CHAPTER 4
COMPARISON OF ANALYSIS RESULTS
4.1. General
In this study, the proposed reinforced concrete building is analyzed with basic
wind speed 90 mph under static analysis and ACI 318-99 guidelines in order to meet
the design member sizes of the frame elements that are same as the assumed member
sizes. After that the proposed building is statically analyzed with cyclone wind speeds
such as 110 mph, 130 mph and 155 mph respectively, the analysis results such as
failed members, storey data are compared only under wind load case. And then
member forces for selected beams and columns are also compared.
C2
C63
C 41
Figure 4.1. Location of Selected Columns
B 52
B 172
(110 mph, 130 mph and 155 mph) in order to know wind effects on the building.
Failed members are compared for different design wind speed without changing
frame member sizes. When the design wind speed of building is increased, many
members are failed and the building is not satisfied with structural stability criteria.
The whole structure is composed of 1029 beams and 620columns. In wind speed 110
mph, 49 numbers of beams are failed. And then, 178 beams and 25 columns are failed
in 130 mph and 421 beams and 91 columns in 155 mph. It can be observed that local
failure is mostly found the wind speed at 110 mph but global failure is mostly found
between the wind speed at 130 mph and 155 mph in accordance with these
comparisons. So, numbers of failed members are summarized in Table 4.1 and total
failure percentages of failed members are described in Table 4.2. Moreover,
percentages of failed members are graphically represented in Figure 4.3 and Figure
4.4.
Beam 0 0
0 0
95 mph
column 0 0
Beam 49 4.76
49 2.97
110 mph
column 0 0
45.00%
40.91%
40.00%
35.00%
Failed Members (%)
30.00%
25.00%
Beam
20.00% column
17.30%
14.68%
15.00%
10.00%
4.76% 4.03%
5.00%
0.00%0.00% 0.00%
0.00%
95 mph 110 mph 130 mph 155 mph
35.00%
Wind Speed (mph)
31.05%
30.00%
25.00%
Total Failed (%)
20.00%
Total failed
15.00%
12.30%
10.00%
5.00%
2.97%
0.00%
0.00%
95 mph 110 mph 130 mph 155 mph
Figure 4.4. Total Failure Percentage of Failed Members (Beams and Columns)
Resisting to SF=
SF= SF= SF= SF= SF= SF= SF=
2.62 > 1.5
Sliding 3.522 2.286 1.705 1.881 1.221 1.323 0.859
7
Overturning SF=
SF= SF= SF= SF= SF= SF= SF=
6.99 > 1.5
Moment 9.377 4.108 3.064 5.007 2.194 3.522 1.543
4
SF=
SF= SF= SF= SF= SF= SF= SF=
Storey Drift 1.24
0.927 2.029 2.720 1.737 3.799 2.468 5.402
3 < 2.88
Torsional SF=
SF= SF= SF= SF= SF= SF= SF=
1.12
Irregularity 1.123 1.191 1.191 1.123 1.191 1.123 1.191
3 < 1.2
SF=
SF= SF= SF= SF= SF= SF= SF=
P-∆ Effect 0.02
0.026 0.037 0.037 0.026 0.037 0.026 0.037
6 < 0.1
0.01
0
Storey Drift Ratio (in)
0
95 mph
0 110 mph
130 mph
0 155 mph
0
0
ROOF 12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Storey Level
0.01
0.01
Storey Drift Ratio (in)
0.01
95 mph
0.01 110 mph
130 mph
155 mph
0
0
ROOF 12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Storey level
Figure 4.6. Comparison of Storey Drift Ratio in Y Direction due to WY
According to Table 4.4, 4.5 and Figure 4.5, 4.6, minimum storey drift ratios
are occurred at twelve-storeyed and the maximum storey drift ratios are found at the
storey 1 for proposed building in both directions. These storey drift ratios are
gradually decreased to the upper stories. It can be observed that there is no particular
changing of storey drift between the wind speed 95 mph to 110 mph but it is found
obviously between the wind speed at 130 mph and 155 mph for both directions. At
storey 1, maximum storey drift ratios are 0.004169 in X direction and 0.009744 in Y
direction for design wind speed 155 mph. The values are approximately increased
1.34 times form 95 mph to 110 mph, 1.87 times from 95 mph to 130 mph and 2.66
times from 95 mph to 155 mph in both directions.
1200
1000
800
Storey Shear (kips)
95 mph
600 110 mph
130 mph
155 mph
400
200
0
ROOF 12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Story Level
Figure 4.7. Comparison of Storey Shear in X Direction due to WX
1800
1600
1400
Storey Shear (kips)
1200
95 mph
1000 110 mph
130 mph
800 155 mph
600
400
200
0
ROOF 12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Storey level
Figure 4.8. Comparison of Storey Shear in Y Direction due to WY
According to Table 4.6, 4.7 and Figure 4.7, 4.8, the maximum storey shear are
occurred at Ground floor and its values are 1134.83 kips in X direction and 1748.07
kips in Y direction for 155 mph. Storey shear in Y direction are more than that in X
65
direction. There is no obviously changed in storey shear between the wind speed 95
mph to 110 mph but it is obviously changed in wind speed 130 mph and 155 mph.
The values are approximately increased 1.34 times form 95 mph to 110 mph, 1.87
times from 95 mph to 130 mph and 2.66 times from 95 mph to 155 mph in both
directions. Storey shear is slightly decreased from bottom to top storey with the
slopping form.
1200000
1000000
Storey Moment (kip-in)
800000
95 mph
600000 110 mph
130 mph
155 mph
400000
200000
0
ROOF 12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Storey Level
Figure 4.9. Comparison of Storey Moment in X Direction due to WX
Table 4.9. Comparison of Storey Moment in Y Direction (kip-in) due to WY
1800000
1600000
1400000
Storey Moment (kip-in)
1200000
1000000 95 mph
110 mph
800000 130 mph
155 mph
600000
400000
200000
0
ROOF 12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Storey Level
Figure 4.10. Comparison of Storey Moment in Y Direction due to WY
In comparison of storey moment in X and Y direction, maximum storey
moment values are 1063915 kip-in in X direction and 1625653.408 kip-in Y direction
for 155 mph at ground floor. Storey moment in Y direction is more critical than storey
moment in X direction. The values are approximately increased 1.34 times form 95
mph to 110 mph, 1.87 times from 95 mph to 130 mph and 2.66 times from 95 mph to
155 mph in both directions. From this figures, it can be found that storey moment
values are slightly decreased from bottom to top storey.
The comparison of axial force for exterior column (C2) due to four different
wind speeds in X direction is described in Table 4.10 and Figure 4.11.
Table 4.10. Comparison of Axial Force for Exterior Column (C2) (kips)
120
100
Axial Force (kips)
80
95 mph
60 110 mph
130 mph
155 mph
40
20
0
12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Storey Level
Figure 4.11. Comparison of Axial Force for Exterior Column (C2) due to WX
69
In this figure, the result of axial force for exterior column (C2) is linearly
increasing from top to bottom storey. The maximum value of axial force for (C2) is
108.01 kips at design wind speed of 155 mph in ground floor.
Table 4.11. Comparison of Shear Force for Exterior Column (C2) (kips)
25
20
Shear Force (kips)
15 95 mph
110 mph
10
130 mph
5 155 mph
0
12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Storey Level
Figure 4.12. Comparison of Shear Force for Exterior Column (C2) due to WX
According to this Figure 4.12, the maximum shear force for exterior column
(C2) is occurred at ground floor of the proposed building and has the values of 8.05
kips, 10.79 kips, 15.07 kips and 21.43 kips for different wind speeds of 95 mph, 110
mph, 130 mph and 155 mph respectively. Shear force value is slightly dropped at 3, 6
and 9 stories because columns sizes are changed in this storey.
2500
Bending Moment (kip-in)
2000
1500
95 mph
110 mph
130 mph
1000 155 mph
500
0
12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Storey Level
Figure 4.13. Comparison of Bending Moment for Exterior Column (C2) due to WX
In this section, bending moment for exterior column (C2) for four different
wind speeds is decreased from bottom to top storey. According to this figure, the
maximum bending moment is occurred in ground floor with different values of
786.595 kip-in for 95 mph, 1054.604 kip-in for 110 mph, 1472.96 kip-in for 130 mph
and 2093.956 kip-in for 155 mph respectively.
4.6.1.4. Comparison of torsion for exterior column (C2) due to WX
The comparison of torsion due to four different wind speed in X direction is
described in Table 4.13 and Figure 4.14.
35
30
25
Torision (kips)
20 95 mph
110 mph
15 130 mph
155 mph
10
0
12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Storey Level
Figure 4.14. Comparison of Torsion for Exterior Column (C2) due to WX
Table 4.14. Comparison of Axial Force for Exterior Column (C2) (kips)
160
140
Axial Force (kips)
120
100
95 mph
80 110 mph
130 mph
60 155 mph
40
20
0
12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Storey Level
Figure 4.15. Comparison of Axial Force for Exterior Column (C2) due to WY
In this figure, the result of axial force for exterior column (C2) is linearly
increasing from top to bottom storey. The maximum value of axial force for (C2) is
141.93 kips at design wind speed of 155 mph in ground floor.
Table 4.15. Comparison of Shear Force for Exterior Column (C2) (kips)
60
Shear Force (kips)
50
40
95 mph
30
110 mph
20 130 mph
10 155 mph
0
12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Storey Level
Figure 4.16. Comparison of Shear Force for Exterior Column (C2) due to WY
According to this Figure 4.16, the maximum shear force for exterior column
(C2) is occurred at storey 1 of the proposed building and has the values of 19.25 kips,
25.81 kips, 36.05 kips and 51.25 kips for different wind speeds of 95 mph, 110 mph,
130 mph and 155 mph respectively. Shear force value is slightly dropped at 3, 6 and 9
stories because columns sizes are changed in this storey.
Table 4.16. Comparison of Bending Moment for Exterior Column (C2) (kip-in)
Storey 95 mph 110 mph 130 mph 155 mph
12F 48.563 65.11 90.939 129.278
75
5000
4500
4000
3500
3000
95 mph
2500 110 mph
130 mph
2000 155 mph
1500
1000
500
0
12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Storey Level
Figure 4.17. Comparison of Bending Moment for Exterior Column (C2) due to WY
In this section, bending moment for exterior column (C2) for four different
wind speeds is decreased from bottom to top storey. According to this figure, the
maximum bending moment is occurred in ground floor with different values of
1761.999 kip-in for 95 mph, 2362.348 kip-in for 110 mph, 3299.478 kip-in for 130
mph and 4690.53 kip-in for 155 mph respectively.
60
50
Torsion (kiips)
40
95 mph
30 110 mph
130 mph
155 mph
20
10
0
12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Storey Level
Figure 4.18. Comparison of Torsion for Exterior Column (C2) due to WY
In above figure, maximum torsion is occurred at storey 1 and suddenly drops
in storey 3, 6 and 9 because maximum storey drift is found that this stories and
column size are changed. The values are increased 1.34 times from 95 mph to110
mph, 1.87 times from 95 mph to 130 mph and 2.66 times from 95 mph to 155 mph.
Table 4.18. Comparison of Axial Force for Corner Column (C41) (kips)
120
Axial Force (kips)
100
80
95 mph
60 110 mph
130 mph
155 mph
40
20
0
12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Storey Level
Figure 4.19. Comparison of Axial Force for Corner Column (C41) due to WX
In above figure, the result of axial force for corner column (C41) is linearly
increasing from top to bottom storey. The maximum value of axial force for (C41) is
112.35 kips at design wind speed of 155 mph in ground floor.
Table 4.19. Comparison of Shear Force for Corner Column (C41) (kips)
25
20
Shear Force (kip)
15
95 mph
110 mph
130 mph
10 155 mph
0
12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Storey Level
Figure 4.20. Comparison of Shear Force for Corner Column (C41) due to WX
It can be found that shear force for corner column (C41) for four different
wind speeds are decreased to storey 12. The maximum values are 8.32 kips at 95 mph,
11.15 kips at 110 mph, 15.58 kips at 130 mph and 22.15 kips at 155 mph respectively.
Table 4.20. Comparison of Bending Moment for Corner Column (C41) (kip-in)
Storey 95 mph 110 mph 130 mph 155 mph
12F 19.34 25.93 36.216 51.485
79
2500
Bending Moment (kip-in)
2000
1500
95 mph
110 mph
130 mph
1000 155 mph
500
0
12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Storey Level
Figure 4.21. Comparison of Bending Moment for Corner Column (C41) due to WX
In this section, bending moment for corner column (C41) for four different
wind speeds is decreased from bottom to top storey. According to this figure, the
maximum bending moment is occurred in ground floor with different values of
838.978 kip-in for 95 mph, 1124.834 kip-in for 110 mph, 1571.05 kip-in for 130 mph
and 2233.401 kip-in for 155 mph respectively.
30
25
Torsion (kips)
20
95 mph
15 110 mph
130 mph
155 mph
10
0
12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Storey Level
Figure 4.22. Comparison of Torsion for Corner Column (C41) due to WX
In above figure, maximum torsion is occurred at storey 1 and suddenly drop in
storey 3 since maximum storey drift is found at storey 1 and column size is changed
in storey 3. The values are increased 1.34 times from 95 mph to110 mph, 1.87 times
from 95 mph to 130 mph and 2.66 times from 95 mph to 155 mph respectively.
Table 4.22. Comparison of Axial Force for Corner Column (C41) (kips)
300
Axial Force (kips)
250
200
95 mph
150 110 mph
130 mph
155 mph
100
50
0
12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Storey Level
Figure 4.23. Comparison of Axial Force for Corner Column (C41) due to WY
In above figure, the result of axial force for corner column (C41) is linearly
increasing from top to bottom storey. The maximum value of axial force for (C41) is
245.34 kips at design wind speed of 155 mph in ground floor.
Table 4.23. Comparison of Shear Force for Corner Column (C41) (kips)
30
25
Shear Force (kips)
20
95 mph
15 110 mph
130 mph
155 mph
10
0
12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Storey Level
Figure 4.24. Comparison of Shear Force for Corner Column (C41) due to WY
It can be found that shear force for Corner column (C41) for four different
wind speeds are decreased from bottom to top storey. The maximum values are 9.9
kips at 95 mph, 13.28 kips at 110 mph, 18.54 kips at 130 mph and 26.36 kips at 155
mph in ground floor.
Table 4.24. Comparison of Bending Moment for Corner Column (C41) (kip-in)
Storey 95 mph 110 mph 130 mph 155 mph
83
3500
3000
2500
2000 95 mph
110 mph
1500 130 mph
155 mph
1000
500
0
12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Storey Level
Figure 4.25. Comparison of Bending Moment for Corner Column (C41) due to WY
In this section, bending moment for corner column (C41) for four different
wind speeds is decreased from bottom to top story. According to this figure, the
maximum bending moment is occurred in ground floor with different values of
1114.989 kip-in for 95 mph, 1494.888 kip-in for 110 mph, 2087.901 kip-in for 130
mph and 2968.155 kip-in for 155 mph respectively.
60
50
Torsion (kips)
40
95 mph
30 110 mph
130 mph
155 mph
20
10
0
12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Storey Level
Figure 4.26. Comparison of Torsion for Corner Column (C41) due to WY
In above figure, maximum torsion is occurred at storey 1 and suddenly drop in
storey 3, 6 and 9 because column size are changed in this stories. The values are
increased 1.34 times from 95 mph to110 mph, 1.87 times from 95 mph to 130 mph
and 2.66 times from 95 mph to 155 mph respectively.
Table 4.26. Comparison of Axial Force for Interior Column (C63) (kips)
250
Axial Force (kips)
200
150
95 mph
110 mph
130 mph
100 155 mph
50
0
ROOF 12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Storey Level
Figure 4.27. Comparison of Axial Force for Interior Column (C63) due to WX
From above figure, the maximum axial value for (C63) is 204.35 kips at
design wind speed of 155 mph in story 1 and the minimum value is 1.33 kips in roof
floor. The results of axial forces in interior column (C63) are increased from upper to
lower stories in various wind speeds.
Table 4.27. Comparison of Shear Force for Interior Column (C63) (kips)
60
Shear Force (kips)
50
40
95 mph
30 110 mph
130 mph
155 mph
20
10
0
ROOF 12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Storey Level
Figure 4.28. Comparison of Shear Force for Interior Column (C63) due to WX
It can be found that the maximum shear value for Interior Column (C63) is
occurred at storey 1 of the proposed building and has the values of 19.23 kips, 25.79
kips, 36.02 kips and 51.2 kips for different wind speeds of 95 mph, 110 mph, 130
mph and 155 mph respectively.
Table 4.28. Comparison of Bending Moment for Interior Column (C63) (kip-in)
4500
Bending Moment (kip-in)
4000
3500
3000
2500 95 mph
110 mph
2000 130 mph
155 mph
1500
1000
500
0
ROOF 12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
l
Storey Level
Figure 4.29. Comparison of Bending Moment for Interior Column (C63) due to WX
According to the figure, the value of bending moment in ground floor is
greater than that of other stories. It has been observed that there is a slightly decreased
to upper story. The minimum bending moment is found in roof floor.
120
100
Torsion (kips)
80
95 mph
60 110 mph
130 mph
155 mph
40
20
0
ROOF 12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Storey Level
Figure 4.30. Comparison of Torsion for Interior Column (C63) due to WX
It can be found that all torsion values are critical in storey 1 for four different
wind speeds and suddenly decreased in storey 2 and storey 3. The values are
increased 1.34 times from 95 mph to110 mph, 1.87 times from 95 mph to 130 mph
and 2.66 times from 95 mph to 155 mph respectively.
Table 4.30. Comparison of Axial Force for Interior Column (C63) (kips)
350
300
Axial Force (kips)
250
200 95 mph
110 mph
150 130 mph
155 mph
100
50
0
ROOF 12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Storey Level
Figure 4.31. Comparison of Axial Force for Interior Column (C63) due to WY
From above figure, the maximum axial value for (C63) is 322.63 kips at
design wind speed of 155 mph in ground floor and the minimum value is 1.84 kips in
roof floor. The results of axial forces in interior column (C63) are increased from
upper to lower stories in various wind speeds.
Table 4.31 Comparison of Shear Force for Interior Column (C63) (kips)
50
45
Shear Force (kips)
40
35
30
95 mph
25 110 mph
130 mph
20 155 mph
15
10
0
ROOF 12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Storey Level
Figure 4.32. Comparison of Shear Force for Interior Column (C63) due to WY
It can be found that the maximum shear value for Interior Column (C63) is
occurred at ground floor of the proposed building and has the values of 17.01 kips,
22.8 kips, 31.85 kips and 45.28 kips for different wind speeds of 95 mph, 110 mph,
130 mph and 155 mph respectively.
Table 4.32. Comparison of Bending Moment for Interior Column (C63) (kip-in)
6000
Bending Moment (kip-in)
5000
4000
95 mph
3000 110 mph
130 mph
155 mph
2000
1000
0
ROOF 12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Storey Level
Figure 4.33. Comparison of Bending Moment for Interior Column (C63) due to WY
According to the figure, the value of bending moment in ground floor is
greater than that of other stories. It has been observed that suddenly drop in storey 1
and slightly decreased from storey 1 to storey 12.
140
120
100
Torsion (kips)
80 95 mph
110 mph
60 130 mph
155 mph
40
20
0
ROOF 12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Storey Level
Figure 4.34. Comparison of Torsion for Interior Column (C63) due to WY
It can be found that all torsion values are critical in ground floor for four
different wind speeds and suddenly decreased in storey 1. The values are increased
1.34 times from 95 mph to110 mph, 1.87 times from 95 mph to 130 mph and 2.66
times from 95 mph to 155 mph respectively.
20
Shear Force (kips)
15
95 mph
110 mph
130 mph
10 155 mph
0
12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Storey Level
Figure 4.35. Comparison of Shear Force for Interior Beam (B52) due to WX
According to the figure, it can be seen that maximum shear force value for
(B52) is 22.58 kips in ground floor and the minimum value is 0.77 kips in storey 12
94
under wind speed 155 mph. And then all shear forces values are slightly decreased
from bottom to top storey.
2000
1600
1400
1200
95 mph
1000 110 mph
130 mph
800 155 mph
600
400
200
0
12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Storey Level
Figure 4.36. Comparison of Bending Moment for Interior Beam (B52) due to WX
It has been observed that the maximum bending moment for interior beam
(B52) is found in ground floor with a value of 674.776 kip-in at 95 mph, 904.686 kip-
in at 110 mph, 1263.57 kip-in at 130 mph and 1796.288 kip-in at 155 mph
respectively. At storey 12, the minimum bending moments are 23.182 kip-in, 31.08
kip-in, 43.409 kip-in and 61.711 kip-in for design wind speeds of 95 mph, 110 mph,
130 mph and 155 mph respectively. The bending values are slightly decreased from
bottom to top storey.
80
Torsion (kips)
70
60
50
95 mph
40 110 mph
130 mph
30 155 mph
20
10
0
12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Storey Level
From Table 4.36 and Figure 4.37, it can be seen that torsion values for interior
beam (B52) are slightly decreased form storey 1 to storey 12. In this comparison,
maximum torsion value is found in storey 1 and has the value of 74.562 kips.
14
12
Shear Force (kips)
10
8 95 mph
110 mph
6 130 mph
155 mph
0
12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Storey Level
Figure 4.38. Comparison of Shear Force for Interior Beam (B52) due to WY
According to the figure, it can be seen that maximum shear force value for
(B52) is 11.71 kips in storey 1 and the minimum value is 0.4 kips in storey 12 under
wind speeds 155 mph. And then all shear forces values are slightly decreased from 1
storey to storey 12.
4.6.2.5. Comparison of bending moment for beam (B52) due to WY
The comparison of bending moment for (B52) due to four different wind
speeds in Y direction is described in Table 4.38 and Figure 4.39.
450
Bending Moment (kip-in)
400
350
300
250 95 mph
110 mph
200 130 mph
155 mph
150
100
50
0
12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Storey Level
Figure 4.39. Comparison of Bending Moment for Interior Beam (B52) due to WY
It has been observed that the maximum bending moment for interior beam
(B52) is found in storey 1 with a value of 149.099 kip-in at 95 mph, 199.9 kip-in at
110 mph, 279.199 kip-in at 130 mph and 396.908 kip-in at 155 mph respectively. At
storey 12, the minimum bending moments are 4.083 kip-in, 5.474 kip-in, 7.646 kip-in
and 10.87 kip-in for design wind speeds of 95 mph, 110 mph, 130 mph and 155 mph
respectively. The bending values are decreased from storey 1 to storey 12.
900
800
Torsion (kips)
700
600
500 95 mph
110 mph
400 130 mph
155 mph
300
200
100
0
12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Storey Level
From Table 4.39 and Figure 4.40, it can be seen that torsion values for interior
beam (B52) are slightly decreased form storey 1 to storey 12. In this comparison,
maximum torsion value is found in storey 1 and has the value of 770.368 kips.
60
Shear Force (kips)
50
40
95 mph
30 110 mph
130 mph
155 mph
20
10
0
12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Storey Level
Figure 4.41. Comparison of Shear Force for Interior Beam (B172) due to WX
From Table 4.40 and Figure 4.41, it has been observed that the shear forces are
increased according to the level of wind speeds. Comparatively, maximum shear is
found in storey 1 with the value are 19.77 kips, 26.51 kips, 37.03 kips and 52.64 kips
for 95 mph, 110 mph, 130 mph and 155 mph respectively.
The comparison of bending moment for (B172) due to four different wind
speeds in X direction is described in Table 4.41 and Figure 4.42.
1400
Bending Moment (kip-in)
1200
1000
800 95 mph
110 mph
600 130 mph
155 mph
400
200
0
12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Storey Level
Figure 4.42. Comparison of Bending Moment for Interior Beam (B172) due to WX
It has been observed that the maximum bending moment for interior beam
(B172) is found in storey 1 with a value of 430.926 kip-in at 95 mph, 577.751 kip-
in at 110 mph, 806.941 kip-in at 130 mph and 1147.145 kip-in at 155 mph
respectively. At storey 12, the minimum bending moments are 6.958 kip-in, 9.329
kip-in, 13.029 kip-in and 18.522 kip-in for design wind speeds of 95 mph, 110 mph,
102
130 mph and 155 mph respectively. The bending values are decreased from storey 1
to storey 12.
200
180
Torsion (kips)
160
140
120
95 mph
100 110 mph
130 mph
80 155 mph
60
40
20
0
12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Storey Level
The shear force of interior beam (B172) for four different wind speeds in Y
direction are clearly mentioned in Table 4.43 and Figure 4.44.
90
Shear Force (kips)
80
70
60
50 95 mph
110 mph
40 130 mph
155 mph
30
20
10
0
12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Storey Level
Figure 4.44. Comparison of Shear Force for Interior Beam (B172) due to WY
From Table 4.43 and Figure 4.44, it has been observed that the shear forces
are increased according to the level of wind speeds. Comparatively, maximum shear
is found in ground floor with the value are 32.06 kips, 42.98 kips, 60.04 kips and
85.35 kips for 95 mph, 110 mph, 130 mph and 155 mph respectively.
104
3500
3000
2500
2000 95 mph
110 mph
1500 130 mph
155 mph
1000
500
0
12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Storey Level
Figure 4.45. Comparison of Bending Moment for Interior Beam (B172) due to WY
It has been observed that the maximum bending moment for interior beam
(B172) is found in ground floor with a value of 1197.437 kip-in at 95 mph, 1605.428
kip-in at 110 mph, 2242.292 kip-in at 130 mph and 3187.636 kip-in at 155 mph. At
storey 12, the minimum bending moments are 4.072 kip-in, 5.459 kip-in, 7.625 kip-in
105
and 7.625 kip-in for wind speeds of 95 mph, 110 mph, 130 mph and 155 mph
respectively. The bending values are decreased from bottom to top storey.
100
Torsion (kips)
90
80
70
60
95 mph
50 110 mph
130 mph
40 155 mph
30
20
10
0
12F 11F 10F 9F 8F 7F 6F 5F 4F 3F 2F 1F GF
Storey Level