Air-To-Water Heat Pump: Shanghai Hezhong Carrier Air-Conditioning Equipment Co., LTD

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

CARRIER AIR-CONDITIONING

30GQ
AIR-TO-WATER HEAT PUMP
NOMINAL COOLING CAPACITY:223.2-355KW
NOMINAL HEATING CAPACITY:232.6-349KW
AIR TO WATER HEAT EXCHANGE
FOR COOLING & HEATING
MULTIPLE COMPRESSORS
ENERGY EFFICIENT OPERATION

ISO9001 ASME ISO14001

SHANGHAI HEZHONG CARRIER AIR-CONDITIONING EQUIPMENT CO., LTD.


Physical data
Unit model no. 30GQ080 30GQ100 30GQ120
Nominal cooling k W 223.3 279 335
capacity k W 71.6 86, 6 107
unit lkW k W 232.6 285 349
Nominal heating k W 68.7 83, 2 103
capacity k W R22 R22 R22
Unit lkW
Refrigerant circuit 1 1...06E6299 1...06E6299 1...06E6299
Compressor circuit 2 1...06E6299 1...06EF275 1...06EF299
circuit 3 1...06EF275 1...06EF299
Cap. control step
no...size 4 4 4
Total oil charge L 18 27 27
Main power supply 380 -3 - 50
Control Automatically adujstment
Safety device system hi- low pressure, discharge over temp., low water temp. and interruption.
Motor cooling Refrigerant cooling
Unit weight
R22 charge kg 25 + 25 26 + 25 +24 26 + 29 + 29
dry weight kg 3300 4050 4300
operating weight kg 3500 4250 4500
Coil
raw...fin/in 3...15 3...15 3...15
2
surface area m 10.6 13.8 15.8
Fan
6...30 10...26 6...30
No...ID
4...26
6...11.8 10...15.5 6...14.3
No...speed(r/s)
4...15.5
Air flow L/s 17500 24000 27080
Fan motor
6...0.75 10...0.55 6...0.75
No...input power
...kW -- -- 4...0.55
Heat exchanger --
No. 1 1 1
Water volume L 74 107 116
Water flow L/s 6.67 - 15 8.33 - 25 10.0 - 25
Max.operating Refrig. 2.75Mpa
side 0.98Mpa
pressure Water 4°± flange 4°± flange 5°± flange
side
Inlet/outlet connector m m 3580 4700 5200
Unit dimension m m 2000 2000 2000
length m m 2350 2350 2350
width
Note: Operation condition: LWT is 7°Ê, outdoor 30°Ê for cooling; LWT is 45°Ê, outdoor 7°Ê for heating.
height

Electrical data(Unit)
Nominal voltage 400V - 3ph - 50Hz

voltage limit (V) 342 - 440

model no kWmax. min. rated current max. fusable current max. instaneous current

30GQ-080 94.5 180 200 378

30GQ-100 115.7 218 275 416


30GQ-120 141.7 263 300 461
Performance data
COOLING CAPACITY
LEAVING CHILLED WATER TEMPERATURE (°Ê)
UNIT OAT
5 7 9 12 15
30GQ (°Ê)
C. cap. k W C. cap. k W C. cap. k W C. cap. k W C. cap. k W

25 223.3 64.1 238.4 67.2 252.3 70.7 274.4 76.5 294.2 83.0

30 209.3 68.6 223.3 71.6 236.0 75.7 257.0 81.6 276.7 88.3

080 35 196.5 72.6 209.3 76.1 222.1 80.2 240.7 86.7 258.1 93.7

40 182.6 76.8 195.4 80.6 205.8 84.9 224.4 91.7 239.5 99.3

45 169.8 97.5 180.3 85.0 190.7 89.6 207.0 96.8 222.1 105.0

25 279 77.7 298 81.4 315 85.5 343 92.4 367 100

30 262 83.0 279 86.6 295 91.21 321 98.4 347 106

100 35 245 87.8 262 91.9 278 96.8 301 104 323 113
40 228 92.7 244 97.2 257 102 280 110 300 119
45 213 97.5 226 102 238 108 259 116 278 126

25 335 96.0 358 101 379 106 412 115 442 125

30 314 103 335 107 355 113 386 122 415 132

120 35 295 109 314 114 334 120 362 130 387 141

40 274 115 293 121 309 127 337 138 359 149

45 255 121 271 128 286 134 310 145 334 158

INSTANTANEOUS HEATING CAPACITY


LEAVNG CHILLED WATER TEMPERATURE (°Ê)
UNIT OAT
35 40 45 50 55
30GQ (°Ê)
H. cap. k W H. cap. k W H. cap. k W H. cap. k W H. cap. k W
15 281.4 65.4 279.1 70.4 276.7 75.8 273.3 81.6 270.9 87.8
7 238.4 60.7 236.0 64.8 232.6 68.7 229.1 73.2 226.7 77.9
4 223.3 59.4 219.8 62.8 217.4 66.5 213.9 70.2 210.5 74.7
0 204.7 58.2 201.2 60.7 197.7 63.6 194.2 66.9 190.7 70.3
080
-5 183.7 57.3 179.1 58.8 175.6 60.8 172.1 62.9 167.4 65.4
-10 165.1 57.0 160.5 57.6 158.1 58.6 151.2 59.7 146.5 61.0
-15 148.8 56.9 143.0 57.2 138.4 57.4 132.6 57.5 127.9 57.6
15 344 79.3 342 85.2 340 91.6 335 98.5 331 106
7 292 73.7 290 78.6 285 83.2 280 88.5 278 94.1
4 273 72.2 270 76.2 266 80.6 262 85.0 258 90.3
0 251 70.8 247 73.7 242 77.2 238 78.1 234 85.1
100
-5 226 69.7 220 71.5 215 73.8 210 76.3 205 79.3
-10 202 69.3 197 70.1 194 71.2 185 72.5 179 74.1
-15 183 70.1 176 69.6 170 69.3 163 69.5 157 69.7
15 422 98.1 419 106 415 114 410 122 407 132
7 358 81.1 355 97.2 349 103 344 110 341 117
4 335 89.1 330 94.2 327 99.8 321 105 316 112
0 307 87.3 302 91.2 297 95.4 292 100 286 105
120
-5 276 86.0 269 88.2 264 91.2 258 94.4 251 98.1
-10 248 85.5 241 86.4 237 87.9 227 89.6 220 91.5
-15 223 86.4 215 85.8 208 85.5 199 85.7 192 86.0

OAT -Outdoor Air Temperature H cap -Heating capacity kW


C cap -Cooling capacity kW k W -Unit Power Input
 Capacity varies slightly with water flow rate. At the maximum flow rate. capacity decrease by 1% from the capacity at the rated flow. At theminimum
flow rate. the capacity increases by 3% from the capacity at the rated flow rate.
 Correcton factors for long term heating capacity are:
factor
OAT(°Ê) 15 7 4 0 -5 -10 -15
factor 1.00 1.00 0.92 0.94 0.95 0.96 0.97
Piping and Wiring Hole Dimension

main power supply Ø 80 hole

control power supply Ø 36 hole

unit model A B C D E F
30GQ - 080 1275 1000 993 778 1800 120
30GQ - 100 1400 1400 1133 728 2035 300
30GQ - 120 1400 1400 1133 728 2035 300

Reference Dimension and Position for Foundation

Service Space
120
30GQ - 080

Frame dimension, add clearance for foundation

Note: Ø 20 foot bolt hole.


unit model A B C D F
30GQ - 080 3580 4 870 2000 1940 foundation is 300mm above the ground.

30GQ - 100 4700 5 920 2000 1940 place a 10 to 20mm isoaltion pad under
30GQ - 120 5200 5 1020 2000 1940 the unit.
Typical wiring and piping

no. usage size

1 Main power supply 380VOL. 3 ph.4 lines(ref. electrical data for current size)

2 To cooling water flow switch 220VOL. 2 control lines


3 To water pump starter interlock 220VOL. 2 control lines(customer option)

4 To remote control box 6 control lines(customer supply)

symbol name size and location suggested

flow switch at outlet level straight pipe. 3 to 5 times of pipe diameter apart from the bending or valve, add 1°±

thermometer conn.

pressure gage 0 - 100°Ê

valve 0 - 10kg/cm2. mounted between valve and flange

filter

notes:
1. Extra length is required for wiring from local power supply to control panel.
2. All wires and cables must be laid and positioned. and marked at ends by the installer.
LEGEND
C - Compressor Contactor FU - Fuse WR -Warning Relay
CB - Circuit Breaker, Comp. FPS - Outdoor Fan Pressure Switch PB1 - Start Push Button
CH - Crankcase Heater FS - Flow Switch PB2 - Stop Push Button
CHC - Cooler Heater Cable Aux. Relay GL - Green Lamp PT1 - Adjusting Knob, Cool
Comp - Compressor HPS - High Pressure Switch PT2 - Adjusting Knob, Heat
CSW1 - Check Switch IPF - Internal Protector, Fan Motor PT3 - Adjusting Knop, Temp, rise
CSW2 - Selector Switch LED - LED Display RR - Reversing Relay
CSW3 - Alarm Reset Switch LPS - Low Pressure Switch RVS - Reversing Valve Solenoid
DFR - Defrost Aux. Relay OFM - Outdoor Fan Relay S - Switch
DGT - Discharge Gas Temperature OL - Orange Lamp SR - Start Relay
A United Technologies Company

OUR MULTINATIONAL COMPANY CUSTOMERS

BASF 30HR, 30HKH NESTLE 30HR


BELL 30HK OTIS 30HK, 30HR
CANON 30DQ P&G 30HK
CARREFOUR 30HR PEPSI 30GQ
DHL 30HR PIZZA HUT 30GQ
DUPONT 30HK RICOH 30HK
ERICSSON 30HR, 30DQ SAMSUNG 19XL
GENERAL MOTORS 30AQA SHARP 19XL
GLAXO 30HR SIEMENS 30GQ, 30HK
HEWLETT PACKARD 30GQ SKF 30HK, 30HR, 19DK
HONDA 19XL UNILEVER 30HK
JANSSEN 19DK, 30HR VOLKSWAGEN 30HR
JOHNSON 30HK VOLVO 30GQ
KFC 30GQ, 30HK XEROX 19DK, 30HK
KODAK 30GQ
MC DONALD 30GQ
MINOLTA 30GQ
MOTOROLA 19XL, 30HR

WHAT IS YOUR CHOICE

SHANGHAI HEZHONG CARRIER AIR-CONDITIONING EQUIPMENT CO., LTD.


ADDRESS: 24 SHUANGYANG ZHI ROAD SHANGHAI CHINA
30GQ-0003-1
TEL: 86-21-65430952 FAX: 86-21-65435404
POST CODE: 200090

MANUFACTORY RESERVES THE RIGHT TO CHANGE AT ANY TIME,


SPECIFICATION WITHOUT NOTICE.