ALS Series: Exd Limit Switch Box

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Indicator Setting

1. Remove four screws and remove indicator cover.


2. Lift up indicator from the cover.
3. Set indicator on cover according to valve position.
4. Replace indicator cover and fasten with cover screws. Check to
C US
ensure that position indicator O-ring is properly located in seal
groove.
INSTRUCTION
- Use only wet cloth when cleanning the indicator.
- Indicators are easily adjusted to match the dome's
clear windows or the special rotor angle indicator,
such as 45o, 60o or 3 way indicator. Simply loosen
ALS Series
the four screws to adjust the indicator. Make sure Exd Limit Switch Box
dome window line up with rotor quadrants. Finally,
tighten
g the screws to insure a ggood seal.
Installation Operating
Installation Operating & &
Maintenance Instructions
Maintenance Instructions

Inspection and Maintenance


Inspect the components of the limit switch box for wear or damage and replace
where necessary.
- RECOMMENDED REPLACEMENT PARTS:
1. Limit switch. 3. Housing O-ring.
2. Position indicator O-ring. 4. Shaft O-rings(top and bottom)
Storage
To store ALS series Exd limit switch box, the following cautions are recommended:
- Ensure the flameproof surface have not any paint and scratch.
- Ensure the limit switch box is completely dry and water free.
- Maintain the entrances of cable by fitting the original or replacement plastic corks.
- Protect from dust, dirt and damage by packing in box or plastic bag.
Special Conditions for Safe Use
Repairs of the flameproof joints must be made in compliance with the structural
specifications provided by the manufacturer. Repairs must not be made on the basis
of values specified in tables 1 and 2 of EN/IEC 60079-1.
Important Notice
* ALL ALS LIMIT SWITCH BOX HAVE BEEN 100% FACTORY TESTED IN OPERATION ,
WATERTIGHTNESS AND PRESSURE TESTED WITH 15BAR WITH 60 SECONDS.

* REPAIRS OF FLAMEPROOF JOINTS MUCH BE MADE IN COMPLIANCE WITH THE


STRUCTURAL SPECIFICATIONS PROVIDED BY THE MANUFACTURER. Alpha Controls Ltd
* INFORMATION HEREIN INCLUDING PRODUCT SPECIFICATION IS SUBJECT TO Tel: +44 (0)1942 525833 Fax: +44 (0)1942 523413
CHANGE WITHOUT NOTICE. Unit 1 Ormside Close, Hindley Industrial Estate,Hindley Green Wigan UK. WN2 4HR
Instruction Limit Switch Adjustment
ALS series Exd limit switch boxes include ALS400, ALS500 and ALS600 which are 1. Loosen limit switch box cover screws and remove cover.
a primary rotary position indication device both for local and remote indication in hazard 2. Rotate actuator to full counterclockwise position. Valve is on fully
area. The ALS products were designed to integrate valve and NAMUR rotary pneumatic open or closed position.
actuator with a variety of mounting options, internal switches or sensors and/or feedback 3. Lift up bottom cam and turn until switch is activated and then
configurations. This kind of limit switch box was designed through advance and release. Engage cam back onto the splined retainer. Spring will
state-of-the-art engineering technology which have the product to be solid, beautiful and maintain cam engagement.
with high-level quality. The product also fully meets Exd explosion proof specifications and 4. Rotate actuator to full clockwise position.Valve is on fully closed
the bracket is designed in light of ISO5211 and NAMUR standard. or open position.
Specification 5. Push down top cam and turn until switch is activated and then
release. Engage cam back onto the splined retainer. Spring will
Model No. □ALS400- □ALS500- □ALS600-
maintain cam engagement.
6. Place cover on limit switch box and tighten.
Photo
INSTRUCTION
- Take care to ensure that housing O-ring is properly located in seal
Die-cast Aluminum with polyester powder coated, □SS304 O-ring sealed groove.
Enclosure O-ring sealed □SS316 O-ring sealed
- Keep the box tight while circuits are alive.
Explosion Proof Ex d IIC T6, IP66 Ex II 2G Ex d IIB T6, IP66 - Disconnect supply circuit before opening.
Temperature Range -20℃~85℃ - Ensure the flameproof surface have not any paint and scratch in
Cable Entry □2×3/4G(BSPP), □2×3/4NPT
Terminal Strips
the process of adjustment.
8~12 8~10
Position Indicator □90°Yellow Open, Red Closed □90°Green OPEN, Red Closed □other
Crouzet Max15A125-250VAC
Electrical Wiring
Mechanical □M2:2SPDT □M3:3SPDT □M4:4SPDT □M5:2DPDT INSTALLATION
Switches □ML2:2SPDTLow Temp: -40℃ □MG2:2SPDT Gold contacts 1. Remove limit switch box cover(Disconnect supply circuit before opening).
□PP: p+f Proximity Sensors NCB2-V3-NO, 2. Remove protection plugs from conduit entries and install conduit or plugs suitable for
Proximity
NAMUR Intrinsical safe(Ex ia II CT6), 8VDC,<=1mA
Sensors
□PA: ALPS Proximity Sensors 24VDC,<=150mA(2or3 wire)
type of protection required.
□QA2: ALMS Magnet Sensor 2SPST, 5~240VAC/DC,<=300mA, 2 wire 3. Engage wires in terminal strip using a small screwdriver.
Magnet Sensors
□QA3: ALMS Magnet Sensor 2SPDT, 5~240VAC/DC,<=300mA, 3 wire INSTRUCTION
Analog Output □F: position transmitter - Ensure the flameproof surface have not any paint and scratch in the process of
Analog output 4-20mA adjustment.
□MB3.3:30x80-130H:20-30(carbon steel with polyester powder coated) - All user connections are made at a numbered terminal strip. A wiring diagram is
Bracket
□MB3.3:30x80-130H:20-30(stainless steel SS304)
located inside the cover and indicated which terminal numbers correspond to switch
Installation CLOSE
contacts: normally open, normally closed common, etc. Simply follow the wiring
1. Attach proper mounting bracket to the limit switch box diagram and electric code to connect switches to your system.
Limit Switch Box
housing using four aniseed cap screws provided. - Solenoids may also be wired through the switch box. At least two auxiliary terminals
2. Align limit switch box shaft to top of actuator shaft and engage it. Bracket are included as an option. A ground screw is also included. Simply wire the solenoid to
3. Attach bracket to actuator using hardware provided. auxiliary terminals, and then connect power leads to the opposite
4. By actuating package the switch and actuator will self-align. Pneumatic Actuator
terminal side.
30

5. Tighten bracket to top of actuator. Limit Switch Box


- Be sure to properly ground the solenoid at provided ground
INSTRUCTION Bracket 130 terminal.
20

- Do not open when energized 80


- ALS series Exd switch boxes include two 3/4" BSPP conduit
Pneumatic
in hazardous atmospheres Actuator
entries. Be sure to follow the National Electric Code regulations
- Use only wet cloth when cleanning the indicator.
for rigid conduit, flexible conduit or cable systems as applicable.
Instruction Limit Switch Adjustment
ALS series Exd limit switch boxes include ALS400, ALS500 and ALS600 which are 1. Loosen limit switch box cover screws and remove cover.
a primary rotary position indication device both for local and remote indication in hazard 2. Rotate actuator to full counterclockwise position. Valve is on fully
area. The ALS products were designed to integrate valve and NAMUR rotary pneumatic open or closed position.
actuator with a variety of mounting options, internal switches or sensors and/or feedback 3. Lift up bottom cam and turn until switch is activated and then
configurations. This kind of limit switch box was designed through advance and release. Engage cam back onto the splined retainer. Spring will
state-of-the-art engineering technology which have the product to be solid, beautiful and maintain cam engagement.
with high-level quality. The product also fully meets Exd explosion proof specifications and 4. Rotate actuator to full clockwise position.Valve is on fully closed
the bracket is designed in light of ISO5211 and NAMUR standard. or open position.
Specification 5. Push down top cam and turn until switch is activated and then
release. Engage cam back onto the splined retainer. Spring will
Model No. □ALS400- □ALS500- □ALS600-
maintain cam engagement.
6. Place cover on limit switch box and tighten.
Photo
INSTRUCTION
- Take care to ensure that housing O-ring is properly located in seal
Die-cast Aluminum with polyester powder coated, □SS304 O-ring sealed groove.
Enclosure O-ring sealed □SS316 O-ring sealed
- Keep the box tight while circuits are alive.
Explosion Proof Ex d IIC T6, IP66 Ex II 2G Ex d IIB T6, IP66 - Disconnect supply circuit before opening.
Temperature Range -20℃~85℃ - Ensure the flameproof surface have not any paint and scratch in
Cable Entry □2×3/4G(BSPP), □2×3/4NPT
Terminal Strips
the process of adjustment.
8~12 8~10
Position Indicator □90°Yellow Open, Red Closed □90°Green OPEN, Red Closed □other
Crouzet Max15A125-250VAC
Electrical Wiring
Mechanical □M2:2SPDT □M3:3SPDT □M4:4SPDT □M5:2DPDT INSTALLATION
Switches □ML2:2SPDTLow Temp: -40℃ □MG2:2SPDT Gold contacts 1. Remove limit switch box cover(Disconnect supply circuit before opening).
□PP: p+f Proximity Sensors NCB2-V3-NO, 2. Remove protection plugs from conduit entries and install conduit or plugs suitable for
Proximity
NAMUR Intrinsical safe(Ex ia II CT6), 8VDC,<=1mA
Sensors
□PA: ALPS Proximity Sensors 24VDC,<=150mA(2or3 wire)
type of protection required.
□QA2: ALMS Magnet Sensor 2SPST, 5~240VAC/DC,<=300mA, 2 wire 3. Engage wires in terminal strip using a small screwdriver.
Magnet Sensors
□QA3: ALMS Magnet Sensor 2SPDT, 5~240VAC/DC,<=300mA, 3 wire INSTRUCTION
Analog Output □F: position transmitter - Ensure the flameproof surface have not any paint and scratch in the process of
Analog output 4-20mA adjustment.
□MB3.3:30x80-130H:20-30(carbon steel with polyester powder coated) - All user connections are made at a numbered terminal strip. A wiring diagram is
Bracket
□MB3.3:30x80-130H:20-30(stainless steel SS304)
located inside the cover and indicated which terminal numbers correspond to switch
Installation CLOSE
contacts: normally open, normally closed common, etc. Simply follow the wiring
1. Attach proper mounting bracket to the limit switch box diagram and electric code to connect switches to your system.
Limit Switch Box
housing using four aniseed cap screws provided. - Solenoids may also be wired through the switch box. At least two auxiliary terminals
2. Align limit switch box shaft to top of actuator shaft and engage it. Bracket are included as an option. A ground screw is also included. Simply wire the solenoid to
3. Attach bracket to actuator using hardware provided. auxiliary terminals, and then connect power leads to the opposite
4. By actuating package the switch and actuator will self-align. Pneumatic Actuator
terminal side.
30

5. Tighten bracket to top of actuator. Limit Switch Box


- Be sure to properly ground the solenoid at provided ground
INSTRUCTION Bracket 130 terminal.
20

- Do not open when energized 80


- ALS series Exd switch boxes include two 3/4" BSPP conduit
Pneumatic
in hazardous atmospheres Actuator
entries. Be sure to follow the National Electric Code regulations
- Use only wet cloth when cleanning the indicator.
for rigid conduit, flexible conduit or cable systems as applicable.
Indicator Setting
1. Remove four screws and remove indicator cover.
2. Lift up indicator from the cover.
3. Set indicator on cover according to valve position.
4. Replace indicator cover and fasten with cover screws. Check to
C US
ensure that position indicator O-ring is properly located in seal
groove.
INSTRUCTION
- Use only wet cloth when cleanning the indicator.
- Indicators are easily adjusted to match the dome's
clear windows or the special rotor angle indicator,
such as 45o, 60o or 3 way indicator. Simply loosen
ALS Series
the four screws to adjust the indicator. Make sure Exd Limit Switch Box
dome window line up with rotor quadrants. Finally,
tighten
g the screws to insure a ggood seal.
Installation Operating
Installation Operating & &
Maintenance Instructions
Maintenance Instructions

Inspection and Maintenance


Inspect the components of the limit switch box for wear or damage and replace
where necessary.
- RECOMMENDED REPLACEMENT PARTS:
1. Limit switch. 3. Housing O-ring.
2. Position indicator O-ring. 4. Shaft O-rings(top and bottom)
Storage
To store ALS series Exd limit switch box, the following cautions are recommended:
- Ensure the flameproof surface have not any paint and scratch.
- Ensure the limit switch box is completely dry and water free.
- Maintain the entrances of cable by fitting the original or replacement plastic corks.
- Protect from dust, dirt and damage by packing in box or plastic bag.
Special Conditions for Safe Use
Repairs of the flameproof joints must be made in compliance with the structural
specifications provided by the manufacturer. Repairs must not be made on the basis
of values specified in tables 1 and 2 of EN/IEC 60079-1.
Important Notice
* ALL ALS LIMIT SWITCH BOX HAVE BEEN 100% FACTORY TESTED IN OPERATION ,
WATERTIGHTNESS AND PRESSURE TESTED WITH 15BAR WITH 60 SECONDS.

* REPAIRS OF FLAMEPROOF JOINTS MUST BE MADE IN COMPLIANCE WITH THE


STRUCTURAL SPECIFICATIONS PROVIDED BY THE MANUFACTURER. Alpha Controls Ltd
* INFORMATION HEREIN INCLUDING PRODUCT SPECIFICATION IS SUBJECT TO Tel: +44 (0)1942 525833 Fax: +44 (0)1942 523413
CHANGE WITHOUT NOTICE. Unit 1 Ormside Close, Hindley Industrial Estate,Hindley Green Wigan UK. WN2 4HR