Basics of Explosion Protection: Introduction To Explosion Protection For Electrical Apparatus and Installations
Basics of Explosion Protection: Introduction To Explosion Protection For Electrical Apparatus and Installations
Basics of Explosion Protection: Introduction To Explosion Protection For Electrical Apparatus and Installations
14 5
2 6
3
Introduction to Explosion Protection
for Electrical Apparatus and Installations
Product Range
Product Range
A company of the
R. STAHL TECHNOLOGY GROUP
PRODUCT RANGE
Switchgear Lighting Instrumentation
2
14
2
3
Introduction
Introduction
6
5
It is a fact that gases, vapours and mists escape during the
production, processing, transportation and storage of flamma-
ble materials in the chemical and petrochemical industries, as
well as in the production of mineral oil and natural gas, in mining
and in many other sectors. During many processes also
flammable dusts are created. These flammable gases,
vapours, mists and dusts, form an explosive atmosphere with
the oxygen of the air. In the case that this atmosphere is ignited,
explosions take place which can result in severe harm to
human life and property
3
Contents
Contents
3 Technical Principles
3.1 Zone Classification
3.2 Explosion Groups and Temperature Classes
3.3 Types of Protection
3.3.1 Application and Combination of Types of Protection ”d” and ”e”
3.3.2 Applications of Type of Protection “Intrinsic Safety“
6 Appendix
6.1
6.2
Comparison of IEC Publications and European Standards (EN)
Safety Characteristics of Flammable Gases and Vapours
6.3 Classification of Hazardous Locations in North America
6.4 Constructional Requirements in North America
6.5 Degrees of Protection to IEC 60529 – IPXX
6.6 Degrees of Protection to NEMA Standards
6.7 Overview of the most important Approval and Testing Authorities
Literature
Index
4
14
2
3
6
5
Page 6-7
Page 8-10
Page 11-15
Page 16-17
Page 18-19
Page 20-26
Page 28
Page 29
5
1. The basic physic Principles and Definition between the lower and upper explosion limit that the mixture
of Explosion Protection reacts explosively when ignited. The explosion limits depend
on the ambient pressure and the proportion of oxygen in the
An explosion is the sudden chemical reaction of a flammable air.
material with oxygen with the simultaneous release of high
energy. Flammable materials may be present in the form of
gases, vapours, mists or dusts. In order for a fire or explosion Substance Lower explosion limit Upper explosion limit
to occur three conditions must exist: designation [Vol. %] [Vol.%]
Acetylene 2.3 78.0 (self-decomposing)
1. Flammable material (in ignitable quantities) Ethylene 2.3 32.4
2. Oxygen (in the air) Gasoline ~ 0.6 ~8
3. Ignition source Benzol 1.2 8
Natural gas 4.0 (7.0) 13.0 (17.0)
Heating oil/diesel ~ 0.6 ~ 6.5
Flammable
brennbarer
MaterialStoff Methane 4.4 16.5
Propane 1.7 10.9
E x p l o s i o n Carbon disulphide 0.6 60.0
Ignition Town gas 4.0 (6.0) 30.0 (40.0)
Sauerstoff
Oxygen Zündquelle
Source Hydrogen 4.0 77.0
no deflagration,
combustion no explosion
6
Ignition can be caused by various sources:
• hot surfaces
1
• electrical arcs and sparks
• electrostatic discharge
• atmospheric discharge (lightning)
• mechanical friction or impact sparks
• electromagnetic radiation
• ultrasonics
• adiabatic compression (shock waves)
• ionizing radiation
• optical radiation
• chemical reactions
• open flames
Integrated
Explosion Protection
Avoiding of the
formation of an
explosive
atmosphere 1
Prevention of the
ignition of an
explosive
atmosphere 2
Limiting of the
results of an explosion
to a harmless
level 3
Secondary Explosion Protection
If the danger of explosions cannot be completely or only partly
avoided by primary explosion protection measures, then mea-
sures must be taken which prevent the ignition of an explosive
atmosphere. The hazardous locations are therefore devided
into zones, according to the probability of an explosive atmos-
phere being created (see Section 3.1). In the USA and other
countries, hazardous locations are classified into Classes and
Divisions (see Section 5). For areas classified in this way,
requirements must be met concerning the apparatus which
are approved to be used in these locations. In addition it is sti- 4094-P
pulated how to prove that these minimum requirements have
been met (see section 2.2.3 and 5.6). Polyester Resin Control Station 8146
7
2. Statutory Regulations and Standards The European Standards series EN 50 014 and following
which deal with electrical explosion protection, have been
2.1 International Standards developed by the Technical Committee CENELEC TC31 and
The IEC (International Electrotechnical Commission) is adopted in the EU states as identical national standards (see
responsible for international standardization in the field of table below).
electrical technology. IEC publications which deal with
explosion protection for electrical apparatus and installations, It is determined that the member states of the European
are developed by the Technical Committee TC31. IEC publica- Union may not forbid the free trade of electrical apparatus, if
tions have the status of recommendations which are used for it complies with these standards and has a Certificate of
orientation purposes for national and regional standards Conformity from a recognized EC testing authority.
(see Appendix 6.1).
The IEC has introduced a procedure - the so called IEC-Ex The European directives and the uniform standards in the
Scheme - intended to become a globally recognized test and field of electrical explosion protection have proved to be very
certification procedure in the field of explosion protected elec- worthwhile in practice.
trical apparatus. Many technical and legal hurdles still have to
be overcome before this procedure can operate world-wide. 2.2.2 EC Directive 94/9/EC (ATEX 100a)
The EC Directive 94/9/EC was issued in 1994 to further
2.2 European Directives and Standards standardize explosion protection and make corresponding
adjustments in line with a new directive concept. It specifies
2.2.1 Introduction the requirements for explosion protected equipment and pro-
Already in 1976 the Council of the European Community esta- tective systems by prescribing essential health and safety
blished the prerequisite for unrestricted trade of explosion requirements. It guarantees the free trade within the Euro-
protected electrical equipment within the European Union pean Community, as agreed in Article 100a of the Treaty esta-
by ratifying the ”Directive on the harmonization of the laws of blished between the European Community member states.
the member states concerning electrical equipment for use This is also where the term ATEX 100a, generally used among
in potentially explosive atmospheres (76/117/EEC)”. the experts , comes from.
This directive has since then been supplemented by further
directives. The directive applies to all industrial potentially
Complete harmonization in this area was achieved in 1994 explosive areas including mining and also covers dust
with the new Directive 94/9/EC. Of course, in addition to a explosion protection. The scope covers all electrical and
uniform statutory regulation, uniform standards are required mechanical equipment and protective systems. In addition to
as well. CENELEC is the European Committee for Electrotech- the basic health and safety requirements, the classification
nical Standardization in which the countries of the European of the equipment and protective systems according to cate-
Union and the West European EFTA states cooperate. gories has also been re-organized, as well as the certification and
European standards (EN) are published in three official versi- marking of these.
ons (French, English and German). The members of CENELEC
are obliged to adopt the European Standards unchanged as
national standards.
8
2
Definitions • A ”potentially explosive atmos-
• ”Electrical installations” are individual or interconnected phere” is an atmosphere which
items of apparatus for the generation, conversion, storage, could become explosive due to
transmission, distribution, measurement, regulation, and local and operational conditions.
consumption of electrical energy.
• ”Equipment” means machines, apparatus, fixed or mobile Scope
devices, control components and instrumentation thereof and The directive applies to equipment and protec-
detection or prevention systems which, separately or jointly, tive systems for use in potentially explosive atmos-
are intended for the generation, transfer, storage, measure- pheres. Safety devices intended for use outside potentially
ment, control and conversion of energy for the processing of explosive atmospheres but required for or contributing to the
material and which are capable of causing an explosion safe functioning of equipment with respect to explosion are
through their own potential sources of ignition. also covered by the scope of this Directive. The Directive
• ”Protective systems” is the definition for design units which ATEX 100a doesn’t include a reference to mandatory stan-
are intended to halt incipient explosions immediately and / or dards, whereas specifies the essential health and safety
to limit the effective range of explosion flames and explosion requirements to be maintained and which are mandatory for
pressures. Protective systems may be integrated into equip- the design and construction. The protection against other
ment separately placed on the market for use as autonomous hazards (e.g. electric shock) which could be caused by this
systems. The components of the above defined equipment equipment, is required as well.
are not to be considered ”protective systems”.
•”Components” means any item essential for the safe func- 2.2.3 Certification and Marking
tioning of equipment and protective systems but with no In potentially explosive atmospheres only approved and
autonomous function marked equipment is allowed to be used. For the placing on
• An ”explosive atmosphere” is a mixture with air, under market of explosion protected equipment two directives
atmospheric condition, of flammable substances in the form apply in parallel.
of gases, vapours, mists, or dusts in which, after ignition has
occured, combustion spreads to the entire unburned mixture.
1) With an ... X if reference special conditions for use etc. 2) new: always present, old: not on Ex components
With a ... U for Ex components 3) Intrinsically safe apparatus: ib / associated apparatus: [ ib ]
9
Manufacturer’s EC Declaration of Conformity (94/9/EC) 2.3 The Statutory Regulations in Germany
The CE conformity marking and the written declaration of con- The Directive 94/9/EC (ATEX 100a) required the last modifica-
formity confirm that the product complies with all require- tion for the time being to the national regulations. It was
ments and assessment procedures specified in the EC Direc- adopted completely into German law on 12 December 1996
tives. when the 11th Regulation on the Equipment Safety Law
The certificates from notified bodies are recognized through- became effective.
out the European Community, moreover many testing authori-
ties have concluded bilateral agreements with other national The requirements concerning equipment used in hazardous
testing authorities outside the EC regulating the acceptance of locations are stipulated in the Regulation on Placing on the
test results (Appendix Overview of Testing Organizations). Market of Equipment and Protective Systems - Regulation
concening Electrical Installations in Explosive Atmospheres
Marking (ExVO)”.
In addition to the usual data such as the name of the manufac- The installation and operation of electrical systems in hazar-
turer, type, serial number and electrical ratings, any data rela- dous locations is governed by the ”Regulation concerning
ting to explosion protection must be contained in the marking Electrical Installations in Explosive Atmospheres (ElexV)”,
(see table above). which includes a reference to the ExVO in respect of the
requirements concerning the equipment.
The CE marking of the equipment confirms that it is designed
and manufactured in compliance with all applicable EC Direc- These new regulations will replace all previous relevant
tives. For example, an explosion protected luminaire marked regulations with effect from 1.7.2003.
with the CE conformity mark must comply with both the During the transition period, equipment can be certified for
”Explosion Protection Code of Practice” as well as the ”EMC - use in explosive atmospheres in accordance with the pre-
Directive”. vious regulation as well as the new Ex-Directive 94/9/EC.
A mixing of both regulations is possible, provided the basic
health and safety requirements of the Directive have been met.
10
3
3. Technical Principles which can also occur in these
areas must be further
3.1 Zone Classification classified as shown in Group II.
Hazardous locations are classified into zones to facilitate the
selection of appropriate electrical apparatus as well as the Electrical apparatus in Group II is
design of suitable electrical installations. Information and further classified into explosion groups
specifications for the classification into zones are included in and temperature classes.
IEC 60 079-10 and in national standards.
Furthermore, a European Directive (ATEX 118a), which deals Explosion Groups
with the installation and operation of electrical systems in The ignitability and explosion characteristics of an explosive
hazardous locations and governs the zone classification within mixture are properties typical of the material. The gases and
the EC, is currently being prepared. vapours are classified into explosion groups. Classification
The following table contains an overview of the zones and criteria are the ”Maximum Experimental Safe Gap (MESG)”
allocation of equipment (equipment category according to and the ”Minimum Ignition Current (MIC)”. The MESG and
94/9/EC) for the relevant zones. MIC are determined for the various gases and vapours
according to a stipulated testing arrangement. The maximum
experimental safe gap is the gap width of a vessel with an
Gases, Vapours, Mists Dusts Definition (94/9/EC) adjustable gap of 25 mm path length at which an internal
explosive ignition of an explosive mixture is not propagated to the exte-
atmosphere is rior (IEC 60 079-1A). The minimum ignition current relates to
present: the minimum ignition current for laboratory methane (IEC
Zone 0 ➞ Category 1 G Zone 20 ➞ Category 1 D continiously or long- 60 079-3).
term or frequently An overview of the maximum experimental safe gaps and
Zone 1 ➞ Category 2 G Zone 21 ➞ Category 2 D occasionally minimum ignition currents for the various explosion groups is
Zone 2 ➞ Category 3 G Zone 22 ➞ Category 3 D infrequently shown in the following table:
or short period
Explosion groups Maximum experi- Minimum ignition current ratio
G = gases, D = dusts
mental safe gap rel. to methane
If there are any doubts with the zone classification, the II A > 0.9 mm > 0.8
scope of the protective measures in the entire hazardous II B 0.5 mm to 0.9 mm 0.45 to 0.8
location should be based on the highest possible degree of II C < 0.5 mm < 0.45
likelihood of the occurance of dangerous explosive atmos-
phere. In such cases use of specialists is recommended. The dangerousness of the gases increases from explosion
group IIA to IIC. The requirements for the electrical
In Zones 0 and 1, only electrical apparatus with a Certificate of apparatus increase accordingly to these explosion groups.
Conformity or EC Type Examination Certificate may be used, For this reason, the marking of the electrical apparatus must
however in Zone 0 only equipment which has been expressly show for which explosion group it is designed. Electrical
approved for this purpose. In Zone 2, electrical apparatus which apparatus approved for IIC may also be used for all other
meet the basic health and safety requirements of the Directive explosion groups.
94/9/EC and which has a Manufacturer’s Declaration of Confor-
mity can be used. Of course, equipment which has been certi-
fied for use in Zones 0 and 1 may also be used in Zone 2.
11
Temperature Classes 3.3 Types of Protection
The ignition temperature of a flammable gas or liquid is the Only explosion protected equipment may be used in areas in
lowest temperature of a heated surface at which the gas/air which a dangerous, explosive atmosphere may still be
or vapour/air mixture ignites. It is ascertained using precisely expected despite the implementation of primary explosion
defined test equipment (IEC 60 079-4) and represents virtually protection measures.
the lowest temperature at which a hot surface can ignite a Electrical, explosion protected equipment can have various
respective explosive atmosphere. Flammable gases and types of protection according to the construction regulations
vapours may be classified into temperature classes using the of the series of standards EN 50 014 following (DIN VDE
ignition temperature. 0170/0171 Part 1 - following). The type of protection used by
The maximum surface temperature of electrical apparatus shall the manufacturer for apparatus essentially depends on the
always be lower than the ignition temperature of the gas/air or type and function of the apparatus. From a safety point of
vapour/air mixture in which it is used. Of course, equipment view, all standardized types of protection should be seen as
classified in a higher temperature class (eg T5) may also be being equal, but it should be noted here that the type of pro-
used for application in which a lower temperature class is tection ”n”can only be used in Zone 2.
required (eg T2 or T3). In North America there is a system The table on page 13 shows an overview of the standardized
incorporating further classification according to temperature types of protection and describes the basic principle as well as
subclasses. the usual applications.
The code letter ”s” is also used in Europe for
non-standardized protection measures.
Examples for the Classification of Gases and Vapours into Explosion Groups and Temperature Classes
T1 T2 T3 T4 T5 T6
I Methane
II A Acetone Ethanol Benzine Acetaldehyde
Ethane i-Amyl acetate Diesel fuel Ethylether
Ethyl ethanoate n-Butane Aircraft fuel
Ammonia n-Butyl alcohol Heating oils
Benzol (pure) n-Hexane
Ethanoic acid
Carbon oxide
Methane
Methanol
Propane
Toluene
II B Coal gas Ethylene
(lighting gas)
II C Hydrogen Acetylene Carbon disulphide
12
3
Type of protection Basic principle Diagram Main application
in accordance with
IEC or EN
Flameproof Parts which can ignite a potentially explosive Switchgear and control
enclosure atmosphere are surrounded by an enclosure gear and indicating
d which withstands the pressure of an explosive equipment, control
IEC 60 079-1 mixture exploding inside the enclosure and pre- systems, motors, trans-
EN 50 018 vents the propagation of the explosion to the formers, heating equip-
atmosphere surrounding the enclosure. ment, light fittings
Increased Additional measures are taken to increase the Terminal and connection
safety level of safety, thus preventing the possibility of boxes, control boxes for
e unacceptably high temperatures and the creation installing Ex-components
IEC 60 079-7 of sparks or electric arcs within the enclosure or (which have a different
EN 50 019 on exposed parts of electrical apparatus parts, type of protection), squir-
where such ignition sources would not occur rel-cage motors, light fit-
under normal operation. tings
Intrinsic safety Apparatus used in a potentially explosive area Measurement and control
i contain intrinsically safe electric circuits only. An technology, communica-
IEC 60 079-11 electric circuit is intrinsically safe if no sparks or tion technology, sensors,
EN 50 020 thermal effects are produced under specified test actuators
conditions (which include normal operation and
specific fault conditions) which might result in the
ignition of a specified potentially explosive atmos-
phere.
Powder filling Filling the casing of an electrical apparatus with a Transformers, capacitors,
q fine granular packing material has the effect of terminal boxes for
IEC 60 079-5 making it impossible for an electric arc created in heating conductors
EN 50 017 the casing under certain operating conditions to
ignite a potentially explosive atmosphere
surrounding the casing. Ignition must not result
either from flames or from raised temperature on
the surface of the casing.
Encapsulation Parts which may ignite a potentially explosive Switchgear with small
m atmosphere are embedded in sealing compound capacity, control and sig-
IEC 60 079-18 such that the potentially explosive atmosphere nalling units, display units,
EN 50 028 cannot be ignited. sensors
Type of protection Electrical apparatus is not capable of igniting a Zone 2 All electrical apparatus
n potentially explosive atmosphere This type of protection includes several methods of for Zone 2, less suitable
IEC 60 079-15 (under normal operation and under defined ignition protection. for switchgear and con-
EN 50 021 abnormal operating conditions). trol gear
13
3.3.1 Application and Combination of Terms and Definitions
Types of Protection ”d” and ”e” Intrinsically safe electrical circuit
The most important type of protection for switchgear is An electric circuit in which neither a spark nor the effect of
”Flameproof Enclosure”, usually in conjunction with “In- heat can cause a certain explosive atmopshere to ignite.
creased Safety”. Switchgear does produce sources of igni-
tion in normal use and therefore ”Increased Safety” alone is Intrinsically safe electrical apparatus
not applicable as type of protection for switchgear, since Electrical apparatus in which all circuits are intrinsically
”Increased Safety” is based on the principle to avoid sour- safe.
ces of ignition by additional measures. However, ”Increased
Safety”, in conjunction with ”Flameproof Enclosure”, cut a Associated electrical apparatus,
great figure for switchgear and control gear. Electrical apparatus which contains circuits some of which
are intrinsically safe and some are not, and which is
designed such that the non-intrinsically safe circuits cannot
negatively influence the intrinsically safe circuits.
14
3
Intrinsically safe apparatus Associated electrical apparatus
This contains intrinsically safe electric circuits only This contains both intrinsically safe and non-intrinsically safe electric circuits
All necessary information is provided such as The square brackets indicate that the associated electrical apparatus contains an intrinsi-
category, gas group and temperature class. cally safe electric circuit which may be introduced into Zone 1, gas groups IIA, IIB and IIC.
The apparatus may be used in Zone 1. The apparatus must be installed outside of The apparatus may be used in zone 1 due to
the potentially explosive area. installation in a flame-proof enclosure (”d”)
4085-P
Temperature field station
15
4. Installation and Operation of Electrical Appara- Electrical apparatus must be selected and installed such that
tus in Potentially Explosive Areas it is protected against external influences which may
adversely affect the explosion protection.
4.1 Duties of Installer, Manufacturer and Operator
Safety in potentially explosive areas can only be guaranteed 4.3 Methods of Installation
by a close and effective working relationship amongst all Essentially, three installation systems are used for electrical
parties involved. facilities in hazardous locations:
Ma
3. Conduit system
ler
nuf
The technical design of the electrical apparatus used with
tal
act
the individual types of installation is accordingly different.
Ins
ure
r
Tes
ion
tin
zat
gA
rdi
uth
nda
ori
Sta
ty
Authority
3023-P
The operator is responsible for the safety of his equipment. It is
his duty to judge where there is a risk of explosion and then
divide areas into Zones accordingly. He must ensure that the The installation systems worldwide;
equipment is installed in accordance with regulations and is left: Cable system with indirect entry
tested before initial use. The equipment must be kept in a fit centre: Cable system with direct entry
state by regular inspection and maintenance. right: Conduit system
The installer must observe the installation requirements and
select and install the electric apparatus correctly for its inten- Only the conduit system or mineral insulated cables (MI) are
ded use. permitted in the USA for all applications in Class 1, Division 1
Manufacturers of explosion protected apparatus are responsi- in accordance with NEC 501-4, whereby the mineral insula-
ble for routine testing, certification and documentation and are ted cables are mainly used as heating lines and fire resistant
required to ensure that each device manufactured complies signal and control lines. Certain types of cable and line are
with the design tested. also permitted in Division 2. A comparison of the various
systems is shown below.
4.2 Classification into Zones and Selection of
Apparatus Cable systems
The question of possible risks of explosion must be Cable systems are mainly used in Europe. For this, high-qua-
addressed at the early stages of planning a new facility. lity cables and lines are laid uncovered. It is only in areas in
When classifying potentially explosive areas, the influence which mechanical damage could be expectd that they are laid in
of natural or artificial ventilation must be considered in conduits which are open at both ends.
addition to the levels of flammable materials being released.
Furthermore, the classification figures relating to explosion In the case of indirect entry, the cables and lines are
technology must be determined for the flammable materials conducted via cable entrances into a wiring space in the type
being used (see Appendix 6.2). Only then a decision can be rea- of protection ”Increased safety” and connected to the termi-
ched on the division of potentially explosive areas into Zones nals also provided in ”Increased Safety”. From here, the indi-
and the selection of suitable apparatus. IEC 60 079-14 (DIN 60 vidual wires are conducted via flameproof line ducts into the
079-14) applies to the installation of electrical apparatus in flame proof enclosure.
potentially explosive areas Group II.
The line ducts are installed by the manufacturer, with the
Equipment shall only be used within the ambient temperature result that, by contrast with direct entry, a routine test of the
range stipulated in its marking. If the marking does not con- factory wired flame proof enclosure can be made.
tain any information, the standard range of between -20°C The installation engineer need only open the wiring space for
and +40°C does apply. the connection, not the flameproof enclosure with factory
Electrical apparatus with the types of protection ”d” and ”i” wiring.
must correspond to a subgroup IIA, IIB or IIC.
16
In the case of direct entry, the connecting lines are
conducted directly into the flameproof enclosure. Only cable
glands which have been specially certified for this purpose
4
may be used for this type of entry. The flexible gasket and the
cable sheath must form a gap through which no flames can
penetrate. For this reason, attention must be paid to the appro-
priate selection of cable union depending on both the type and
structure of cable and installation location. The flame proof
enclosure primarily depends here on the care taken by the
installation engineer when laying the cables and lines.
Conduit system
In the case of installation using the conduit system, the elec-
trical lines are drawn as single wires into enclosed metal
tubes. The tubes are connected to the housings by means of
unions and equipped with a seal at each entrance point.
The entire conduit system is flame proof.
The aim of the seal is to prevent explosions which may occur
inside the housing from penetrating the pipeline. Otherwise
extremely high explosive pressures would be created as a
result of pre-compression in long cylindrical tubes. For this
reason, it is recommended that seals be installed not just at
the entrance points but at specific intervals. Drains must be
installed at low points at which condensate can accumulate.
Wires
Close-up plug
non-asbestos
packing fiber Drain
Conduit
17
5. Explosion Protection in North America 5.3 Regulations for Installation
The National Electrical Code in the USA and the Canadian
5.1 Introduction Electrical Code in Canada apply to electrical apparatus and
The basic principles of explosion protection are the same all installations for hazardous locations.
over the world. However, technologies have developed in North
America in the field of explosion protection for electrical These have the character of installation regulations for elec-
equipment and installations which deviate considerably from trical facilities in all locations and refer to a number of further
those of the IEC (International Electrotechnical Commission). standards of other institutions which contain specifications
The differences from IEC technologies are among others the for the installation and construction of suitable equipment.
classification of hazardous locations, the construction of
apparatus and the installation of electrical systems. The methods of installation for the zone concept in accor-
dance with the NEC are similar to the traditional Class/Division
5.2 Classification of Hazardous Locations system. New to the NEC 1996 is the use of listed Metal Clad
For potentially explosive atmospheres the term ”hazardous (MC) cables in addition to rigid conduit and Mineral Insulated
(classified) locations” is used in North America. They are cables in Class I, Division 1 or Zone 1.
defined in Articles 500 and 505 of the National Electrical Code
(NEC) in the USA and in Section 18 and Annex J of the Cana- One significant advantage of the CEC is the increased
dian Electrical Code (CEC) in Canada.The hazardous locati- possibility of using wires and cables. In contrast to the USA,
ons are those locations, where fire or explosion hazards may Canada has, for some time now, also permitted the use
exist due to flammable gases, vapours or liquids (Class I), of special cables similar to the IEC steel-wire armoured
combustible dusts (Class II), or ignitable fibers or flyings cables.
(Class III).
Based on the likelihood or risk that an ignitable concentra- 5.4 Constructional Requirements
tion of a flammable material will be present the hazardous The regulations of the National Electrical Code and the
locations are traditionally subdivided into Division 1 and Divi- Canadian Electrical Code stipulate which apparatus and
sion 2. methods of protection may be used in different hazardous
locations.
In 1996 the IEC classification system was introduced as a
parallel system to the existing system for Class I in the USA. Various standards and regulations govern the construction
This system was implemented by the new Article 505. This and testing of explosion-protected electrical apparatus and
now gives the end user the possibility to choose the system installations in North America. In the USA, these are mainly
which best suits his needs. the standards issued by Underwriters Laboratories Inc. (UL),
Factory Mutual Research Corporation (FM) and the Inter-
The IEC zone classification for Class I was also introduced in national Society for Measurement and Control (ISA). In
Canada (CEC, 1988 edition). All newly built facilities in Canada, those of the Canadian Standards Association (CSA)
Canada need to be classified according to this principle. apply.
The traditional North American classification system divides The tables in appendix 6.4 provide an overview of the
Class I flammable gases, vapours, mists and liquids into Gas constructional requirements for hazardous locations and
Groups A, B, C and D and Class II combustible dusts into methods of protection.
Groups E, F and G.
Group A is the most hazardous gas group in the traditional 5.5 Degrees of Protection provided by Enclosures
NEC system whereas Group IIC is the most volatile in the IEC The standard IEC 60 529 defines the degrees of protection
system in Article 505 of the NEC. provided by enclosures. In the USA the degrees of protec-
tion are included in the NEMA Publication No. 250 (National
In Canada both gas grouping systems may be used with the Electrical Manufacturing Association). These enclosure
zone classification system. types could not be exactly equated with the IEC enclosure
classification designation since NEMA additional environ-
The maximum surface temperature classification given in the mental influences (such as cooling lubricant, cutting coo-
new Article 505 maintains a pure IEC approach of having six lant, corrosion, iceing, hail) takes into account.
main temperature classes T1 to T6. This deviates from the
traditional NEC temperature class structure which has fur-
ther subdivisions between the main temperature classes.
In the 1998 CEC this traditional structure T1-T6 with interme-
diate subdivisions was maintained.
18
NEMA Enclosure IEC Enclosure Classification (2) Zone Equipment: Equipment
Type Numbers meeting one or more of the pro-
tection techniques described in
5
1 IP 10
2 IP 11 Article 505 of the NEC or Section
3 IP 54 18 of the CEC shall be marked with
3R IP 14 the following in the order shown:
3S IP 54 1. Class (optional in Canada)
4 and 4X IP 56 2. Zone (optional in Canada)
5 IP 52 3. AEx (USA) or Ex or EEx (Canada)
6 and 6P IP 67 4. Method(s) of protection
12 and 12K IP 52 5. Equipment group II or applicable gas group(s) IIA, IIB or IIC
13 IP 54 6. Temperature class
Example: Class I Zone 0 AEx ia IIC T6
Note:
As the NEMA Types meet or exceed the test requirements for the associated IEC
Classifications the table cannot be used to convert from IEC Classifications to NEMA
Types.
19
6. Appendix
6.1 Comparison of IEC Publications and European Standards (EN)
IEC publications EN
IEC 60079-0 EN 50 014 General requirements
IEC 60079-1 EN 50 018 Construction and verification test of flameproof enclosures of electrical apparatus
IEC 60079-1A ----- Method of test for ascertainment of maximum experimental safe gap
IEC/TR 60079-2 EN 50 016 Electrical apparatus, type of protection ’p’
IEC 60079-3 EN 50 020 Spark-test apparatus for intrinsically-safe circuits
IEC 60079-4
IEC 60079-4A ----- Method of test for ignition temperature
IEC 60079-5 EN 50 017 Powder filling ’q’
IEC 60079-6 EN 50 015 Oil-immersion ’o’
IEC 60079-7 EN 50 019 Increased safety ’e’
IEC 60079-10 EN 60079-10 Classification of hazardous areas
IEC 60079-11 EN 50 020 Intrinsic safety ’i’
IEC 60079-12 EN 50 014 Classification of mixtures of gases or vapours with air according to their maximum experimental safe gaps and minimum ignition currents
IEC/TR 60079-13 ----- Construction and use of rooms or buildings protected by pressurization
IEC 60079-14 EN 60079-14 Electrical installations in hazardous areas (other than mines)
IEC 60079-15 pr EN 50 021 Electrical apparatus with type of protection ’n’
IEC/TR 60079-16 Artificial ventilation for the protection of analyser(s) houses
IEC 60079-17 EN 60079-17 Inspection and maintenance of electrical installations in hazardous areas (other than mines)
IEC 60079-18 EN 50 028 Encapsulation ’m’
IEC 60079-19 prEN 60079-19 Repair and overhaul for apparatus used in potentially explosive atmospheres (other than mines or explosives)
IEC/TR 60079-20 ----- Data for flammable gases and vapours, relating to the use of electrical apparatus
IEC publications EN
20
6.2 Safety Ratings of Flammable Gases and Vapours 6
Material Ignition temperature °C Temperature class Gas group
1,2-dichloroethane 440 T2 II A
Acetaldehyde 140 T4 II A
Acetone 540 T1 II A
Acetylene 305 T2 II C (3)
Ammonium 630 T1 II A
Benzins, petrol fuels 220 to 300 T3 II A
Boiling point < 135 °C
Benzole (pure) 555 T1 II A
Cyclohexan0ne 430 T2 II A
Diesel fuels (DIN 51601) 220 to 300 T3 II A
Jet fuels 220 to 300 T3 II A
Acetic acid 485 T1 II A
Acetic anhydride 330 T2 II A
Ethane 515 T1 II A
Ethyl ethanoate 460 T1 II A
Ethanol 425 T2 II A / II B
Ethyl chloride 510 T1 II A
Ethene 425 T2 II B
Ethylene oxide 440 (self-decomposing) T2 II B
Diethyl ether 170 T4 II B
Ethyl glycol 235 T3 II B
EL fuel oil (DIN 51603) 220 to 300 T3 II A
L fuel oil (DIN 51603) 220 to 300 T3 II A
M and S fuel oils (DIN 51603) 220 to 300 T3 II A
i-Amyl acetate 380 T2 II A
Carbon monoxide 605 T1 II A / II B
Methane 595 (650) T1 II A
Methanol 455 T1 II A
Methyl chloride 625 T1 II A
Naphthalene 540 T1 II A
n-Butane 365 T2 II A
Butanol 340 T2 II A
n-Hexane 240 T3 II A
n-Propyl alcohol 405 T2 -*)
Oleic acid 360 (self-decomposing) T2 -*)
Phenol 595 T1 II A
Propane 470 T1 II A
Carbon disulphide 95 T6 II C (1)
Hydrogen sulphide 270 T3 II B
Special benzines 200 to 300 T3 II A
Boiling point > 135 °C
Coal gas (lighting gas) 560 T1 II B
Tetralin 425 T2 -*)
(1,2,3,4-tetrahydronaphthalene)
Toluol 535 T1 II A
Hydrogen 560 T1 II C (2)
Extract from the tabular work ”Sicherheitstechnische Kennzahlen brennbarer Gase und Dämpfe [Safety ratings of
flammable gases and vapours]”
by K. Nabert and G. Schön - (6th edition)
-*) The gas group for this substance has not yet been determined.
(1) Also gas groups II B + CS2
(2) Also gas groups II B + H2
(3) Also gas groups II B + C2 H2
21
6.3 Classification of Hazardous Locations in North America
Gases, Flammable Vapours or Mists Combustible Dusts, Fibres and Ignitable Flyings
Class I Area Classification Class II Area Classification Class III Area Classification
Zone 1
Locations where ignitable concen-
trations of flammable gases,
vapours or liquids can exist some of
the time under normal operating
conditions.
Class I Temperature Classes Class II Temperature Classes Class III Temperature Classes
22
6.4 Constructional Regulations for North America 6
Applicable standards for approval
Area Type of ignition protection UL FM CSA
23
6.5 Ingress Protection Codes in accordance with IEC 60 529 - IPXX
Table 1: Scope of Protection for the IP Protection Classes
Enclosure
Type Degree of Protection Use
Type 1 Protection against limited amounts of falling dirt Indoor
Type 2 Protectionn against limited amounts of falling water and dirt Indoor
Type 3 Protection against rain, sleet, windblown dust, and damage for external ice formation Outdoor
Type 3R Protection against rain, sleet, and damage for external ice formation Outdoor
Type 3S Protection against rain, sleet, windblown dust, and for operation of external mechanisms when ice laden Outdoor
Type 4 Protection against windblown dust and rain, splashing water, hose directed water, and damage from external ice Indoor or Outdoor
formation
Type 4X Protection against corrosion, windblown dust and rain, splashing water, hose directed water, and damage from Indoor or Outdoor
external ice formation
Type 5 Protection against settling airborne dust, falling dirt, and dripping noncorrosive liquids Indoor
Type 6 Protection against hose directed water, the entry of water during occasional temporary submersion at a limited Indoor or Outdoor
depth, and damage from external ice formation
Type 7 For use in locations classified as Class I, Groups A, B, C, or D as defined in the NEC Indoor
Type 8 For use in locations classified as Class I, Groups A, B, C, or D as defined in the NEC Indoor or Qutdoor
Type 9 For use in locations classified as Class II, Groups E, F, G as defined in the NEC Indoor
Type 10 Constructed to meet the applicable requirements of the Mine Safety Health Administration Mining
Type 11 Protection against the corrosive effects of liquids and gases by oil immersion Indoor
Type 12, 12K Protection against circulating dust, falling dirt, and dripping non corrosive liquids Indoor
Type 13 Protection against dust, spraying of water, oil, and non corrosive coolant Indoor
24
6
6.7 Overview of the most important Approval and Testing Authorities *
Country Approval authority Testing authority Country Approval authority Testing authority
Australia Quality Assurance Services International Testing and Certification IBExU - Institut für Sicherheitstechnik GmbH
R Jacobi Services (ITACS) Institut an der Bergakademie Freiberg
Locked Bag 2032 2 Second Street Fuchsmühlenweg 7
STRATHFIELD NSW 2135 BOWDEN S A 5007 D 09599 FREIBERG
Tel: +61 2 9746 4900 Tel: +61 8 83468680 Tel: +49 3731 3805 19
Fax: +61 2 9746 8460 Fax: +61 8 83467072 Fax: +49 3731 23650
Denmark DEMKO SIRA Certification Service (SCS) SIRA Test and Certification Ltd
Lyskaer 8 South Hill Saighton Lane
DK-2730 HERLEV M Shearman A J McMillan
Tel: +45 44 947 266 CHISELHURST KENT BR7 5EH GB - Chester CH3 6EG
Fax: +45 44 947 261 Tel: +44 181 467 2636 Tel: +44 1244 332200
Fax: +44 181 295 1990 Fax: +44 1244 332112
Federal Physikalisch-Technische
Republic Bundesanstalt (PTB) Hungary Hungarian testing authority for explosion-proof
of Germany Bundesallee 100 electrical apparatus (BKI)
D 38116 Braunschweig Mikoviny S. u. 2-4
Tel: +49 531 592 3400 H 1037 Budapest
Fax: +49 531 592 3405 Tel: +36 1 168 7260
Fax: +36 1 250 1720
DMT - Gesellschaft für Forschung und Prüfung mbH
Fachstelle für Sicherheit elektrischer Betriebsmttel Italy Centro Elettrotecnico Sperimentale Italiano (CESI)
Bergbau-Versuchsstrecke (BVS) Via Rubattino 54
Beylingstr. 65 I 20134 Milano
D 44329 DORTMUND Tel: +39 2 212 53 72
Tel: +49 231 2491 0 Fax: +39 2 212 54 40
Fax: +49 231 2491 224
25
Country Approval authority Testing authority Country Approval authority Testing authority
Japan The Technical Institution of Industrial Safety (TIIS) Sweden Swedish National Testing and
1-4-6 Umezono Kiyose Research Institute (SP)
Tokyo 204 Brinellgatan 4
Tel: +81 424 91 4514 Box 857
Fax: +81 424 95 2461 S-501 15 BORAS
Tel: +46 33 16 5000
Luxemburg Service de l´Energie de l´Etat Luxembourgeois Fax: +46 33 13 5502
B.P. 10
L 2010 Luxembourg Switzerland Eidgenössisches Schweizerischer Elektrotechnischer
Tel: +352 46 97 48 Starkstrominspektorat (ESTI) Verein (SEV)
Fax: +352 22 25 24 Luppmenstraße 1 Luppmenstraße 1
CH 8320 FEHRALTORF CH 8320 FEHRALTORF
Netherlands KEMA Tel: +41 1 956 12 12 Tel: +41 1 956 11 11
Postbus 9035 Fax: +41 1 956 12 22 Fax: +41 1 956 11 12
NL 6800 ET ARNHEM
Tel: +31 26 3 56 34 28 Ukraine Test and certification centre for
Fax: +31 26 3 51 01 78 explosion-proof and flame-proof
electrical apparatus (ISZ VE)
Norway NEMKO ul. Gvardeiskoi Divisii 17
P O Box 73 Blindern 340052 Donezk
N 0314 OSLO Tel: +
Tel: +47 22 960330 Fax: +
Fax: +47 22 698636
USA Underwriters Laboratories Inc. (UL)
Poland Glowny Institut Gornictwa 333 Pfingsten Road
Kopalnia Doswiadczalna ”BARBARA” Northbrook, IL 60062-2096
ul. Podleska 72, skrytka pocztowa 72 Tel: +847 272 8800
PL 43-190 Mikolow Fax: +847 272 8129
Tel: +58 2028 024 9
Fax: +58 2028 745 Factory Mutual Research Corporation (FM)
1151 Boston-Providence Turnpike
Republic Korea Industrial Safety Corp. (KISCO) P.O. Box 9102
Korea 34-4 Kusa-dong, Poopyoung-gu Tel: +781 255 4840
Inchon 403-120 Fax: +781 762 9375
The Republic of Korea
Tel: +82 32 5100 865 Yugoslavia SAVEZNO MINISTARSTVO ZA RAZVOJ,
Fax: +82 32 518 6483-4 NAUKU i ZIVOTNU SREDINU
SAVEZNI ZAVOD ZA
Rebublic of South African Bureau of Standards (SABS) STANDARDIZACIJU (SZS)
South Africa 1 Dr. Lategan Road, Groenkloof, Pretoria Federal Ministry for Development,
Private Bag X191 Science and Environment
Pretoria 0001 Federal Institution for Standardization
Tel: +12 428 7911 Kneza Milosa 20
Fax: +12 344 1568 YU Beograd
Tel: +11 681 999
Romania INSEMEX PETROSANI Fax: +235 10 36
Equipment Ex. Certification Service
Str. Gen. Vasile Milea nr.32-34
Cod 2675 Petrosani.
Tel: +4 054 541 621
Fax: +4 054 232 277
26
27
7. Literature
Directive 94/9/EU of the European Parliament and the council DIN EN 60 079-14 VDE 0165 Part 1:1998-08
of 23 March 1994 on the approximation of the laws of the Electrical apparatus in areas prone to gas explosions
member states concerning equipment and protective sytems Electrical installations in hazardous areas
intended for use in potentially explosive atmos- VDE-Verlag GmbH, Berlin
pheres
Official Journal of the European Communities DIN VDE 0105 Part 9: 1986-05 Operation of high-voltage
equipment - supplementary specifications for potentially
Second Order to the equipment safety law and amendments explosive areas
to equipment safety law safety legislation dated 12.12.1996, VDE-Verlag GmbH, Berlin
Federal Gazette 1996 Part I No. 65
Dust explosion protection on machines and apparatus, ISSA
Bulletin of the new edition of the Order on electrical Prevention Series No. 2033(G), Mannheim 1998
apparatus in potentially explosive areas dated 13.12.1996,
Federal Gazette 1996 Part I No. 65 NFPA 70 - 1996 National Electrical Code, 1996 edition
National Fire Protection Association, Quincy, MA, USA
Explosion protection of electrical apparatus; order on electrical
apparatus in potentially explosive areas (ElexV), commentary NFPA 70 - 1999 National Electrical Code, 1999 edition
and collected texts] Erich Schmidt Verlag, Berlin National Fire Protection Association, Quincy, MA, USA
Code of practice for explosion protection (Ex-RL) - code of 1998 Canadian Electrical Code, 18th edition
practice for the avoidance of the dangers of potentially Canadian Standards Association, Etobicoke, ON, Canada
explosive atmospheres with collected examples (ZH1/10)
BG-Chemie (1998) 1996 National Electrical Code Review and Application Guide
Werbe-Druck Winter, Sandhausen Killark Electric Manufacturing Company, St. Loius, MO, USA
K. Nabert and G. Schön: 1998 Canadian Electrical Code Review and Application Guide
Safety ratings of flammable gases and vapours Hubbell Canada Inc. - Killark, Pickering, ON, Canada
Deutscher Eichverlag, Braunschweig
28
8. Index
Basic health and safety requirements 8 Potentially explosive area, hazardous location 9, 11, 16
BVS/DMT (Bergbauversuchsstrecke Dortmund) 25 Potentially explosive atmosphere 9, 11
Primary explosion protection 7
Cable system 16, 17 Protective systems 9
Categories (equipment categories) 11 PTB (Physikalisch-Technische Bundesanstalt) 10, 25
CEC (Canadian Electrical Code) 18, 22
CE marking 10 Quality assurance 10
CENELEC 8
Certificate of conformity 8, 9 Routine testing 16
Class 18, 22
Components 9 Safety barrier 15
Conduit system 17 Safety factor 14
Construction regulations EUROPE 8 Secondary explosion protection 7
NORTH AMERICA 23 Sources of ignition 6, 7
Special protection 12
Danger Class 6 Safety caracteristic 21
Declaration of conformity 9, 10 Surface temperature 12, 18
Degree of protection (IP code) 24
Division 18, 22 Testing authority 25, 26
Dust 11, 18 Temperature class 11, 12, 18, 21, 22
Dust explosion protection 8 Type examination certificate, EC 10
Types of protection 12
EC Directive 8, 9
Electrical apparatus 9 Zener diode 15
EMC Directive 10 Zones 11, 12, 18, 22
EN (European Standard) 8, 20
Equipment 9
Equipment category 11
Equipment group
Explosion 6, 11
Explosion limits 6
ExVo 10
Galvanic isolation 15
Gas group 11, 21
German Technical Regulations for Flammable
Liquids (TRbF) 6
Group 18, 22
Maintenance 16, 17
Marking 10, 19
MESG (maximum experimental safe gap) 11
MIC (minimum ignition current) 11
Minimum ignition energy 14
29