Scope: Leakage Current Meter For Surge Arresters
Scope: Leakage Current Meter For Surge Arresters
Scope: Leakage Current Meter For Surge Arresters
SA 10i
Leakage Current Meter For
Surge Arresters
1 3
4 Keypad
4
5 4
8*:8<<
The Measurement
SA10i measures resistive leakage current as per IEC standard 60099 – 5 – B1. According to
IEC 60099 – 5 – B1. Harmonics are generated in the leakage current in LA because of the non-linear
voltage current characteristics of the arresters. Out of harmonics 3rd harmonics content depends on the
order harmonics current from it. This current is shown as resistive current.
!
conductor of LA. Also as System voltage and ambient temperature keeps on varying; SA 10i applies
correction factors for system voltage correction and also temperature correction to get corrected
resistive leakage current.
www.scopetnm.com
SCOPE
Special Features
@ !
'
'"
'
#'G "
@ Measures 3rd harmonic resistive current, and the total leakage current
@ In built temperature measurement facility enables calculation of temperature compensated leakage
currents
@
G
@ Date and time stamp on test results
@ Results are displayed on LCD and can be stored in the in-built memory of the instrument. 1000 test
records can be stored
@ The SA 10i is powered by easily available re-chargeable Lithium-ion batteries. It works for a day’s
testing needs on a single charge
@ The SA 10i is a switchyard compatible instrument. This makes the instrument extremely convenient
to use.
@ USB communication port to transfer data to PC and Windows based PC Downloading &
AnalysisSoftware.
@ Data Management, Analysis and Trending through SAData software
SAData : PC Downloading& Analysis software
SAData is windows based software that enables creating folders of LA Identity details on PC and up-
loading the same to instrument as well as downloading of test results from instrument to PC. This ensures
that library of various LA ID’s is generated in software. Once you create & upload the LA ID to instrument,
all result taken on that LA will be stored under same ID folder even when they are downloaded to PC.
It ensures structured storage of results of even huge nos. of LAs. Instrument can be connected to PC in
plug-n-play mode through USB port saving time.
!
&
&
"
#
dict the healthiness of a LA. The report generation for the tests taken is also possible. This report can
be exported to various formats like PDF, Excel, Word, HTML, etc. and also can be printed. You can add
operator name and any additional notes if you want to add.
@ 8
"
G
@ Simple tool to assess the residual life of Lightning arrester
@ J
G
@ Battery operation enables measurement in absence of AC supply
@ Suits equally to utilities, OEM’s, Test labs as well as testing and commissioning companies
www.scopetnm.com
SA 10i
Parameters SA 10i
Total leakage current Range Up to 10mA
Resistive leakage current Range Up to 10mA
Resolution 1μA
Inputs External Clamp-on CT
Display 2 line x 16 character backlit LCD
Compensation
*
N!
Temperature sensor Inbuilt silicon thermometer
PC Connectivity Yes
Memory for storage of 1000 results
Power supply 7.4V / 1150mAh, Internal rechargeable battery
Battery charging 100-270V AC, 50 / 60Hz ± 10%, 1 Phase
Dimension 190 x 129 x 50mm
Instrument Weight 1.5 kg
Accessories
Standard
Description Quantity
Low noise, Clamp-on CT 1 Set
Test Lead Set carrying CT cable, Charger and Master Earthing cable 1 Set
SAData - Data management and analysis Software CD *
Instruction Manual *
Elegant Carrying Case *
Optional
Large size low noise clamp on CT *
www.scopetnm.com