SFT INC
Easy setup, “Setting download” in the menu of
F0514.ai
each parameter must be executed after parameter
3) Select an appropreate operation level by moving the is changed. Without the execution, any parameter
cursor with [INC] or [DEC] switch. changed is not stored into the device.
Passcode is not necessary for “Operator”. For
“Maintenance” and “Specialist”, passcode is
necessary for each.
NOTE 5
For passcode setting, [SFT] is for position change,
and [INC] is for number, then twice [SET] is for entry If 10 minutes past without operation in the Setting

Basic Operating Procedures


completion. Mode, the screen goes back to the Display Mode.
The default passcode at the factory shipment is set to
“0000”.
Pass code
00 : 00
Parameter form
****
0000 There are three types of parameter form below.
0000 9999
SET SFT INC Type Example of display Contents
F0515.ai Select type 00 : 00 Select the adequate data
Unit
from among alternatives
4) When the Operation Level is determined, the screen m3
▲l(liter) which are detemined in
moves to “Device setup” as the Setting Mode where ▼cm3 advance.
SET SFT INC
parameters can be configured. F0516.ai

5) After completing parameter setting, push [ESC] Numeric type 00 : 00 Specify the data with a
Span
combination of number and a
switch. The screen returns to the Display Mode. +7200.00
+2200.00 decimal point into each digit.
+0.00001 +999999
SET SFT INC
F0517.ai
Alphanumeric 00 : 00 Configure the data with a
Tag No
type combination of alphanumeric
FT-1234
FT-1234 characters. (Tag No., Special
SET SFT INC
unit, etc…)
F0518.ai

The alphanumeric type indicates alphanumeric


characters in the following order.
0123456789ABCDEFGHIJKLMNOPQRSTUVWXYZabcdefghijklmnopqrstu
vwxyz!"#$%&'()*+,-./:;<=>?@[\]^_`{|}~"space"

IM 01E22A01-01EN
<5. Basic Operating Procedures> 60
5.4 Parameter Setting from 5.4.2 Setting example of Numeric type
Data: Flow rate span
Display Panel
The following is the procedure of changing the Flow rate
This section explains how to specify the parameters from
span as Numeric type parameter.
display panel. Select “Specialist” at the Operation Level Display Menu Path:
referring to Section 5.3. And select the parameters to be Device setup ► Detailed setup ► Pro var ► Volume ► Span
specified in the Setting Mode.

NOTE NOTE
Be sure to set the Flow rate unit in the beginning when
For the device with the ordering information specified at
the Flow rate unit and Flow span value are changed at
ordering, the specified parameters (flow span and unit,
the same time.
tag number, etc.) are stored in the device at the factory
When the unit is changed, the value of flow rate span is
shipment. Without the ordering information specified,
converted to related values automatically according to
parameter setting needs to be done by user.
the unit change.
5.4.1 Setting example of Select type
Data: Flow rate unit 00 : 00 Specify the Flow rate span unit.
Volume Move cursor with [INC] and [DEC] according
Time unit /h
The following is the procedure of changing the flow rate

Span +7200.00 to the menu path above, and select the


unit as Select type parameter. ▼Setting download “Span” then push [SET].
SET SFT INC

The flow rate unit needs to be specified with “Physical F0524.ai

unit” and “Time unit” individually. When the flow rate unit 00 : 00 The switch's functionality of setting the Flow
Span rate span is as below:
needs to be set “l/min”, select “l (litter)” at the Physical unit +7200.00
Plus/minus and mumeric change: [INC]
+2200.00
and “/min” at the Time unit. +0.00001 +999999 Movement on digits: [SFT]
Display Menu Path:
SET SFT INC
Determination of parameter: [SET]
F0525.ai
Device setup ► Detailed setup ► Pro var ► Volume ► Unit L : Minimum value
Device setup ► Detailed setup ► Pro var ► Volume ► Time Unit U : Maximum value
Push [SET] to decide while the value of Flow
00 : 00 Specify the Physical unit for volumetric flow. rate span is blinking. The screen returns to
Volume Move cursor with [INC] and [DEC] according the setting page after the setting.
▲Damp pls/ttl
Unit to the menu path above, and select the “unit”
▼Time unit then push [SET].
SET SFT INC
F0519.ai 5.4.3 Setting Example of Alphanumeric type
00 : 00 Move cursor with [INC] and [DEC], and Data: Tag No.
Unit select the “l(liter)” then push [SET]. As the
m3
selected unit is blinking, push [SET] to The following is the procedure of changing the Tag No. as
▲l(liter)
▼cm3 determin. The screen returns to the setting Alphanumeric type parameter.
SET SFT INC
page. Display Menu Path:
F0520.ai
Device setup ► Detailed setup ► Device info ► Order info ► Tag No.
00 : 00 Specify the Time unit for volumetric flow.
Volume Move cursor with [INC] and [DEC] according
▲Unit 00 : 00 Specify the Tag No..
Time unit to the menu path above, and select the “Time Device info Move cursor with [INC] and [DEC] according
Span unit” then push [SET]. ▲Date/Time ►

SET SFT INC Order info ►


to the menu path above, and select the
F0521.ai ▼Ver/Num info ► “Order info” then push [SET].
SET SFT INC

00 : 00 Move cursor with [INC] and [DEC], and F0526.ai


Time unit select the “/min” then push [SET]. As the

/s 00 : 00 For Tag No., up to 8 characters can be
/min selected unit is blinking, push [SET] to Tag No entered from display panel.
/h determin. The screen returns to the setting FT-1234

FT-1234 The switch's functionality of setting the Flow


SET SFT INC
page after the setting. rate span is as below:
F0522.ai
SET SFT INC
Plus/minus and mumeric change: [INC]
00 : 00 After completing the parameter setting, push F0527.ai
Movement on digits: [SFT]
0.00000l/min
PRV
[ESC] then the screen returns to the Display
Determination of parameter: [SET]
Mode.
0.00000m/s VEL Available characters: ASCII characters
FLB
SET SFT INC
Push [SET] to decide while the value of Tag
F0523.ai No. is blinking. The screen returns to the
setting page after the setting.

NOTE
Be sure to set the Flow rate unit in the beginning when
the Flow rate unit and Flow span value are changed at
the same time.
When the unit is changed, the value of flow rate span is
converted to related values automatically according to
the unit change.

IM 01E22A01-01EN
<5. Basic Operating Procedures> 61
5.5 microSD Card Setting 5.6 BRAIN Configuration Tool
For the device with optional code MC, by setting the The connection of the BRAIN configuration tool
dedicated microSD card into the slot on the display unit, (BRAIN TERMINAL (BT200) or FieldMate (Versatile
the parameter setting can be stored into it. The Device Management Wizard)) is shown as below.
stored data can be restored to the device. For the Read the user’s manual of BT200 (IM 01C00A11-01E)
detailed function, read the user’s manual of applicable for the operation, and the user’s manual of BRAIN
communication type as listed in Table 1.1. communication type as listed in Table 1.1 for the detailed
parameter setting via BRAIN communication

WARNING The communication signal is superimposed onto the 4 to


20 mA DC analog signal to be transmitted. The BRAIN
Use only micro SD cards sold by YOKOGAWA. configuration tool can interface with this device from
Operation cannot be guaranteed when other cards are the control room, this device site, or any other wiring
used. termination point in the loop, provided there is a minimum
load resistance of 250 Ω between the connection and the
receiving product.
(1) Installing microSD Card To communicate, it must be connected in parallel with this
Carefully insert the dedicated microSD card into the slot device, and the connections must be non-polarized. See
on the display unit until the slot holds the card. (see Figure 5.6.
Figure 5.5). 4 to 20 mA DC Control Room
Signal
Relaying Transmission Line Terminal Distributor
microSD card Terminals Board
Iout+
Iout-

Magnetic Flowmeter
Terminal Box Load
USB Resistance
FieldMate 250 to 450 Ω
Modem

00 : 00 USB

0.00000m/s VEL

PC/FieldMate BT200
5
0.0% FLP
F0529.ai
22.000mA A01

Basic Operating Procedures


SET SFT INC Figure 5.6 
Connecting the BRAIN Configuration tool

IMPORTANT
F0528.ai
Communication signal is superimposed on analog
output signal. It is recommended to set a low-pass
Figure 5.5 
microSD setting
filter (approximately 0.1s) to the receiver in order to
reduce the output effect from communication
(2) Removing microSD Card signal. Before online-communication, confirm that
The microSD is released from the slot by pushing it. To communication signal does not give effect on the
prevent from losing the microSD card, be careful to upper system.
handle the card.

IMPORTANT IMPORTANT
If the microSD card is removed without execution of Restrictions exist with regard to the distance over
“Unmount” on parameter setting, it may result in which communication is possible. Read the general
the corruption of stored data and the abnormal specifications as listed in Table 1.1.
operation of device.

For explosion protection type, the configuration tool


Display Menu Path: should be connected at the safe site of “no explosive
Device setup►microSD►Unmount atmosphere”.

IM 01E22A01-01EN
<5. Basic Operating Procedures> 62
5.7 HART Configuration Tool For explosion protection type, the configuration tool
should be connected at the safe site of “no explosive
The connection of the HART configuration tool atmosphere”.
(FieldMate (Versatile Device Management Wizard))
is shown as below. Read the user’s manual of HART 5.7.2 HART Configuration Tool and
communication type as listed in Table 1.1 for the DeviceRevision
detailed parameter setting via HART communication.
IMPORTANT
NOTE
Protocol revision supported by HART configuration tool
• For more details regarding the operations of the must be the same protocol revision or later than that of
HART configuration tool, read the manual of HART the device. If it is not, communication error occurs.
configuration tool.
• When using FieldMate, be sure that the revision is
(1) Device Description (DD) and Device Revision
R3.02.00 or later.
Before using the HART configuration tool, confirm that
the DD (Device Description) of this device is installed in
the configuration tool.
NOTE If correct DD is not installed to the configuration tool,
install a correct DD from the HART official site, otherwise,
Perameters on HART configuration tool are displayed
contact the respective vendors of the configuration tool
in English only. Even if any language other than
for its upgrade information.
English is selected as “display language” from display
The device revision is as follows.
panel, parameters are displayed in English on HART
DD Revision 1 or later
configuration tool.
Device Type AXG4A (0x371A)
Device Revision 1

5.7.1 Connections with HART Configura-


• Confirmation of DD revision
tion Tool (a) Turn on the power of the configuration tool under
The HART configuration tool can interface with this the standalone condition.
device from the control room, this device site, or any (b) Confirm the device revision from the installed DD
other wiring termination point in the loop, provided there file name according to the procedure provided for
is a minimum load resistance of 230 Ω between the the configuration tool.
connection and the receiving product. To communicate, DD file name is four digits, upper two digits are device
it must be connected in parallel with this device, and the revision and lower two digits are DD revision.
connections must be non-polarized.
Read Figure 5.7.
Control Room
NOTE
4 to 20 mA DC
Relaying Signal Terminal
Terminals Transmission Line Board Distributor Device revision of DD file is given in hexadecimal.
Iout+
Iout-

Magnetic Flowmeter • Confirmation of Device revision


Terminal Box Load
USB Resistance Connect the configurator to this device and confirm
230 to 600 Ω
FieldMate
Modem
the revision by the following parameter.
HART Communication Menu Path:
USB Device root menu ► Detailed setup ►
Device information ► HART setup ► Fld dev rev
PC/FieldMate
F0530.ai

Figure 5.7 Connecting the HART Configuration Tool

IMPORTANT
Communication signal is superimposed on analog
output signal. It is recommended to set a low-pass filter
(approximately 0.1s) to the receiver in order to reduce
the output effect from communication signal. Before
online-communication, confirm that communication
signal does not give effect on the upper system.

IM 01E22A01-01EN
<5. Basic Operating Procedures> 63
(2) Device Type Manager (DTM) and Device 5.8 Modbus Configuration Tool
Revision
The connection of the Modbus configuration tool is shown
When configuring the parameters by FieldMate, use the
as below.
DTM (Device Type Manager) of the following table.
Read the user’s manual of Modbus communication type
DTM Name AXG HART 7 DTM
as listed in Table 1.1 for the detailed parameter setting via
DTM Revision 5.6.4.0 or later *
Device Type AXG4A (0x371A)
Modbus communication.
Device Revision 1
5.8.1 Connections with Modbus
* : The DTM is included in Yokogawa DTM Library HART 6.5 Configuration Tool
or later.
The Modbus configuration tool is connected to the
transmitter instead of Modbus host.
NOTE RS-485 USB Adaptor is required to connect transmitter
to PC.
The DTM revision can be confirmed by “DTM setup”.
See Figure 5.8.
Device Files is a Media included in FieldMate. The user
e.g. FieldMate
registration site provides Device Files with the latest D R
update programs.
Pull Up
(URL: https://voc.yokogawa.co.jp/PMK/)
When updating the DTM, following operation by “DTM LT Balanced Pair D1 (+) LT
setup” is required. D0 (-)

• Update DTM catalog B AC Common Pull Down

• Assign corresponding DTM to the device.


R R LT: Line Termination
For details, read the user’s manual of FieldMate. D D
ADMAG Slave n
F0531.ai

Figure 5.8 Connecting the Modbus Configuration tool

5.8.2 Modbus Configuration Tool and


Device Revision
5
When configuring the parameters by FieldMate, use the

Basic Operating Procedures


DTM (Device Type Manager) of the following table.
DTM name AXG4A Modbus DTM
DTM Revision 1.0.1.0 or later
Device type AXG4A
Device Revision 1

NOTE
The DTM revision can be confirmed by “DTM setup”.
Device Files is a Media included in FieldMate. The user
registration site provides Device Files with the latest
update programs.
(URL: https://voc.yokogawa.co.jp/PMK/)
When updating the DTM, following operation by “DTM
setup” is required.
• Update DTM catalog
• Assign corresponding DTM to the device.
For details, read the user’s manual of FieldMate.

IM 01E22A01-01EN
<6. Operation> 64

6. Operation
After the installation of sensor into process piping, the 00 : 00 Select “Execute”.
wiring of input/output terminals, the configuration of Autozero

required parameters, and the zero adjustment prior to ▲ Execute


Result ►
peration, the flowmeter outputs a flow signal from its

SET SFT INC


F0603.ai
terminals as soon as the fluid is sent in the pipe.
00 : 00 Select “Execute”.
Execute
6.1 Pre-operation Zero ▲
Not execute
Execute
Adjustment ▼Not execute
SET SFT INC
F0604.ai

Zero adjustment is carried out to ensure that the output


When “Execute” blinks, touch [SET] to
for zero flow is 0% (i.e., 4 mA). Although adjustment to
00 : 00
Execute execute.
zero is performed at the manufacturing plant prior to Execute

shipment, this procedure must be carried out once again


SET SFT INC

following the installation of piping in order to match the F0605.ai

magnetic flowmeter to its operating conditions.


00 : 00 Autozero starts, and the progress is
This section describes the zero adjustment procedure Autozero function desplayed with a remaining time and a
executing...
using the display unit. For AXFA11, read the applicable bar graph. Wait for the completion.
user’s manual as listed in Table 1.1. 00 : 08 The time remaining
SET SFT INC
until the end.
F0606.ai

IMPORTANT Autozero
00 : 00 After Autozero finished, the display
returns to “Autozero” menu.
▲ Execute
• Zero adjustment should be carried out before actual ▼ Result ►
SET SFT INC
operation. Note that parameter setting or change F0607.ai

cannot be carried out during execution of zero


adjustment (i.e., for approximately 30 seconds). • Confirmation of zero adjustment result
• Zero adjustment should only be carried out when 00 : 00 For the result of Autozero, select “Result”
the sensor has been filled with measurement fluid Result and then “Zero value”.
and the fluid velocity is completely zero by closing ▲
▼ Zero value
the valve. SET SFT INC
F0608.ai
• Each time that the fluid being measured is changed,
be sure to carry out zero adjustment with the new 00 : 00 Result of Autozero is indicated as on
Zero value
fluid. – 00.018cm/s
the left.
– 00.018cm/s
– 99.999 + 99.999
SET SFT INC
F0609.ai

6.2 Zero Adjustment from


Display Unit
A procedure of executing zero adjustment is as follows;
NOTE
Display Menu Path: When the zero adjustment result exceeds defined
Device setup ► Diag/Service ► Autozero ► Execute
Device setup ► Diag/Service ► Autozero ► Result ► Zero value value, the warning [092: AZ wam] is indicated.
Enter the Setting Mode. (Read Section 5.3)
Zero adjustment can be executed with the following
00 : 00 Select “Diag/Service” accoriding to the
Device setup menu path above. parameter.
▲Process variables ►
Diag/Service ► BRAIN Communication:
▼Easy setup wizard ►
B50:AUTOZERO EXE
SET SFT INC
F0601.ai HART Communication Menu Path:
Device root menu ► Basic setup ► Autozero ► Autozero Exe
00 : 00 Select “Autozero”. Modbus Communication:
Diag/Service
▲Verification ► Register Address: 40361
Autozero ►
▼AO/AI trim ►
SET SFT INC
F0602.ai

IM 01E22A01-01EN
<6. Operation> 65
6.3 Hardware Switch Setting
NOTE
NOTE On the front of the amplifier, the burnout switch (SW1-1)
and the write protect switch (SW1-2) are located
The integral type is explained as an example. Pay same adjacent to each other. Accordingly, special care should
attention to the AXG4A remote transmitter. be taken when making switch settings.

6.3.1 Integral Type and AXG4A Remote


Transmitter WARNING
To prevent electric shock and maintain performance,
IMPORTANT do not remove the safety cover.

• Removing and installing the cover are necessary for


hardware switches. Perform removing and installing ● Setting of Burnout Switch
the cover as described in Section 3.6. When opening The burnout function sets the direction of current output
the cover, wait for more than 20 minutes after turning in situations where the CPU has become damaged.
off the power. This work must be carried out by the Upon shipment from the manufacturing plant, the burnout
trained personnel having knowledge of safety standard. direction is set to High (i.e., > 21.6 mA); however, in cases
• To preserve the safety, do not touch the electrical circuit where the optional codes C1 or C2 have been specified,
and the cables except the setting switches. the output direction will be set to Low (i.e., < 2.4 mA).
• When installing the cover, in order to contact the Modification of the burnout direction must be carried out
housing and the cover, be sure to screw it firmly into the using the burnout switch (SW1-1) (See Figure 6.3.1).
housing without any space between them.
Table 6.3.1 
Burnout switch (SW1-1)
(1) Remove the cover.
Position of Burnout Burnout
(2) While holding the display by hand, loosen the two Description
Switch Direction Output
mounting screws. 1 2 When optional code
(3) While holding the display by hand (careful for C1 or C2 is not
H ON High > 21.6 mA
L OFF specified, the setting
connecting cable), set the switches. Never remove
connector in this case. 1 2
is “High”.
When optional
6
code C1 or C2 is
H ON Low < 2.4 mA
specified, the setting

Operation
Address switch Pull up and Pull down Line termination L OFF
is “Low”.
(ADDRESS) switch (SW3) switch (SW2)

● Setting of Write Protect Switch


7654 3210 12 12 The write protect function is to prevent the overwriting of
1 ON parameters.
0 OFF
Write protection can be carried out using either the write
ADDRESS SW3 SW2
protection switch (SW1-2) (See Figure 6.3.1) or software
Burnout switch function with parameter setting. If either of these items is
Safety cover (SW1-1) activated, the overwriting of parameters will be prohibited.
Write protect
switch (SW1-2)
Table 6.3.2 
Write protect switch (SW1-2)
ON
1 2 Position of
Write Protect Function
H Switch
L
SW1 OFF 1 2
OFF (Factory setting)
H ON
L OFF
Parameter can be overwritten.
F0610.ai

Figure 6.3.1 Hardware switches 1 2


ON
H ON
L OFF
Parameter can not be overwritten.
(4) Taking care not to entangle the cables, tighten the two
screws on the display.
(5) Install the cover.

IM 01E22A01-01EN
<6. Operation> 66
● Setting of Line Termination Switch (SW2)
NOTE This switch is only available for the product with Modbus
communication.
• If the hardware switch is set to “ON”, the condition of Line terminations of two ends on the bus are required to
preventing parameter overwriting kept until the switch communicate Modbus.
is set to “OFF”. One termination mode can be set using the line
• For the software write protect, read the user’s manual termination switch (SW2) (See Figure 6.3.1).
of applicable communication type as listed in Table
1.1. Table 6.3.4 Line termination switch (SW2)

Position of Termination
Description
● Setting of Address Switch (ADDRESS) Switch mode
This switch is only available for the product with Modbus 1 2 Available when both SW2-1 and
communication. ON Bus end SW2-2 are“ON”.
For the product with Modbus communication, it is OFF (Resistance is 150 Ω)
necessary to set the device address. 1 2 Available when both SW2-1 and
The device address can be set using either the address
ON Not bus end SW2-2 are“OFF”.
switch (ADDRESS) (See Figure 6.3.1) or software OFF Factory setting.
function with parameter setting.
Both SW2-1 and SW2-2 must be set at the same position.
• Address Switch (Position 7)
By using the address switch (Position 7), select the ● Setting of Pull up and Pull down Switch
device address to be used from the device address (SW3)
specified by either the hardware switch or the This switch is only available for the product with Modbus
parameter setting. communication.
When the bus is in an idling state, it becomes unstable
potentially without setting D1 for “pull up” and D0 for “pull
Table 6.3.3  Address switch (Position 7)
down”.
Position of Switch Description
Pull up and pull down mode can be set using the pull up
7 6 5 4 3 2 1 0
1 The device address set by Address Switch and pull down switch (SW3) (See Figure 6.3.1).
0
(Position 0 to 6) is used.

7 6 5 4 3 2 1 0 Table 6.3.5  Pull up and pull down switch (SW3)


The device address set by parameter
1 setting is used.
0 Factory setting. Pull up and
Position of
Pull down Description
Switch
mode
• Address Switch (Position 0 to 6) Available when both SW3-1 and
1 2
By using the address switch (Position 0 to 6), the SW3-2 are“ON”.
ON Used
device address is set. OFF (Resistance : 600 Ω, Pull-up voltage:
Setting range: 1 to 127 +5 V)

If the address switch is set to 0, the device address is 1 2 Available when both SW3-1 and
automatically converted to 1. ON Not used SW3-2 are“OFF”.
OFF Factory setting.
Setting example:
If only the address switch “position 6” is set to 1, the Both SW3-1 and SW3-2 must be set at the same position.
resulting the device address is 64.
Master
(1 * 26 + 0 * 25 + 0 * 24 + 0 * 23 + 0 * 22 + 0 * 21 + 0 * 20)
D R
Pull Up

LT Balanced Pair D1 (+) LT


D0 (-)
B AC Common Pull Down

R R LT:Line Termination
D D
ADMAG Slave n
F0611.ai

Figure 6.3.2 Modbus connection

IM 01E22A01-01EN
<6. Operation> 67
6.3.2 AXFA11 Remote Transmitter
NOTE
IMPORTANT On the front of the amplifier’s, the burnout switch (i.e.,
Switch 1) and the write protect switch (i.e., Switch 2) are
• Removing and installing the cover are necessary for
located adjacent to each other. Accordingly, special care
hardware the switches. Perform removing and installing
should be taken when making switch settings.
the cover as described in Subsection 4.4.5. When
opening the cover, wait for more than 20 minutes after
turning off the power. This work must be carried out (1) Setting of Burnout Switch
by the trained personnel having knowledge of safety The burnout function sets the direction of current output
standard. in situations where the CPU has become damaged.
• To preserve the safety, do not touch the electrical circuit Upon shipment from the manufacturing plant, the burnout
and the cables except the setting switches. direction is set to High (i.e., 25 mA); however, in cases
where the optional codes C1 have been specified, the
(1) Loosen the two display unit mounting screws while output direction will be set to Low (i.e., 0 mA).
supporting it with your hand (See Figure 6.3.3). Modification of the burnout direction must be carried
Display unit mounting out using the burnout switch (i.e., Switch 1) (See Figure
screws (x2) 6.3.4).

Table 6.3.6 
Burnout switch (Switch 1)
Position of Burnout Burnout
Description
Switch Direction Output
Low High When optional code
High 25 mA C1 is not specified,
the setting is “High”.
Low High When optional code
Low 0 mA C1 is specified, the
setting is “Low”.
F0612.ai

Figure 6.3.3 Removing Mounting Screws of Display Unit (2) Setting of Write Protect Switch
The write protect function is to prevent the overwriting of
(2) Taking care of the connector and cable connecting parameters. 6
to the display unit, move the display unit as shown Write protection can be carried out using either the write
in Figure 6.3.4, and set the switches. Never remove protect switch (Switch 2) (See Figure 6.3.4) or software

Operation
connector in this case. function with parameter setting. If either of these items is
activated, the overwriting of parameters will be prohibited.

Table 6.3.7 
Write protect switch (Switch 2)

Position of
Write Protect Function
Switch

Enable (Factory setting)


Enable Protect Parameter can be overwritten.

Protect
Enable Protect Parameter can not be overwritten.
Low High

Switch 1
Switch 2
2
1
Burnout switch
Write protect switch
NOTE
Enable Protect F0613.ai
• If the hardware switch is set to “Protect”, the condition
Figure 6.3.4 Hardware switches
of preventing parameter overwriting kept until the
switch is set to “Enable”.
(3) After setting the switches, taking care not to entangle
• For AXFA11, read the user’s manual of applicable
the cables, install the display unit with two mounting
communication type as listed in Table 1.1.
screws.
(4) Install the cover.

IM 01E22A01-01EN
<7. Errors and Countermeasures (Display unit)> 68

7. Errors and Countermeasures


(Display unit)
The error messages are described in the following tables.
For AXFA11, read the applicable user’s manual as listed in Table 1.1.

Explanation of NE107 status:


NE107 status Status of the device

F Failure Device malfunction, Parts malfunction

C Function Check The output signal is temporarily invalid for the local operation or manual operation.

The device works in out of specification.


S Out of Specification
The output signal is uncertain for the process or the ambience.

Maintenance
M The maintenance is required in the near future.
Required

N No Effect Other issue

 System Alarm
Device breaks down and causes abnormal measurement.
Device replacement is needed.
NE107 Error Message
Error Description Countermeasure
Status Display

F 010:Main CPU FAIL CPU (Main board) failure was detected. Contact Yokogawa service center.

F 011:Rev calc FAIL Failure of reverse calculation was detected. Contact Yokogawa service center.

Turn on the power again within the temperature range. If the problem
F 012:Main EEP FAIL Failure of EEPROM (Main board) was detected.
does not improve, contact Yokogawa service center.

F 013:Main EEP dflt EEPROM (Main board) was reseted to default values. Contact Yokogawa service center.

F 014:Snsr bd FAIL Failure of sensor board was detected. Contact Yokogawa service center.

F 015:Snsr comm ERR Communication error of sensor was detected. Contact Yokogawa service center.

Failure of A/D transumitter 1 [flow velocity signal] was


F 016:AD 1 FAIL[Sig] Contact Yokogawa service center.
detected.

F 017:AD 2 FAIL[Excit] Failure of A/D transmitter 2 [Exciting current] was detected. Contact Yokogawa service center.

F 018:Coil open Coil of sensor was disconnected. Turn off the power, check coil of sensor and excitation cable.

F 019:Coil short Coil of sensor was shorted. Contact Yokogawa service center.

F 020:Exciter FAIL Failure of excitation circuit was detected. Contact Yokogawa service center.

F 021:PWM 1 stop Error of pulse width modulation 1 was detected. Contact Yokogawa service center.

F 022:PWM 2 stop Error of pulse width modulation 2 was detected. Contact Yokogawa service center.

F 023:Opt bd mismatch Mismatch of option board was detected. Contact Yokogawa service center.

F 024:Opt bd EEP FAIL Failure of EEPROM (option board) was detected. Contact Yokogawa service center.

F 025:Opt bd A/D FAIL Failure of A/D (option board) was detected. Contact Yokogawa service center.

F 026:Opt bd SPI FAIL Failure of SPI (option board) was detected. Contact Yokogawa service center.

F 027:Restore FAIL Restore of parameters was failed. Retry parameter restoration.

Check the ambient temperature of display is within the range. If the


F 028:Ind bd FAIL Failure of indicator board was detected.
problem does not improve, contact Yokogawa service center.

Turn on the power again within the temperature range. If the problem
F 029:Ind bd EEP FAIL Failure of EEPROM (indicator board) was detected.
does not improve, contact Yokogawa service center.

F 030:LCD drv FAIL Failure of LCD driver was detected. Contact Yokogawa service center.

F 031:Ind bd mismatch Mismatch of Indicator board was detected. Contact Yokogawa service center.

F 032:Ind comm ERR Communication error of indicator board was detected. Check connection of Indicator & main board.

F 033:microSD FAIL Failure of microSD card was detected. Change microSD card.

IM 01E22A01-01EN
<7. Errors and Countermeasures (Display unit)> 69
 Process Alarm
The device works normally and some issue of process causes abnormal measurement.
Maintenance work is needed.
NE107 Error Message
Error Description Countermeasure
Status Display

S 050:Signal overflow Failure of input signal was detected. Check signal cable and grounding.

Empty inside of sensor was detected.


S 051:Empty detect Fill flow tube with fluid.
(Empty pipe detection)

N 052:H/L HH/LL alm Flow rate exceeded upper limit or lower limit. Check flow rate and setting value.

The resistance value of the electrodes exceeded Level 4.


S 053:Adh over lv 4 Clean electrodes.
(Adhesion detection of insulation to electrode)

 Setting Alarm
The device works normally but parameter setting error occurs.
Parameter setting is needed.
NE107 Error Message
Error Description Countermeasure
Status Display

Setting error of flow span was detected.


S 060:Span cfg ERR Check or change span parameter setting.
(fulfill "0.05 m/s < Span < 16 m/s")

S 061:PV F cfg ERR PV was set to flow noise. Check or change PV FLOW SEL parameter setting.

Setting error of Current output 1 was detected.


S 062:AO 1 4-20 lmt Check or change Analog output 1 parameter setting.
(fulfill "LRV < HRV")

Setting error of Current output 2 was detected.


S 063:AO 2 4-20 lmt Check or change Analog output 2 parameter setting.
(fulfill "LRV < HRV")

Setting error of ararm high/low limit function was detected.


N 065:H/L cfg ERR (fulfill "Hi Alarm - Lo Alarm > H/L Hys" and "HH Alarm - LL Check and change H/L, HH/LL parameter setting.
Alarm > HH/LL Hys")

Setting error of density value was detected when PV was


S 066:Density cfg ERR Check and change Density parameter setting.
set to mass flow rate.

S 067:Pls 1 cfg ERR Setting error of Pulse output 1 was detected. Change Pulse output 1 parameter setting.

S 068:Pls 2 cfg ERR Setting error of Pulse output 2 was detected. Check and change Pulse output 2 parameter setting.

Configuration error of nominal size was detected.


C 069:Nomi size cfg (fulfill "0.99 mm < nominal size < 3000.10 mm (0.01 inch < Check and change nominal paramter setting. 7
nominal size < 120.10 inch)")

Errors and Countermeasures (Display unit)


Setting error of electrode adhesion detection function was
C 070:Adh cfg ERR detected. Check and change adhesion parameter setting.
(fulfill "Level1 < Level2 < Level3 < Level4")

Setting error of flow noise verification function was


C 071:FLN cfg ERR detected. Change flow noise paramter setting.
(fulfill "Level1 < Level2 < Level3 < Level4")

C 072:Log not start Data logging failed to start. Insert microSD card.

IM 01E22A01-01EN
<7. Errors and Countermeasures (Display unit)> 70
 Warning
The device works normally and measurement is also normal but warning occurs.
NE107 Error Message
Error Description Countermeasure
Status Display

S 080:AO 1 saturate Saturation of Analog output 1 was detected. Check process value and current output 1 parameter setting.

S 081:AO 2 saturate Saturation of Analog output 2 was detected. Check process value and current output 2 parameter setting.

S 082:Pls 1 saturate Saturation of Pulse output 1 was detected. Check process value and pulse output 1 parameter setting.

S 083:Pls 2 saturate Saturation of Pulse output 2 was detected. Check process value and pulse output 2 parameter setting.

S 084:AI saturate Saturation of Analog input was detected. Check current input value and current input parameter setting.

C 085:Cable miscon Misconnection of cable was detected. Check the signal cable and excitation cable connection.

C 086:Coil insulation Insulation deterioration of coil was detected. Contact Yokogawa service center.

The resistance value of electrode exceeded Level 3.


M 087:Adhesion lv 3 Recommend cleaning electrode.
(Adhesion detection of insulation to electrode)

N 088:LC warn Decrease of conductivity was detected. Check fluid conductivity.

M 089:Insu detect Insulation deterioration of electrode was detected. Contact Yokogawa service center.

N 090:FLN over lv 3 Flow noise exceeded Level 3. (Detection of flow noise) Check fluid conductivity or bubble.

N 091:FLN over lv 4 Flow noise exceeded Level 4. (Detection of flow noise) Check fluid conductivity or bubble.

Result of Autozero adjustment |Mag Flow Zero| exceeded


C 092:AZ warn Check fluid is stopped when executing auto-zero adjustment.
10 cm/s.

C 093:Verif warn Interruption of verification function was detected. Execute Verification again.

C 094:Fact noise warn Fluctuation of flow became larger. Check the fluid.

Test mode was executed for any of Flow velocity,


C 095:Simulate active Volumetric flow rate, Mass flow rate, Calorie, Current Release simulation or test mode.
output, Pulse output, Status input, Status output.

S 096:AO 1 fix It was detected that fixied value is set to Current output 1. Check current output 1 is test mode or not.

S 097:AO 2 fix It was detected that fixied value is set to Current output 2. Check current output 2 is test mode or not.

S 098:Pls 1 fix It was detected that fixied value is set to Pulse output 1. Check pulse output 1 is test mode or not.

S 099:Pls 2 fix It was detected that fixied value is set to Pulse output 2. Check pulse output 2 is test mode or not.

S 100:AI fix It was detected that fixied value is set to Current input. Check current input is test mode or not.

C 101:Param restore run Restore function of parameter is running. ―

N 102:Disp over Number of digits available for display exceeded the limit. Check Display format parameter.

N 103:SD size warn Free space of microSD card decreased to less than 10%. microSD card may run out of memory space.

M 104:Bkup incmplt Parameter backup failed. Retry parameter backup.

S 105:SD mismatch Mismatch of microSD card was detected. Change microSD card.

M 106:SD removal ERR Removal of microSD card failed. Remove microSD in appropriate rocedure.

N 131:Trans mismatch Mismatch of sensor and transmitter was detected. Contact Yokogawa service center.

 Information
The device works normally and measurement is also normal. Just reference information.
NE107 Error Message
Error Description Countermeasure
Status Display

N 120:Watchdog Error of Watchdog timer was detected. Contact Yokogawa service center.

N 121:Power off Power-off was detected. ―

N 122:Inst power FAIL Instantaneous power failure was detected. ―

N 123:Param bkup run Parameter backup is running. ―

N 124:Data log run Data log is running. ―

N 130:DevID not enter No data entry of Device ID was detected. Contact Yokogawa service center.

132:Modbus cfg The Modbus configuration has been changed, but the
N Restart Modbus communication.
update device is not operating according to its configuration.

As a result of self-test, inconsistency of internal circuit was


N 133:G/A mismatch Contact Yokogawa service center.
detected.

IM 01E22A01-01EN
71

Revision Information
 Title : ADMAG TI Series AXG Magnetic Flowmeter Installation Manual
 Manual No. : IM 01E22A01-01EN

Edition Date Page Revised Item


1st June 2017 — New publication
2nd Sep. 2018 Front page Small revisions and add notes for explosion protected type.
1 Add new manual numbers and small revisions.
5 Add (10) to 1.1.
6 Add an item to IMPORTANT.
7 Add small revisions.
36 Revise Figure 3.6.3.
37 Add an item to CAUTION.
44 Add an item to CAUTION.
45 Add CAUTION.
49 Revise Figure 4.5.2, 4.5.3. Add an item to CAUTION.
50 Add CAUTION.
56 Revise figure of 5.2.1.
61 Revise figure 5.5.
65 Revise figure 6.3.1.
3rd Oct. 2018 1 Add new manual number for Modbus communication type.
2 Add trademark informations (HART, Modbus).
7 Revise the table for blanking plug quantity.
37, 39, 43, 49 Add the WARNING for explosion protection type.
39 Add the explanation of cable for Modbus communication.
47 Add the table for connection terminal for Modbus communication type.
57 Add the explanations for Modbus communication.
63 Add the explanation of Modbus configuration tool.
64 Add the information of parameter for Modbus communication.
65, 66 Add the explanation of hardware switch setting for Modbus communication type.
68 to 70 Revise the table of error messages.

IM 01E22A01-01EN

You might also like